Loading…
Loading…
| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹15.4 LAdmitted-Finance 21 10 SHOP NO 1 SECTOR 3 MAHABINI DELHI 110085 | NORTH WEST | DELHI | 110085 | L1 | Admitted-Finance | ||
| 2 | L2₹15.7 L+₹28,710.16 (1.86%)Admitted-Finance | L2 | Admitted-Finance | ||
| 3 | L3₹16.7 L+₹1.3 L (8.13%)Admitted-Finance NONE | L3 | Admitted-Finance | ||
| 4 | L4₹17.0 L+₹1.6 L (10.4%)Admitted-Finance | L4 | Admitted-Finance |
Tender Value
₹29.0 L
EMD Value
₹58,000
Closing Date
5 Mar 2026, 3:00 pmClosed
EE(E)
North Electrical Division, PWD, Dr. BSA Hospital, Sector -6, Rohini, Delhi - 110085
Upgradation of 17 Nos Type-II Flats in Sindhora Kalan under NESD II Delhi. SH E.I. Work
2026_PWD_287810_1
110/NED/PWD/M-352/2025-26
Open Tender
Electrical Works
Percentage
120 days
as per nit
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
₹58,000
Yes
9 Mar 2026
26 Feb 2026
5 Mar 2026
26 Feb 2026
5 Mar 2026
26 Feb 2026
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable in surface/ recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable etc. as required. a) Group A
Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required. a) 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
b) 2 X 4 sq. mm + 1 X 4 sq. mm earth wire
c) 2 X 6 sq. mm + 1 X 6 sq. mm earth wire
d) 2 X 10 sq. mm + 1 X 6 sq. mm earth wire
e) 4 X 4 sq. mm + 2 X 4 sq. mm earth wire
Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS/HFFR PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required. a) Group A
Supplying and drawing following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. a) 3 x 1.5 sq. mm
b) 6 x 1.5 sq. mm
c) 3 x 4 sq. mm
d) 6 x 4 sq. mm
e) 3 x 6 sq. mm
Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required. a) 20 mm
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. a) 5/6 A switch
b) 15/16 A switch
c) 3 pin 5/6 A socket outlet
d) 6 pin 15/16 A socket outlet
e) Bell push
Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required. a) 1 or 2 Module (75 mm x 75mm)
b) 3 Module (100 mm x 75 mm)
c) 4 Module (125mmX75mm)
d) 6 Module (200 mm x 75 mm)
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.
Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required.
Supplying & fixing suitable size GI box with modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, "C" curve including connections, painting etc. as required.
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) a) 16 way, Double door
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. a) Single pole
Supplying and fixing Cable End Box (Loose Wire Box) suitable for following single pole and neutral, sheet steel, MCB distribution board, 240 Volts, on surface/ recess, complete with testing and commissioning etc. as required. a) For 14 way, Double door SPN MCBDB
Supplying, Installation, Testing & Commissioning of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140- 270 Volt, frequency 50/60 hz, Operating temp range -5 °C to 40 °C, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10%, P.F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED, Driver & electrical circuitry), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6500°K (As per ANSI Bin), SDCM (Standard Deviation Colour Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard. Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in- Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body (Thickness > 1.20 mm) a) 36 watt
Supply, Installation, Testing and Commissioning of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal( Aluminium alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, suitable for operation with regulator for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 0C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC supply, Ceiling Fan compliant to IS 374:2019 fan i/c external connections with 1.5 sq.mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required. a) 1200mm, service value ≥ 6.0 CM/Min/Watt, air delivery 210 CM/Min (Minimum)
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. a) Upto 35 sq. mm (clamped with 1mm thick saddle)
Supplying and fixing ding dong call bell suitable for single phase, 230 volts, complete as required
Supplying & fixing of 9-10 watt batten type LED Mirror light fitting of length 2 feet with diffuser complete with all accessories including connection etc. as required.
Supplying and Installation of 300 mm sweep 900 rpm heavy duty exhaust fan alongwith aluminium louvers shutter in the existing opening, i/c making the hole suitable the size of the above fan making good the damage, connection testing commisioning with 1.5 Sqmm FR PVC insulated copper conductor single core cable etc as reqd.
Supplying and fixing roof ceiling fan round sheet cover on the existing junction box/ wooden block including connections etc. as required.
Supplying and fixing T cover on the existing junction box/ wooden block including connections etc. as required.
Supplying and Installation of 250 mm dia PVC ventilation / fresh air fan alongwith louvers including making the hole to suitable the size of the above fan i/c making good the damage, connections, testing, commissioning etc as reqd.
Supplying, Installation, testing and commissioning of pre-wired LED wall mounted Bracket fixture made up of polycarbonate,suitable for 9-10W LED lamp with B22 Base, having minimum 100 lumens per watt. CCT 5000K to 6000K, power factor >0.90, CRI > 70% , with 9-10W LED Lamp, complete with all accessories for mounting directly on wall including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required. a) 9-10 watts LED Wall Bracket Fitting
S.I.T.C of 10 W LED bulkhead fitting made out of CRCA sheet duly power coated/Cast Aluminum body, confirming to IP66, suitable for operation on 240 V, 50 Hz AC Supply having power factor ≥ 0.90, complete i/c making connection, testing and commissioning etc complete as reqd.
Supplying and fixing following rating, double pole, 240 volts, MCB in the existing MCB DB complete with connections, testing and commissioning etc. as required. a) 63 Amp DP MCB
Less credit for dismantle material received from the work. Copper Wire assorted
5/15 switch, socket, bellpush, regulator
Holder assorted
G.I. box assorted
SP, SPN, DP MCB Assorted
Ceiling fan
Ex. Fan
Ding dong/ Fish bell
DB Assorted
Batten light assorted
stage.html
html • 0.03 MB
technical_381498.pdf
techsummary_381498.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.95 MB
BOQ_381498.xls
BOQ • 0.43 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .