GENERAL MANAGER, Transmission Zone-VII, DHANBAD
GENERAL MANAGER, Transmission Zone-VII, DHANBAD
Carrying out Preventive / Schedule and breakdown maintenance of 132/33 kV, 2x50 MVA Grid Sub-Station, Chandankyari, Bokaro for the period from 01.06.2026 to 31.03.2027 (i.e., 10 Months).
2026_JSEB_113736_1
116/PR/JUSNL/2026-27
Open Tender
Electrical Works
CHANDANKYARI BOKARO
Please refer Tender documents.
2 documents required · 2 mandatory
₹5,900
Yes
₹49,400
Yes
4 Jun 2026
8 May 2026
22 May 2026
8 May 2026
21 May 2026
8 May 2026
Preventive/ Routine/Breakdown Maintenance and periodic testing of Grid Sub-station with the help of as, 01 no. Highly Skilled, 02 nos. of skilled , 02 nos. of unskilled as per provided daily, weekly, monthly, quarterly , half yearly & yearly maintenance schedule of various EHT & LT equipments provided by Engineer Incharge & as per direction of Engineer Incharge.
Maintenance / Emergency Maintenance of Grid Substation as per schedule and JOB provided by Engineer In-charge.
Replacement of 132/33kV CT
Replacement of 132/33kV PT
Replacement of 132/33 kV LA
Replacement of 33kV CB Pole
Replacement of 132kV CB Pole
Fixing and replacement of Energy meter/ MW meter/ Voltmeter/Ammeter/Relay (132/33 KV)
Misc. work of Grid Substation as per schedule and JOB provided by Engineer In-charge
Material/Equipment manual shifting & movement in Grid Premises
Measurement of Earth footing resistance of all earth pits
Laying of control cable
Break down maintenance
Supply of emergency gang with T&P for work like conductor snapping of main bus.
Supply of Hydra/ Crane (upto 8MT capacity) as per requirement
Complete overhauling with painting of 50MVA Transformer Cooling Fans with supply of all materials if required
Transportation of materials & equipments through truck/pickup upto 3MT including loading,unloading of the materials.
Upto first 50 km
50km<distance<500km
Transportation of materials & equipments through truck/pickup upto 6MT including loading,unloading of the materials.
Upto first 50 km
50km<distance<500km
Repair of 132kV SF6 Breaker 1Ph spring charged motor if required
Repair of 33 kV VCB 1Ph spring charge motor if required
Erection, connection, testing and commissioning as per direction of E/I
33 kV Vacuum circuit Breaker with support structure and marshalling boxes including grouting of foundation bolts and wiring of cable from pole to pole including termination.
Erection of following equipments with Crane/ Derrick at site including handling the material/ equipments carefully at site including labour charges for all incidental and operational items of work (excluding cost of transportation charges from store to site)
132 kV Current transformer, Potential transformer & CVT including cable termination
132 kV Lighting arrestors
Dismantling of following equipments with Crane/Derrick at site including handling the material/ equipment carefully at site including labour charges for all incidental and operational items of work ( Excluding cost of transportation charges from store to site)
132kV Current transformer, Potential transformer & CVT including cable termination.
132 kV Lighting Arrestors
33 kV Vacuum circuit Breaker including pole to pole cable termination
Routine maintenance and gas refilling of air conditioners (1.5/2TR, ACs) and servicing to prevent leakage of condensate water from indoor ACs including top up of Gas as per requirement.
Testing of Transformers/ICTs including Tan Delta Test of all bushing & winding , winding resistance test, turn ratio test, magnetic balance test, short & open circuit test , IR & PI test etc.
132/33KV , 50 MVA Power Transformer
Testing of Transformer oil by recognised laboratory including supply of sampling bottle.
Water content Measurement (PPM)
Total Acidity
Specific Resistance(Resistivity)
Dielectric Dissipation factor(Tan Delta)
Inter Facial Tension(IFT)
Flash Point
Sludge Content
FURAN Analysis
Servicing of 100 KVA Asok Leyland make DG set
Oil Filter for 100 KVA DG Set
Mobil Filter
Air ( Inner + Outer ) Filter
Mobil premium blue 15W40
Coolant inhibitor
Coolant ( Exhibitor Corrosion )
Assesment of defects of battery chargers.
Maintenance and replacement of minor defective parts/equipments of battery chargers
Repair and Overhauling of 3-ph Sub-mersible pump including materials, lifting & lay down of Sub-mersible pump from Borewell , repair of water supply pipe all complete job & Transporation cost.
Filtration of Transformer oil with Oil filtaration machine.
Wiring of TBC control & Relay Panel including commissioning of panel
Supply of Consumables viz. Markin cloth, Distilled water, grease, Mobil, Nuts & Bolts, cotton waste, Joute, Petrolium Jelly, Kerosine, WD-40 rust remover etc. Required time to time for O&M works of GSS.
Enter Percentage (%)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.56 MB
Tendernotice_2.pdf
PDF • 0.71 MB
PricePart.xls
Additional Documents • 0.05 MB
Download all tender documents and submit your bid