Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹18.8 LAccepted-AOC | L1 | Accepted-AOC Being Lowest | |
| 2 | L2₹22.9 L+₹2.8 L (14.1%)Rejected-Finance 212 B 8 PARDEWANPUR LAL BANGLA KANPUR 208007 | KANPUR | KANPUR NAGAR | UTTAR PRADESH | 208007 | L2 | Rejected-Finance Other than lowest | |
| 3 | L3₹24.2 L+₹4.2 L (20.8%)Rejected-Finance 11 82 GROUND FLOOR BLOCK 11 KALYANPURI EAST DELHI DELHI 110091 | EAST DELHI | DELHI | 110091 | L3 | Rejected-Finance Other than lowest | |
| 4 | L4₹25.7 L+₹5.6 L (28.1%)Rejected-Finance BHU | L4 | Rejected-Finance Other than lowest | |
| 5 | L5₹28.0 L+₹7.9 L (39.5%)Rejected-Finance | L5 | Rejected-Finance Other than lowest |
Tender Value
₹30 L
EMD Value
₹60,000
Closing Date
21 Sept 2023, 6:00 pmClosed
GE (AF) E/M CHAKERI KANPUR
GE(AF) EM Chakeri
REPAIR/MAINT/REPLACEMENT OF U/S LT PANEL/FEEDER PILLAR BOX , U/S UG CABLES, REROUTING OF CABLE AND OTHER CONNECTED WORKS AT 7 AFH KANPUR.
2023_MES_615289_1
8646/E8
Open Tender
Civil Works
Item Rate
180 days
Area under GE(AF) EM Chakeri
As per tender documents
9 documents required · 9 mandatory
₹500
GE (AF) E/M CHAKERI
₹60,000
Yes
17 Nov 2023
23 Aug 2023
27 Sept 2023
24 Aug 2023
21 Sept 2023
8 Sept 2023
Amount
Excavation in trenches n.exc. 1.5 m wide and n.exc.1.5m in depth for laying of XLPE insulated Cable including getting out in soft/loose soil all as specified & directed by Engr-in-Charge
Returning filling in and including spreading leveling watering and well ramming in layers not exceeding 25 cm in soft/loose soil all as directed by Engineer in Charge.
Removing excavated material n.exc. 50m and depositing where directed at a level n.exc 1.5 m above starting point all as directed by Engineer in Charge.
M&L for spreading & leveling dry clean Ganga sand in trenches for cushioning UG cable (8 cm before laying of cable and 15 cm after laying of cable ) complete all as specified and directed. (Note: For payment purpose punned thickness of sand shall be measured)
M&L for sub class old size of Brick in trenches for cable protection of LT Cables with width equal to length of brick complete all as specified and directed.
S&F in replacement of 100 mm dia light grade galvanised steel tubing with all fittings and fixed to poles / walls with mild steel clamps, bolts, nuts and washers complete all as spefified and directed
S&F in replacement of 80 mm dia light grade galvanised steel tubing with all fittings and fixed to poles / walls with mild steel clamps, bolts, nuts and washers complete all as spefified and directed
S&F in replacement of 50 mm dia light grade galvanised steel tubing with all fittings and fixed to poles / walls with mild steel clamps, bolts, nuts and washers complete all as spefified and directed
M & L for boring through existing road with trench less method for passing of UG Cable all as directed by Engineer in Charge.
Supply and laying XLPE insulated , screened, PVC bedded galvanised steel strip or wire armoured electric power cable heavy duty with aluminium conductor 1100 volts grade cross sectional 10 sq mm 2 core ,laid in trenches /ducts /encased in GI pipe /fixed to pole including taking out of existing unserviceable cable / OH conductor all as specified and directed. Note:- Layout digram/Key plan of cable laid shall be recored in MB
All as per item no. 10 here in before but XLPE cable of size 10 Sqmm, 4 core
All as per item no. 10 here in before but XLPE cable of size 16 Sqmm, 4 core
All as per item no. 10 here in before but XLPE cable of size 25 Sqmm, 4 core
All as per item no. 10 here in before but XLPE cable of size 35 Sqmm, 3.5 core
All as per item no. 10 here in before but XLPE cable of size 50 Sqmm, 3.5 core
All as per item no. 10 here in before but XLPE cable of size 70 Sqmm, 3.5 core
All as per item no. 10 here in before but XLPE cable of size 95 Sqmm, 3.5 core
All as per item no. 10 here in before but XLPE cable of size 120 Sqmm, 3.5 core
All as per item no. 10 here in before but XLPE cable of size 150 Sqmm, 3.5 core
All as per item no. 10 here in before but XLPE cable of size 185 Sqmm, 3.5 core
All as per item no. 10 here in before but XLPE cable of size 240 Sqmm, 3.5 core
All as per item no. 10 here in before but XLPE cable of size 300 Sqmm, 3.5 core
Taking out old defective UG cable of any size up to 300 Sqmm, 3/3.5 core all as directed by Engineer in Charge.
Re laying of serviceable Cable obtained of any size and discription in any position complete all as directed by Engineer in Charge. (i) Excavation, earth work, sand cushioning, protection cover/GI pipe shall be measured and paid separately under respective item of Schedule 'A'. (ii) Layout of cable rout shall be mentioned in MB for record purpose.
Supply only LT PVC Tape role of 25/26 mtrlength, 3/4 Inch wide, ISI marked of approved make for using connection in Panels/ Transformerand all as specified and directed.
Supply, installation, commissioning and testing in replacement of APFC panel of capacity 125 KVAR powder coated factory made outdoor type of suitable size made of Robust steel sheet construction made from min 2.10 mm steel sheet with countersunk holes at bottom for base mounting brackets and sheet steel gland plates for cable entry, formed gasket arround doors, with provision of Lock inserts, earthing straps, door stay complete panel prewired with suitable size of copper cable not less than 2.5 sqmm and grouted in ground by using angle iron frame of size 50mm x 50mm x 6mm, PCC (1:2:4) type C-1 with 20mm graded stone aggregate.Panel comprising with following:-
(a) Incoming MCCB 4 pole 250 Amp 35 KA alongwith Spreader terminals with adjustable thermal setting – 01 Nos b) Multifunctional 4 in 1 meter like Amp,Voltage, frequency, powerfactor as per capacity of panel = 01 No. (c) Phase Indicator Lamp RYB with sheds LED Type - 01 Set of three (d) Capacitor MPPH type with suitable size 3 phase power contactors and with individual 3 pole 415 volt MCBs of suitable capacity. Size of capacitor is 1 KVAR =01 No.,2 KVAR = 2 No. 5 KVAR = 1 No, 10 KVAR=2 No,20 KVAR=1 No., 25 KVAR= 03 No including indication lamp of each capacitor. (e) Microprocessor based 3 phase current transformer sencing relay 12 stage = 01 No( for operating of capacitor bank) (f) Auto/Manually switch of capacitor bank (g) PCC 1:2:4 for installation of panel
Supply, installation, commissioning and testing in replacement powder coated factory made panel board outdoor type CPRI approved confirming to IP 64 protaction, of suitable size made of Robust steel sheet construction made from min 2.10 mm steel sheet with countersunk holes at bottom for base mounting brackets and sheet steel gland plates for cable entry, formed gasket arround doors, with provision of Lock inserts, earthing straps, door stay and grouted in ground by using angle iron frame of size 50mm x 50mm x 6mm, PCC (1:2:4) type C-1 with 20mm graded stone aggregate. The panel will be prewired with suitable size PVC insulated copper conductor cable, multistranded housed with the following accessories:-
M&L for replacement of floor mounted LT panel board outdoor type factory made and tested (CPRI approved) 415 volts 3 phase 4 wire 50 HZ AC supply having busbar chamber 800 Amps Aluminium strip TPN, installed on porcelain insulators, and copper conductor wiring , the panel shall be dust and vermin proof and made up of 3.15 mm CRCA mild steel sheet and 40x40x6 mm thick angle iron frame work , powder coated finish over one coat of red oxide primer out side and in side, front and rear opening type, with aprons for cable entry with double door shutter and locking arrangement, internal wiring with PVC insulated solid copper conductor FRLS cables, IS -694 marked of adequate size but not less than 4 sq mm and suitable to accomodate and including the following acessories:-
M&L for preparing old painted surface of panel board by cleaning removing of the old paint by scracthing with wire bursh/sand paper etc and including denting/patching of brocken/rusted surfaces etc and apply two coat of 1st quality synthetic enamel paint by spray painting on inside/outside surface of panel,all as specified and directed by Engr-in- charge.
M&L in replacement for fabrication of door/surfaces of LT panel indoor/outdoor as per existing size / thickness/shape and fitted in the panel with door handle, formed gasket around doors, lock insets, earthing strips, door stay, hinges,rivets etc. including two coat of synthetic enamel paint by spray painting on inside/outside surface of panel,all as specified and directed by Engr-in- charge.
Supply and fix in replacement copper bus bar in the panel of exsiting size and capacity for phase and neutral with heat shrinkable including PVCsleeves in different colour codes for phase indication all as per directed by Engr-in-charge.
Allas per item no. 31 here in before but for Alumnium bus bars
S & F in replacement LED type phase indication lamp of Red /blue/Yellow colour for phase indication in existing panels complete all as specified and directed by Engr-in-charge .
Allas per item no. 34 here in before but for checking of Voltage
S & F in replacement of MCCB, thermal magnetic protection type of 630 Amps ,36 KA, 4 Pole, 415V , Ics=100%Icu, fixed with and including lugs, nuts, bolts, washers, spacers, studs, links etc. testing and commissioning complete all as specified and directed.Make MCCB :- Legrand / L&T / ABB / C&S as approved by GE
All as per Item No. 36 above but MCCB of rating 500 Amps 36 KA, 4 Pole, 415V
All as per Item No. 36 above but MCCB of rating 400 Amps 36 KA, 4 Pole, 415V
All as per Item No. 36 above but MCCB of rating 350 Amps 36 KA, 4 Pole, 415V
All as per Item No. 36 above but MCCB of rating 250 Amps 36 KA, 4 Pole, 415V
All as per Item No. 36 above but MCCB of rating 200 Amps 36 KA, 4 Pole, 415V
All as per Item No.36 above but MCCB of rating 160 Amps 25 KA, 4 Pole, 415V
All as per Item No. 36 above but MCCB of rating 100 Amps 25 KA, 4 Pole, 415V
All as per Item No. 36 above but MCCB of rating 63 Amps 16 KA, 4 Pole, 415V
M&L Repairs & overhauling to LT ACBs of any capacity(400 A to 1000 A) of any make by removing out the breaker from the respective panels after taking proper electric shut down & disconnecting the breaker, checking it thoroughly for the defects & tripping system of the ACB and rectifing them, lubrication of moving contacts, overhauling of the ACB, replacement of wornout minor spares like springs, washers, levers, nuts & bolts etc reassembling , re-installation ,testing & commissioning of ACB complete all as directed by Engineer-in- charge Note :(i) Cost of lubricants, cleaning agents, testing tools and minor spares shall be deemed to be including in quoted rates (ii) Machine Number with location of repaired VCB shall be recoreded in MB.
Supply only Moving Arcing contacts and adjust the contact pressure of LT ACB of any make any capacity
Supply only fixed Arcing contact and adjust the contact pressure of LT ACB of any make any capacity
M&L for replacement of main shaft assembly with crank & cam spacer of existing capacity LT ACB of existing make & model and testing for proper operation complete all as directed by Engineer-in-charge
M&L for replacement of Trip coil of LT ACB of any make any capacity all as specified and directed by Engr-in-charge
S& F in relacement of solar street light 18 W All in one type with 2 days back up. complete all as specified and directed by Engr-in-charge.
M&L for grouting of LT/APFC Panel by using angle iron frame of size 50mm x 50mm x 6mm, PCC (1:2:4) type C-1 with 20mm graded stone aggregate.including shifting of existing LT/APFC panel with disconeection of existing cables and reconnecting it after grouting of panel complete all as specified and directed by Engr-in-charge.
M & L for hardcore of broken stone or boulders gauge of 40mm to 63 mm , deposited, spread and levelled in layers n exc. 15cm thick complete all as specified
Supply and fix in repair of LT sides brass stud with nuts, bolts and washers of exisiting transformer of 100 to 500 KVA including decanning of transformer oil,connection & reconnection of cable opening of top cover replacement of nut bolts complete all as specified and directed. Note:- SM / MES Number of concerned Transformer with location shall be recorded in MB
Supply and fix in repair of HT sides brass stud with nuts, bolts and washers of exisiting transformer of 100 to 500 KVA including decanning of transformer oil,connection & reconnection of cable opening of top cover replacement of nut bolts complete all as specified and directed. Note:- SM / MES Number of concerned Transformer with location shall be recorded in MB
Supply and fix ruber seal/gland on HT/LT studs of transformer including decanning of transformer oil,connection & reconnection of cable opening of top cover replacement of nut bolts complete all as specified and directed. Note:- SM / MES Number of concerned Transformer with location shall be recorded in MB
Supply & fix in replacement of HT procelain transformer bushing insulator 11/.433 KV for 100 to 500 KVA transformer including decanning of transformer oil,connection & reconnection of cable opening of top cover replacement of nut bolts complete. Note:- SM / MES Number of concerned Transformer with location shall be recorded in MB
Supply & fix in replacement of LT procelain transformer bushing insulator 11/.433 KV for 100 to 500 KVA transformer including decanning of transformer oil,connection & reconnection of cable opening of top cover replacement of nut bolts complete. Note:- SM / MES Number of concerned Transformer with location shall be recorded in MB
Clearing away (Three time) all grass vegetation ,saplings, shrubs, brush wood undergrowth roots and trees not exceeding 30 CM girth (measured one metre above ground level) and removing rubbish upto a distance of 50 metres outside the periphery of the area under clearance soft/loose soil and getting out including sprinkling anti vegitation chemical for complete area with spray machine complete all as specified & directed.Note: Quoted rate shall be deemed to included for three cutting/cleaning i.e. 1st shall be just commencement of contract , 2nd shall be in middle of contract PDC and 3rd shall be prior to one month of physical completion of CA PDC
S&F 1100 Volts grade heavy duty cable one twin core, flat or circular 16 Sqmm PVC insulated aluminium stranded conductor served with inner sheathing of PVC tapes and overall PVC sheathed in service connection from pole to Main Switch complete all as specified and directed.
All as per item no.61 Here in before but for 10 Sqmm Cable
All as per item no.61 Here in before but for 6 Sqmm Cable
M & L fabrication of MS busbar chamber of nominal dimension 900 mm x 600 mm x 300 mm duly provided with aluminimum busbar of size 50 mm x 6mm dixed on porcelain insulators TPN type out door weather/vermin proof with both way open ing duly provided with neoprene rubber gasket along the doors openings pedestal type duly painted powder coated on CRCA steel sheet encloser ( 2.15mm thick sheet) with one No incommer MCCB 200 Amp 25 KA complete all as sepcified and directed incl making connection /thimbles etc complete.
All as per srl item No 64 here-in-before but of size 600 mm x 600 mm x 300 mm and without MCCB
M&L for cleaning and preparation of old painted surface of HT Pole complete and painting with one coat of aluminium paint including channels/ brackets, street light brackets, cross arms and making blue & white strips with synthetic enamelled paint of 30 cm height, each alternative strip upto 1.5 mtr height and writing pole numbers with yellow synthetic enamelled paint after making circular base with black synthetic enamelled paint complete all as specified. Note:- Number of concerned Pole with location shall be recorded in MB.
M&L for cleaning and preparation of old painted surface of LT Pole complete and painting with one coat of aluminium paint including channels/ brackets, street light brackets, cross arms and making blue & white strips with synthetic enamelled paint of 30 cm height, each alternative strip upto 1.5 mtr height and writing pole numbers with yellow synthetic enamelled paint after making circular base with black synthetic enamelled paint complete all as specified. Note:- Number of concerned Pole with location shall be recorded in MB.
Supply ,fixing ,commisioning and testing of Nature timer switch control Street Lights complete with MCB, Power and Panel duly complete with wiring Model : SWADEEP-02EC 8KW 3P, three phase ,max load 8 KW Manufactured by KAKATIYA ENERGY SYSTEMS LTD HYDERABAD or equivalent of other make complete all as specified and directed. Note :- CA No & date of installations shall be painted/marked on all timer switch provided by the contractor
Supply ,fixing ,commisioning and testing of Nature timer switch control Street Lights complete with MCB, Power and Panel duly complete with wiring Model : SWADEEP-02EC 5KW 1P, single phase ,max load 5 KW Manufactured by KAKATIYA ENERGY SYSTEMS LTD HYDERABAD or equivalent of other make complete all as specified and directed. Note :- CA No & date of installations shall be painted/marked on all timer switch provided by the contractor
M&L for earthing complete with galvanised or steel earth plate electrode of size 600x600x6mm thick burried directly in ground vertically ( to a depth not less than 2.25mtr deep below normal ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, connected to strip 32x 6 mm size drwn throun 40mm GI light grade pipe with nuts, bolts , check nuts , washers, earth plate surrounded by packed layers of charcoal dust and common salt 15cm thick all around, top & bottom watering pipe 20mm bore of GI medium grade with funnel and wiremesh all as shown in electrical plate No. 3 of SSR -2009 Part-I and connecting to earthing test point,main switch board and testing on completion including PCC chamber concrete (1:3:6) type C-2 and RCC cover 75mm thick reinforced with mild steel TMT bar 8mm dia @ 150mm c/c both ways in cement concrete(1:2:4) type B-1 all as shown in electrical plate in No 3 of SSR(Pt-I)2009 and including providing earth identification plate (indicating earth test results, earthing number & date of earthing with black paint over white paint back ground) of 1.6mm thick welded with 25x25x5mm angle iron goruted in ground in PCC 1:3:6 type C2 complete all as specified and dirfected by Engineer-in-charge. Note:- up to 7.5mtr earth strip shall be deemed to be inclusive in quoted unit rate.
Supply and fixing/laying of galvanized iron strip of size 32x6 mm as earth continuity conductor provided in between earth test point terminal and upto the equipment incl nuts, bolts and washers complete all as specified and directed.
Supply and fixing in replacement of danger notice plate of 1.6mm thick, MS sheet, vitreous enamelled white, with letters, figuers and conventional skull and bones in signal red colour and fixed with MS clamps made out of flat iron 25x3 mm, nuts-bolts, of approved size for LT 20 x 15 cm.
M&L for in replacement of bus bar chamber made out of 1.6mm thick powder coated sheet, fixed on wall, 4 ways, 100 Amps ,415 V powder coated, water & vermin proof , IP-66 protection duly provided with front openable door including provision of TPN copper bus bar heat shrinkable colored PVC sleeve coated for phase and neutral complete all as specified and directed.
M&L for in replacement of bus bar chamber made out of 1.6mm thick powder coated sheet, fixed on wall, 4 ways, 63 Amps ,415 V powder coated, water & vermin proof , IP-66 protection duly provided with front openable door including provision of TPN copper bus bar heat shrinkable colored PVC sleeve coated for phase and neutral complete all as specified and directed.
Supply and fixing Isolator 4pole 63 Amps,415 Volts all as specified and directed.
Supply and fixing Isolator 4pole 100 Amps,415 Volts all as specified and directed.
Supply and fixing Isolator 2 pole 40 Amps,220 Volts all as specified and directed.
Supply and fixing in replacement of HT 11 KV busbar outdoortype weather and vermin proof factory fabricated CPRI approved , pedestal type made out of mild steel sheet 3.15 mm thick powder coated,factory made using angle iron 40 mm x 40 mm x 6 mm and 500 mm high,front opening double door shutter weather proof,rust proof, dust proof with provision of rubber gasket and locking arrangement including HT bush,insulator & busbar (80 x6 mm) with colour code - 03 Nos and making connection with suitable size of thimbles, nuts, bolts and washers etc incl necessary earth work to fix 60 cm above ground level all as directed by Engineer in Charge.
Supply and Fix HT insulation tapes (25/26mtr length) ISI Marked for terminating high voltage cables for insulation sealing of connection of wire and cable for bus bar insulation, transformer terminal insulation etc complete all as specified and directed.
S & F in replacement sheet metal enclosure suitable for fixing 4 pole MCCB of any capacity mounted type with fixing arragement in existing wall / angle iron frame incl welding work etc including making electrical connections complete all as specified and directed.
S & F in replacement on load change over switch, 800 Amps, 4 pole with steel sheet metal enclosure, panel mounted type with fixing arragement in existing wall angle iron frame 50x50x4mm with welding work and PCC works etc including making electrical connections complete all as specified and directed.
S & F in replacement on load change over switch, 630 Amps, 4 pole with steel sheet metal enclosure, panel mounted type with fixing arragement in existing wall angle iron frame 50x50x4mm with welding work and PCC works etc including making electrical connections complete all as specified and directed.
M&L for detection of HT/LT fault by using fault locator machine highering from civil authority complete all s specified and directed by Engr-in -Charge. Note :- In one length of cable from Panel/DB/Transformer to Panel/Transformer all faults considered as single job. replacement heat shrinkable type end termination joint suitable for cable of size 25 to 400 Sqmm, 3.5 Core, 1100 Volts grade complete all as specified and directed. Note:Proper record generated by fault detecting machine shall be provided while claiming payment by contractor.
Supply Joining , commissioning and testing in replacement of Heat Shrinkable straight though joint suitable for cable of size 120 to 185 sqmm 3 core complete with all fittings and jointing materials suitable for HT11 KV ( E ) XLPE cable all as specified and directed.
Supply Joinging , commissioning and testing in replacement of Heat Shrinkable end termination joint Out door type and suitable for cable of size 240 to 300 sq mm 3 core complete with all fittings and jointing materials suitable for HT11 KV ( E ) XLPE cable all as specified and directed.
Supply Joinging , commissioning and testing in replacement of Heat Shrinkable straight through joint suitable for cable of size 240 to 300 sq mm 3 core complete with all fittings and jointing materials suitable for HT11 KV ( E ) XLPE cable all as specified and directed.
M&L for replacement heat shrinkable type straight through joint suitable for cable of size 25 to 50 Sqmm, 3.5 Core, 1100 Volts grade coomplete all as specified and directed.
M&L for replacement heat shrinkable type straight through joint suitable for cable of size 70 to 150 Sqmm, 3.5 Core, 1100 Volts grade coomplete all as specified and directed.
M&L for replacement heat shrinkable type straight through joint suitable for cable of size 185 to 400 Sqmm, 3.5 Core, 1100 Volts grade coomplete all as specified and directed.
M&L for replacement heat shrinkable type straight through joint suitable for cable of size 185 to 400 Sqmm, 3.5 Core, 1100 Volts grade coomplete all as specified and directed.
M&L for replacement heat shrinkable type End joint suitable for cable of size 25 to 50 Sqmm, 3.5 Core, 1100 Volts grade coomplete all as specified and directed.
M&L for replacement heat shrinkable type End joint suitable for cable of size 70 to 150 Sqmm, 3.5 Core, 1100 Volts grade coomplete all as specified and directed.
M&L for replacement heat shrinkable type End joint suitable for cable of size 185 to 400 Sqmm, 3.5 Core, 1100 Volts grade coomplete all as specified and directed.
santosh electronics
Bharat Sales Corporation
Lalta Prasad vijay kumar Forwarding Agency
YS CONSTRUCTION
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .