Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹33.9 CrAccepted-AOC | ₹33.9 Cr | L1 | Accepted-AOC Lowest Bidder |
| 2 | L2₹38.6 CrRejected-Finance | ₹38.6 Cr | L2 | Rejected-Finance Other than lowest bidder |
| 3 | L3₹46.5 CrRejected-Finance | ₹46.5 Cr | L3 | Rejected-Finance Other than lowest bidder |
| 4 | L4₹47.7 CrRejected-Finance | ₹47.7 Cr | L4 | Rejected-Finance Other than lowest bidder |
| 5 | L5₹49.7 CrRejected-Finance | ₹49.7 Cr | L5 | Rejected-Finance Other than lowest bidder |
Tender Value
Refer Docs
EMD Value
₹15 L
Closing Date
28 Dec 2021, 6:00 pmClosed
Chief Engineer Udhampur Zone
HQ Chief Engineer Udhampur Zone PIN - 900386 C/o 56 APO
PROVN OF TECH ACCN FOR 45 BEDDED HOSPITAL AT POONCH
2021_MES_475742_1
87878-A/E8
Open Tender
Civil Works
761 days
Poonch
Please refer Tender documents.
10 documents required · 10 mandatory
₹3,000
GE 881 EWS
₹15 L
Yes
26 Feb 2022
17 Sept 2021
1 Jan 2022
17 Sept 2021
28 Dec 2021
11 Dec 2021
Amount
Total Amount of Sch 'A' Part - I (Sec A) (Builiding Work)
Sch 'A' Part - I (Sec B) (Building Works) Note : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
Construction of Septic Tanks, exc, in ordinary soil, foundation in PCC 1:2:4, brick work in CM 1:4, Rcc slab covers including RCC precast manhole covers having 6mm plate embedded all around/fiber reinforced cover with angle iron frame vent shaft and sludge chamber etc. complete for 100 users, complete all as speicifed and shown on drawings and directed.
Construction of Septic Tanks, exc, in ordinary soil, foundation in PCC 1:2:4, brick work in CM 1:4, Rcc slab covers including RCC precast manhole covers having 6mm plate embedded all around/fiber reinforced cover with angle iron frame vent shaft and sludge chamber etc. complete for 10 users , complete all as speicifed and shown on drawings and directed.
Construction of Soakage wells exc, in ordinary soil, foundation in PCC 1:3:6, wells of honey combed and solid in M-25 concrete, including intercepting chamber, screen chamber, brick work in CM, RCC cover slab in M-25/RR masonary/filling with brick bats, complete of size 3.6m dia x 4.50m deep , complete all as speicifed and shown on drawings and directed.
Total Amount of Sch 'A' Part - II (Sec A) (Internal Eletcrification)
Sch 'A' Part - II (SEC-B ) (INTERNAL ELECTRIC SUPPLY ) Note : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
Supply and Fixing of Stove enamelled, blank, Rigid steel conduit, welded, conduit inclusive of boxes (junction/terminal) , tees, bends,elbows, reducers,flexible GI conduit (upto 1.5m per point), bell mouth tube ends and fixing accessories such as couplers, locknuts, saddles,pipe hooks etc. Complete in all respect as specified and directed.
20mm Dia , 1.6mm thickness
25mm Dia , 1.6mm thickness
32mm Dia , 1.6mm thickness
Supply & Fixing 24W LED Recess Mounted 2'x2' Light Fixture complete with all accessories pre-wired and including connecting up with flexible copper conductor wire with suitable size, complete all as specified and directed.
Supply & Fixing 15W LED, SURFACE MOUNTED ROUND Light fixture complete with all accessories pre-wired and including connecting up with flexible copper conductor wire with suitable size, complete in all respect as specified and directed.
Supply & Fixing 20W LED Tube ,Surface mounted light fixture, complete with all accessories internally prewired and including connecting up with flexible copper conductor wire with suitable size, complete all as specified and directed.
Supply & Fixing 10W LED Recess Mounted Round Light Fixture complete with all accessories pre wired and including connecting up with flexible copper conductor wire with suitable size, complete all as specified and directed.
Supply & Fixing 15W LED Recess Mounted Round Light Fixture complete with all accessories pre wired and including connecting up with flexible copper conductor wire with suitable size, complete all as specified and directed.
Supply & Fixing 24W LED Recess Mounted Round Light Fixture complete with all accessories pre wired and including connecting up with flexible cable , complete all as specified and directed.
Supply & Fixing 10W LED BULK HEAD LIGHT, complete all as specified and directed.
Supply & Fixing 5W LED Mirror Light Fixture complete with all accessories pre-wired and including connecting up with flexible copper conductor wire with suitable size, complete all as specified and directed.
Supply & Fixing 7W Foot LED Light Recess Mounted complete with all accessories pre-wired and including connecting up with flexible copper conductor wire with suitable size, complete all as specified and directed.
Supply & Fixing 15-20W LED Bracket Light Surface Mounted complete with all accessories pre-wiredand including connecting up with flexible copper conductor wire with suitable size, complete in all respect as specified and directed.
Supply and fixing of LED Street light Fitting having die cast aluminium body and diffuser with driver set suitable for 60 watt to 70 Watt. Confirming to IP 66 protection complete in all respect including accessories. , complete all as specified and directed.
Supply & Fixing 0.5W LED Red/Green Bulb Surface Mounted complete with all accessories pre-wired and including connecting up with flexible copper conductor wire with suitable size, complete all as specified and directed.
Supplying, installation, testing and commissioning of Fire Exit Sign (RED illuminated) with Double sided LED signage ,with upto 2 Hrs Battery Backup, complete in all respect as specified and directed.
Supply and fix fans ceiling complete with electronic type regulator and accessories 230 V,1200 mm sweep. BEE 5 star rated and including connecting up with flexible copper cable conductor with suitable size, complete all as specified and directed.
Supply & Fixing WALL FAN ( 300MM ). complete with all accessories pre-wired and including connecting up with twin core twisted flexible copper conductor cable with suitable size, complete all as specified and directed.
Supply and fix exhaust fans AC single phase 230/ 240 V of size 300 mm sweep with louver and including connecting up with flexible copper cable conductor with suitable size, complete all as specified and directed.
Supplying and Fixing 63 Amp 4P, 415V MCB 10 kA Curve C, complete all as specified and directed.
Supplying and Fixing 40 Amp 4P, 415V MCB 10 kA Curve C, complete all as specified and directed.
Supplying and Fixing 40 Amp DP, 240V MCB 10 kA Curve C, complete all as specified and directed.
Supplying and Fixing MCB SP 6 to 25 Amps 240 Volts 'C' curve, complete all as specified and directed.
Supply and fix FLAME PROOF fans ceiling complete with accessories 230 V,1200 mm sweep. BEE 5 star rated, complete all as specified and directed.
Supply and fix FLAME PROOF Fan Regulator, complete all as specified and directed.
Supply and fix Flame Proof Exhaust fans AC single phase 230/ 240 V of size 300 mm sweep with louver , complete all as specified and directed.
Supply & Fixing Flame Proof switch 1 way 6A, 1 module, complete all as specified and directed.
Supply & Fixing Flame Proof switch 1 way 16A, 1 module, complete all as specified and directed.
Supply & Fixing Flame Proof Socket, 6A - 2/3 pin combined 2 module,, complete all as specified and directed.
Supply & Fixing Flame Proof socket outlet multipurpose 3 pin, 15 Amps and one pin, 5 Amp controlled by one switch, complete all as specified and directed.
Supply & Fixing FLAME PROOF Triple pole and earth encolsure with a three pin and earth plug with socket complete with one triple pole MCB of 32Amp, complete all as specified and directed.
Supplying and fixing of PVC conduit surface/ recess type ISI marked exclusive of boxes (junction/ terminal) but inclusive of all tees, bends, elbows, reducers, fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc. (For DATA, TELEPHONE), complete all as specified and directed.
20mm Dia , 1.6mm thickness
25mm Dia , 1.6mm thickness
32mm Dia , 1.6mm thickness
Supplying and fixing following modular switch/ socket on the existing modular plate and switch box including connections but excluding modular plate etc. , complete all as specified and directed.
Telephone socket outlet
TV socket outlet
Data / RJ 45 socket outlet
Supplying and fixing following size/ modules, GI box alongwith modular base and cover plate for modular switches in recess etc. as required, complete all as specified and directed.
1 or 2 Module (75mmX75mm)
3 Module (100mmX75mm)
Supplying and drawing 1 run of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel conduit as required. (For Data and CCTV), complete all as specified and directed.
Supplying and fixing following size Data Switch or Hub switch, complete all as specified and directed.
Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor, unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required (2 Pair), complete all as specified and directed.
Supply and installation of KRONE connector type main telephone tag block of following sizes in sheet metal enclosure of suitable dimensions fabricated out of 16 SWG sheet steel with castle key lock, hinged type cover including termination of telephone cables, making connections, painting of box etc., complete all as specified and directed. as required:-
30 Pairs
20 Pairs
Supplying, laying, testing and terminating with soldered terminals on both ends for 0.5 mm dia PVC insulated, PVC sheathed armoured annealed tinned copper conductor, telephone Cables with GI wire / strip armouring generally conforming to ITD specification S/WS-113C and S/WS-114 on surface / recessed / false ceiling / cable Tray / GI pipe / Hume pipe etc. , complete all as specified and directed. as required:-
20 Pairs
30 Pairs
Supply, installation ,testing & commisioning of EPABX System configured for 6 lines and 110 extensions, and can be expanded to a maximum configuration of 10 lines and 130 extensions, complete all as specified and directed.
Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/ PVC conduit as required., complete all as specified and directed.
Supply, installation, testing and commissioning of Bed call Unit with NURSE CALL, CODE BLUE and Additional Help complete with corded handset,with CLEAR-suitable for single bed, complete all as specified and directed. Note: The rate shall also include cost of modular metal box for fixing the Bed calling unit, complete in all respect as specified and directed.
Supply, installation, testing and commissioning of BED INDICATOR for single Bed - Composite Indicates various Call types and Status. The rate shall include cost of all necessary accessories as required, complete all as specified and directed.
Supply, installation, testing and commissioning of DOOR/ CORRIDOR INDICATOR - Composite Indicates various Call types and Status. The rate shall include cost of all necessary accessories as required, complete all as specified and directed.
Supply, installation, testing and commissioning of Bathroom (Emergency) Pull Cord Modules CALLING Unit - TOILET for SINGLE Room., complete all as specified and directed. Note: The rate shall also include cost of modular metal box for fixing the toilet calling unit.
Supply, installation, testing and commissioning of Bathroom/TOILET (Emergency) Pull Cord Modules CALLING Unit - SHARED TOILET for Multiple beds. , complete all as specified and directed. Note : The rate shall also include cost of modular metal box for fixing the toilet calling unit
Supply, installation, testing and commissioning of nurse call processor which shall communicate to min. 6 Nos of calling units per loop and shall be expandable with extenders upto 16 calling units. The NCP shall have voice module, call forwarding, call escallation and sms facility. The enclosure shall be made out of Aluminium. Also nurse station controller should interact with supervisory controller, complete all as specified and directed.
Supply, installation, testing and commissioning of 19" LCD monitor. The rate shall include cost of all necessary accessories as required, complete all as specified and directed.
Supply, installation, testing and commissioning of supervisory controller , which can communicate to nurse station controller, comminication device with GPS modem. The supervisory controller should have call forwarding, call escalation features., complete all as specified and directed. Note : The rate shall include cost of all necessary accessories as required
Supply, installation, testing and commissioning of nurse call system software which can generate report like call density, average response time, record of escalated call calls profile etc., complete in all respect as specified and directed.
Supply, drawing and connecting of cat-6, UTP cable in existing conduit for LAN network, complete all as specified and directed.
Total Amount of Sch 'A' Part - III (Sec A) (Internal Water Supply)
Sch 'A' Part - III (SEC-B ) (INTERNALWATER SUPPLY ) Note : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
Supply and fixing PTMT bottle trap for wash basin with 25 mm minimum water seal, complete including cutting and making good the walls, wherever required , complete all as specified and directed.
Supply and fixing C.P brass towel rail complete with C.P brass brackets fixed to wooden cleats with C.P brass screws, complete all as specified and directed.
Supply and fixing uplasticised PVC connection pipe with brass unions, 45 cm length, 15 mm nominal bore, complete all as specified and directed.
Supply and fixing C.P brass angle valve 15 mm dia for basin mixer and gyser points of approved quality conforming to IS : 8931, complete all as specified and directed.
Providing and fixing toilet paper holder C.P brass, complete all as specified and directed.
Supply and fixing liquid soap container of standard shape with bracket of the same material with snap fitting approved quality and colour, complete all as specified and directed.
Supply and fixing sink cock of approved quality and colour, 15 mm nominal bore, complete all as specified and directed.
Supply and fixing CP brass Health faucet with 1.5M S.S. Flexible Tube with wall hook including screws, nut, bolts, cutting wall/floor and making good the same whatever required , complete all as specified and directed.
Supply and Fixing C.P. Brass bib cock including wall fange, connections, screws, nut, bolts, cutting wall/floor and making good the same whatever required , complete all as specified and directed.
Supply and Fixing C.P. wall mount double Robe Hook fixed to wooden cleats with C.P. brass screws, cutting wall/floor and making good the same whatever required , complete all as specified and directed.
Supply and fixing push fit type WC pan connector with factory supplied spring loaded seal guard oincluding bush/adaptor for use with C.I. Pipe as supplied with the pan connector , complete all as specified and directed.
Supply and Fixing Over head shower 100 mm dia with Shower Arm complete as per instructions of the engineer-incharge, complete all as specified and directed.
Supply and Fixing shower mixture with complete as per instructions of the engineer-incharge, complete all as specified and directed.
Supply and Fixing Basin mixture with complete as per instructions of the engineer-incharge, complete all as specified and directed.
Supply and Fixing Sink mixture with complete as per instructions of the engineer-incharge, complete all as specified and directed.
Total Amount of Sch 'A' Part - IV (Sec A) (Plumbing Works)
Sch 'A' Part - IV (SEC-B ) (PLUMBING WORKS ) Note : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
Supply and fixing sound clean out cap plug (FCO/COP) for celaning of same materials (POLO KAL NG) PP 110 mm dia Pipe, complete all as specified and directed.
Supply and fixing sound insulated pp piping system as per ON EN 1451-Part 1-6 and EN 12056 Part 1-5 with 3 layer pipe made of PP-C + PP-MV + PP-C in Blue Ral 5014 (halogen and calcium free) colour, push-fit type, food safe, having high impact and stiffness, offering sound levels of not more than 22 dBA at a flow rate of 4 l/s and having pipe ring stiffness as per 1S0/DIS 9969 and tightness as per EN 1277/B and C and DIN 19560, with all necessary fittings in blue colour, fitted with factory fitted lip ring PP 110 mm dia Pipes., complete all as specified and directed.
Supply and fixing sound insulated pp piping system as per ON EN 1451-Part 1-6 and EN 12056 Part 1-5 with 3 layer pipe made of PP-C + PP-MV + PP-C in Blue Ral 5014 (halogen and calcium free) colour, push-fit type, food safe, having high impact and stiffness, offering sound levels of not more than 22 dBA at a flow rate of 4 l/s and having pipe ring stiffness as per 1S0/DIS 9969 and tightness as per EN 1277/B and C and DIN 19560, with all necessary fittings in blue colour, fitted with factory fitted lip ring PP 40/50 mm OD Pipes . (For Indirect waste/ Wash Basin/Floor Drain ), complete all as specified and directed.
Supply and fixing Floor Trap with minimum 50mm water seal with rubber seal on inlet to push fit hopper for indirect waste connections 110 mm inlet and 110 mm outlet Long height , complete all as specified and directed..
Supply and fixing 110 x 50mm Floor Drain / Plain Floor trap complete , complete all as specified and directed.
Supply and fixing CP Grating over Floor trap and floor Drain 125 x 125 , complete all as specified and directed.
Material and labour for concrete bed to drain pipes including packing under, and haunching against the sides of pipes after they are laid and tested. Cement concrete 1:4:8 type D-2 PP 40/50 mm dia Pipes, complete all as specified and directed.
Supply and fixing clean out piece with all necessary fittings , fitted with factory fitted lip ring .material PP 110 mm dia, complete all as specified and directed.
Total Amount of Sch 'A' Part - V (Site clearnace works)
Total Amount of Sch 'A' Part - VI (Sewage Disposal Work)
Total Amount of Sch 'A' Part - VII (Area Drainage Work)
Total Amount of Sch 'A' Part - VIII (Protective Work)
Total Amount of Sch 'A' Part - IX (Road, Path, Culvert and Hard Standing Work)
Total Amount of Sch 'A' Part - X (Fencing and Steel gate works)
Total Amount of Sch 'A' Part - XI (Sec A) (Deep Freezer)
Sch 'A' Part - XI (Sec B) (DEEP FREEZER) Note : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
Supply and Fixing of Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type and designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of +/- 2.5% and of capacity 2 KV, complete all as specified and directed.
Total Amount of Sch 'A' Part - XII (Sec A) (External Electrification)
PART- XII(SEC-B) : LIST OF WORKS AND PRICES FOR EXTERNAL ELECTRIFICATION Note : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
Supply, laying and testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 11000 volts grade, of size 3 core 185 sq mm., complete all as specified and directed. Note :- Under ground cable includes earth Work, sand cushioning, brick or PCC/RCC covering, light Grade, route cable indicator necessary,testing etc. Nothing extra is permissible on this account.
Supply, installation, testing and commissioning of 500KVA Transformer 11/0.433KV 3Phase, 50 HZ, ONAN cooled oil immersed with +5% to -5% taps on HV in steps of 1.56 % through OFF Load circuit tap links, Copper wound indoor type with oil as per IS, Cable termination BOX on both HT side and LT side. The transformer shall be complete with all accessories covered in specification laid with tender doc with making all connections and carrying out all routine tests before commissioning, complete all as specified and directed. Note - Construction of suitable Platform for transformer of size 4m x 3m x 1.2m high (external size) from ground level and 30cm below GL, with burnt brick construction in wall and steps, XPM fencing with angle iron post including gate with locking arrangement, PCC (1:5:10) type E-2 in foundation, brickwork in cement mortar (1:4), 10mm thick rendering in cement mortar (1:4) to walls, 50mm thick PCC (1:2:4) type B-1 (using 20mm graded crushed stone aggregate) as in flooring, 40mm thick PCC (1:2:4) type B-1 on steps, painting to XPM fencing with two coats of synthetic enamel paint over a coat of red oxide primer, complete all as specified and shown in drawings.
Supply, installation, testing and commissioning of 400KVA Transformer 11/0.433KV 3Phase, 50 HZ, ONAN cooled oil immersed with +5% to -5% taps on HV in steps of 1.56 % through OFF Load circuit tap links, Copper wound indoor type with oil as per IS, Cable termination BOX on both HT side and LT side. The transformer shall be complete with all accessories covered in specification laid with tender doc with making Note - Construction of suitable Platform for transformer of size 4m x 3m x 1.2m high (external size) from ground level and 30cm below GL, with burnt brick construction in wall and steps, XPM fencing with angle iron post including gate with locking arrangement, PCC (1:5:10) type E-2 in foundation, brickwork in cement mortar (1:4), 10mm thick rendering in cement mortar (1:4) to walls, 50mm thick PCC (1:2:4) type B-1 (using 20mm graded crushed stone aggregate) as in flooring, 40mm thick PCC (1:2:4) type B-1 on steps, painting to XPM fencing with two coats of synthetic enamel paint over a coat of red oxide primer, complete all as specified and shown in drawings. all connections and carrying out all routine tests before commissioning, complete all as specified and directed.
Supply and fix servo Voltage stabilizer for automatic operation, three phase, naturally oil cooled, indoor type, copper winding and designed for input variation between 300 V to 480 V with output voltage stabilized at 415 with accuracy ± 2.5% and speed of correction 8 Volts per second and of capacity 500 KVA, complete all as specified and directed. Note: The unit rate includes construction of platform of suitable size voltage stabilizer (platform shall be made out of brick masonry one feet below ground level and one feet above ground level, hallow space to filled by PCC 1:3:6 type C-2 and including plastering, floor of platform etc.)
Supply and fix servo Voltage stabilizer for automatic operation, three phase, naturally oil cooled, indoor type, copper winding and designed for input variation between 300 V to 480 V with output voltage stabilized at 415 with accuracy ± 2.5% and speed of correction 8 Volts per second and of capacity 400 KVA, complete all as specified and directed. Note: The unit rate includes construction of platform of suitable size voltage stabilizer (platform shall be made out of brick masonry one feet below ground level and one feet above ground level, hallow space to filled by PCC 1:3:6 type C-2 and including plastering, floor of platform etc.)
Supply, installation, testing and commissioning of M.V. PANEL BOARDS with the following specifications, complete in all respect as specifed and directed. NOTE2: All Panels SLD should be referred . MAIN LT PANEL (INDOOR DUTY) This will be floor mounted with MS stand of 300mm height, free standing, Indoor duty, dust proof, vermin proof, front operated,front/ back access, electrical panel fabricated as per specifications laid in this document and will be complete with the extendable main and auxiliary bus bars, interconnection, earth bus and will be powder coated finish with 70 micron thickness. INCOMINGS: INCOMER-1 (500kVA Transformer) Section One number incomer breaker 800A 4P MDO ACB-1 (Ics =50kA) with microprocessor based releases for over current, short ckt , earth fault with time delay from transformer etc. complete in all respects as mentioned in specifications below. Digital flush type class-1.0 accuracy multifunction meter showing V, A, PF, KVAR , KWH, Frequency / Harmonics etc. with 3 Nos. current transformers of 800/5 ratio, 15 VA Class 1.0 metering. 1 Number phase to phase, phase to neutral and neutral to earth 7 mode spark gap surge suppressor for 200KA with appropriate fuses, 1 Number 3 phase voltage monitoring relay cum phase sequence meter Red/Green/Amber ON/OFF and TRIP indicating lamps with 2A SP MCB backup protection. 1 set of three phase indicating lamps along with 2A SP MCB backup protection. Separate set of Class 5P10, 15VA CT of suitable capacity for protection/Capacitor Panel for APFC Relay Control MCB, control terminalsand wiring as required.
Supply, installation, testing and commissioning of 800A 4P BY PASS CHANGE OVER SWITCH -1 with the following specifications, complete in all respect as specifed and directed. One number of 800A 4P BY PASS COS followed by 500kVA transformer, is used to by pass the 500kVA Servo Stabilizer power in case of fault/maintenace . It should be complete with indicating lamp for Servo/By Pass with protection 2A MCB complete in all respect. Bus Bar-1 : High conductivity Aluminium three phase and neutral busbars rated at 415V, 50 Hz., 1200 Amps, 50kA, insulated with heat shrinkable coloured PVC sleeves and clip on shrouds for joints. Outgoings from Bus Bar-1 : 1 N0. 630Amp 415 volt TP MCCB Ics=36kA alongwith one ammeter and ammeter selesctor switch having matching cast resin CT's (Class-1) and rotary handle. 1 Set of ON/OFF indicating lamps AUTO TRANSFER SWITCH-1 800A 4P Auto Transfer Switch with DG AMF Logic and Manual Operation. Two Incoming supplies coming from 500kVA DG set-1 and 1200A Bus Bar-1 Indication lamp of Source-1 and 2 with 2A SP MCB backup protection complete in all respect. DG AMF LOGIC Complete AMF logic along with cranking relays to start the DG incase of power failure and DG stoping incase of power restoration and AMF shall be microprocessor based with indication for DG ON/OFF and load ON. In the case of failure of normal power supply DG to start after a prefixed time of three second on any of the following conditions : Total absence of voltage. Failure of one or two phases. Voltage below 380 volts.
After a lapse of 10-12 seconds normal power supply breaker to open and DG supply breaker to close. All auxilliaries of DG sets to run automatically. In the case of Resumption of Normal Power supply : DG breaker to open and normal power supply breaker to close after 30 sec. on resumption of normal power on the following conditions. All the three phases available at the normal supply breaker. 380-415 volts available at the normal supply breaker. DG to over run for three minutes and stop automatically. All auxiliaries to stop automatically. DG to be ready for the next operation automatically. 800A EDO ACB-2 One number incomer breaker 800A 4P EDO ACB-2 (Ics =50kA) with microprocessor based releases for over current, short ckt , earth fault with time delay from transformer etc. complete in all respects as mentioned in specifications below. Digital flush type class-1.0 accuracy multifunction meter showing V, A, PF, KVAR , KWH, Frequency / Harmonics etc. with 3 Nos. current transformers of 800/5 ratio, 15 VA Class 1.0 metering. Red/Green/Amber ON/OFF and TRIP indicating lamps with 2A SP MCB backup protection. 1 set of three phase indicating lamps along with 2A SP MCB backup protection. Control MCB, control terminalsand wiring as required. Bus Bar-3 : High conductivity Aluminium three phase and neutral busbars rated at 415V, 50 Hz., 1200 Amps, 50kA, insulated with heat shrinkable coloured PVC sleeves and clip on shrouds for joints.
Outgoings from Bus Bar-3 : All outgoing feeders shall be provided with two set of 2A SP MCB backup protection and 1 Set of ON/OFF indicating lamps . All Outgoing MCCB's should have Ics=36kA 1 N0. 630Amp 415 volt 4P MCCB with rotary handle. 1 Number digital MFM (showing all V/A/F/KW/ KWHr parameters) and matching cast resin Class-1 CT's 1 N0. 100Amp 415 volt 4P MCCB with rotary handle. 1 Number digital MFM (showing all V/A/F/KW/ KWHr parameters) and matching cast resin Class-1 CT's 1 N0. 63Amp 415 volt 4P MCCB with rotary handle. 1 Number digital MFM (showing all V/A/F/KW/ KWHr parameters) and matching cast resin Class-1 CT's SPARE: 1 N0. 250Amp 415 volt 4P MCCB with rotary handle. 1 Number digital MFM (showing all V/A/F/KW/ KWHr parameters) and matching cast resin Class-1 CT's 1 N0. 160Amp 415 volt 4P MCCB with rotary handle. 1 Number digital MFM (showing all V/A/F/KW/ KWHr parameters) and matching cast resin Class-1 CT's SPACE: 1 Nos. SPACE suitable for TPN feeder for 250A 4P MCCB. INCOMER-2 (400kVA Transformer) Section One number incomer breaker 800A 4P MDO ACB-3 (Ics =50kA) with microprocessor based releases for over current, short ckt , earth fault with time delay from transformer etc. complete in all respects as mentioned in specifications below. Digital flush type class-1.0 accuracy multifunction meter showing V, A, PF, KVAR , KWH, Frequency / Harmonics etc. with 3 Nos. current transformers of 800/5 ratio, 15 VA Class 1.0 metering. 1 Number phase to phase, phase to neutral and neutral to earth 7 mode spark gap surge suppressor for 200KA with appropriate fuses,
1 Number 3 phase voltage monitoring relay cum phase sequence meter Red/Green/Amber ON/OFF and TRIP indicating lamps with 2A SP MCB backup protection. 1 set of three phase indicating lamps along with 2A SP MCB backup protection. Separate set of Class 5P10, 15VA CT of suitable capacity for protection/Capacitor Panel for APFC Relay Control MCB, control terminalsand wiring as required. 800A 4P BY PASS CHANGE OVER SWITCH -2 One number of 800A 4P BY PASS COS followed by 400kVA transformer, is used to by pass the 400kVA Servo Stabilizer power in case of fault/maintenace . It should be complete with indicating lamp for Servo/By Pass with protection 2A MCB complete in all respect. Bus Bar-2 : High conductivity Aluminium three phase and neutral busbars rated at 415V, 50 Hz., 1200 Amps, 50kA, insulated with heat shrinkable coloured PVC sleeves and clip on shrouds for joints. Outgoings from Bus Bar-2 : 1 Number 400Amp 415 volt TP MCCB Ics=36kA alongwith one ammeter and ammeter selesctor switch having matching cast resin CT's (Class-1) and rotary handle. 1 Set of ON/OFF indicating lamps 1 Number 100Amp 415 volt 4P MCCB with rotary handle. 1 Number digital MFM (showing all V/A/F/KW/ KWHr parameters) and matching cast resin Class-1 CT's AUTO TRANSFER SWITCH- 800A 4P Auto Transfer Switch with DG AMF Logic and Manual Operation. Two Incoming supplies coming from 500kVA DG set-2 and 1200A Bus Bar-2 Indication lamp of Source-1 and 2 with 2A SP MCB backup protection complete in all respect.
DG AMF LOGIC Same as in above section 800A EDO ACB-4 One number incomer breaker 800A 4P EDO ACB-4 (Ics =50kA) with microprocessor based releases for over current, short ckt , earth fault with time delay from transformer etc. complete in all respects as mentioned in specifications below. Digital flush type class-1.0 accuracy multifunction meter showing V, A, PF, KVAR , KWH, Frequency / Harmonics etc. with 3 Nos. current transformers of 800/5 ratio, 15 VA Class 1.0 metering. Red/Green/Amber ON/OFF and TRIP indicating lamps with 2A SP MCB backup protection. 1 set of three phase indicating lamps along with 2A SP MCB backup protection. Control MCB, control terminalsand wiring as required. Bus Bar-4 : High conductivity Aluminium three phase and neutral busbars rated at 415V, 50 Hz., 1200 Amps, 50kA, insulated with heat shrinkable coloured PVC sleeves and clip on shrouds for joints. Outgoings from Bus Bar-4 : All outgoing feeders shall be provided with two set of 2A SP MCB backup protection and 1 Set of ON/OFF indicating lamps . All Outgoing MCCB's should have Ics=36kA 1 N0. 250Amp 415 volt 4P MCCB with rotary handle. 1 Number digital MFM (showing all V/A/F/KW/ KWHr parameters) and matching cast resin Class-1 CT's 2 N0. 160Amp 415 volt 4P MCCB with rotary handle. 1 Number digital MFM (showing all V/A/F/KW/ KWHr parameters) and matching cast resin Class-1 CT's 3 N0. 100Amp 415 volt 4P MCCB with rotary handle. 1 Number digital MFM (showing all V/A/F/KW/ KWHr parameters) and matching cast resin Class-1 CT's
1 N0. 63Amp 415 volt 4P MCCB with rotary handle. 1 Number digital MFM (showing all V/A/F/KW/ KWHr parameters) and matching cast resin Class-1 CT's SPARE: 1 N0. 250Amp 415 volt 4P MCCB with rotary handle. 1 Number digital MFM (showing all V/A/F/KW/ KWHr parameters) and matching cast resin Class-1 CT's 1 N0. 160Amp 415 volt 4P MCCB with rotary handle. 1 Number digital MFM (showing all V/A/F/KW/ KWHr parameters) and matching cast resin Class-1 CT's SPACE: 1 Nos. SPACE suitable for TPN feeder for 250A 4P MCCB. Bus Coupler: This will have electrically operated having 800A 4P EDO ACB (Ics =50kA) with ON/OFF/TRIP indicating lights. Bus coupler shall be interlocked electrically and mechanically with two 800A EDO ACB incomers no-2,4. Interlocking shall be done to avoid parallel operation of two supply shall be on either side of coupler, Incomers can operate simultaneously with bus coupler open. Control wiring, MCB, ferruling, danger plate, name plates etc, complete all as specified and directed.
Supply, installation, testing and commissioning of 300 KVAR CAPACITOR PANEL (INDOOR DUTY) with the following specifications, complete in all respect as specifed and directed. This will be floor mounted with MS stand of 300mm height, free standing, Indoor duty, dust proof, vermin proof, front operated,front/ back access, electrical panel fabricated as per specifications laid in this document and will be complete with the extendable main and auxiliary bus bars, interconnection, earth bus and will be powder coated finish with 70 micron thickness. CAPACITOR PANEL SHALL BE 300KVAR (1X100KVAR+ 3X50KVAR + 1X15KVAR + 3X10KVAR + 1X5KVAR). THESE CAPACITOR VALUES SHOULD BE NET AT 415V AND ACCORDINGLY CAPACITORS SHALL BE DERATED AT 480V. MINIMUM 500 CFM FAN WILL BE USED FOR AIR COOLING. CAPACITOR PANEL SHALL BE EXPENDABLE TYPE. INCOMER: Supply, testing and commissioning of 300 KVAR at 480V capacitor panel having 1 Number 630Amps TP Isolator Ics=36kA as incomer. Incomer shall have 3 nos indicating lights with control MCB for incoming power, 1 Number Multifunction meter showing V/A/PF parameters with matching cast resin CT's, 3 phase 12 set automatic power factor correction relay. BUS BAR: A set of TPN Aluminium bus bar rated for 700A (after derating factor of 0.75) 3 phase 4wire, 50Hz System. The bus bar size after derating shall be equal to the ampere given in the BOQ The conductivity of bus bar shall not be less than 58% and earth bus size shall be 10% of phase bus bar. Neutral Bus Bar is 50% capacity of phases.
Supply, installation, testing and commissioning of 200 KVAR CAPACITOR PANEL (INDOOR DUTY) with the following specifications, complete in all respect as specifed and directed This will be floor mounted with MS stand of 300mm height, free standing, Indoor duty, dust proof, vermin proof, front operated,front/ back access, electrical panel fabricated as per specifications laid in this document and will be complete with the extendable main and auxiliary bus bars, interconnection, earth bus and will be powder coated finish with 70 micron thickness. CAPACITOR PANEL SHALL BE 200KVAR ( 3X50KVAR + 4X10KVAR + 2X05KVAR). THESE CAPACITOR VALUES SHOULD BE NET AT 415V AND ACCORDINGLY CAPACITORS SHALL BE DERATED AT 480V. MINIMUM 500 CFM FAN WILL BE USED FOR AIR COOLING. CAPACITOR PANEL SHALL BE EXPENDABLE TYPE. INCOMER: Supply, testing and commissioning of 200 KVAR at 480V capacitor panel having 1 Number 400Amps TP Isolator Ics=36kA as incomer. Incomer shall have 3 nos indicating lights with control MCB for incoming power, 1 Number Multifunction meter showing V/A/PF parameters with matching cast resin CT's, 3 phase 12 set automatic power factor correction relay. BUS BAR: A set of TPN Aluminium bus bar rated for 600A (after derating factor of 0.75) 3 phase 4wire, 50Hz System. The bus bar size after derating shall be equal to the ampere given in the BOQ The conductivity of bus bar shall not be less than 58% and earth bus size shall be 10% of phase bus bar. Neutral Bus Bar is 50% capacity of phases.
Supply, installation, testing and commissioning of UPS OUTPUT PANEL (G.F) (INDOOR DUTY) with the following specifications, complete in all respect as specifed and directed This will be floor mounted/ Wall mounted, free standing, indoor duty, dust proof, vermin proof, front operated, dead back access, electrical panel fabricated as per specifications laid in this document and will be complete with the extendable main and auxiliary bus bars, interconnection, earth bus and will be powder coated finish with 70 micron thickness. 2 Nos. of 63A 4P MCB with ON/OFF indications , Digital flush type class-1.0 accuracy multifunction meter showing V, A, KWH, Frequency with 3 Nos. of CT of 100/5 ratio, 15 VA Class 1.0 metering. 1 set of three phase indicating lamps along with 2A SP MCB backup protection complete in all respect. 63A 4P COS -1 and 2 Two number of 63A 4P CHANGE OVER SWITCH, connections should be as per SLD Bus Bar 1: One set of TPN, Al. bus bar rated 100 Amps (after considering necessary deratings of 75%) for phases and neutral 150% capacity of phases. Outgoings : 3 nos. 63 amps 10 kA 230 volt grade DP MCB. SPARE: 1 nos. 63 amps 10 kA 230 volt grade DP MCB. Bus Bar 2: One set of TPN, Al. bus bar rated 100 Amps (after considering necessary deratings of 75%) for phases and neutral 150% capacity of phases. Outgoings : 3 nos. 63 amps 10 kA 230 volt grade DP MCB. SPARE: 1 nos. 63 amps 10 kA 230 volt grade DP MCB. Control wiring, MCB, ferruling, danger plate, name plates etc complete in all respect
Supply, installation, testing and commissioning of FDB EMERGENCY PANEL-1 (Ground Floor) (INDOOR DUTY) with the following specifications, complete in all respect as specifed and directed This will be floor mounted, free standing, indoor duty, dust proof, vermin proof, front operated, dead back access, electrical panel fabricated as per specifications laid in this document and will be complete with the extendable main and auxiliary bus bars, interconnection, earth bus and will be powder coated finish with 70 micron thickness. 1 No 63 Ampere DP MCB, 18kA , ON/OFF indication complete in all respects as mentioned in specifications and as required. Bus Bars: High conductivity Aluminium single phase and neutral busbars rated at 230V, 50 Hz., 100 Amps 25kA, insulated with heat shrinkable coloured PVC sleeves and clip on shrouds for joints. Outgoings : 3 nos. 40 amps 10 kA 230 volt grade DP MCB. SPARE: 2 nos. 40 amps 10 kA 230 volt grade DP MCB. Control wiring, MCB, ferruling, danger plate, name plates etc complete in all respect
Supply, installation, testing and commissioning of FDB EMERGENCY PANEL-2 (First Floor) (INDOOR DUTY) with the following specifications, complete in all respect as specifed and directed This will be floor mounted, free standing, indoor duty, dust proof, vermin proof, front operated, dead back access, electrical panel fabricated as per specifications laid in this document and will be complete with the extendable main and auxiliary bus bars, interconnection, earth bus and will be powder coated finish with 70 micron thickness. 1 No 63 Ampere DP MCB, 18kA , ON/OFF indication complete in all respects as mentioned in specifications and as required. Bus Bars: High conductivity Aluminium single phase and neutral busbars rated at 230V, 50 Hz., 100 Amps 25kA, insulated with heat shrinkable coloured PVC sleeves and clip on shrouds for joints. Outgoings : 6 nos. 40 amps 10 kA 230 volt grade DP MCB. SPARE: 2 nos. 40 amps 10 kA 230 volt grade DP MCB. Control wiring, MCB, ferruling, danger plate, name plates etc complete in all respect
Supply, installation, testing and commissioning of FDB EMERGENCY PANEL-3 (Second Floor) (INDOOR DUTY) with the following specifications, complete in all respect as specifed and directed This will be floor mounted, free standing, indoor duty, dust proof, vermin proof, front operated, dead back access, electrical panel fabricated as per specifications laid in this document and will be complete with the extendable main and auxiliary bus bars, interconnection, earth bus and will be powder coated finish with 70 micron thickness. 1 No 63 Ampere DP MCB, 18kA , ON/OFF indication complete in all respects as mentioned in specifications and as required. Bus Bars: High conductivity Aluminium single phase and neutral busbars rated at 230V, 50 Hz., 100 Amps 25kA, insulated with heat shrinkable coloured PVC sleeves and clip on shrouds for joints. Outgoings : 3 nos. 40 amps 10 kA 230 volt grade DP MCB. SPARE: 2 nos. 40 amps 10 kA 230 volt grade DP MCB. Control wiring, MCB, ferruling, danger plate, name plates etc complete in all respect
Supply, installation, testing and commissioning of FDB EMERGENCY PANEL-4 (3rd Floor) (INDOOR DUTY) with the following specifications, complete in all respect as specifed and directed This will be floor mounted, free standing, indoor duty, dust proof, vermin proof, front operated, dead back access, electrical panel fabricated as per specifications laid in this document and will be complete with the extendable main and auxiliary bus bars, interconnection, earth bus and will be powder coated finish with 70 micron thickness. 1 No 63 Ampere DP MCB, 18kA , ON/OFF indication complete in all respects as mentioned in specifications and as required. Bus Bars: High conductivity Aluminium single phase and neutral busbars rated at 230V, 50 Hz., 100 Amps 25kA, insulated with heat shrinkable coloured PVC sleeves and clip on shrouds for joints. Outgoings : 3 nos. 40 amps 10 kA 230 volt grade DP MCB. SPARE: 2 nos. 40 amps 10 kA 230 volt grade DP MCB. Control wiring, MCB, ferruling, danger plate, name plates etc complete in all respect
Supply, installation, testing and commissioning of FDB EMERGENCY PANEL-5 (4th Floor) (INDOOR DUTY) with the following specifications, complete in all respect as specifed and directed This will be floor mounted, free standing, indoor duty, dust proof, vermin proof, front operated, dead back access, electrical panel fabricated as per specifications laid in this document and will be complete with the extendable main and auxiliary bus bars, interconnection, earth bus and will be powder coated finish with 70 micron thickness. 1 No 63 Ampere DP MCB, 18kA , ON/OFF indication complete in all respects as mentioned in specifications and as required. Bus Bars: High conductivity Aluminium single phase and neutral busbars rated at 230V, 50 Hz., 100 Amps 25kA, insulated with heat shrinkable coloured PVC sleeves and clip on shrouds for joints. Outgoings : 3 nos. 40 amps 10 kA 230 volt grade DP MCB. SPARE: 2 nos. 40 amps 10 kA 230 volt grade DP MCB. Control wiring, MCB, ferruling, danger plate, name plates etc complete in all respect
RISING MAINS Supply, Unloding at site on foundation, testing and commissioning of sheet enclosed following sized indoor IP 54 with separate cover TPN "ALUMINIUM" bus bar trunking compact air insulated type (neutral = 50%) suitable for Indoor installation including connecting the bus duct with terminal flanges along with all accessories bends including rising main support, Tranposition pieces etc. as required, complete bends, including expansion joint, external / internal earthing strip suitable for fault level, adopter or flange box, busbar supports, Class - F insulating materials, all mounting accessories, complete as required as per specifications with GI enclosure, aluminium conductivity shall be minimum 58%. All the ratings should be Type Tested as per IEC60439-1and2 for Temperature Rise to conform Rise within Specified limits. (Measurement of bus duct shall be along centerline along Y phase and shall be inclusive of bends etc.). The calculation for temp. rise and power loss has to be given.
Supply and fixing of Compact air insulated AlUMINIUM (Ics -35KA) for one second, current rating 800A (after all deratings) at the temperature rise of 50 deg. above ambient of 45 deg. with min.2 nos. external alm. earth strip suitable for 35KA, end cover, with expansion joints and necessary expansion bellow and all items described above in heading as complete with arrangement of center feed meter unit having in built TAP OFF BOX connectivity , complete all as specified and directed.
Supply and fixing of Compact air insulated AlUMINIUM, (Ics -35KA) for one second, current rating 400A (after all deratings) at the temperature rise of 50 deg. above ambient of 45 deg. with min.2 nos. external alm. earth strip suitable for 35KA, end cover, with expansion joints and necessary expansion bellow and all items described above in heading as complete with arrangement of center feed meter unit having in built TAP OFF BOX connectivity , complete all as specified and directed.
Supply and fixing of Reducer for Compact air insulated AlUMINIUM from current rating 800A to 400A (after all deratings) at the temperature rise of 50 deg. above ambient of 45 deg. with min. 2 nos. external alm. earth strip suitable for 35KA for continous earth connectivity., complete all as specified and directed.
Supply, Unloding at site, testing and commissioning of TPN cable end feed box having one Number 630A TP MCCB with electrostatic releases and isolable neutral with rotary handle for 800A rising mains with suitable 3 nos. 300sqmm "AlUMINIUM" XLPE arm cable connections.
Supply and fixing of Plug in box (TAP OFF BOX) spring loaded suitable for above bustrunk complete with 160A TP MCCB Ics = 25KA with earthing links, complete all as specified and directed.(For Ground Floor)
Supply and fixing of Plug in box (TAP OFF BOX) spring loaded suitable for above bustrunk complete with 200A TP MCCB Ics = 25KA with earthing links, complete all as specified and directed. (For 2nd.Floor, 3rd Floor)
Supply and fixing of Plug in box (TAP OFF BOX) spring loaded suitable for above bustrunk complete with 250A TP MCCB Ics = 25KA with earthing links , complete all as specified and directed. (For 1st Floor, 4th Floor)
Supply, installation, testing and commissioning of FLOOR DISTRIBUTION BOARDS (FDB) FOR LIGHTING and POWER with the following specifications, complete in all respect as specifed and directed These will be floor mounted, free standing, indoor duty, dust proof, vermin proof, front operated, dead back access, electrical panel fabricated as per specifications laid in this document and will be complete with the extendable main and auxiliary bus bars, interconnection, earth bus and will be powder coated finish with 70 micron thickness. All Incomer MCCB Ics=36kA FDB PANEL (LandP) - 1 (Ground Floor) (INDOOR DUTY) 1 No 160 Ampere 4P MCCB with isolable neutral having over current, Earth fault and short circuit protections with all indications, metering, protections, push buttons etc. complete in all respects as mentioned in specifications and as required. Digital flush type class-1.0 accuracy multifunction meter showing V, A, PF, KVAR , KWH, Frequency etc. with 3 Nos. current transformers of 160/5 ratio, 15 VA Class 1.0 metering. Red/Green ON/OFF indicating lamps with 2A SP MCB backup protection. 1 set of three phase indicating lamps along with 2A SP MCB backup protection. Bus Bars: High conductivity Aluminium three phase and neutral busbars rated at 415V,50 Hz., 200 Amps, 35kA, insulated with heat shrinkable coloured PVC sleeves and clip on shrouds for joints.
Outgoings : 1 nos. 63 amps 10 kA 415 volt grade 4P MCB. 2 nos. 32 amps 10 kA 415 volt grade 4P MCB. 12 nos. 40 amps 10 kA 230 volt grade DP MCB. SPARE: 1 nos. 63 amps 10 kA 415 volt grade 4P MCB. 1 nos. 32 amps 10 kA 415 volt grade 4P MCB. 2 nos. 40 amps 10 kA 230 volt grade DP MCB. Control wiring, MCB, ferruling, danger plate, name plates etc complete in all respect
Supply, installation, testing and commissioning of FDB PANEL (LandP) - 2 (1st Floor) (INDOOR DUTY) with the following specifications, complete in all respect as specifed and directed 1 No 250 Ampere 4P MCCB with isolable neutral having over current, Earth fault and short circuit protections with all indications, metering, protections, push buttons etc. complete in all respects as mentioned in specifications and as required. Digital flush type class-1.0 accuracy multifunction meter showing V, A, PF, KVAR , KWH, Frequency etc. with 3 Nos. current transformers of 250/5 ratio, 15 VA Class 1.0 metering. Red/Green ON/OFF indicating lamps with 2A SP MCB backup protection. 1 set of three phase indicating lamps along with 2A SP MCB backup protection. Bus Bars: High conductivity Aluminium three phase and neutral busbars rated at 415V,50 Hz., 300 Amps, 35kA, insulated with heat shrinkable coloured PVC sleeves and clip on shrouds for joints. Outgoings : 1 nos. 63 amps 10 kA 415 volt grade 4P MCB. 6 nos. 40 amps 10 kA 415 volt grade 4P MCB. 4 nos. 32 amps 10 kA 415 volt grade 4P MCB. 13 nos. 40 amps 10 kA 230 volt grade DP MCB. SPARE: 1 nos. 63 amps 10 kA 415 volt grade 4P MCB. 1 nos. 32 amps 10 kA 415 volt grade 4P MCB. 2 nos. 40 amps 10 kA 230 volt grade DP MCB. Control wiring, MCB, ferruling, danger plate, name plates etc complete in all respect
Supply, installation, testing and commissioning of FDB PANEL (LandP) - 3 (2nd Floor) (INDOOR DUTY) with the following specifications, complete in all respect as specifed and directed 1 No 200 Ampere 4P MCCB with isolable neutral having over current, Earth fault and short circuit protections with all indications, metering, protections, push buttons etc. complete in all respects as mentioned in specifications and as required. Digital flush type class-1.0 accuracy multifunction meter showing V, A, PF, KVAR , KWH, Frequency etc. with 3 Nos. current transformers of 200/5 ratio, 15 VA Class 1.0 metering. Red/Green ON/OFF indicating lamps with 2A SP MCB backup protection. 1 set of three phase indicating lamps along with 2A SP MCB backup protection. Bus Bars: High conductivity Aluminium three phase and neutral busbars rated at 415V,50 Hz., 300 Amps, 35kA, insulated with heat shrinkable coloured PVC sleeves and clip on shrouds for joints. Outgoings : 1 nos. 63 amps 10 kA 415 volt grade 4P MCB. 4 nos. 32 amps 10 kA 415 volt grade 4P MCB. 19 nos. 40 amps 10 kA 230 volt grade DP MCB. SPARE: 1 nos. 63 amps 10 kA 415 volt grade 4P MCB. 1 nos. 32 amps 10 kA 415 volt grade 4P MCB. 2 nos. 40 amps 10 kA 230 volt grade DP MCB. Control wiring, MCB, ferruling, danger plate, name plates etc complete in all respect
Supply, installation, testing and commissioning of FDB PANEL (LandP) - 4 (3rd Floor) (INDOOR DUTY) with the following specifications, complete in all respect as specifed and directed 1 No 200 Ampere 4P MCCB with isolable neutral having over current, Earth fault and short circuit protections with all indications, metering, protections, push buttons etc. complete in all respects as mentioned in specifications and as required. Digital flush type class-1.0 accuracy multifunction meter showing V, A, PF, KVAR , KWH, Frequency etc. with 3 Nos. current transformers of 200/5 ratio, 15 VA Class 1.0 metering. Red/Green ON/OFF indicating lamps with 2A SP MCB backup protection. 1 set of three phase indicating lamps along with 2A SP MCB backup protection. Bus Bars: High conductivity Aluminium three phase and neutral busbars rated at 415V,50 Hz., 300 Amps, 35kA, insulated with heat shrinkable coloured PVC sleeves and clip on shrouds for joints. Outgoings : 8 nos. 40 amps 10 kA 415 volt grade 4P MCB. 6 nos. 20 amps 10 kA 415 volt grade 4P MCB. 13 nos. 40 amps 10 kA 230 volt grade DP MCB. SPARE: 2 nos. 40 amps 10 kA 415 volt grade 4P MCB. 1 nos. 20 amps 10 kA 415 volt grade 4P MCB. 1 nos. 40 amps 10 kA 230 volt grade DP MCB. Control wiring, MCB, ferruling, danger plate, name plates etc complete in all respect
Supply, installation, testing and commissioning of FDB PANEL (LandP) - 5 (4th Floor) (INDOOR DUTY) with the following specifications, complete in all respect as specifed and directed 1 No 250 Ampere 4P MCCB with isolable neutral having over current, Earth fault and short circuit protections with all indications, metering, protections, push buttons etc. complete in all respects as mentioned in specifications and as required. Digital flush type class-1.0 accuracy multifunction meter showing V, A, PF, KVAR , KWH, Frequency etc. with 3 Nos. current transformers of 250/5 ratio, 15 VA Class 1.0 metering. Red/Green ON/OFF indicating lamps with 2A SP MCB backup protection. 1 set of three phase indicating lamps along with 2A SP MCB backup protection. Bus Bars: High conductivity Aluminium three phase and neutral busbars rated at 415V,50 Hz., 300 Amps, 35kA, insulated with heat shrinkable coloured PVC sleeves and clip on shrouds for joints. Outgoings : 4 nos. 63 amps 10 kA 415 volt grade 4P MCB. 1 nos. 40 amps 10 kA 415 volt grade 4P MCB. 4 nos. 32 amps 10 kA 415 volt grade 4P MCB. 12 nos. 40 amps 10 kA 230 volt grade DP MCB. SPARE: 1 nos. 63 amps 10 kA 415 volt grade 4P MCB. 1 nos. 32 amps 10 kA 415 volt grade 4P MCB. 4 nos. 40 amps 10 kA 230 volt grade DP MCB. Control wiring, MCB, ferruling, danger plate, name plates etc complete in all respect
Supply, installation, testing and commissioning of EXTERNAL LIGHTING FEEDER PILLAR (OUTDOOR TYPE) with the following specifications, complete in all respect as specifed and directed One number TPN incomer feeders comprising of 100A 4P MCCB with ON/OFF indication, Red/Green ON/OFF indicating lamps with 2A SP MCB backup protection. Bus Bars: One set of TPN, Al. bus bar rated 150 Amps (after considering necessary deratings of 75%) for phases and neutral for half capacity of phases. Outgoings : 3 Nos. 25A TPN feeders each having one Number 25A 4P MCB's with 24 hour real timer and contactor for auto switching of load. 1 Nos. 25A SPN feeders each having one Number 25A DP MCB's with 24 hour real timer and contactor for auto switching of load. 3 Nos. 16A SPN feeders each having one Number 25A DP MCB's with 24 hour real timer and contactor for auto switching of load. 2 nos. 25 amps 10 kA 230 volt grade DP MCB. 2 nos. 25 amps 10 kA 230 volt grade DP MCB. 1 set of complete wiring
Supply, Installation, testing, commissioning of aluminium conductor cables and of 1100 V grade aluminium / copper conductor (as specified below) extruded XLPE insulated PVC innersheath, unarmoured / GI wire/tape armoured (as specified below) and outer PVC sheathed cable of following specifications and sizes in trenches, cable racks or trays or pipes, including supply of GI clamps and screws and providing aluminum cable tags at every 20 metres and at both termination points, including unloading and transportation of cables at site, unpacking, complete all as specified and directed.
3.5 core, 300 sqmm Aluminium. Armoured XLPE cable
3.5 core,185 sqmm Aluminium. Armoured XLPE cable
3.5 core, 95 sqmm Aluminium. Armoured XLPE cable
3.5 core, 70 sqmm Aluminium. Armoured XLPE cable
3.5 core,50 sqmm Aluminium. Armoured XLPE cable
3.5 core,35 sqmm Aluminium. Armoured XLPE cable
4 core, 25 sqmm Aluminium. Armoured XLPE cable
4 core,16 sqmm Aluminium. Armoured XLPE cable
4 core, 10 sqmm Aluminium. Armoured XLPE cable
4 core, 6 sqmm Aluminium. Armoured XLPE cable
2 core, 16 sqmm Aluminium. Armoured XLPE cable
2 core, 10 sqmm Aluminium. Armoured XLPE cable
Supply, laying and testing PVC insulated, PVC sheathed cable galvanized steel strip or wire armoured, electric control cables (Heavy duty) with stranded copper conductor of following size:
12 core, 2.5 sqmm Copper armoured control cable.
10 core, 2.5 sqmm Copper armoured control cable
4 core, 2.5 sqmm Copper armoured control cable
Supplying and making end termination with brass compression gland and aluminium/ copper lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade, complete all as specified and directed.
3.5 core, 300 sqmm Aluminium. Armoured XLPE cable
3.5 core, 185 sqmm Aluminium. Armoured XLPE cable
3.5 core, 95 sqmm Aluminium. Armoured XLPE cable
3.5 core, 70 sqmm Aluminium. Armoured XLPE cable
3.5 core, 35 sqmm Aluminium. Armoured XLPE cable
4 core,25 sqmm Aluminium Armoured stranded XLPE cable
4 core, 16 sqmm Aluminium Armoured stranded XLPE cable
4 core, 10 sqmm Aluminium Armoured stranded XLPE cable
2 core, 16 sqmm Aluminium Armoured stranded XLPE cable
2 core, 10 sqmm Aluminium Armoured stranded XLPE cable
12 core, 2.5 sqmm Copper armoured control cable
10 core, 2.5 sqmm Copper armoured control cable
4 core, 2.5 sqmm Copper armoured control cable
Supply, laying and testing pipe galvanized, “Heavy class”, including fittings, 80mm dia/ bore, complete all as specifed and directed.
Supply, laying and testing pipe galvanized, “Heavy class”, including fittings, 100mm dia/ bore, complete all as specifed and directed.
Supply, laying and testing pipe galvanized, “Heavy class”, including fittings, 150mm dia/ bore, complete all as specifed and directed.
Supply, laying and testing pipe galvanized, “Heavy class”, including fittings, 200mm dia/ bore, complete all as specifed and directed.
Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts and nuts, painting suspenders etc , complete all as specifed and directed.
100 mm width X 50 mm depth X 1.6 mm thickness, as approved by Engineer-in-charge
150 mm width X 50 mm depth X 1.6 mm thickness, as approved by Engineer-in-charge
300 mm width X 50 mm depth X 1.6 mm thickness, as approved by Engineer-in-charge
450 mm width X 50 mm depth X 2.0 mm thickness, as approved by Engineer-in-charge
600 mm width X 75 mm depth X 2.0 mm thickness, as approved by Engineer-in-charge
750 mm width X 75 mm depth X 2.0 mm thickness, as approved by Engineer-in-charge
Supply and Fixing of Rubber mat of 1 meter x 2 meter x 10 mm thick suitable for 11 KV as approved by Engineer-in-charge
Supply and Fixing of Rubber mat of 1 meter x 2 meter x 19 mm thick suitable for 11 KV as approved by Engineer-in-charge
Supply and Fixing of Electric rubber hand gloves suitable for 11 KV as approved by Engineer-in-charge
Supply and fix hot dipped galvanised mild steel step pole with grey powder finish. Compatible for all Havells post top range. Window - Plasma cut and duly chamfered opening window of 300x110 mm for terminal connections and mounting accessories. Window cover is fitted with allen screws to the pole.3.5 meter long complete with CI base plate and finial including foundation and coping, complete all as specified and directed.
Supply and fixing of decorative 30 to 40 Watt LED Post top light luminaire having Pressure die cast aluminium body and Clear glass with driver set confirming to IP 65 and above protection complete in all respect including accessories, complete all as specified and directed.
Supply and fixing of LED Street light Fitting having die cast aluminium body and diffuser with driver set suitable for 60 watt to 70 Watt. Confirming to IP 66 protection complete in all respect including accessories, complete all as specified and directed.
Supply, installation testing and commissioning of Solar LED Standalone Street Light 7mtr Octagonal Pole including 60W Solar LED street Light with in-built SCC, SPV Panel, Dry Battery, Octagonal Pole , complete in all respect including foundation, complete all as specified and directed.
Total Amount of Sch 'A' Part - XIII (Sec A) (External water supplly)
Sch 'A' Part - XIII (Sec B) (EXTERNAL WATER SUPPLY AND HOT WATER SUPPLY) Note : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
Construction massonry valve chamber 60x60x75cm inside in brick work in cement mortar 1:4 for sluice valve with CI surface box 100mm top dia 160mm bottom dia and 180mm deep inside with RCC top slab complete as per standard design with common burnt clay FPS brick of class designation 75, complete all as specified and directed.
Supply and fix water heater storage type, electric capacity 25 Litres, BEE 5 star rated, complete all as specified and directed.
Supply and Installated Horizontal type submersible pumping set, electric driven complete up to 2 x 10HP inclusive of starter and PCC foundation complete all as specified and directed" (One working and one stand by)
Total Amount of Sch 'A' Part - XIV (Sec A) (Water Cooler and Water purifier)
Sch 'A' Part - XIV (Sec B) (WATER COOLER AND WATER PURIFIER) Note : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
Supply, install and testing RO (Reverse Osmosis) Water Purifier system having storage tank capacity 50 Ltrs per day, for mounting on wall, suitable for all types of raw water with and including all accessories. Input Voltage 160-300 Volts AC (50 HZ), Max Duty Cycle 250 Ltrs per day, complete all as specified and directed.
Supply, installation and testing of Voltage stabilizer for automatic operation, Each 3789.0 single phase naturally air cooled indoor type and designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of + 2.5% and of capacity 2 KVA, complete all as specified and directed.
Sch 'A' PART-XV : MECHANICAL LAUNDRY Note : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
Supply, Installation, Testing and Commisioning of WASHER EXTRACTOR of CAPACITY 30 Kgs, with steam heating , complete in all respect as specified and directed.
Supply, Installation, Testing and Commisioning of TUMBLE DRIER of CAPACITY 30 Kgs, with steam heating, complete in all respect as specified and directed.
Supply, Installation, Testing and Commisioning of FLAT WORK IRONER with ROLLER LENGTH 3300MM and ROLLER DIA 800 MM with steam heating, complete in all respect as specified and directed.
Supply, Installation, Testing and Commisioning of VACUUM IRONING TABLE, complete in all respect as specified and directed.
Supply, Installation, Testing and Commisioning of WASH ROOM TROLLEY of capacity 50KGS, complete in all respect as specified and directed.
Supply, Installation, Testing and Commisioning of DRY LINEN TROLLEY of capacity 50KGS, complete in all respect as specified and directed.
Supply, Installation, Testing and Commisioning of SHELF TROLLEY of capacity 100KGS WITH 4 SHELVES, complete in all respect as specified and directed.
Supply, Installation, Testing and Commisioning of SS MOBILE TROLLEY WITH UNDERSHELF (WITHOUT WHEELS), complete in all respect as specified and directed.
Supply, Installation, Testing and Commisioning of SS MOBILE TROLLEY WITH UNDERSHELF (WITH WHEELS), complete in all respect as specified and directed.
Supply, Installation, Testing and Commisioning of LAUNDRY SCRUB STATION WITH 2 INKS with underneath SS Shelf , complete in all respect as specified and directed.
Supply, Installation, Testing and Commisioning of LAUNDRY PANEL (2nd Floor) (INDOOR DUTY) with the following specifications, complete in all respect as specifed and directed. This will be floor mounted, free standing, indoor duty, dust proof, vermin proof, front operated, dead back access, electrical panel fabricated as per specifications laid in this document and will be complete with the extendable main and auxiliary bus bars, interconnection, earth bus and will be powder coated finish with 70 micron thickness. Incomer MCCB Ics=36kA 1 No 100 Ampere 4P MCCB having over current, Earth fault and short circuit protections with all indications, metering, protections etc. complete in all respects as mentioned in specifications and as required. Bus Bars: High conductivity Aluminium three phase and neutral busbars rated at 415V,50 Hz., 150 Amps, 35kA, insulated with heat shrinkable coloured PVC sleeves and clip on shrouds for joints. Outgoings : 3 nos. 40 amps 10 kA 415 volt grade 4P MCB. 2 nos. 25 amps 10 kA 415 volt grade 4P MCB. 2 nos. 16 amps 10 kA 230 volt grade DP MCB. SPARE: 2 nos. 40 amps 10 kA 415 volt grade 4P MCB. 1 nos. 25 amps 10 kA 415 volt grade 4P MCB. 1 nos. 16 amps 10 kA 230 volt grade DP MCB. Control wiring, MCB, ferruling, danger plate, name plates etc complete in all respect
SCH 'A' PART-XVI : MEDICAL GAS SUPPLY SYSTEM Note : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
Designing, supplying, installing, testing and commissioning of medical gases supply control station for the entire hospital consisting of the following , complete in all respect as specified and directed. (A) Oxygen System
(a) Oxygen Manifold 20 + 20 cylinders with NRVs, tail pipes etc. W/O cylinder. Indigenous
(b) Emergency Oxygen System manifold of 8 + 8 cylinder, w/o cylinder Indigenous
(c) Fully automatic Oxygen Control Panel Imported
(d) Oxygen Gas Outlet point
(e) Oxygen Flow meters with humidifier bottle Indigenous
(B) Nitrous Oxide System
(a) Nitrous Oxide Manifold – 4 + 4 with NRVs, tail pipes etc. w/o cylinders Indigenous
(b) Emergency N2O Manifold of – 1 +1 cylinder with regulator Indigenous
(c) Fully Automatic 500LPH Control Panel
(d) Gas Outlets Point for N2O
(C) Compressed air system
(a) Oil less compressor system (compressors in triplex, skid mounted with facility for single point connection)
(b) Gas Outlet Point for Air 4 Bar
(c) Gas Outlet Point for Air 7 Bar
(D) Vacuum System
(a) Vacuum system (Duplex pump system, skid mounted with facility for single point connection)
(b) Gas Outlet point for Vacuum
(E) Vacuum Accessories
(a) Ward vacuum unit with one regulator one collection bottle complete Indigenous
(b) Theatre vacuum unit mounted on the trolley with 1 vacuum regulator and 2 collection bottles (2 units for each major and minor OT) Indigenous
(F) Alarm System
(a) For 5 services (O2, N2O, M. Air(4) S. Air (7) Vac)
(b) For 4 services (O2, N2O, C. Air (4), Vac)
(c) For 3 services (O2, C. Air (4) Vac)
(d) For 2 services (O2, Vac)
Horizontal Bed Head Panel Length – 1.8 mtr, made of extruded aluminum having provision for gas outlets (as per the outlet list) and separate segregated channel for high voltage 6 Number Electrical Sockets and a channel for low voltage- Nurse Call/ Monitor cabling/ Telephone cable etc. and other items, complete in all respect as specifed and directed.
Matching Probes for Outlets
(b) Nitrous Oxide
(c) M. Air – 4 bar
(d) S. Air – 7 bar
(e) Vacuum
Copper Piping (with third party inspection certificate)
(a) 54.1mm OD x 12 mm thick
(b) 42 mm OD x 1.2 mm thick
(c) 28 mm OD x 0.9 mm thick
(d) 22 mm OD x 0.9 mm thick
(e) 15 mm OD x 0.9 mm thick
(f) 12 mm OD x 0.7 mm thick
Valve Box
Supply, fixing, testing and commisioning Rigid Retractable ceiling mount type pendant for OT provision for -2 x O2, 1 x N2O, 1 x Air (4), 1 x Air (7) and 2 x Vac, 1 x AGSS outlets, 6 x Electrical Sockets , complete all as specifed and directed.
Supply, fixing, testing and commisioning H.P. Antistatic Rubber tube (100 mtrs, for O2-white, 50mtr N2O-Blue, 100 Mtr Air- Black and 100 mtr for Vacuum – Yellow. , complete all as specifed and directed.
Supply, fixing, testing and commisioning Electrical Control Panel (input panel) for both vacuum Pumps and Compressors for the Manifold Room and cabling for all alarms , complete all as specifed and directed.
Supply, Fixing and testing of low pressure rubber/ silicon tube for suction 100 m , complete all as specifed and directed.
Supply, Fixing and testing of pin index Nitrous Oxide Pipe with high pressure tubing 2 m, complete all as specifed and directed.
Supply, fixing and testing of pin index Oxygen Pipe with high pressure tubing 2 m, complete all as specifed and directed.
Total Amount of Sch 'A' Part - XVII (Sec A) (FIRE HYDRANT, SPRINKLE SYSTEM and FIRE ALARM SYSTEM)
PART- XVII (Sec B): LIST OF WORKS AND PRICES FOR FIRE HYDRANT, SPRINKLE SYSTEM and FIRE ALARM SYSTEM Note : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
Supplying, installation, testing and commissioning of repeater panel wih 320 character/ Touch screen LCD display with inbuilt reset, acknowledge and silence switches , complete all as specifed and directed.
Supply, installation, testing and commissioning of Talk Back/ Telephone Jack Complete in all respect as specified and directed.
Supply, installation, testing and commissioning of Telephone Handset Complete in all respect as specified and directed.
Supply, installation, testing and commissioning of 5 Lopp Talk Back Panel Comprising of following items complete in all respect as specified and directed.
Supply and Fixing of Stove enamelled, blank, Rigid steel conduit, welded, conduit inclusive of boxes (junction/terminal) , tees, bends,elbows, reducers,flexible GI conduit (upto 1.5m per point), bell mouth tube ends and fixing accessories such as couplers, locknuts, saddles, pipe hooks etc. Complete in all respect as specified and directed.
20mm Dia , 1.6mm thickness
25mm Dia , 1.6mm thickness
32mm Dia , 1.6mm thickness
Supplying, laying, testing and commissioning of cabling for fire detection and alarm system with 2C x 1.5 sq mm Copper Unarmoured cable as per specifications complete as required. Complete in all respect as specified and directed.
Supplying and drawing of cable Fire Retardant PVC insulated copper conductor cable in the existing surface / recessed steel conduit of following pairs, cores and size including connections and interconnections etc. , complete in all respect as specifed and directed.
Supply installation testing and commissioning of standard fire mans axe with heavy insulated rubber , complete in all respect as specifed and directed.
Supply, laying jointing and testing in trenches the 80mm dia size of MS class C pipe confirming to IS 1239 with accessories complete all as specified and directed.
Supply, laying jointing and testing in trenches the 100mm dia size of MS class C pipe confirming to IS 1239 with accessories complete all as specified and directed.
Supply, laying jointing and testing in trenches the 150mm dia size of MS class C pipe confirming to IS 1239 with accessories complete all as specified and directed.
Supply and fixing MS cabinet fabeicated from 16g MS sheet with full front glass door and locking arrangement with suitable platform, complete all as specifed and directed.
Supply and fixing pre fabeicated 5mm thick glass door opf Size 2.1x0.9m with center opening of fire hose cabinet , complete all as specifed and directed.
Supply and fixing reinforced neoprene rubber vibration eliminators / expansion joints suitable for upto 20 Kg/sqcm pressure complete for 150mm dia., complete all as specifed and directed.
Supply install testing and commissioning of UL Listed test and drain assembly, complete all as specifed and directed.
Supply install, testing of following type of extinguisher with provision of wall bracket , complete all as specifed and directed.
Supply and fixing ISI marked portable chemical fire extinguisher water type capacity 9 Ltr with gun metal cap and nozzle, complete all as specifed and directed.
Supply and fixing ISI marked portable chemical fire extinguisher carbon di oxide type capacity 3 Kg with gun metal cap and nozzle, complete all as specifed and directed.
Supply and fixing ISI marked portable chemical fire extinguisher carbon di oxide type capacity 4.5 Kg with gun metal cap and nozzle, complete all as specifed and directed.
Supply and fixing ABC power type fire extinguisher capacity 4 Kg with gun metal cap and nozzle, complete all as specifed and directed.
Supply and fixing ABC power type fire extinguisher capacity 6 Kg with gun metal cap and nozzle, complete all as specifed and directed.
Supply and fixing on terrace polyethylene water storage tank IS 12701 marked with cover and suitable locking arrangement and making necessary holes for inlet outlet and overflow, complete all as specifed and directed.
PART- XVIII: LIST OF WORKS AND PRICES FOR UPS SYSTEM Note : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
Supply,Installation,Testing and Commissioning of micro processor controlled True On line double conversion, Parallel mode 3 Phase input and Three phase 415V output UPS and each UPS consisting of 1 Number 100% Rectifier + Inverter, Integrated in UPS module Battery Circuit breaker, complete all as specifed and directed.
Supply and fixing Galvanic Isolation transformer at the inverter input of UPS Module Inbuilt Static switch for bypass and inverter in UPS module Manual Maintenace bypass , complete all as specifed and directed.
Supply and fixing Sealed Maintenance free batteries for 30 minutes backup time with UPS and inerconnectors, Rack and accessories and UPS to battery DC cable upto 10 meters., complete all as specifed and directed.
Supply, fixing and testing of 1x20 kVA UPS (for Emergency Lighting,Work Stations, Fire Alarm, Server and CCTV)., complete all as specifed and directed.
PART- XIX: LIST OF WORKS AND PRICES FOR DG SET Note : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
Supply, installation, commissioning and testing of Silent Diesel Engine Generating Set comprising of diesel engine , liquid- cooled (latest CPCB- Norms Compliance) as per IS 10001/10002 complete with AMF panel and alternator (as per IS13364), of output capacity not less than 500 KVA at site (DG Set to be installed at HAA 950 metre above MSL) 3 phase, 415 V, 50 Hz., 0.8pf at 1500 RPM, both coupled and aligned on a common base frame complete with standard accessories like MS Fuel tank (having the minimum fuel capacity for running of DG set continously for 12 hours), AVM Pads fitted on base frame, Control Panel with digital measurement devices, alongwith accoustic enclosure with the confirmination of latest BS/IS and complete in all respects Including lubricating oil filled in engine, DG Set Manual comprising of following complete as as specified and directed
Material and Labour for earthing complete with copper earth plate electrod 600mmx600mm x3.15 mm thick burried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of earth plate not less than 1.5 mtr deep below normal ground level connected to in and including copper strip 20x3 mm upto test point including providing test point inclulding funnel,wire mesh, charcoal dust, salt etc and 40mm bore 5 mtr long light grade GI protection pipe for earth strip and GI watering pipe 20mm dia bore light grade, 40mm thick precast RCC 1:2:4 type B1 cover reinforced with XPM, weight not less than 4 Kg /Sqmm with suitable handle of 6mm round MS bars and angle iron 40x40x3mm frame of pit cover, PCC pit of PCC 1:3:6 type C-2 excavation earth work in soft/dense soil , complete in all respect as specifed and directed.
Material and Labour for Construction of platform suitable for 500 KVA Generator set, of size 6.0m x 3.0m x 0.60 m (Platform shall be made of one brick thick built in cement mortar (1:4) brick masonary 30cm below ground level and 30 cm above ground level, hollow space 500mm thick shall filled with PCC (1:3:6) type C-2,over well rammed and watered earth, and floor of platform shall be 100 mm thick in cement concrete (1:2:4) type B-2 ,exposed surface of platform shall be plastered 15mm thick in cement mortar (1:4), complete all as specified and directed.
SCH 'A' PART- XX : AIR CONDITIONING PLANT Note : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
(v) NPLV: Shall be less than 0.39 Ikw/TR. Procedure for calculations shall be as per AHRI guidelines. (vi) Installation, Testing and commissioning of factory designed and pre-fabricated Vapor Compression refrigeration water chilling machines of following actual capacity as described above and in the specifications.The refrigerant acceptable is R -134A . (vii) 40 TR Actual Capacity water cooled screw type chiller with VFD (2 Nos.Working +1 Number Standby) (Acceppted ±5% Variation on actual capacity)
COOLING TOWER (80 TR) Supply, installation, testing and commissioning of FRP Induced draft counter flow, Twin Cell site erected cooling tower of capacity as mentioned below based on the parameters given below and complete with PVC Fill, Louvers, Drift Eliminator, Weather Proof IP 55 TEFC Motor (IE-3), Propeller Fan, FRP Basin with additional sump in the bottom of the basin on every outlet point to avoid vortex formation in the condenser water pipe line, Hot dip galvanised Steel Ladder, Stainless Steel hardware including nut, bolt, washer etc. The cooling tower shall conform to technical specifications given in the tender. The maximum allowable sound power at a distance of 1 M from the cooling Tower shall be less than 65 dB. Tower fan motor shall be suitable for VFD operation and operation of VFD system shall be based approach of cooling tower. Duty Parameters:- (a) Water Flow - 320 GPM (4 GPM / TR) (b) Designed Wet Bulb Temperature - 83 Deg. F. (c) Water Inlet Temperature - 97.5 Deg. F (d) Water Outlet Temperature - 90 Deg. F (e) 80 TR (1W +0 Standby)
CONDENSER WATER PUMPS Supply,installation,testing and commissioning of vertical inline centrifugal pumps for condenser water recirculation , complete with TEFC squirrel cage motors, and all necessary accessories.Capacity of pump sets , nett head is as given below:All the pumps mentioned below shall also be complete with mechanical seals, and drain connections , and shall be suitable for operation on 415+/- 10 % Volts , 50 Hz , 3 Phase AC power supply., complete all as specifed and directed. 320 USGPM * 30 M for Screw chiller, (1Working + 1Standby)
PRIMARY CHILLED/HOT WATER PUMPS (FIXED SPEED) Primary circuit:Supply, installation, testing and commissioning of vertical Inline pumps centrifugal pumps for chilled water/Hot Water recirculation, complete with TEFC squirrel cage motors and all necessary accessories. Capacity of pump sets, nett head is as given below: All the pumps mentioned below shall also be complete with mechanical seals, and drain connections, and shall be suitable for operation on 415±10% Volts, 50 Hz, 3 Phase AC power supply. , complete all as specifed and directed.
96 USGPM * 20 M for primary Chilled water circuit , complete all as specifed and directed.(2Working + 1Standby)
320 USGPM * 20 M for Hot water circuit, complete all as specifed and directed. (1Working + 1Standby)
SECONDARY PUMPS WITH VARIABLE SPEED SYSTEM (a) Supply, installation, testing and commissioning of centrifugal vertical Inline pumps factory mounted with electric motor for re circulation of water for the central air conditioning system.. The pump motor shall be suitable for 415± 10% volts, 50 cycles, 3 phase AC power supply. Secondary chilled water/Hot Water pumps shall be suitable for operation on adjustable frequency drives .Secondary Variable Speed Pumping System consisting (In Each circuit) of 6No.’s adjustable frequency drives (one dedicated for each pump)( 1 # provision for future), 2 No. Microprocessor based Pump Logic Controller for controlling 4/2 working +1(stand-by) pumps in parallel , with sensorless control. (b) The Pump Logic Controller shall be capable of accepting analog inputs from Flow Sensor / Transmitter and from Kw Sensor / Transmitter to provide lowest Kw draw based on Efficiency Optimisation Program and multiple differential pressure sensor / transmitters. Controller shall be capable of accepting input from flow sensor transmitter,to ensure end of the curve protection. (c) The system shall be complete in all respects and suitable for following ratings and duty.
96 USGPM * 32 M for Chilled water circuit , complete all as specifed and directed.(2Working + 1Standby)
PLC Controller for Pump, complete all as specifed and directed.
Hot water generator (a) Supply and fix HT 11 KV out door type gang operated air-break switch suitable for horizontal or vertical mounting rotating type complete with drop out fuse having 12 insulators of rating upto 400 Amps (b) Supply Installation,testing and commissioning of Hot water generator as per specifications . (c) Blank (d) Inlet Water Temperature 50 °C (e) Outlet Water Temperature 55 °C (f) 138.0 KW Hot water generator (with multiple circuit), complete all as specifed and directed. (1 Working + 1 Standby)
AIR HANDLERS (With Coil System) (a) Supply, installation testing and commissioning of factory built floor mounted chilled water Double skin type horizintal/vertical air handling units made of 25mm ±2mm thick panels consisting of pre plasticized GI casing of thickness 0.8mm outside layerand 0.8mm inside layer with polyurethene foam (PUF) insulation factory injected between them by injection moulding machine, complete with blower section with blower suitable for static pressure as required , min. 2 bend GSS/PVC eliminators, cooling coil section with aluminium finned copper tubes ( tube thickness not less than 0.5 mm ) cooling coil of 6 row deep, filter section with 50 mm thick metal viscous filter /washable synthetic type air prefilters, AHU Blower Direct driven, squirel cage induction motor (Its suitable for VFD or with plug fan) package with TEFC drive motor of efficiency class IE3 suitable for 415±10% V, 50Hz, 3 phase AC supply suitably designed for variable frequency drive applications, drain connections , stainless steel (18G) drain pain with PUF insulation,150 mm dia. dial type pressure gauges (2 Nos.) and industrial type thermometers (2 nos.) at the inlet and outlet of coil, auto purge valve wherever required, necessary vibration isolation arrangement etc. complete as per specification and AHU schedule and of following capacities as: (b) Supply , installation testing and commissioning of Double skin floor mounted Horizontal/vertical Two pipe system (One coil) AHUs as per the mentioned in AHU schedule. (All AHU Should Be BMS/VFD Compitable) Note: If AHU With fine filter or Fine and Hepa Filter than these filters with sections shall be separate considerable as defined below , complete all as specifed and directed.
Ground Floor Double skin Ceiling mounted Horizontal two pipe system (one coil)AHU 1000 CFM / 2.5 TR, 6 row deep chilled water coil ,pre and Fine filter, 25 mm SP WG with three phase motor
Third Floor Double skin Ceiling mounted Horizontal two pipe system (one coil)AHU 1600 CFM / 4.0 TR, 6 row deep chilled water coil ,pre and Fine filter, 25 mm SP WG with three phase motor
Third Floor Double skin Ceiling mounted Horizontal two pipe system (one coil)AHU 1200 CFM / 3.0 TR, 6 row deep chilled water coil ,pre and Fine filter, 25 mm SP WG with three phase motor
Fourth Floor Double skin Ceiling mounted Horizontal two pipe system (one coil)AHU 1000 CFM / 2.5 TR, 6 row deep chilled water coil ,pre and Fine filter, 25 mm SP WG with three phase motor
Double skin floor mounted Horizontal 8-Row Depth chilled water Coil (1 Coil) with Supply Fan 2800 CFM with pre, fine and Hepa filter on terminal, S.P. is 125 mm and Exhaust fan 1150 CFM with Pre and HEPA Filter, S.P. 80 mm , Heat Recovery Wheel (Enthalpy Wheel) AHU Coil is 8.0.0 TR, pre filter with mixing box ., complete all as specifed and directed. (For OT -1)
Double skin floor mounted Horizontal 8-Row Depth chilled water Coil (1 Coil) with Supply Fan 2400 CFM with pre, fine and Hepa filter on terminal, S.P. is 125 mm and Exhaust fan 1000 CFM with Pre and HEPA Filter, S.P. 80 mm , Heat Recovery Wheel (Enthalpy Wheel) AHU Coil is 6.5.0 TR, pre filter with mixing box ., complete all as specifed and directed. (For OT -2)
FAN COIL UNITS (Standard) (a) Supply,Installation , testing and commissioning of fan coil units of specified capacities and air flow as per the specifications , complete with auxillary drain pan. (b) Fan coil unit shall be supplied with approved make of factory fitted adequately sized insulated (with nitrile foam) two way motorized valves , insulated ball valves-one with Y strainer, and the other without Y strainer complete with room thermostat for fan speed control , associated conduiting and wiring between the thermostat , 2 - way valve .etc. (c) Cost of fan coil unit shall be inclusive of approved make room thermostat (heatig and cooling, with fan speed control), and associated MS conduiting and wiring etc.between the thermostat and two way valve , for a standard length of approximately 5-7 M per fan coil unit. (d) Providing and fixing in position the following Fan Coil units complete with all valves and accessories as described above. (e) 1.5 TR nominal capacity ( 600 CFM)
PRESSURISED EXPANSION TANK Supply, Installation, Testing and Commissioning of PRESSURISED CHILLED WATER EXPANSION TANK Including with Microbubble air, dirt separator, safety valve, pressurisaion unit other accessories. suitable for total volume of water in chilled water circuits along with necessary accessories such as centrifugal air separator, pumps etc. in order to keep chilled water system under pressure and to prevent entrapment of pressure and to prevent entrapment of air in the system. The tank shall be recharged steel expansion tank with replaceable heavy duty butyl rubber bladder. The tank shall have 50 MM system connection and 20 mm drain and charging valve connection to facilitate the on site charging of the tank to meet system requirement. The tank and air separator must be constructed in accordance with section VIII of the ASME Boiler and pressure vessel code. The complete system shall be sourced from single manufacturer and supplied and installed with all accessories and safety fixtures required for proper functioning of the complete hydronic system complete as required. Tank Capacity shall be 500 Liter with PN16 rating., complete all as specifed and directed.
CABINET TYPE INLINE FAN FOR OT EXHAUST: (a) Installation, testing and commissioning of INLINE FANS suitable for installing in any position in vertical or horizontal ducts. The casing shall be double skin, internally acoustically lined and constructed of galvanised steel. The fan shall be DIDW with forward curve impeller fitted with maintenance free external rotor motor. The motor upto 1000 CFM shall be suitable for 220±10% volt single phase 50 cycles AC supply and above shall be suitable for 415 + 10% volt three phase SD cycles AC supply. (b) The fan shall have low sound level exceeding not more than 35 DBA at three metre distance.
500 CFM at 40mm SP Normal Exhaust Air (For OT)
1310 CFM at 40mm SP Normal Exhaust Air (For OT)
Condenser Water Piping Supplying, laying, fixing, testing and commissioning of prefabricated MS class `C' pipes confirming to IS 1239 Part 'II' of 1979 upto date for pipe size upto 150 mm dia and IS 3589 for 200 mm dia pipes and above, minimum thickness of pipes shall be 6.3 mm, complete with all necessary fittings such as bends, tees, reducers, flanges,bolts, nuts,seals, etc and supports such as clamps, anti-vibration hangers etc. all pipes fitting/supports with WOOD/PUF shall be painted of approved colour of synthetic enamel paint and direction of flow of fluid in the pipes shall be visibly marked with identifying arrows complete as per specifications and drawings., complete all as specifed and directed.
125 mm dia
100 mm dia
80 mm dia
65 mm dia
50 mm dia
Chilled Water Piping Supplying, laying, fixing, testing and commissioning of prefabricated MS class `C' pipes confirming to IS 1239 Part 'II' of 1979 upto date for pipe size upto 150 mm dia and IS 3589 for 200 mm dia pipes and above, minimum thickness of pipes 200 mm dia and above shall be 6.3 mm, complete with all necessary fittings such as bends, tees, reducers, flanges etc and supports such as clamps, anti-vibration hangers etc. all pipes fitting/supports shall be painted of approved colour of synthetic enamel paint and direction of flow of fluid in the pipes shall be visibly marked with identifying arrows complete as per specifications and drawings., complete all as specifed and directed.)
100 mm dia
80 mm dia
65 mm dia
50 mm dia
40 mm dia
32 mm dia
25 mm dia
DRAIN PIPING Supply, fixing and testing GI 'B' Class drain piping for condensate complete with all required fittings and providing clean out plug at suitable location for roding the pipe when required., complete all as specifed and directed.
Motorised Butterfly Valves With SS Disc Supply, installation, testing and commissioning of motorised on / off butterfly valves with modulating motor in return chilled and condenser water line of each chiller, condenser and cooling tower operated through BMS and of following sizes: (PN-16), complete all as specifed and directed.)
80 mm dia (For Chillers IN)
100 mm dia (For Condenser IN and Cooling Towers IN/OUT)
Manual Balancing Valves Supply, installation, testing and commissioning of Manual balancing valves in return chilled and condenser water line of each chiller, condenser and cooling tower as per tender specification and of following sizes:, complete all as specifed and directed.
80 mm dia (For Chillers)
125 mm dia (For Condenser and Cooling Towers)
Supply, installation and testing Butterfly Valves (PN-16), complete all as specifed and directed.
50 mm dia
65 mm dia
80 mm dia
100 mm dia
125 mm dia
Supply, installation and testing Dual Plate Check Valves (PN-16), complete all as specifed and directed.
80 mm dia
100 mm dia
125 mm dia
Supply, installation and testing Y-strainer (PN-16), complete all as specifed and directed.
80 mm dia.
100 mm dia.
125 mm dia
Supply, installation and testing BALL VALVES, complete all as specifed and directed.
20 mm dia
25 mm dia
32 mm dia
40 mm dia
2-Way High Rangeability Pressure balancing control valve with modulating type actuator including Thermostat for AHU's Supply, installation, testing and commissioning of complete set of High rangeability control valve or Pressure independant control valve, kit comprising of Two Way Control Valve of Brass construction rotary / ball type for DN15 and DN32 of PN25 rating with screwed connections. DN 40-DN150 shall be C.I body of PN16 ratings, motorised modulating actuators with linear stroke of minimum 15 mm, LCD display digital controller(BMS compatible),three nos NTC sensors with complete wiring with in AHU room,one thermowell,one power supply unit of 230Vac/24Vac.Control box for mounting Digital controller and power supply unit and 10 Amps Double pole MCB should be also provided.The valve size shall be suitable for pipe size/coil TR capacity, complete all as specifed and directed.
25 mm dia.
32 mm dia.
40 mm dia.
Pot Strainer Supply, installation, testing and commissioning of Pot - Strainer of the following sizes, complete all as specifed and directed.
150 mm dia
125 mm dia
Supply, installation, testing and commissioning of alcohal fitted 'V' form thermometer, complete all as specifed and directed. (For Floor Mounted AHU, Chiller and All Pumps)
Supply, installation, testing and commissioning of pressure guage, complete all as specifed and directed. (For Floor Mounted AHU, Chiller, and All Pumps)
Supply, installation, testing and commissioning of auto air vent valve of 25 mm dia auto air vent valve, complete all as specifed and directed.
Expansion Bellow / Flexible Connectors Supply and installation of rubber flexible connection at the pump inlet and outlet complete with flanged joints, nuts, bolts and gasket. The flexible connectors shall be with AISI 321 SS corrugated tubing with AISI 304 SS single overbraid and SS fittings, complete all as specifed and directed..
125 mm connection
80 mm connection
Supply, Installation, Testing and Commissioning of Probe Type Flow Meter to measure the Condenser and Chilled water Flow., complete all as specifed and directed.
125 mm dia for Condenser water Pipe.
100 mm dia for Chilled water Pipe.
Supply and Fixing Anti Corrosive Treatment for Buried and Exposed Pipes Supply and installation of pipe treatment for buried UG piping complete with 500 gauge polythene sleeve wrapped to the pipe One layer of tarfelt stuck with hot bitumen and all joints sealed with bitumen. 2mm thick tarfelt, complete all as specifed and directed.
125 mm dia
100 mm dia.
Chilled Water Pipe Insulation Supply and installation of Insulation on chilled water piping with Class-O Closed Cell Elastomeric Nitrile Rubber with pre covered with Arma Check-GC (Black) resistant film faced polyethylene pipe sectionsof specified thickness in the tender specification and suitable for indoor application., complete all as specifed and directed.
100 mm dia (32 mm Thickness)
80 mm dia (32 mm Thickness)
65 mm dia (32 mm Thickness)
50 mm dia (32 mm Thickness)
40 mm dia (32 mm Thickness)
32 mm dia (25 mm Thickness)
25 mm dia (25 mm Thickness)
DRAIN PIPE INSULATION Supply and installation of Insulation on chilled water piping with Class-O, Closed Cell Elastomeric Nitrile Rubber with with pre covered with Arma Check-GC (Black) resistant film faced polyethylene pipe sectionsof specified thickness in the tender specification and suitable for indoor application., complete all as specifed and directed.
50 mm dia (19 mm Thickness)
40 mm dia (19 mm Thickness)
32 mm dia (19 mm Thickness)
25 mm dia (19 mm Thickness)
CHILD WATER VALVE INSULATION Supply and installation of Insulation on valves same as per on chilled water pipe sizes. Thickness of Insulation used on valves is same which is used on the pipe sizes as under., complete all as specifed and directed.
Butterfly Valves (PN-16), 80 mm dia
Butterfly Valves (PN-16), 100 mm dia
Check Valves (PN-16), 80 mm dia
Check Valves (PN-16), 100 mm dia
Y-Strainer (PN-16), 80 mm dia
Y-Strainer (PN-16), 100 mm dia
Ball Valves (AHU), 25 mm dia
Ball Valves (AHU), 32 mm dia
Ball Valves (AHU), 40 mm dia
2-Way Control Valve (For AHU), 25 mm dia
2-Way Control Valve (For AHU), 32 mm dia
2-Way Control Valve (For AHU), 40 mm dia
DUCT INSULATION Supplying and fixing of following thickness duly laminated aluminum foil of mat finish closed cell Nitrile rubber (class “O”) insulation on existing duct after applying two coats of cold setting adhesive (CPRX compound). The joints shall sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required., complete all as specifed and directed.
9 mm thick
25 mm thick
ACOUSTIC LINING OF DUCTS Supply and Application of accoustic lining on the supply air duct with 15 mm thick open cell nitrile rubber as per specification, complete all as specifed and directed.
UNDER DECK INSULATION OF EXPOSED ROOF Supply and installation of Underdeck Thermal insulation with 32 MM closed cell nitrile rubber insulation with adhesive including all accessories like GI strip /with screw/dash fasteners and sealed with imported black tape of 50 mm width as per specifications., complete all as specifed and directed.
ACOUSTIC LINING OF PLANT ROOM Supplying and Installation, of acoustic lining on wall and ceiling of AHU rooms/Plant room with 50mm (25+25mm) thick Rigid Board of Glasswool one side aluminum faced and other side black glass cloth lamination, density 70 to 80 kg/m3 has to be fitted directly on the wall of the room with the help of screw (2 inch) and GI washers (3 inch x 3 inch) and PVC Gitti (1 inch). Please note that if the acoustic board has been placed with the help of GI washer, it has to be painted in black color to match the cloth color. The accoustic board should be placed in such a way that black glass cloth is visible from inside the plant room, complete all as specifed and directed.
AIR DISTRIBUTION Site Fabricated GI Duct Supply, installation, balancing and commissioning of Site fabricated GSS sheet metal rectangular ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness , complete all as specifed and directed.
24 gauge
22 gauge
Site Fabricated Aluminium Ducting (FOR OT) Supply, fabrication, installation and testing of Aluminium sheet metal ducting duly polysulphide sealed complete with Spliter Damper, vanes etc. as required for OT and as per ISI specifications and as per approved, complete all as specifed and directed.
22 gauge
20 gauge
18 gauge
ALUMINIUM MOTORISED DAMPER (FRESH AIR/EXHAUST AIR FOR OT ONLY) Supply, installation , testing and commissioning of motorised extruded aluminium dampers for fresh air induction actuated by CO2 sensors as per the approved shop drawings and specifications, complete all as specifed and directed.
Bare Dampers
Supply, installation , testing and commissioning of Actuator complete with control/power wiring between the actuator and indoor unit to shut off / switch on the dampers in the event of indoor unit getting switched off/ on . Electrical contractor will only supply power at 230V, 50Hz AC supply at a Junction box near each fire damper and fire alarm contractor will provide potential free relay contacts, near fire damper. The onward power wiring, control wiring and any step down transformers for 230V stepping down to usable voltage for fire damper, damper relay control box / auxiliary relays for tripping etc. need to be considered as part of supply and installation of fire dampers (i.e. in the scope of AC Contractor. Electrical contractor shall provide power in a junction box in the vicinity of 0.45M from each fire damper. The wiring and MS / GI Conduiting from the Junction box to fire damper / Control panel shall be part of fire damper supply and installation (i.e. in the scope of AC Contractor). Since fire dampers are to be interlocked with the fire alarm system, control cabling and MS / GI Conduiting from the nearest fire detection systems relay control module shall be part of the fire damper supply and installation (i.e. in the scope of AC Contractor). A control wiring length of maximum 3.5 meter to be considered for each fire damper (within the AHU Room). AC Contractor to co-ordinate with other agencies and ensure correct linkage, interlockings and operation of each fire damper on receiving a fire signal., complete all as specifed and directed.
FLEXIBLE CANVASS Supply,Installing,testing of fire retardant double flexible canvass connector 150 mm deep made of imported FIBER GLASS WEAVE fabric with Silicon Rubber Coating and 30 mm Extruded Aluminium Frame., complete all as specifed and directed.
ALUMINIUM CONSTRUCTION DUCT VOLUME CONTROL DAMPERS - MANUAL Supply, installation, testing and commissioning of AL. volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc, as per specifications or as directed by GE
SUPPLY AIR GRILLE WITH AL. VCD Supplying and fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers, complete all as specifed and directed.
RETURN AIR GRILLE WITHOUT AL. VCD Supplying and fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers, complete all as specifed and directed.
SUPPLY AIR DIFFUSER WITH AL. VCD Supplying, fixing testing commissioning of supply air diffusers of powder coated aluminium with aluminium volume control dampers with anti smudge ring and removable core, complete all as specifed and directed.
RETURN AIR DIFFUSER WITHOUT AL. VCD Supplying, fixing testing commissioning of Return air diffusers of powder coated aluminium without volume control dampers with anti smudge ring and removable core (300mm X 300mm), complete all as specifed and directed
FRESH AIR LOUVERS WITH Al. DAMPERS WITH BIRD SCREEN Supply, installation, testing and balancing of Powder coated/Anodised extruded aluminium construction inlet air louvers with bird screen and volume damper for fresh air as per specifications and approved shop drawings., complete all as specifed and directed
EXHAUST AIR LOUVERS WITHOUT DAMPERS WITH BIRD SCREEN Supply, installation, testing and balancing of Powder coated/Anodised extruded aluminium construction louvers with bird screen for exhaust air as per specifications and approved drawings., complete all as specifed and directed
AL. VCD'S FOR LINER GRILL SUPPLY AIR SHUTES. Supply, installation, testing and balancing of Aluminium key operated volume control dampers for supply air shutes of liner grills. , complete all as specifed and directed
BACK DRAFT DAMPER Supply, installation, testing and balancing of galvanized Iron Back draft damper construction at outlet of fan as per specifications and approved shop drawings., complete all as specifed and directed
1 Nos. 40A TPN feeder having one no. 40A TP MCCB and ON/ OFF indication. The starter shall use all for 415 VAC, 3 phase, 50 Hz, 3phase 4wire supply system. The panel shall have 1No. DOL Starter feeder with single phase preventer and outgoing feeder to pump motor (1 no. 10HP) with MCCB and contactor switch gears rating as per type II co-ordination alongwith 1no ammeter and 1no. matching cast resin CT including Start/Stop push bottons, toggle switch for `ON'/`TRIP' status of motor complete in all respect. (Hot water pumps) Necessary cable alleys, space for spare switches, internal wiring, control wiring/cabling and copper earthing of all equipment shall also be included. All switches and other components shall be motor duty rating. Spare 2 Nos 160 amps TPN MCCB Spare 2 Nos 63 amps TPN MCCB
All starters shall be provided with suitable potential free contact for connections to the Building Automation System. 3 Nos of Single Pole MCB's Shall be provided at the incoming section of the starter panel for DDC Panel , fire damper actuator and as a spare. 220 / 24 V Transformer (as required by application)
Supply and Fixing of Suitable Size MPCB for 2HP, complete all as specifed and directed.
Supply and Fixing of Suitable Size MPCB for 5 HP for supply Air Blower and 2 HP for Ex. Air Blower for OT AHU., complete all as specifed and directed.
POWER and CONTROL CABLING Supply, laying, testing and commissioning of power and control cabling as per specification given in the tender.A) Power cabling (XLPE insulated Aluminium conductor armoured cables of 1.1 KV Grade) including cable end termination with brass compression glands and aluminium lugs etc as per specification., complete all as specifed and directed
3.5 Core, 25 Sq. mm
4 Core, 16 Sq. mm
4 Core, 10 Sq. mm
4 Core, 6 Sq. mm
4 Core, 4 Sq. mm
Supply and Fixing Control cabling (PVC insulated Copper conductor of 1.1 KV Grade armoured cable), complete all as specifed and directed.
3 Core, 1.5 Sq. mm
4 Core, 1.5 Sq. mm
5 Core,1.5 Sq. mm
Supplying, fixing and laying of heavy duty PVC conduit in ceiling, wall panelling or partitions etc. includes all chase cutting and making the surface good alongwith the 2mm dia size GI pull wire complete with all the accessories, of 25 mm dia., complete all as specifed and directed.
Supply and Fixing of Earthing Strip / Wires as per specifications , complete all as specifed and directed..
Supply and Fixing of 32 x 6 mm GI strip recess / surface as strip earth lead including soldering etc. as required.
Supply and Fixing of 25 x 3 mm GI strip recess / surface as strip earth lead including soldering etc. as required.
Supply and Fixing of 4 mm dia. copper wire or in recess for loop earthing as required.
Supply and Fixing of 6 mm dia. copper wire or in recess for loop earthing as required.
Cable Tray Supply and Fixing, Fabricating and installing following size of G.I. perforated Cable trays including horizontal and vertical bends, reducers, tees, cross members and other accessories as required and duly suspended from the ceiling with suspenders etc as required., complete all as specifed and directed.
100 mm wide x 50 mm x 1.6 mm
150 mm wide x 50 mm x 1.6 mm
300 mm wide x 50 mm x 1.6 mm
450 mm wide x 50 mm x 2 mm
600 mm wide x 50 mm x 2 mm
SCH 'A' PART- XXI : REFRIGERATOR Note : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
Supply, installation, testing and commisioning of refrigerators, electric driven (Single Phase), Capacity 180 Ltrs., complete all as specifed and directed.
Supply, installation, testing and commisioning of Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type and designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of +/- 2.5% and of capacity 2 KVA, complete all as specifed and directed.
SCH 'A' PART- XXII : LIFT WORK Note : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
Supply, Installation, testing, commissioning of 15 Passenger Lift at OPD Block with 5 Stops With (all opening on the same side) , complete all as specifed and directed. CAPACITY (kgs) : 1020 Kg, 15 persons. SPEED (mps) : 1 mps RISE (m ) : 17 m STOPS : 5 Stops With (all opening on the same side) CONTROLLER TYPE : ACD3-MRL DRIVE : VF Regenerative (Closed Loop) POWER SUPPLY : 400/415 Volts (3 Phase AC) OPERATION : Full collective operation CAR GROUP : One car (simplex) MACHINE : PM Gearless (Located in shaft on top of guide rails) TRACTION MEDIA : Flat Coated Steel Belt CAR FINISH : Rear Mid Panel = Stainless Steel Rear Corner Panels = Stainless Steel Side Mid Panels = Stainless Steel Side Corner Panels = Stainless Steel Front Panels = Stainless Steel FLASE CEILING FINISH : Stainless Steel VENTILLATION : Cross flow fan HAND RAILS : Stainless Steel Mirror Finish Handrails on rear car panels FLOORING : PVC VINYL TILES CAR DOOR FINISH : Stainless Steel LANDING DOORS FINISH : Stainless Steel FIRE RATED DOORS : Fire rating-60mins PIT DEPTH : 1600 OVERHEAD 4400
HOISTWAY DIMENSIONS (W x D – mm) : 1950 mm W x 3000 mm D CAR DIMENSIONS (W x D x H - mm) : 1000 mm W x 2400 mm D x 2300 mm D CAR and HOISTWAY DOOR TYPE : Telescopic 2 speed doors DOOR OPENING (W x H - mm) : 900 mm W x 2100 mm H DOOR OPERATOR : DC Door Operator COP : COP for stops <= 12 (950mm) in Stainless Steel CAR POSITION INDICATOR : Monochrome LCD-Blue Background and White font Dot matrix (LED) Scrolling Display HALL BUTTON ARRANGEMENT : LCD Monochrome type STANDARD FEATURES : Anti-nuisance Car Call Protection Independent Service (for Duplex only) Overload Device Nudging Emergency Firemen’s Service Emergency Car Light UnitInfrared Curtain DoorProtection Door Time Protection Emergency Alarm Button Extra Door Time of Lobby and Parking Door Open/Close Button Manual Rescue Operation Belt Inspection Drive Auto Fan Cut Off
Supply, Installation, testing, commissioning of 15 Passenger Lift at OT Block with 4 Stops With (3 opening on the same side, 1 opening on both side) complete as per particular specifications or as directed by GE CAPACITY (kgs) : 1020 Kg, 15 persons. SPEED (mps) : 1 mps RISE (m ) : 14 m STOPS : 4 Stops With (3 opening on the same side, 1 opening on both side) CONTROLLER TYPE : ACD3-MRL DRIVE : VF Regenerative (Closed Loop) POWER SUPPLY : 400/415 Volts (3 Phase AC) OPERATION : Full collective operation CAR GROUP : One car (simplex) MACHINE : PM Gearless (Located in shaft on top of guide rails) TRACTION MEDIA : Flat Coated Steel Belt CAR FINISH : Rear Mid Panel = Stainless Steel Rear Corner Panels = Stainless Steel Side Mid Panels = Stainless Steel Side Corner Panels = Stainless Steel Front Panels = Stainless Steel FLASE CEILING FINISH : Stainless Steel VENTILLATION : Cross flow fan HAND RAILS : Stainless Steel Mirror Finish Handrails on rear car panels FLOORING : PVC VINYL TILES CAR DOOR FINISH : Stainless Steel LANDING DOORS FINISH : Stainless Steel FIRE RATED DOORS : Fire rating-60mins PIT DEPTH : 1600 OVERHEAD 4400
HOISTWAY DIMENSIONS (W x D – mm) : 2030 mm W x 3000 mm D CAR DIMENSIONS (W x D x H - mm) : 1000 mm W x 2400 mm D x 2300 mm D CAR and HOISTWAY DOOR TYPE : Telescopic 2 speed doors DOOR OPENING (W x H - mm) : 900 mm W x 2100 mm H DOOR OPERATOR : DC Door Operator COP : COP for stops <= 12 (950mm) in Stainless Steel CAR POSITION INDICATOR : Monochrome LCD-Blue Background and White font Dot matrix (LED) Scrolling Display HALL BUTTON ARRANGEMENT : LCD Monochrome type STANDARD FEATURES : Anti-nuisance Car Call Protection Independent Service (for Duplex only) Overload Device Nudging Emergency Firemen’s Service Emergency Car Light UnitInfrared Curtain DoorProtection Door Time Protection Emergency Alarm Button Extra Door Time of Lobby and Parking Door Open/Close Button Manual Rescue Operation Belt Inspection Drive Auto Fan Cut Off
Supply, Installation, testing, commissioning of 20 Passenger Lift at OPD Block with 5 Stops With (all opening on the same side) complete as per particular specifications or as directed by GE CAPACITY (kgs) : 1360 Kg, 20 persons. SPEED (mps) : 1 mps RISE (m ) : 17 m STOPS : 5 Stops With (all opening on the same side) CONTROLLER TYPE : ACD3-MRL DRIVE : VF Regenerative (Closed Loop) POWER SUPPLY : 400/415 Volts (3 Phase AC) OPERATION : Full collective operation CAR GROUP : One car (simplex) MACHINE : PM Gearless (Located in shaft on top of guide rails) TRACTION MEDIA : Flat Coated Steel Belt CAR FINISH : Rear Mid Panel = Stainless Steel Rear Corner Panels = Stainless Steel Side Mid Panels = Stainless Steel Side Corner Panels = Stainless Steel Front Panels = Stainless Steel FLASE CEILING FINISH : Stainless Steel VENTILLATION : Cross flow fan HAND RAILS : Stainless Steel Mirror Finish Handrails on rear car panels FLOORING : PVC VINYL TILES CAR DOOR FINISH : Stainless Steel LANDING DOORS FINISH : Stainless Steel
FIRE RATED DOORS : Fire rating-60mins PIT DEPTH : 1600 OVERHEAD 4500 HOISTWAY DIMENSIONS (W x D – mm) : 2050 mm W x 2850 mm D CAR DIMENSIONS (W x D x H - mm) : 1800 mm W x 1700 mm D x 2400 mm D CAR and HOISTWAY DOOR TYPE : Telescopic 2 speed doors DOOR OPENING (W x H - mm) : 1100 mm W x 2100 mm H DOOR OPERATOR : DC Door Operator COP : COP for stops <= 12 (950mm) in Stainless Steel CAR POSITION INDICATOR : Monochrome LCD-Blue Background and White font Dot matrix (LED) Scrolling Display HALL BUTTON ARRANGEMENT : LCD Monochrome type STANDARD FEATURES : Anti-nuisance Car Call Protection Independent Service (for Duplex only) Overload Device Nudging Emergency Firemen’s Service Emergency Car Light UnitInfrared Curtain DoorProtection Door Time Protection Emergency Alarm Button Extra Door Time of Lobby and Parking Door Open/Close Button Manual Rescue Operation Belt Inspection Drive Auto Fan Cut Off
Supply, installation , testing and commissioning of LIFT PANEL - 1 with the following specifications, complete in all respect as specifed and directed. This will be floor mounted, free standing, indoor duty, dust proof, vermin proof, front operated, dead back access, electrical panel fabricated as per specifications laid in this document and will be complete with the extendable main and auxiliary bus bars, interconnection, earth bus and will be powder coated finish with 70 micron thickness. One number TPN incomer feeder comprising of 100A TP MCCB with electrostatic earth fault, short circuit releases with isolable neutral and ON/ OFF indication.. Digital flush type class-1.0 accuracy multifunction meter showing V, A, KWH, Frequency with 3 Nos. current transformers of 100/5 ratio, 15 VA Class 1.0 metering. Red/Green ON/OFF indicating lamps with 2A SP MCB backup protection. 1 set of three phase indicating lamps along with 2A SP MCB backup protection. Bus Bars: One set of TPN, Al. bus bar rated 150 Amps (after considering necessary deratings of 75%) for phases and neutral for half capacity of phases. Outgoings : 2 nos. 63 amps 10 kA 415 volt grade 4P MCB. 1 nos. 40 amps 10 kA 230 volt grade DP MCB. SPARE: 2 nos. 63 amps 10 kA 415 volt grade 4P MCB. 1 set of complete wiring
Supply, installation , testing and commissioning of LIFT PANEL - 2 with the following specifications, complete in all respect as specifed and directed. This will be floor mounted, free standing, indoor duty, dust proof, vermin proof, front operated, dead back access, electrical panel fabricated as per specifications laid in this document and will be complete with the extendable main and auxiliary bus bars, interconnection, earth bus and will be powder coated finish with 70 micron thickness. One number TPN incomer feeder comprising of 63A TP MCCB with electrostatic earth fault, short circuit releases with isolable neutral and ON/ OFF indication.. Digital flush type class-1.0 accuracy multifunction meter showing V, A, KWH, Frequency with 3 Nos. current transformers of 100/5 ratio, 15 VA Class 1.0 metering. Red/Green ON/OFF indicating lamps with 2A SP MCB backup protection. 1 set of three phase indicating lamps along with 2A SP MCB backup protection. Bus Bars: One set of TPN, Al. bus bar rated 150 Amps (after considering necessary deratings of 75%) for phases and neutral for half capacity of phases. Outgoings : 1 nos. 63 amps 10 kA 415 volt grade 4P MCB. 1 nos. 40 amps 10 kA 230 volt grade DP MCB. SPARE: 1 nos. 63 amps 10 kA 415 volt grade 4P MCB. 1 set of complete wiring
PART- XXIII : LIST OF WORKS AND PRICES FOR OT WORKS Note : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
2 Bay Scrub Station Automatic Supply, Installation and testing Of 2 bay scrub station made out of SS 304 complete with all accessories i.e. touch less imported sensor, imported thermostatic mixing valve, strainers and manual foot operated bypass system etc. 1400 mm, complete all as specifed and directed.
Plenum Laminar Air Flow Supply, Installation and testing Of Plenum Laminar Air Flow- Planer Ceiling System Size 2400 mm X2400 mm With Unidirectional Airflow , Plenum Unit, Holding Structure and Top Plenum Are Conforming To Din 4799 Standards For The Air Distribution System Complete . Diffusers Are Made Out Of Anodized Aluminums Perforation., complete all as specifed and directed.
Supply, Installation and testing Of Automatic Operated Hermetically Sealed Sliding Door (1500 mm Wide X 2100 mm Height) Complete With Glass Vision Window Of 300mm X 300 Mm With All Necessary Accessories Etc. , complete all as specifed and directed.
Supply, Installation and testing Of Automatic Operated Hermetically Sealed Sliding Door (1000 mm Wide X 2100 mm Height) Complete With Glass Vision Window Of 300mm X 300 Mm With All Necessary Accessories Etc., complete all as specifed and directed.
Surgeon Control Panel and Distribution Board Supply, Installation and testing Of Surgeon Control Panel with Touch Screen and 6 Features - Digital Time Clock Medical Gas Alarm Temperature and Humidity Display ON/OFF for Periphiral Lights Handsfree Telephone Day Clock (Digital), complete all as specifed and directed.
Led X-Ray Viewing Screen Supply, Installation and testing Of Two Plate X-Ray View Screen With Flicker Free Illumination Having Imported Led System For Uniform Illumination. The System Having Electrical Safety Codes For High and Low Voltage System., complete all as specifed and directed.
Pressure Relief Dampers Supply, Installation and testing Of Two Plate X-Ray View Screen With Flicker Free Illumination Having Imported Led System For Uniform Illumination. The System Having Electrical Safety Codes For High and Low Voltage System. , complete all as specifed and directed.
Led- Peripheral Lights Supply, Installation and testing Of Recess Mounted Sealed Ip54 Protocol, Non-Hygroscopic Peripheral Lights (2' X 1') Led Lighting System. These Lights Are Having Electrical Safety Code For Voltages , complete all as specifed and directed.
OT Pendent Supply, Installation and testing Of Double Arm Pendent Having Weight Carrying Capacity Of More Than 100kg, Console 600mm Long, Six Electrical Sockets 5/15 Ampere, one Monitor Tray Gas Outlets (6nos). , complete all as specifed and directed
Hatch Box Supply, Installation and testing Of Hatch box made of – SS304 Size 600X600X600, complete all as specifed and directed.
Total Amount of Sch 'A' Part - XXIV (INCINERATOR)
Total Amount of Sch 'A' Part - XXV (Lightening Protection)
Total Amount of Sch 'A' Part - XXVI (Conduit Pipe)
Total Amount of Sch 'A' Part - XXVII (Air Curtain)
Total Amount of Sch 'A' Part - XXVIII (Walk in Cooler)
Total Amount of Sch 'A' Part - XXIX (Solar Water Heater)
SCH 'A' PART- XXX : RAIN WATER HARVESTING Note : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
Construction of Soakage wells exc, in ordinary soil, foundation in PCC 1:3:6, wells of honey combed and solid in M-25 concrete, including intercepting chamber, screen chamber, brick work in CM, RCC cover slab in M-25/RR masonary/filling with brick bats, complete of size 3.6m dia x 6.00m deep , complete all as speicifed and shown on drawings and directed.
Total Amount of Sch 'A' Part - XXXI (Demolation and Dismantling)
SCH 'A' PART- XXXII : MISC ITEM WORK (HAND DRYER AND GATE) Note : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
Supply, Installation, testing, commissioning of Stainless Steel Wall mounted HAND DRYER complete as per particular specifications or as directed by GE
Schedule of Credit Deduct Schedule of credit worth Rs. 1208494.00 (Minus) as listed in Schedule 'A' Part - XXXIII Note : Tenderers will not quote against this item being a firm amount at present. Contract Sum will be worked out after deducting the credit schedule amount during acceptance of tender.
Chandra Construction
M/S MOOL RAJ SHARMA
Onkar Nath Bhalla And Sons Contractor Pvt. Ltd.
Komal Buildcon Pvt. Ltd.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid