Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹164.7 CrAccepted-AOC | ₹164.7 Cr | L1 | Accepted-AOC Being the lowest tenderer (L1) and reasonable |
| 2 | L2₹166.6 CrRejected-Finance | ₹166.6 Cr | L2 | Rejected-Finance Not being the lowest |
| 3 | L3₹175.6 CrRejected-Finance | ₹175.6 Cr | L3 | Rejected-Finance Not being the lowest |
| 4 | L4₹188.7 CrRejected-Finance | ₹188.7 Cr | L4 | Rejected-Finance Not being the lowest |
Tender Value
Refer Docs
EMD Value
₹15 L
Closing Date
11 May 2021, 6:00 pmClosed
CE (Navy) Mumbai
HQ CE (Navy) Mumbai, 26 Assaye Building, Colaba, Mumbai-400005
PROVISION OF DEFICIENT SAILORS MARRIED ACCOMMODATION 464 DUs AT COLABA MUMBAI
2021_MES_410649_2
87880/E8
Open Tender
Civil Works
1460 days
GE (P) (NW) Mumbai
Please refer Tender documents
8 documents required · 8 mandatory
₹3,000
GE (P) (NW) Mumbai
₹15 L
Yes
30 Jun 2021
22 Mar 2021
13 May 2021
22 Mar 2021
11 May 2021
20 Apr 2021
Amount
Schedule-A Part-I ''Buildings & Structures'' Total of Schedule-'A' Part-I B/F from serial page No. 33
Schedule-A Part-II ''Excavation, Earth Work & Site Clearance'' Total of Schedule-'A' Part-II B/F from serial page No. 35
Schedule-A Part-III ''Internal Water Supply'' Total of Schedule-'A' Part-III B/F from serial page No. 37
Schedule-A Part-IV ''Internal Electrification'' Total of Schedule-'A' Part-IV B/F from serial page No. 41
Schedule-A Part-V ''LIFT'' Total of Schedule-'A' Part-V B/F from serial page No. 42
Schedule-A Part-VI ''Fire Fighting'' Total of Schedule-'A' Part-VI B/F from serial page No. 46
Schedule-A Part-VII "Lightning Protection" Total of Schedule-'A' Part-VII, B/F from serial page No. 47
Schedule-A Part-VIII "DG Set" Total of Schedule-'A' Part-VIII B/F from serial page No. 48
Schedule-A Part- IX ''Compound wall, Gate'' Total of Schedule-'A' Part- IX, B/F from serial page No. 50
Schedule-A Part-X ''Road,Pathways'' Total of Schedule-'A' Part-X B/F from serial page No. 52
Schedule-A Part-XI "SEWAGE DISPOSAL" Total of Schedule-'A' Part-XI B/F from serial page No. 55
Schedule-A Part-XII ''Area Drainage'' Total of Schedule-'A' Part-XII B/F from serial page No. 57
Schedule-A Part-XIII ''External Water Supply'' Total of Schedule-'A' Part-XIII, B/F from serial page No. 59
Schedule-A Part-XIV ''External Electric Supply'' Total of Schedule-'A' Part-XIV, B/F from serial page No. 61
Schedule-A Part-XV "Aviation Light " Total of Schedule-'A' Part-XV B/F from serial page No. 62
Schedule-A Part-XVI "ARBORICULTURE" Total of Schedule-'A' Part-XVI B/F from serial page No. 63
SCH 'A' PART-XVII (MISCELLENEOUS ITEMS)
INTERNAL WATER SUPPLY
Providing, fixing, testing and commissioning of CP brass swan neck sink cock 15mm dia with wall flange and swinging casted spout with 6 LPM flow rate as/GRIHA requirement complete as required and making good the walls wherever required.
Providing, fixing, testing and commissioning of 15 mm dia CP brass bib cock with export pettern & with hose union for washing machine with CP wall flange and with flow rate as/GRIHA requirement of approved quality complete as required and making good the walls wherever required
Providing, fixing, testing & commissioning of water regulating angle valve with CP wall flange 15mm dia etc. complete as required and making good the walls wherever required.
Providing, fixing, testing and commissioning of CP Brass 115mm long Shower Arm with wall flange 15mm dia and pressure adjustable Shower Rose with 6 LPM flow rate as/GRIHA requirement complete with all accessories as required and making good the walls wherever required.
Providing, fixing, testing and commissioning of CP brass bath and shower mixer with wall flange and with flow rate as/GRIHA requirement complete with all accessories as required and making good the walls wherever required.
Providing, fixing, testing & commissioning of ABS body (push type) Health faucet 15mm dia of 5 LPM flow rate as/GRIHA requirement with wall hook and 1.2 metre SS braided rubber hose pipe complete as required and making good the walls wherever required.
S&F two way bib cock 15 mm dia. Make - Jaquar Model No CQT-23041 or equivalent as given in Particular Specifications.
Providing and fixing, testing and commissioning of pressure regulating valve (PRV) for water supply line. PRV is tested to a pressure not less than 15.0 kg/cm2 and suitable to reduce the pressure as desired, including flanges/unions, nuts, bolts and washers complete as required for application.
15 mm dia
20 mm dia
25 mm dia
40 mm dia
50 mm dia
S&F Gun-metal, globe or gate valves, with iron wheel head, screwed both ends for iron pipe and fixed complete all as specified and directed.
25mm dia nominal bore
65 mm dia nominal bore
75mm dia nominal bore
32mm dia nominal bore
"INTERNAL ELECTRIFICATION"
S &F TV Socket ( Similar to 5734 25 of Legrand or Equal) all as specified and as directed.
S & F modular type 1 module RJ 11 telephone socket with shutter complete all as specified and directed.
S &F modular AC Box sheet metal with socket 3 pin, suitable for 20 Amps flush type universal including 16 amp c series MCB protected all as specified and as directed.(For Geyesr/AC)Make:- L&T cat no DBMPS320SD/ Havells or equivalant of secure
S&F Energy efficient BEE five star rated ceiling fan, 1200 mm sweep and connecting up including provision of three core flexible copper wire of size 23/0076 from ceiling rose to ceiling fan complete in all respect all as specified and directed.Make : HAVELLS Cat No :- ES Neo Crompton Greaves/ Bajaj/Orient
S&F Exhaust fan heavy duty of size 300 mm sweep metal body complete with and louvers connecting up including provision of three core flexible copper wire of size 23/0.0076 from ceiling rose to exhaust fan all as specified and as directed. Make Make , - Havells cat no :- Turbojet SP/ Bajaj/Crompton
S&F Fresh air Exhaust fan of size 230/250 mm sweep PVC body complete with and louvers connecting up including provision of three core flexible copper wire of size 23/0.0076 from ceiling rose to exhaust fan all as specified and as directed. Make Make , - Havells Cat No :- Ventil Air-DS /Crompton Greaves/Bajaj
S &F LED tube light fittings decorative ultra slim linear fixture with extrudedalluminium heat sink envioromentel friendly Energy efficient ready to use pack ,1x18/20 Watt ,4 feet,surface mounting type extruded pvc, snap on installers and domestic electronic Driver ,connector block ect.with all assoceries intenallt prewired & includingconeecting up with 2 core flexible cppper conductor cable with sutable size & suitable for and mounting clamps PVC squre box 75x75mm - 2 nosetc. make-HAVELLSLHEXBLP7PN1W020WIPRO /JAQUAR /PHILLIPS
S &F LED tube light fittings decorative ultra slim linear fixture with extrudedalluminium heat sink envioromentel friendly Energy efficient ready to use pack ,1x10 Watt ,2 feet,surface mounting type extruded pvc, snap on installers and domestic electronic Driver ,connector block ect.with all assoceries intenallt prewired & includingconeecting up with 2 core flexible cppper conductor cable with sutable size & suitable for and mounting clamps PVC squre box 75x75mm - 2 nosetc all as specified and as directed. make- HAVELLS Cat no :- LHEXBTP7IN1W010/WIPRO / /JAQUAR /PHILLIPS
S &F LED tube light fittings decorative ultra slim linear fixture with extrudedalluminium heat sink envioromentel friendly Energy efficient ready to use pack ,1x9 Watt ( for mirror light) ,2 feet,surface mounting type extruded pvc, snap on installers and domestic electronic Driver ,connector block ect.with all assoceries intenallt prewired & includingconeecting up with 2 core flexible cppper conductor cable with sutable size & suitable for and mounting clamps PVC squre box 75x75mm - 2 nosetc all as specified and as directed. make-HAVELLS CAT NO LHEXBLP7IN1W009/ WIPRO /JAQUAR /PHILLIPS
S&F lamp holder PVC/polycarbonate with back plate suitable for angle batten fittings including LED lamp 9 watt complete all as specified and as directed.
S & F 10/12W Ceiling surface mounted decorative LED Light fixtures all assoceries internally prewired & including conecting up with 2 core flexible copper conductor cable with sutable size & mounting clamps etc all as specified and as directed. Make ;- Crompton Cat No LCSR-12-CDL/Havells INTEGRANEO SURFACE DLS 10W LED or equivalent Philips/Wipro/CG/ Bajaj Make
S&F deep drawn Rugby bulk head fitting 9/10 watt cast aluminium housing& foosted glass. Body epoxy white powder coated heat resistant prismatic glass cover with specially designed gasket complete all as specified and as directed. Make : Crompton Cat No ; LBHE-10CDL/Havells/SYSKA
S & F LED Security/Street light fittings 25 Watt wall mounting type extruded metal/aluminium body, and electronic LED driver, ect. with all accessories internal prewired & including connecting up with 2 core flexible cppper conductor cable with suitable size etc and fix GI pipe bracket 25mm dia- 0.9m long & 2 set of clamps made out of 30x5mm ms flat & fixed with anchor bolt suitable for 15w ssecurity light fitting all as specified and as directed. Make- HAVELLS Cat No ; ENDURAPEARLSL25WLED757SASYTOPCMP/WIPRO / /JAQUAR /PHILLIPS
S&F for MCB TPN 415 Volts, 'C' series , breaking capacity 10KA of rating 40Amps all as directed.Make L&T cat no :- BB40400C/Havells/schneider/ ABB
S&F for MCB TPN 415 Volts, 'C' series , breaking capacity 10KA of rating 32 Amps all as directed.Make L&T cat no :- BB40320C/Havells/schneider/ ABB
S&F for MCB TPN 415 Volts, 'C' series , breaking capacity 10KA of rating 63 Amps all as directed.Make L&T cat no :- BB40630C/Havells/schneider/ ABB
MCB SP 6-32 Amps 'C' series, breaking capacity 10 KA of rating all as directed. Make L&T cat no BB10060C to BB10320C /Havells/ schneider/ ABB
MCB SPN 240 Volts, 'C' series, breaking capacity 10 KA of rating 32Amps all as directed. Make L&T cat no BB20320C /Havells/ schneider/ ABB
MCB SPN 240 Volts, 'C' series, breaking capacity 10 KA of rating 40 Amps all as directed. Make L&T cat no BB20400C /Havells/ schneider/ ABB
MCB SPN 240 Volts, 'C' series, breaking capacity 10 KA of rating 63 Amps all as directed. Make L&T cat no BB20630C /Havells/ schneider/ ABB
S & F Geyser BEE 5 star rated ,25 Ltr capacity incl grouting nut bolt of suitable size and making good surface all as specified and as directed. Make:- Havells cat No (Quatro)GHWEQTTIB025/Bajaj/Venus/Racold
Supply, installation, testing and commissioning of sandwich type (3L + N + PE), busbar trunking system complete with two runs of 50 mm x 6 mm aluminium earthing strip and accessories all as specified and directed. Make: L&T/Schneider/ABB/Siemens The busbar trunking system shall conform to the following technical specifications:
[A] General: [i] The busbar trunking system (BTS), both feeder and plug-in, shall be of sandwich construction. All components and fittings (straight length, elbow, tees, flanged ends, cable tap box and circuit breaker, etc.) shall be in accordance with IEC 61439 Part 6 (2012) or UL857 and from the same manufacturer as the busbar trunking system. Degree of protection of the BTS shall be IP 65 in accordance with IEC 60529. [ii] Rated operation voltage of the BTS shall be 1 kV. The neutral conductor shall have the same cross-sectional area as the phase conductor. The earth busbar must be one continuous piece without bolting on housing.
[B] Certificate: [i] The busbar, of full range and each rating, shall pass full type tests specified in IEC 61439-6. The certificate shall be issued by an international independent testing authority (e.g. ASTA, KEMA, UL). [ii] A product safety mark (e.g. KEMA-KEUR, ASTA DIAMOND, UL) shall be on the product offering a visible assurance to all of full product safety testing, factory inspection and ongoing surveillance under independent authority to ensure the ongoing safety of product. [iii] The BTS shall pass seismic tests with actual physical product and being certified complying with UBC seismic Zone 5 condition by an international recognized earthquake research body, e.g. Asian Pacific Network of Centers for Earthquake Engineering Research (ANCER). The OEM shall also furnish a certificate to confirm taht the BTS assembly is capable of withstanding the additional vibration in shaft owing to air movements.
[C] Short-Circuit Ratings & Tests: [i] The whole BTS shall be capable of withstanding the short circuit of the electrical installation without undergoing any electrical, mechanical and thermal stress under fault condition at a service voltage of 1 kV at 50 Hz frequency. The minimum rated insulation voltage shall be 1 kV. [ii] The Minimum certified short circuit withstand capacity for 400 A rating shall be 25 kA for 1 set [iii] The Minimum certified short circuit withstand capacity for 800 A rating shall be 50 kA for 1 set [iv] The Minimum certified short circuit withstand capacity for 1250 A rating shall be 65kA for 1 set [v] The Minimum certified short circuit withstand capacity for 2000 Arating shall be 80kA for 1 set
[D] Housing: [i] The busbar trunking housing shall be constructed of 1.6 mm thick electro- galvanized steel and aluminum to reduce hysteresis and eddy current loses and shall be provided with a suitable protective finish of ANSI 49 grey epoxy paint. [ii] The busbar trunking housing shall be totally enclosed non-ventilated for protection against mechanical damage and dust accumulation. And it shall pass at least 2000 hr salt spray test to ensure the anticorrosion ability. [iii] The totally enclosed housing shall be manufactured by the BTS OEM and modifications of busbar trunking to make it totally enclosed by housing other than the busbar trunking OEM shall be unacceptable without the written consent of the manufacturer.
[E] Busbars: [i] Busbars shall be of aluminum with copper cladding utilized Molecular Fusion technology. [ii] There shall be no bolts passing through the busbars of the busway. [iii] Each busbar shall be insulated with Class B (130 ℃) DuPont Mylar insulation. Epoxy insulation is unacceptable. [iv] The temperature rise at any point of the busbar trunking enclosure shall not exceed 55° C above the ambient temperature of 40° C when operated at rated current.
[F] Joints: [i] The busbar trunking joint shall be of the one-bolt type which utilizes a high strength steel bolt(s) and Belleville washers to maintain proper pressure over a large contact surface area. [ii] The bolt shall be torque indicating and at earth potential. [iii] The bolt shall be two-headed design to indicate when proper torque has been applied and require only a standard long handle wrench to be properly activated. [iv] Access shall be required to only one side of the busbar trunking for tightening joint bolts. [v] It shall be possible to remove any joint connection assembly to allow electrical isolation or physical removal of a busbar trunking length without disturbing adjacent busbar trunking lengths.
[G] Plug-in Openings: [i] The connecting jaw of the plug-in unit shall plug directly on to the busbar and have full contact with busbar itself. Welded tab at plug-in busbar is unacceptable. [ii] All contact on joint and plug-in opening should be silver plated copper. [iii] On plug-in busbar trunking there shall be three dead front, hinged cover type plug-in openings on each side. [iv] All openings shall be usable simultaneously. [v] Busbar trunking shall be installed so that plugs are side mounted to permit practical use of all plug-in openings. [vi] It shall be possible to inspect the plug-in opening and busbars prior to the installation of the plug-in units.
[H] Plug-in Units: [i] The plug-in jaw shall be spring design composed of different metal to ensure the firm and tight contact with the busbar. [ii] Plug-in Units shall be type tested in accordance with IEC 61439-6 (Annex D: Part 1-5 and 9-13). [iii] The earthing contact of the plug-in unit shall always be made before that of the live conductors and the last to break during removal. And it must connect to the earth bar of busway to ensure the safety. [iv] Covers of all plug-in units must have interlocks to prevent the cover from being opened when the switch is in the ON position. [v] Plug-in units (circuit breaker type or fusible switch type) shall be operated with visible blade quick-make and quick-break mechanism. [vi] Presence of transparent shield shall be inside to avoid direct contact of human. [vii] The plug-in units shall be equipped with internal barriers to prevent accidental contact of fish tape and conductors with live parts on the line side of the protective device during time of wire pulling.
[I] Supporting Structure: (i) Support structure shall be provied as per OEM's recommendation. (ii)Indoor feeder and plug-in busbar trunking shall be approved for hanger spacing of up to 3 meters for horizontally mounted run and 4.88 meters for vertically mounted runs. Outdoor feeder busbar trunking shall be approved for spacing of up to 1.5 meters for horizontally or vertically mounted runs. [J] Voltage Drop: [i] The voltage drop (sending end voltage minus receiving end voltage) specified shall be based on the busway operating at full rated current and stabilized operating temparature in [ii] The 3-phase line to line voltage drop 40% power factor concentrated loadshall not exceed 3.4 V per hundred ft. [iii] The line-to line voltage drop at the load power factor shall not exceed 4.1 V per hundred feet.
(H) INSPECTION / SUPPORT OF INSTALLATION (i) The installation of BBT shall be executed by skilled professionals with minimum experience of 4 yrs. Having sufficient installation base and pre- commissioning experiences. (ii) The entire installation shall be directly supervised by the OEM. (iii) The OEM shall be also fuenish a commissioning report underlining satisfactory installation after the commissioning of BBT system 800 A BBT
800 A straight Run feeder (IP54 Protection)
630 A straight Run feeder (IP54 Protection)
400 A straight Run feeder (IP54 Protection)
Flange End with Equilizer/ Shorting plate
Horizontal/ Vertical Bend
Plug-in-point
Vertical Spring Hanger /Fix Hanger
Expansion Joint
Tinned copper braided Flexibles with Hardware- Nuts&Bolts
Adapter Box
End Feed Unit with 400A ,415V,36kA,50Hz,FP MCCB STANDERD PLUG-IN-BOX/TAP -OFF UNIT WITH FP MCCB
SUPPORTING STRUCTURE
Supply, installation, testing and commissioning of following Inverter system for a constant secondary voltage of 240 volts at 50 Hz, single phase, batteries backup of minimum 90 minutes duration including, SMF batteries, battery chargers, rectifiers, transformers, controls, protection and instruments etc. complete as required. Cost to include battery stand/rack, interconnecting cables etc all as specified and as directed.
LIFTS
Supply, Installation,Testing & Commissioning of Electric Traction Type fully automatic with Machine room Elevator with AC variable voltage & variable frequency drive unit (G+32) suitable for operation on 415V, 3 Phase, 50Hz. AC supply, power operated central opening/two-panel center opening type car and landing doors, electro-magnetic brake system, two numbers of operating panel with luminous button , overload warning indicator, battery operated alarmbell, emergency light, infra red ray sensing door protection for full height, reverse phase relay on controller, fireman's switch at ground floor, digital car position indicator in car (at all floors) with up/down direction, light fixtures, ventilation fan, main beam in shaft for machine, pit ladder and with Automatic Rescue Device (ARD) complete and as under: - Make: SCHINDLER, OTIS, MITSUBISHI, HITACHI, THYSSENKRUPP
Capacity - 16 passengers Speed - 2.5 mps Rise - 103.25m (Approx) No. of stops & openings - 33 - 33 Car size - As per IS/NBC (Vary from Vendor to Vendor) Interior - S/S Grade 304-N Automatic centre opening doors 900-1000 mm wide Operation - Microprocessor based single automatic push button/quadruplex full collective with / without attendant, group operation control for four lifts. ARD for emergency operation Gong for landing in lobby Car Position indicator Hall button Car operating panel Counter weight provision
Display inside the car Intercom Facility Ready for software integtation (with BMS & FAS System) Handrail - SS mirror finish on rear wall only Car ceiling type & finish - CD41 - SS hairline finish Ceiling interior and LED light fixture shall be in scope of vendor as per OEMs design Infra Red protection for door opening & Closing On each Landing outside the lift, a steel plate with illumination sign shall be provided with written on it:- DO NOT USE LIFT IN CASE OF FIRE Voice announcement system in the car to announce the position of the elevator in the hoistway as the car passes or stops at a floor served by the elevator. Controller: A.C. variable voltage & variable frequency Power- 415 V, 3 phase, 50 Hz, 4 wires system. Type of doors - SS hairline finish Car Power operated, centre opening horizontal sliding SS Hair line finish Landing doors : Stainless Steel Should have regenerative drives to save electricity
Note: Additional load of 200kg shall be considered for Interior Designing. Operation / Grouping: Full Collective Other General Requirements Emergency Light and Alarm Bell Over Load Indicator (Visual & Audible) 3 Way Build in Intercom with EPABX System Fireman Switch in Ground Floor Automatic rescue device (Access Hatch to be consider for each lift for emergency rescue) Car Announcement system Digital indicator with direction of travel indicator in car. Direct Axial 3 speed Fan in Car, with auto switch off if no call is made for 120 sec Self Levelling- ±5 mm Elevator ceiling height – min. 2600mm. Initial inspection by lift manufacture. Passenger Elevator as described above Make: SCHINDLER, OTIS, MITSUBISHI, HITACHI, THYSSENKRUPP
Supply, Installation,Testing & Commissioning of Electric Traction Type fully automatic with Machine room Elevator with AC variable voltage & variable frequency drive unit (G+ 32) suitable for operation on 415V, 3 Phase, 50Hz. AC supply, power two-panel side opening type car & landing doors, electro-magnetic brake system, One number of operating panel with luminous button , overload warning indicator, battery operated alarmbell, emergency light, infra red ray sensing door protection for full height, reverse phase relay on controller, fireman's switch at ground floor, digital car position indicator in car (at all floors) with up/down direction, light fixtures, ventilation fan, main beam in shaft for machine, pit ladder, simplex automatic & manual dual controlled operation and with Automatic Rescue Device (ARD) complete as under: -
Capacity - 13 passengers Speed - 2.5 mps Rise - 103.25m (Approx) No. of stops & openings - 33 - 33 Car size - As per IS/NBC (Vary from Vendor to Vendor) Interior - S/S Grade 304 Flooring - As per OEMs design Automatic side opening doors 900-1000 mm wide Operation - Microprocessor based single automatic push button/simplex full collective with / without attendant. ARD for emergency operation Gong for landing in lobby Car Position indicator Hall button Car operating panel Counter weight provision
Display inside the car Intercom Facility Ready for software integtation (with BMS & FAS System) Handrail - SS mirror finish on rear wall only Car ceiling type & finish - CD41 - SS hairline finish Ceiling interior and LED light fixture shall be in scope of vendor as per OEMs design Infra Red protection for door opening & Closing On each Landing outside the lift, a steel plate with illumination sign shall be provided with written on it:- DO NOT USE LIFT IN CASE OF FIRE Voice announcement system in the car to announce the position of the elevator in the hoistway as the car passes or stops at a floor served by the elevator. Controller: A.C. variable voltage & variable frequency Power- 415 V, 3 phase, 50 Hz, 4 wires system. Type of doors - SS hairline finish Car Power operated, centre opening horizontal sliding SS Hairline Landing doors : Stainless Steel ( On Ground Floor) and MS Painted on Above floors Should have regenerative drives to save electricity
Note: Operation / Grouping: Simplex Other General Requirements Emergency Light and Alarm Bell Over Load Indicator (Visual & Audible) 3 Way Build in Intercom with EPABX System Fireman Switch in Ground Floor Automatic rescue device (Access Hatch to be consider for each lift for emergency rescue) Car Announcement system Digital indicator with direction of travel indicator in car. Direct Axial 3 speed Fan in Car, with auto switch off if no call is made for 120 sec Self Levelling- ±5 mm Elevator ceiling height – min. 2600mm. Initial inspection by lift manufacture. Service Elevator as described above
Supply, Installation,Testing & Commissioning of Electric Traction Type fully automatic with Machine room Elevator with AC variable voltage & variable frequency drive unit (G+32) suitable for operation on 415V, 3 Phase, 50Hz. AC supply, power operated central opening/two-panel center opening type car & landing doors, electro-magnetic brake system, One number of operating panel with luminous button , overload warning indicator, battery operated alarmbell, emergency light, infra red ray sensing door protection for full height, reverse phase relay on controller, digital car position indicator in car (at all floors) with up/down direction, light fixtures, ventilation fan, main beam in shaft for machine, pit ladder, simplex automatic & manual dual controlled operation and with Automatic Rescue Device (ARD) complete as under : - Make: SCHINDLER, OTIS, MITSUBISHI, HITACHI, THYSSENKRUPP
Machine room (MR) Capacity - 13 passengers (884 Kgs) Speed - 2.5 mps Rise - 103.25m (Approx) No. of stops & openings - 33 - 33 Car size - As per IS/NBC (Vary from Vendor to Vendor) Interior - Hairline SS Flooring - As per OEMs design Automatic centre opening doors 900-1000 mm wide Landing doors : Stainless Steel ( On Ground Floor) and MS Painted on Above floors Operation - Simplex
Other General Requirements Gong for landing in lobby Car Position indicator, as per ID Hall button, as per ID Car operating panel, as per ID Display inside the car, as per ID. Intercom Facility Ready for software integration (with BMS & FAS) Ceiling interior and light fixture shall be in scope of vendor, as per ID. Direct Axial 3 speed Fan in Car, with auto switch off if no call is made for 120 sec Infra Red protection for door opening & Closing Self Levelling- ±5 mm Elevator ceiling height – min. 2600mm. Initial inspection by lift manufacture. Fire Elevator as described above
FIRE FIGHTING & FIRE DETECTION WORKS
PUMP ROOM EQUIPMENT
Supply, installation, testing and commissioning of electric driven Main Fire Pump to deliver 2850 LPM flowrate at 200 MWC head and suitable for automatic operation and consisting of following, complete with accessories as specified and directed by engineer-in-charge.
[i] Horizontal type, single suction, multi-stage multi-outlet pump of cast iron body & stainless steel impeller with stainless steel shaft, mechanical seal, etc. conforming to IS 12469: 2019, suitable to deliver 2850 LPM flowrate at 200 MWC head. [ii] Suitable HP squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation on 3- Ph, 415 V, 50 Hz AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class 'F' insulation, conforming to IS 12615: 2018. [iii] Suitable Soft Starter Model EMX3-0220B-411 Make L&T [iv] MS fabricated common base-plate, coupling, coupling guard, foundation bolts, etc. complete with accessories as required. [v] Suitable cement concrete foundation duly plastered with anti vibration pads.
Supply, installation, testing and commissioning of Diesel engine driven main fire pump to deliver 2850 LPM flowrate at 200 MWC head and suitable for automatic operation and consisting of following, complete with accessories as specified and directed by engineer-in-charge.
[i] Horizontal type, single suction, multi-stage multi-outlet pump of cast iron body & stainless steel impeller with stainless steel shaft, mechanical seal, etc. conforming to IS 12469: 2019, suitable to deliver 2850 LPM flowrate at 200 MWC head. [ii] Suitable HP, 1800 RPM diesel engine, water cooled with radiator, conforming to IS 10002: 1981, complete with auto starting mechanism, 12/24 V electric starting equipment, diesel tank, exhaust pipe extended upto 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour, etc. as required. [iii] Suitable Soft Starter Model EMX3-0220B-411 Make L&T [iv] MS fabricated common base-plate, coupling, coupling guard, foundation bolts, etc. complete with accessories as required. [v] Suitable cement concrete foundation duly plastered with anti vibration pads.
Supply, installation, testing and commissioning of electric driven Jockey Pump to deliver 180 LPM flowrate at 200 MWC head and suitable for automatic operation and consisting of following, complete with accessories as specified and directed by engineer-in-charge.
[i] Horizontal type, single suction, multi-stage multi-outlet pump of cast iron body & stainless steel impeller with stainless steel shaft, mechanical seal, etc. conforming to IS 12469: 2019, suitable to deliver 180 LPM flowrate at 200 MWC head. [ii] Suitable HP squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation on 3- Ph, 415 V, 50 Hz AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class 'F' insulation, conforming to IS 12615: 2018. [iii] Suitable Starter [iv] MS fabricated common base-plate, coupling, coupling guard, foundation bolts, etc. complete with accessories as required. [v] Suitable cement concrete foundation duly plastered with anti vibration pads.
Supply, installation, testing and commissioning of factory made, CPRI type tested, indoor, cubical compartmental type "Motor Control Center" (MCC) of suitable size, conforming to IEC 61641, having both sides openable with hinged double doors & locking arrangement and IP 54 protection made out of 2.00 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labeling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel sheet, vitreous enameled (white) with letters figures and conventional skull and bones in signal red colour, suitable for 3- Phase 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length & size, including fixing lugs, bolts, screws etc. complete all as specified and directed.
M & L for low smoke zero helogen (LS0H) fire survival control cable with circuit integrity, conforming to BS 7846 and rated for 600 V, having plain annealed stranded copper conductor with fire-resistant mica tapes covered by an extruded layer of cross-linked polyethylene, extruded layer of thermoplastic low smoke zero helogen (LS0H) compound, single layr of galvanized steel wires and thermoplastic LS0H compound sheath, suitable for operating temperature range -40 ˚C to +90 ˚C and minimum bending radius being 12 times the overall cable diameter, including laying, clamping, termination and ferruling complete all as specified and directed by engineer-in-charge. Make: Havells, Polycab, Finolex, RR Kabel
2 core, 2.5 mm² (for instrumentation)
3 core, 2.5 mm² (for auto start/stop panel)
12 core, 2.5 mm² (for diesel engine pump)
M & L for ISI marked MS ERW pipes conforming to IS: 1239 (Part 1 & 2) with all accessories like all fittings including tees, elbows, reducers, union, flanges, rubber gaskets, GI nuts bolts, washer, including supporting/fixing the pipe on floor/wall/ceiling with clamps, hangers, angles, channels (using anchor fastners) with painting of one coat primer and 2 or more coats of synthetic enamel paint complete all as specified and directed
NOTES: - [i] Standard MS fittings with welded joint shall be used on the pipes. [ii] All hangers, clamps, brackets etc. shall be of galvenized iron. [iii] Welding of any kind on the galvenised support / hanger shall not be permitted. [iv] The pipe size 150 mm NB & below shall be MS 'C' class as per IS 1239 (Part- 1): 2004 & IS 1239 (Part- 2): 2011. [v] The pipe size above 150 mm NB shall be welded black steel pipe heavy class as per IS 3589: 2001. [v] Pipes of size more than 50 mm NB shall be butt welded with fittings of equal or higher thickness whereas pipes below 50 mm NB size shall be socket welded. Make: Tata, Jindal, BST
300 mm NB (Suction header sump)
250 mm NB (Common header for fire hydrant / sprinkler)
M & L for PN 1.6 rated CI 'Y' -type strainer for suction conforming to IS: 907- 1984 with SS filter screen and flange drilling standard end connection conforming to IS: 1538- 1993 and necessary accessories for suction side of fire pumps all complete as specified and directed. Make: Leader, Sant, Venus
M & L for PN 1.6 rated 200 mm NB polypropelene vortex inhibitor suction lift, conforming to BS 4504 with stainless wire mesh, bolts, nuts and washers, etc. complete all as specified and directed by engineer-in-charge.
S & F Butterflyvalve handle, screwed both ends for iron pipe or for unions and necessary accessories all complete as specified and directed. Make: Leader, Sant, Venus
S & F of CL 150 rated ball valve, designed & manufactured as per IS: 9890 (1981) and tested as per BS 6755 Part- I, having floating type three piece design, CS body, SS- 304 ball, PTFE seal/packing/gasket, CS fastners and lever and screwed/socket weld end connection, etc. with accessories complete all as specified and directed. Make: Leader, Sant, Venus
HYDRANT SYSTEM
S & F gunmetal fire hydrant single landing valve with 80 mm NB flanged inlet, brass spindle controlled 63 mm NB female instantaneous outlet type gunmetal coupling, blank cap, chain, twist release type lug & all accessories conforming to IS:5290- 1993 including fixing and flanged tapping from stand post type fire hydrant complete all as specified and directed. Make: Newage, AAAG, Minimax
S & F of orifice plate made out of 6 mm thick SS 304 with orifice of required size to be fitted between flange and landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete all as specified and directed by engineer-in-charge. Make: Newage, AAAG, Minimax
S & F non-percolating rubber reinforced lined RRL hose type- A 15 m long fire hose of 63 mm NB size, conforming to IS 636: 1988, rated for bursting pressure of 35.7 kg/cm² complete with gunmetal male & female coupling conforming to IS: 903- 1993, bound and rivetted to the hose pipe with copper rivets and 1.5 mm² copper wire complete as specified and directed. Make: Newage, AAAG, Minimax
S & F branch pipe, conforming to IS 903: 1993, having 63 mm NB instantaneous gunmetal inlet, made threaded outlet, 15 mm NB long nozzle, suitable for inter connection to hose pipe coupling complete all as specified and directed. Make: Newage, AAAG, Minimax
S & F swinging type 36 m long First Aid Hose Reel, conforming to IS:884-1969, having 19 mm NB thermoplastic reinforced hose reel tubing, conforming to IS: 12585- 1988, 25 mm NB ball valve, stop cock, terminating with gunmetal coupling & nozzle of 6 mm NB outlet with shut-off valve, conforming to IS: 8090- 1976 complete with MS socket for tap-off, red colour drum, brackets (including painting) for fixing on wall with anchor fastner, bolts, nuts, etc. complete all as specified and directed. Make: Newage, AAAG, Minimax
Supply, installation, testing and commissioning of 4- way fire brigade inlet connection, conforming to IS: 5290- 1993, with four 63 mm NB inbuilt gunmetal non-return valves, four 63 mm NB instanteneous couplings arranged on 150 mm NB pipe manifold and connected to fire hydrant ring main and fire hydrant wet riser pipe all complete as specified and directed. Make: Newage, AAAG, Minimax
Supply, installation, testing and commissioning of 2- way fire brigade draw- off connection with two 63 mm NB inbuilt gunmetal non-return valves instanteneous coupling type arranged on 100 mm NB pipe manifold and connected to wet riser main as well as to fire water tank including CI butterfly valve, CI non-return valve and MS cabinet with mounting supports, etc. all complete as specified and directed. Make: Newage, AAAG, Minimax
AUTOMATIC SPRINKLER SYSTEM
M & L for installation 100 mm NB sprinkler drawn valve, UL listed of cast iron body, brass / bronze working parts comprising of water motor alarm, bronze seat clapper, clapper arm and hydraulically driven mechanical gong bell to sound continuous alarm when the sprinkler system activates, pressure gauges, emergency releases, strainer, pressure switch, cock valve complete with drain valve and bypass, test control box, ball valves, MS pipe of required size, flanges, orifice plate, gasket etc. all complete as specified and directed by engineer-in-charge.
S & F PN 1.6 rated CI sluice valve, conforming to IS: 14846- 2000, with SS spindle conforming to IS: 6603- 2001 and flange drilling standard end connection conforming to IS: 1538- 1993 and necessary accessories all complete as specified and directed. Make: Leader, Kirloskar, Venus
M & L for FM approved and UL listed standard response, standard coverage glass-bulb type spray sprinklers, conforming to IS 15105: 2002, and having discharge coefficient K = 8.0, maximum working pressure 175 psi (12.1 bar), bronze frame, brass/copper button, bronze compression screw, copper defletor, TEFLON sealing assembly, etc. with 15 mm NB screwed emd connection, suitable for 68° C temperature rating complete all as specified and directed by engineer-in-charge. Make: Tyco, HD, Viking
Pendent Sprinkler
Upright Sprinkler
Sidewall Sprinkler
S & F Flow switch 80mm dia
S & F Flow switch 100mm dia
Providing and fixing standard fireman's axe with heavy insulated rubber handle conforming to IS: 926 complete.
Providing, fixing, testing & commissioning of annunciater Panel for flow control switches, providing Audio/visual Indication of actuation of Automatic sprinkler system for each zone complete as per specifications. The panel should have interface for connection to complete controlled building management system. The panel should have : a) Fault indication for each zone. b) indication of zone fire c) Fire/fault hooter. d) Alarm Panel for fire/fault. e) Battery for emergency. f) Battery charger. g) Mains supply. and shall cater for
25 zones (33 working and 8 spare)
Supply, installation, testing & commissioning of 25 mm dia inspecting & testing assembly with gunmetal isolation valve, gunmetal sight glass, bypass valve & connected to drain line complete (excluding the cost of drain pipe).
Supply, Installation, Testing & Commissioning of ISI marked (IS:15683) Portable fire extinguisher, of 3.0 kg capacity Carbon-dioxide type flat base including valve, discharge hose of not less than 10 mm dia 1m long & complete in all respects including initial fill with CO2 gas confirming to IS: 307-1966 filled to a filling ratio of not more than 0.667of not more than 0.667and wall suspension bracket.
Supply, Installation, Testing & Commissioning of ''ABC' stored pressure type Dry chemical powder (Mono-Ammonium Phosphate) fire extinguisher with fixing hangers, hose, brackets, screws to required size etc., complete as per IS:15683, 4.0 Kg.
Supply, fabricating and fixing of hot dip mild steel sleeves (IS:1239 Part-I) heavy class cutting to sizes, drilling welding fixing to insert plates as per drawings and specification issued by Engineer in charge. Before finaling, the vendor should take prior approval from Engineer in charge.
100 mm dia
150 mm dia
Providing and fixing MS conduit of 16 SWG ISI marked (15:9537-1981, Part-11) complete with all fittings viz. tees, bends, junction boxes, clamps/supports etc. To be concealed in slabs/brick work as required or surface laid. (Exact quantities will be measured as per site conditions)
25mm dia
Providing and laying FRLS insulated ISI marked copper control cable in MS conduit (IS:694) from individual flow switches from towers & stilt floor ceiling to annunciation panel installed in fire control room including sleeves cable clips, supports for horizontal runs etc. complete of size (Exact quantities will be measured as per site conditions).
Providing and fixing 6 mm thick orifice plates of brass with central hole of required dia as per TAC design having a projected identification tag duly marked with 'K' factor complete in all respect.
For 80 mm dia pipes
Supply, installation, testing & commissioning of pressure regulating valve (PRV) for fire line. PRV is tested to a pressure not less than 25.0 kg/cm2 and suitable to reduce the pressure as desired, including flanges/unions, nuts, bolts and washers complete as required for application.
80 mm dia
100 mm dia
Supply & placing 4 Bucket set of 9 Ltr. Capacity with MS Stand and fills with sand complete in all respect. Intelligent type addressable Fire Alarm system NOTE :- (a)The Fire Panel shall also be interfaced with the ventilation & pressurization System (b)Contractor need to submit the system Architecture and Riser diagram. (c)Panel should work satisfactorily at voltage 240V+/-10%
M&L of Addressable-Multi Sensor DETECTOR Detectors Complying with and type certified to EN - 45 Addressable type multisensor detector with heat and smoke combination.
M&L of Addressable-Heat DETECTOR Detectors Complying with and type certified to EN - 45 Addressable type heat detector with base with rate of rise cum fixed temperature as per lS:2175
M&L Short circuit isolators complete all as specified
M&L Remote response indicators complete all as specified
Supply, installation, testing & Commissioning of micro processor based 2 wire fault tolerant loop, 12 loop networkable type (each loop accessing minimum 125 detectors and 125 modules ) fire alarm/detection control panel. The panel shall be able to give location of all fire/fault conditions of addressable units via the address codes. Further, the panel must be able to automatically switch ON /OFFrespective control module when ever any alarm is triggered. The panel shall have rectifier, Loop cards, L C D unit to indicate Fire/Fault Signal with address and analog output, external/inbuilt printer to log all fire or fault events complete in all respects.The panel shall have a built in power supply and battery charger along with maintenance free 24 AH, 2 x 12 volt SMF Lead acid batteries capable of running for a minimum of 8 hours with battery charger complete as required including 16 Channel Integrated Digital Voice Evacuation and Two Way Fire Fighter Telephone communication System capable of supervision of all the speaker circuits, with required suitable digital amplifiers, mic and acessories required to compelete the system. The system shall be of the same make as the panel and shall be UL Listed. The system shall also have capability to be integrated with EPBAX. NOTE-The panels shall be Networked with each other .The panel shall be complete with all accessories as required for detection, PA & hooter, talk back as per norms and complete as required.
Supply, installation, testing & commissioning of Intelligent Network Repeater Panel with minimum 10" Color Touch Screen display, mapping minimum 2,00,000 points on network. The NRP shall act as an independent node communicating on the peer to peer network and shall not be dependant on the Fire Panel CPU for operation. Failure of Fire Panel CPU shall not result in failure of NRP operation. UL and FM Approved
Supply, laying including termination with proper connection & temination of wiring with 2 x 1.0 sqmm PVC insulated solid copper conductor FRLS 660/1100 volts grade wires in conduit complete as required. Note:-The conduit and it's accessories measured and paid separately
Supply, installation, testing & commissioning of 2c x 1.5 sq.mm Fire Survival Circuit Integrity unarmoured cable of 300/500V rated with Class-2 annealed copper conductor having crosslinkable ceramified Silicon insulation as per BS EN 50363 along with drain wire, aluminium tape screening and LSZH outer sheath. Should comply to EN 61034-2 & EN 60754-1. Should meet fire performance circuit integrity test as per BS EN 50200 & BS 6387 CWZ (950 Deg. C for 3 hrs). Outer sheath should be in red colour. Cable shall be laid in conduits. Make :- Finolex/RR cable/ Polycab
Fire Fighter's Telephone Supply, installation, testing and commissioning of recess/surface mounting intelligent analogue addressable Fire Fighter's Telephone Module/ jack with stainless steel face plates for connections of Fireman's handsets including the cost of supplying all the required control modules, mounting accessories and and complete as required.
Supply ,installation,testing and commissioning of 2 way communication Fire Fighter's handset complete as required.
Supply and Fixing Rigid non-metallic PVC conduit exclusive of boxes (junction/terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc.
20mm dia
25mm dia
32mm dia
Supply and Fixing Junction boxes (1 to 4 way)
20mm dia
25mm dia
32mm dia
M & L for Construction of fly-ash brick masonary valve chamber of size 1000 mm X 800 mm X 1000 mm (internal dimenssions) with PCC foundation 1:4:8 type D2 using 40 mm graded stone aggregate, 150 mm thick & 150 mm wide offsets around over 100 mm thick hardcore , 200 mm thick fly-ash brick masonry walls built in CM 1:6, 100 mm thick PCC 1:2:4 Type B1 coping finished even and smooth, rendering 10 mm thick in cement mortar (1:6) finished even and smooth, with out using extra cement internally including top of floor including excavation earth work in hard/Dense soil 6 mm thick MS sheet cover fixed on 25 mm X 25 mm X 6 mm thick angle iron frame with hold fasts embedded in PCC coaping with locking arrangement, mild steel handle and painting to steel surfaces with two coats of synthetic enamel paint over one coat of primer including disposal of surplus soil to a distance not exceeding 50 m etc complete all as specified and directed.
Pressurisation (Axial Flow Fans)
24000 CFM; SP 25 mm of wg; Power 7.5 KW for Liftwell Pressurization all as specified and as directed.
22000 CFM; SP 25 mm of wg; Power 7.5 KW for Liftwell Pressurization all as specified and as directed.
11000 CFM; SP 25 mm of wg; Power 3.7KW for Liftwell Pressurization all as specified and as directed.
Ducting
Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required all as specified and as directed.
Dampers/Grilles
Supply, installation, testing and commissioning of GI volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc., as per specifications all as specified and as directed.
Supplying & fixing of powder coated extruded aluminium Supply Air Grills with louvers but without volume control dampers complete as required all as specified and as directed.
Electrical Control Panel
Weather Proof Isolators
Supply, installation, testing and commissioning of out door weather proof switch box of continuous welded construction, fabricated out of 2 mm thick G.I. sheet complete with water tight gasket with front openable and lockable door including earthing, painting, glands,danger boards etc.suitable for mounting on wall with M.S. angle iron frame of size 40x40x6 mm consisting of relevant I.S all as specified and as directed.
63 Amps TPN Isolator
40 Amps TPN Isolator
Cables
Supplying, laying, testing and commissioning of XLPE insulated copper conductor armored cables of 1.1 KV grade of following sizes directly on wall/structural frame/ cable trays or racks using approved type of clamps, With/ Without End terminations with Double Compression type glands on both ends, double earthing with GI strip/wire of suitable size and hardware as per specifications including terminatio of cables to feeders all as specified and as directed.
3 C x 4 Sq. mm
3 C x 6 Sq. mm
GI perforated Cable tray to carry Cables from panel to Fans , all inclusive Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts& nuts, painting suspenders etc all as specified and as directed.
150 mm width X 50 mm depth X 1.6 mm thickness
"LIGHTNING PROTECTION"
Supply,Installation,Testing & Commisioning of 1 metre Vertical Aluminium Air terminal of dia 16mm to meet the requirement of IS/IEC 62305.Tested for Electrical, Mechanical, Environmental test and should have Impulse current withstand capability of 100KA (Class H)and as per IEC 62561-1&2.
Supply,Installation,Testing & Commisioning of 25x3mm Aluminum Tape Conductor with fixing accessories and should be tested for electrical resistivity test , Tensile strength, Environmental Test (salt spray & humidity test) to meet the requirements of IS/IEC 62305 and IEC 62561-1&2.
Supply,Installation,Testing & Commisioning of Aluminum Square Tape Clamp for Cross connection and T connection of 25x3mm Aluminium Tape should be tested for electrical resistivity test ,Environmental Test (salt spray & humidity test),Mechanical test and Impulse current withstand capability of 100KA (Class H)to meet the requirements of IS/IEC 62305 and IEC 62561-1&2.
Supply,Installation,Testing & Commisioning of U bolt rebar to Cable Clamp should be tested for Environmental Test (salt spray & humidity test),Contact resistance test and Impulse current withstand capability of 100KA (Class H)to meet the requirements of IS/IEC 62305 and IEC 62561-1&2.
Supply,Installation,Testing & Commisioning of 50sq mm Green/Yellow PVC insulated Copper cable with terminal Lug, should have Each stranded of 1.7 mm diameter as per requirements of IS/IEC 62305 and IEC 62561-2:2012.
Supply,Installation,Testing & Commisioning of Bi-mettalic Connector should be tested for Environmental Test (salt spray & humidity test), Contact resistance test ,Mechanical test and Impulse current withstand capability of 100KA (Class H)to meet the requirements of IS/IEC 62305 and IEC 62561-1&2.
Supply,Installation,Testing & Commisioning of Moisturing inhibiting compound to meet the requirements of IS/IEC 62305.
Supply,Installation,Testing & Commisioning of Test link should be tested for Environmental Test (salt spray & humidity test),Contact resistance test, Mechanical test and Impulse current withstand capability of 100KA (Class H)to meet the requirements of IS/IEC 62305 and IEC 62561-1&2.
Supply,Installation,Testing & Commisioning of maintenance free Earthing system comprising of 250micron copper bonded earth rod 3 mtr x 3/4" Dia long Earth electrode, inspection pit with polymer lid is load rated to 5000kg and suitable for general to heavy duty, copper rod to tape clamp and 25Kg of Earth Enhancing compound whose resistivity is less than 0.12 as per IEEE 80-2013 & IS 3043-2018 for normal soil condition . The compound shall be free from carbon and graphite and conductive in nature and should accomodate 60% of its volume. The rod should be threaded on both ends and all component should be tested as per IEC 62561. Note: 3m length shall vary depending upon soil resistivity.
"AVIATION LIGHT"
Supply and fixing aviation light luminaire,LED 9 W,IP 65 protection type comprising of aluminium housing with polycarbonate enclosure complete all as specified.
DG SET
Supply, installation, testing and commissioning of silent DG Set, conforming to IS: 10002- 1981, complete with Diesel Engine of suitable BHP & AC Brushless SPDP alternator, conforming to IS: 13364- 1992, mounted on a common base frame & coupled through a flex disc complete with platform, control panel having meters, sound-proof canopy, etc. of capacity 500 kVA complete all as specified and directed. Make: Kirloskar, Crompton Greves,Ashok Leyland,Mahindra
[a] Engine: 12 cylinder, in-line, 4 stroke, radiator cooled engine, well designed air handling system with dry type, heavy duty, replaceable paper element air cleaner with restriction indicator, air to air aftercooling, optimised turbocharger for increased altitude,Inline fuel pump with class H electronic governing, spin on fuel filter, standard integral set-mounted radiator system, designed and tested for 50°C ambient temperature, full flow spin on lube oil filter, electrical starter motor with soft start engagement feature, battery charging alternator with 1 x 24 or 2 X 12 V DC dry type battery. [b] Alternator: Brushless type, screen protected, revolving field, self-excited alternator, conforming to IS/IEC 60034-1 3-phase reconnectable winding with 12 terminals brought out for connection, dedicated winding specially designed for single operation, impregnation on all wound components for better mechanical strength. [c] Control Panel: Manufactured with 14/16 gauge CRCA sheet and powder coated for weather-proof and long lasting finish. The control panel consists of the following parts: [i] Controller: Aluminum bus bars with suitable capacity with incoming/outgoing terminals [ii] Indicating lamps for ‘Load ON’ and ‘Set Running’
[iii] Instrument fuses duly wired and ferruled [iv] MCCB of suitable rating with overload and short circuit protections [d] Microprocessor based generator set monitoring and control system including an intuitive operator interface that allows for complete generator set control as well as system metering, fault annunciation, configuration and diagnostics, LED backlit LCD display with tactile feel soft-switches & generator set status LED lamps, remote START-STOP [e] Engine Metering: Oil pressure, engine temperature, starting battery voltage, engine running hours [f] AC Alternator Metering: L-L voltage and L-N voltage, current (phase and total), kVA (phase and total) and frequency [g] Engine Protection: Low lube oil pressure, high/low coolant temperature, battery over/under/weak volts, fail to crank/start, sensor failure, cranking lockout, low fuel level [h] AC Alternator Protection: Over/under voltage, over/under frequency, loss of AC sensing. [i] Data Logging: Engine hours, control hours and upto 5 recent fault codes [j] Configurable glow plug control [k] 24 V DC operation
[l] Silencer: Critical grade silencer suitably optimized to meet stringent noise emission standards laid down by MoEF / CPCB [m] Mounting Arrangement: Engine and alternator are mounted on a common MS fabricated base frame with AVM pads. [n] Base frame with integral fuel tank is provided with drain plug, air vent, inlet and outlet connection, level indicator and provision for cleaning (h) Civil works:- All civil works related to foundation, installation of panel and equipment & depth of foundation shall be minimum 300mm with ant vibration pads, or as recommended by manufacturers. Cable from DG set to AMF panel, AMF panel to main panel will be measured under relevant schedule. Note:-The fuel for final testing of 12 hours shall be supplied by the contractor and cost deemed to be included in the above offer. All other necessary equipments like resistance load strip heater of suitable capacity/rating and any other items required for final testing shall be provided by the contractor without any extra cost to department.
M&L for Manually operated sheet steel enclosed on load mannual Changeover Switchof range Capacity 400Amps,415V,Three phase+neutral with Black handle padlockable in 0-I-li position, 2 external earthing points on each side, Door locking system allows opening of door only in off position, Coating of epoxy polyester powder, removable plate top & bottom, Door with solid hinges, Suitable for horizontal as well as vertical mounting all as directed. Make: L&T Cat No CO44000OOOO/ Havells/ ABB
M&L for Manually operated sheet steel enclosed on load mannual Changeover Switchof range Capacity 250Amps,415V,Three phase+neutral with Black handle padlockable in 0-I-li position, 2 external earthing points on each side, Door locking system allows opening of door only in off position, Coating of epoxy polyester powder, removable plate top & bottom, Door with solid hinges, Suitable for horizontal as well as vertical mounting all as directed. Make: L&T Cat No CO32500OOOO/ Havells/ ABB
M&L for Manually operated sheet steel enclosed on load mannual Changeover Switchof range Capacity 630Amps,415V,Three phase+neutral with Black handle padlockable in 0-I-li position, 2 external earthing points on each side, Door locking system allows opening of door only in off position, Coating of epoxy polyester powder, removable plate top & bottom, Door with solid hinges, Suitable for horizontal as well as vertical mounting all as directed. Make: L&T Cat No CO46300OOOO/ Havells/ ABB
"ROAD AND PATHWAYS"
Providing and laying 150mm thick Dry lean concrete (DLC) of compressive strength not less than 10 Mpa at 7 days for each consecutive group of 5 cubes or in dual strength of cube shall not be less than 7.5 Mpa at 7 days using table 600-1 Mpa for grading of aggregate, minimum cement content shall not be less than 150 kg/cum as per MORTH>IRC specification 49 including spreading and compacting by using mechanical vibratory roller of capacity 8 to 12 tonnes and testing as per IS complete all as specified and directed.
"EXTERNAL WATER SUPPLY"
Supply, installation, testing and commissioning of end-suction & top-discharge, non-self-priming, single-stage, centrifugal volute type pump having cast iron casing, enclosed type dynamically balanced phosphor-bronze/SS impeller, high tensile steel shaft, carbon steel stuffing box (sealed by mechanical seal), deep groove ball bearings, TEFC squirrel cage induction motor having IE- 3 efficiency, conforming to IS: 12615- 2018 at 2900 RPM speed star/delta starter panel, base plate, mounting channel frame, accessories and fittings, viz. mechanical seal, pressure gauges, thermometers, drains, coupling, coupling guard, vibration isolation arrangement by means of spring/rubber type mounting suitable for operation on 3- Phase, 415 V ± 10%, 50 Hz AC supply.
Horizontal End Suction Long Coupled type pump with insulation suitable for 700 LPM water flow rate at 125 m head for domestic water supply. [2 W + 1 S]
Horizontal End Suction Long Coupled type pump with insulation suitable for 300 LPM water flow rate at 125 m head for flushing water supply. [2 W + 1 S]
Supply, installation, testing and commissioning of PN 1.6 rated CI 'Y' -type strainer for suction conforming to IS: 907- 1984 with SS filter screen and flange drilling standard end connection conforming to IS: 1538- 1993 and necessary accessories for suction side of fire pumps all complete as specified and directed.
Supply, installation, testing and commissioning of factory made, CPRI type tested, indoor cubical compartmental type WATER SUPPLY PANEL of suitable size, conforming to IEC 61439-1 & 2 and IEC 61641, having both sides openable with hinged double doors and locking arrangement, IP 43 protection made out of 2.0 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labelling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel vitreous enamelled (white) with letters, figures and conventional skull and bones in signal red colour suitable for 3- Phase, 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length and size, including fixing lugs, bolts, screws, etc. complete all as specified and directed by engineer-in-charge. Make: L & T, Schneider, Siemens, ABB
The Water Supply Panel shall comprise of the following: [A] BUSBAR CHAMBER [i] 01 Set (3L + N) of copper busbar of rated capacity 400 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection [B] INCOMING [i] 250 A, 415 V, Ics = 100% Icu = 36 kA, 50 Hz FP MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (Ready, Overload and pre-alarm & Overload), etc.- 01 Nos. [iii] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 07 Nos. [iv] LED phase indicators (Red, Yellow, Blue)- 01 Set
[iii] 32 A, 415 V, Ics = 100% Icu = 36 kA, 50 Hz FP MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (Ready, Overload and pre-alarm & Overload), etc.- 01 Nos. [for Area Lighting DB] [iv] 32 A, 415 V, Ics = 100% Icu = 10 kA, 50 Hz DP MCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (Ready, Overload and pre-alarm & Overload), etc.- 01 Nos. [for Pump room DB] [v] LED phase indicators (Red, Yellow, Blue)- 07 Set [vi] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 07 Nos. NOTES: [i] The Panel shall be completely Ethernet communication ready to communicate with Energy Management System. [ii] 06 Nos. of ON / OFF / TRIP status and operations counters as well as meters shall be wired to Ethernet gateway part of the Panel.
Supply, installation, testing and commissioning of Water Level Controller, one/two level detection of water in tank, Draining & filling for monitoring of two tanks, Supports upto 1000 m length cable for longer distance probe sensing, Adjustable sensitivity of water from 1K to 200K ohm, Manual Start Switch to allow manual pump start for filling while taking care of dry run condition and overfill conditions all complete as specified and directed.
M & L for ISI marked 1.1 kV grade 2 core 1.5 mm² copper conductor, XLPE insulated armoured cables, conforming to IS: 7098 (Part 1)- 1988 having stranded copper compact shaped conductor as per Cl. 2, IS: 8130- 1984, PVC inner sheath, single armouring of galvanized steel strip/wire and PVC Type ST- 2 outer sheath conforming to IS: 5831- 1984, including termination complete as specified and directed.
"EXTERNAL ELECTRIC SUPPLY"
MAIN UTILITIES PANEL
Supply, installation, testing and commissioning of factory made, CPRI type tested, indoor cubical compartmental type MAIN UTILITIES PANEL of suitable size, conforming to IEC 61439-1 & 2 and IEC 61641, having both sides openable with hinged double doors and locking arrangement, IP 43 protection made out of 2.0 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labelling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel vitreous enamelled (white) with letters, figures and conventional skull and bones in signal red colour suitable for 3- Phase, 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length and size, including fixing lugs, bolts, screws, etc. complete all as specified and directed by engineer-in-charge. Make: L & T, Schneider, Siemens, ABB
[B] OUTGOING [i] 630 A, 415 V, Ics = 100% Icu = 50 kA, 50 Hz FP MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (Ready, Overload and pre-alarm & Overload), etc.- 01 Nos. [for Firefighting Panel] [ii] 400 A, 415 V, Ics = 100% Icu = 50 kA, 50 Hz FP MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (Ready, Overload and pre-alarm & Overload), etc.- 02 Nos. [Block Utilities Panel] [iii] 250 A, 415 V, Ics = 100% Icu = 50 kA, 50 Hz FP MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (Ready, Overload and pre-alarm & Overload), etc.- 01 Nos. [for Water Supply Panel] [iv] LED phase indicators (Red, Yellow, Blue)- 04 Set [v] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 04 Nos.
NOTES: [i] The Panel shall be completely Ethernet communication ready to communicate with Energy Management System. [ii] 06 Nos. of ON / OFF / TRIP status and operations counters as well as meters shall be wired to Ethernet gateway part of the Panel. [iii] The bidder shall furnish dimensional drawings of the items offered, indicating all the fittings, dimensional tolerances, typical GADs, etc. with details of insulation at each point and core construction, etc. for approval of the Garrison Engineer.
BLOCK UTILITIES PANEL
Supply, installation, testing and commissioning of factory made, CPRI type tested, indoor cubical compartmental type BLOCK UTILITIES PANEL of suitable size, conforming to IEC 61439-1 & 2 and IEC 61641, having both sides openable with hinged double doors and locking arrangement, IP 43 protection made out of 2.0 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labelling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel vitreous enamelled (white) with letters, figures and conventional skull and bones in signal red colour suitable for 3- Phase, 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length and size, including fixing lugs, bolts, screws, etc. complete all as specified and directed by engineer-in-charge. Make: L & T, Schneider, Siemens, ABB
The Block Utilities Panel shall comprise of the following: [A] BUSBAR CHAMBER [i] 01 Set (3L + N) of copper busbar of rated capacity 630 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection [B] INCOMING/OUTGOING [i] 400 A, 415 V, Ics = 100% Icu = 50 kA, 50 Hz FP MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (Ready, Overload and pre-alarm & Overload) etc.- 01 Nos. [ii] 400 A (J Frame), 4P, 7000 Series ATS with overlapping neutral with a WCR of 36 kA for 3 cycles, in open frame (w/o enclosure) [iii] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 07 Nos. [iv] LED phase indicators (Red, Yellow, Blue)- 07 Set
NOTES: [i] The Panel shall be completely Ethernet communication ready to communicate with Energy Management System. [ii] 06 Nos. of ON / OFF / TRIP status and operations counters as well as meters shall be wired to Ethernet gateway part of the Panel. [iii] The bidder shall furnish dimensional drawings of the items offered, indicating all the fittings, dimensional tolerances, typical GADs, etc. with details of insulation at each point and core construction, etc. for approval of the Garrison Engineer.
ROOF PANEL
Supply, installation, testing and commissioning of factory made, CPRI type tested, indoor cubical compartmental type ROOF PANEL of suitable size, conforming to IEC 61439-1 & 2 and IEC 61641, having both sides openable with hinged double doors and locking arrangement, IP 43 protection made out of 2.0 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labelling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel vitreous enamelled (white) with letters, figures and conventional skull and bones in signal red colour suitable for 3- Phase, 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length and size, including fixing lugs, bolts, screws, etc. complete all as specified and directed by engineer-in-charge. Make: L & T, Schneider, Siemens, ABB
The Roof Panel shall comprise of the following: [A] BUSBAR CHAMBER [i] 01 Set (3L + N) of copper busbar of rated capacity 320 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection [B] INCOMING [i] 250 A, 415 V, Ics = 100% Icu = 36 kA, 50 Hz FP MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (Ready, Overload and pre-alarm & Overload), etc.- 01 Nos. [ii] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 01 Nos. [iii] LED phase indicators (Red, Yellow, Blue)- 01 Set
[B] OUTGOING [i] 63 A, 415 V, Ics = 100% Icu = 36 kA, 50 Hz FP MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (ready, overload and pre-alarm & overload), etc.- 09 Nos. [for elevator, booster pump & staircase pressurization] [ii] 32 A, 10 kA, 230 V, 50 Hz, SPN MCB- 03 Nos. [iii] LED phase indicators (Red, Yellow, Blue)- 09 Set [iv] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 09 Nos. NOTES: [i] The Panel shall be completely Ethernet communication ready to communicate with Energy Management System. [ii] 06 Nos. of ON / OFF / TRIP status and operations counters as well as meters shall be wired to Ethernet gateway part of the Panel. [iii] The bidder shall furnish dimensional drawings of the items offered, indicating all the fittings, dimensional tolerances, typical GADs, etc. with details of insulation at each point and core construction, etc. for approval of the Garrison Engineer.
M & L for 1.1 kV grade copper conductor, XLPE insulated armoured cable conforming to IS 7098 (Part 1): 1988, having stranded copper compact shaped conductors as per Cl. 2 of IS 8130: 1984, PVC inner sheath, single armouring of galvanised steel strip/wire and PVC Type ST-2 outer sheath conforming to IS 5831: 1984, including necessary clamping / dressing with cable ties and termination complete all as specified and directed by engineer-in-charge.
3.5 core, 300 mm²
3.5 core, 185 mm²
S&F LED streetlight having high efficiency long life LED module with SMD LED package mounted on MCPCB with high LED efficiency of > 100 lm/W, integral SMPS based constant current electronic LED driver with THD < 10%, surge voltage protection and other safety tests as per IS 15885 (Part- 2/Sec-13): 2012, IP 66 protection, polycarbonate cover with integrated lens housed in pressure die-cast aluminium alloy heat sink for effective thermal management, separate optical and control gear compartment & top opening for easy maintenance, suitable for side side entry, pole mounting with bracket arm OD 35 mm to 42 mm, including necessary electrical connection to the fixture with 3 core flexible Cu conductor cable of appropriate sizer and 1.5 m long bracket having 40 mm diameter light grade GI pipe, nuts, bolts, washers, GI clamps with two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed by engineer-in-charge. Make: BAJAJ, Philips, Havells
S & F weather- proof PVC junction box of size 250 mm x 200 mm x 100 mm, having IP 65 protection for outdoor installation fixed with 4 way bakelite cable terminals including 03 Nos. of polymide gland with check nuts fixed on poles with flat aluminium clamps of size 20 mm x 3 mm, nuts, bolts, washers, etc. complete all as specified and as directed by engineer- in- charge. Make: Sintex, Hensel, HPL
M & L for hot dipped galvanized iron octagonal pole of 6mtr height, minimum galvanizing of 70 micron, top -70mm dia , bottom 130 mm dia and 3 mm sheet thickness in single section with joints with box plate of minimum dimensions 200mm x200mmx 12mm , foundation bolts, single area GI bracket of 900-1000 mm for mounting the light fitting at an angle of 120°,Bakelite sheet with one 6A SP MCB and 16 mm stud type connector (4 Nos) inside the pole at door opening for cable connection, common templates minimum 1 for each 15 poles, all fixed and bolted on suitable PCC pedestal as per manufactures recommendation & specifications and all as directed. Make of poles shall be Bajaj/ Crompton/ Subham/Jindal.
Supply, installation, testing and commissioning of intelligent street light control (ATSC) suitable for 6 kW maximum load, wall/pole mounted, having built-in networking support, built-in astronomical timer, 32 A TP contactor, 40 A TPN MCB housed in 3.15 mm thick powder CRCA sheet housing all complete as specified and directed by engineer- in- charge. Make: Havells, HPL, Insu
COMPREHENSIVE MAINTENANCE OF LIFTS
Comprehensive maintenance and repair of fully automatic electrically operated passenger lift of any make and 16 Passenger capacity lift installed against Sch 'A' BOQ Item No. 20.01, herein before in building (G+32), (Total 08 Lifts) comprising of all devices and accessories through out 12 months on all days including holidays for period of 04 years after expiry of defects liability period as shown below and all as specified and directed by GE.
(a) 1st year after expiry of defects liability period
(b) 2nd year after expiry of defects liability period
(c) 3rd year after expiry of defects liability period
(d) 4th year after expiry of defects liability period
Comprehensive maintenance and repair of fully automatic electrically operated passenger lift of any make and 13 Passenger capacity lift installed against Sch 'A' BOQ Item No. 20.05 & 20.09, herein before in building (G+32), (Total 04 Lifts) comprising of all devices and accessories through out 12 months on all days including holidays for period of 04 years after expiry of defects liability period as shown below and all as specified and directed by GE.
(a) 1st year after expiry of defects liability period
(b) 2nd year after expiry of defects liability period
(c) 3rd year after expiry of defects liability period
(d) 4th year after expiry of defects liability period
IRON TRIANGLE LIMITED
VISHAL INFRASTRUCTURE LTD
Som Projects Pvt Ltd
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
Download all tender documents and submit your bid