Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹30.2 LAccepted-AOC | L1 | Accepted-AOC L1 Bidder | |
| 2 | L2₹32.0 L+₹85,740 (2.75%)Rejected-AOC | L2 | Rejected-AOC Being not L1 | |
| 3 | L3₹32.9 L+₹1.8 L (5.65%)Rejected-AOC | L3 | Rejected-AOC Being not L1 | |
| 4 | L4₹33.2 L+₹2.1 L (6.66%)Rejected-AOC NO 133 RASHTRAPATHI ROAD SECUNDERABAD 500 003 | SECUNDERABAD | HYDERABAD | TELANGANA | 500003 | L4 | Rejected-AOC Being not L1 | |
| 5 | L5₹38.6 L+₹7.4 L (23.8%)Rejected-AOC | L5 | Rejected-AOC Being not L1 |
Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
15 Sept 2022, 6:00 pmClosed
Shri M Saravanan, IDSE, GE
Garrison Engineer North 35 Allenby Lines Secunderabad 500087
REPAIRS REPLACEMENT OF UNSV MAIN DISTRIBUTION BOARD ALONGWITH SUBMAIN WIRING AND CONNECTED ITEMS INCLUDING REPAIR REPLACEMENT OF INTERNAL WIRING FIXTURES IN MAP ACCN IN BOWENPALLY UNDER AGE E M N OF GE NORTH SECUNDERABAD
2022_MES_546153_1
8606
Open Tender
Electrical and Maintenance Works
Item Rate
300 days
GARRISON ENGINEER NORTH SECUNDERABAD
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GARRISON ENGINEER (NORTH) SECUNDERABAD
₹80,000
Yes
1 Nov 2022
18 Aug 2022
17 Sept 2022
18 Aug 2022
15 Sept 2022
1 Sept 2022
Amount
Taking down existing unserviceable point wiring of any description/type/ size of light/fan/power/two way /bell etc., on TW batten/conduit including removal of batten / conduit / gutties / wooden boards / switches / sockets / regulators/ light fittings etc., and removal of unserviceable material out of site area and making good the disturbed surfaces of wall/ceiling complete all as specified and as directed.
M & L for Point wiring with 1.5 Sqmm FRLS copper conductor single core PVC insulated sheathed 1100 V multistranded drawn through existing conduit and including rigid 20 mm PVC conduit and conduit accessories of suitable dia medium grade and modular accessories including fixing/grouting sunken/ surface along with existing flush box of suitable thickness covered with suitable modular cover plate including running up of 1.5 Sqmm FRLS copper conductor PVC insulated cable as earth continuity conductor along with wiring and connecting to the common earth dolly for fixing the switches/ sockets/ regulators etc., complete all as specified and as directed for one Light/Fan/Bell Point Controlled by One Switch NOTE: 1. Modular Cover Plate is inclusive of the rated quoted by the contractor 2. Cutting & Chases will be measured and paid separately
All as per Sl item No 2 here in before, but for one 3 pin 5 Amps switch socket outlet point controlled by one switch on independent board complete all as specified and as directed.
All as per Sl item No 2 here in before, but for one 3 pin 5 Amps switch socket outlet point controlled by one switch on the same board complete all as specified and as directed.
All as per Sl item No. 2 here in before, but for using 2.5 Sqmm single core copper conductor cable of multistranded PVC insulated sheathed FRLS 1100 Volts grade for 3 Pin 15 Amps switch socket combination point on independent board including running of 2.5 Sq mm FRLS copper conductor PVC insulated cable as earth continuity conductor complete all as specified and as directed.
S & F single pole Modular switch 1 way 10 Amps, 1 Module complete all as specified and as directed.
S & F single pole Modular switch 1 way 16 Amps, 1 Module complete all as specified and as directed.
S&F Modular Bell Push 10A, 1 Module complete all as specified and as directed.
S & F socket outlet modular type multipurpose 2/3 Pin, 6 amps, 230 volts combined 2 Module complete all as specified and as directed.
S & F socket outlet modular type multipurpose 2/3 Pin, 6/16 amps, 230 volts combined 2 Module complete all as specified and as directed.
S & F Modular ceiling fan regulator stepped type heavy duty suitable to work on 230 volts, 2 Module complete all as specified and as directed.
M & L for Point wiring with 1.5 Sq mm copper conductor single core PVC insulated FRLS 1100 Volts multistranded drawn through and including 20 mm rigid PVC conduit surface and conduit accessories of suitable dia medium grade on existing pressed steel terminal boxes including fixing/grouting sunken/ surface as per site requirement covered with suitable laminated sheet for fixing switches / sockets/ regulators etc including running up of 1.5 Sq mm FRLS copper conductor PVC insulated cable as earth continuity conductor along with wiring and connecting to the common earth dolly complete all as specified and as directed for one light/fan/bell point controlled by one, one way switch 5 amps, SP Note: Cutting/chases will be measured and paid separately
All as per Sl item No 12 here in before, but for One 3 pin 5 Amps switch socket outlet point controlled by one switch on independent board complete all as specified and as directed.
All as per Sl item No 12 here in before, but for One 3 pin, 5 Amps switch socket outlet point controlled by one switch on the same board complete all as specified and as directed.
All as per Sl item No. 12 here in before, but for using 2.5 Sqmm single core copper conductor cable of multistranded PVC insulated sheathed FRLS 1100 Volts grade for 3 Pin 15 Amps switch socket combination point on independent board including running of 2.5 Sq mm FRLS copper conductor PVC insulated cable as earth continuity conductor complete all as specified and as directed.
S & F switch piano single pole flush type 5 amps, 230 volts complete all as specified and as directed.
S & F bell push 5 A flush type complete all as specified and as directed.
S & F socket outlet flush type multipurpose 2 in 1, 3 Pin, 5 amps, 230 volts complete all as specified and as directed.
S & F switch socket combination flush type multipurpose 2/3 pin 5 amps 2 in 1 230 Volts complete all as specified and as directed.
S & F switch socket combination 2 in 1 multipurpose 3/5 pin 5/15 amps flush type with complete all as specified and as directed.
S & F electronic type regulator stepped heavy duty for ceiling fan suitable to work on 230 volts complete all as specified and as directed.
S&F bell ding dong working on 230 volts AC complete all as specified and as directed.
S & F in replacement of wall mounted LED batten of 10 watt with LED Lamp, extruded aluminium heat sink provided for efficient heat dissipation & integrated electronic driver and connecting to all accessories from ceiling rose to fitting complete all as specified and as directed. Make: Havells Model LUMILINEBS9WLED 865SPCWH or equivalent in Wipro/Phillips/Shakti.
S & F in replacement of wall mounted box type LED batten suitable for 20 watts with LED tube 20 watts lamp along with integrated driver and connecting to all accessories from ceiling rose to fitting complete all as specified and as directed. Make:Havells REGALBATTENT8UPTO1X22WD SBSWH & Tube rod Cat No PHOTONULTRAE 2.01213T8SSTL18WLED865SPC or equivalent in Wipro/Phillips/Shakti.
Dismantling/taking down old/UNSV distribution panel and supply, fixing and testing of indoor 3 phase LT distribution panel board factory, made out of 2mm thick CRCA sheet CPRI approved of size not less than 600x450x200mm duly powder coated wall mounted/semi grouted in wall with locking arrangement double door type, compartmentalised and provision for tapping incoming & outgoing electric connections with suitable size of copper nut bolts & lugs, glands, one MCCB will be pre fitted/mounted on proper din rails and with earth link at top/bottom detachable plates and suitable for accommodating complete all as specified and as directed including the following items :- (a) Copper bus bar strips for TPN of 200 amps rating (min length of 300mm) and connected with MCCB by spreader terminals. ( set of 4 strips). (b) Phase indicating lamp LED type - one set of 3. (c) MCCB 4 pole, 100 Amps rating 25/26 KA breaking capacity, 415 volts - 01 No. ( Make - HPL/C&S/Standard/) (d) MCB SPN 10 Amps 240 Volts 'C' curve - 01 No.
Dismantling/taking down old/unserviceable distribution panel and supply, fixing and testing of indoor 3 phase LT distribution panel board factory, made out of 2mm thick CRCA sheet CPRI approved of size not less than 600x450x200mm duly powder coated wall mounted/semi grouted in wall with locking arrangement double door type, compartmentalised and provision for tapping incoming & outgoing electric connections with suitable size of copper nut bolts & lugs, glands, one MCCB will be pre fitted/mounted on proper din rails and with earth link at top/bottom detachable plates and suitable for accommodating and including the following items :- (a) Copper bus bar strips for TPN of 200 amps rating (min length of 300mm) and connected with MCCB by spreader terminals. ( set of 4 strips). (b) Phase indicating lamp LED type - one set of 3. (c) MCCB 4 pole, 63 Amps rating 25/26 KA breaking capacity, 415 volts - 01 No. ( Make - HPL/C&S/Standard/) (d) MCB SPN 10 Amps 240 Volts 'C' curve - 01 No.
S & F in replacement of MCB SP 6 to 32 Amps 240 volts for fixing on MCB DB's complete all as specified and as directed. Make : Havells - Cat No DHMGCSPF006-032, Standard Cat No - DSMGCSPF006-032, C&S Cat No - CSMBS1C6-32N.
S & F in replacement of MCB SPN 40 Amps 240 volts for fixing on MCB DB's complete all as specified and as directed. Make : Havells Cat No DHMGCSNF040, Standard Cat No - DSMGCNF040, C&S Cat No - CSMBS1C40N.
S & F in replacement of MCB Four pole, 415 volts suitable for fixing on MCB DB of capacity 63 Amps complete all as specified and as directed. Make : Havells Cat No - DHMZCTNF063, Standard Cat No - DSMGCTNF063, C&S Cat No - CSMBS3C63N.
S & F sheet metal enclosure MCB DB SPN 8 way with 200 amps rated bus bar 240 volts double door with locking system complete including taking down unserviceable DB complete all as specified and as directed. Make : Havells - CAT Part No DHDPSHODRWO8, Standard Cat No - DSDCSHODOW08, C&S Cat No - CSDBSPNPDD08.
All as per Sl item No 30 here in before, but SPN 12 way DB complete all as specified and as directed. Make : Havells - CAT Part No DHDPSHODRW12, Standard Cat No - DSDCSHODOW12, C&S Cat No - CSDBSPNPDD12.
S & F in replacement of horizontal type TPN DB 4 way double door made out of CRCA sheet housing with powder coating & conforming to IS 13032, IS 8623, BS 5486 accommodated suitably in a MS enclosure weather proof made out of 3 mm thick MS sheet having hinged and robust locking arrangement including painting by red-oxide one coat and powder coated complete including taking down unserviceable DB complete all as specified and as directed. Make : Havells - CAT Part No DHDNTHODAW04, Standard Cat No - DSDNTSODAW04, C&S Cat No - CSDBTPNHPDD04.
S & F vertical type TPN distribution board of 4 way double door with incoming MCCB TPN 415 volts AC, 3 phase, 50 Hz, 25 KA Breaking Capacity with fixed magnetic setting for current ranging of capacity 100 Amps including MCCB 4P conforming to IS 13947 (P-2) IEC: 947 made out of CRCA sheet housing with powder coated confirming to IS 13032, IS 8623, BS 5486 accommodated suitably in a mild steel enclosure weather proof mild steel sheet having hinged and robust locking arrangement including painting by red-oxide one coat and duly powder coated complete including taking down unserviceable DB complete all as specified and as directed. Make: C & S cat Part No. CSDBMCCB100DD 04IP43S or equivalent in Havells/Standard.
S & F in replacement of Modular Single pole and Neutral enclosure (Modular AC Box) with a two pin and earth plug and socket complete with one single pole MCB 25 Amps (AC Box) complete all as specified and as directed.
Supply & replace MCB Three pole, 415 volts suitable for fixing on MCB DB of capacity 63 Amps complete all as specified and as directed.
M & L for Submain wiring with 2 runs of single core 4 sqmm PVC insulated sheated multistranded FR 1100 volts grade with copper conductor drawn through existing non-metallic rigid PVC conduit and conduit accessories of medium grade not not less than 25mm dia including one run of single core 4 sqmm PVC insulated sheated multistranded 1100 volts grade with copper conductor cable as earth continuity conductor along with the wiring and connected from DB to DB/main board including removing the existing unserviceable submain wiring complete all as specified and as directed. Note: 3 runs of 4 Square mm cable and 1 run of PVC conduit with accessories shall be measured as 1 unit of running metre.
All as per Sl item No 36, but 2 runs of single core 6 Sqmm and one run of single core 6 Sqmm as earth continuity conductor complete all as specified and as directed. Note: 3 runs of 6 Sqmm cable and 1 run of PVC conduit with accessories shall be measured as 1 unit of running metre.
S & F in replacement of LED security Light luminaire 24/25 watts with deep drawn housing including all accessories and Lamp, with suitable pipe bracket 25 mm dia 0.60 Mtr length fixed on wall with suitable flat iron clamps and nut bolts complete all as specified and as directed. Make: Havells Cat No - ENDURASUNDOWN SL25WLED765PASYBOPCIHD or equivalent in Wipro/Phillips/Shakti.
Material and labour for earthing with galvanized mild steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground vertically to a depth not less than 2.25 metres below ground level, the top edge of the earth plate at a depth of not less than 1.5 metres below ground level connected to galvanized iron earth wire of 4 mm dia by means of bolts, nuts and washers made out of GI / steel earth wire protected by GI light grade pipe 15 mm bore, 20mm dia light grade galvanised iron pipe with funnel wire mesh for watering and connecting to main switch board / control board all s shown in electrical plate of SSR Pt - I connected to earthing test point and including testing on completion complete all as specified and as directed. NOTE: The unit rate shall also include for excavation, earth work in hard/dense soil, plain cement concrete 1:3:6 type C1 by using 20 mm graded aggregate in pit, 50 mm thick reinforced cement concrete 1:2:4 type B1 using 20 mm graded aggregate cover duly reinforced with 8 mm dia TMT bars @ 100mm centre to centre both ways, PCC cover galvanised iron funnel with watering pipe, wire mesh, complete.
M&L for earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc., as required 4mm dia galvanised iron or steel wire complete all as specified and as directed.
M&L for Cutting chases, pinning in making good to facings where required and pointing in cement mortar 1:3 to ends or edges of andings, steps, cills, sunshades, shelves, lintels, etc., and cutting chases for concealed water tubing or concealed conduit wiring, etc., and making good, cutting not exceeding 10 cm girth complete all as specified and as directed.
M&L for taking down ceiling fans 48”/56” sweep or exhaust fans upto 300mm, removing/cleaning of dust properly cleaning, greasing & overhauling of bearings including refixing in same location and connecting up complete all as specified and as directed. Note : Replacement of defective/worn out parts will be measured & paid for separately.
Supply & replace 2.00/2.50 Mfd capacitor complete all as specified and as directed.
Supply & replace ball bearing/Gun Metal Bush of existing ceiling fans of 1200/1400mm sweep on site complete all as specified and as directed.
Material and labour for rewinding of burnt ceiling fan motor of size 48"/56" sweep with super enameled copper wire of suitable size as per details given below of any make, type, model including transportation complete all as specified and as directed.
S&F in replacement of plastic body including louvers 200 to 300 mm size fan complete all as specified and as directed.
S&F in replacement of motor of plastic body exhaust fan 200 to 300mm size complete all as specified and as directed.
Taking down the geysers of capacity 25/35 from its mounting position by removing all water and electric connections and de-assembling the geyser after carrying out the following works complete all as specified and as directed:- (a) Descaling, cleaning the inner tank thoroughly and there should not be any bad taste of water. (b) Examining the water tightness of storage tank after cleaning. (c) Examining the physical condition of thermostat, base assembly fusible plug and outer tank for its serviceability. (d) Inspection of pilot lamps. (e) Reassembling the geyser parts and testing including checking all electrical system (ensuring there is no current leakage) and also conducting hydraulic testing. (f) Re-fixing the Geyser and making electric connections, inlet and outlet water connections and testing and checking of all water inlet, outlet valves connected with geysers. Note : Defective /worn out parts if required shall be measured and paid separately under relevant items in this schedule.
Supply and fix rubber PVC connection of 2 feet complete all as specified and as directed.
Supply & fix rubber PVC connection of 3 feet complete all as specified and as directed.
Supply & fix MS base plate cup any type with screws of suitable size as per requirement complete all as specified and as directed.
Supply & fix heating element of the 1/1.5 KW rating as required at site including rubber washers of any make and type complete all as specified and as directed.
Supply & fix heating element of the 2 KW rating as required at site including rubber washers of any make and type complete all as specified and as directed.
Supply & fix Steel inner tank of 25 litre capacity geyser tank by made out of steel sheets appropriate thickness complete all as specified and as directed.
Supply & fix thermostat suitable for the geysers of 25 to 35 Liters capacities complete all as specified and as directed.
Supply & fix auto cut suitable for the geysers of 25 Liters capacities complete all as specified and as directed.
Supply & replace Air Release Valve suitable for geyser 25/50 ltrs complete all as specified and as directed.
S&F in replacement of 1100 Volt grade cable flexible 3 core PVC insulated PVC sheathed with stranded copper conductor of size 2.5 Sqmm complete all as specified and as directed.
M/S P UDAY RAJ CONSTRUCTION
gsrinivasarao
THE DECAN ENGINEERING AND REFRIGERATION COMPANY
VISHAL CONSTRUCTIONS
Universal refrigeration and Engineering Company
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .