Supply and Installation of the Surge Protection Device as per annexure attached
2020_IIAP_604573_1
RFT/IND/276/20-21
Open Tender
Electrical Goods/Equipment
Supply
20 days
VainuBappu Observatory, IIA, KavalurAlangayam, TN
Please refer Tender documents.
5 documents required · 5 mandatory
₹0
Exempted
4 Feb 2021
22 Dec 2020
13 Jan 2021
22 Dec 2020
11 Jan 2021
22 Dec 2020
120 days
Amount
Supply and Installation of the Surge Protection Device (SPD) [As per NIT, Annexure and Terms & Conditions]
Supply and installation of DIN rail mounted Type 1+2 three phase AC power SPD tested as per IEC61643 with following specification Uo/Un=230V,Uc(mcov)=260V(L-N),Iimp at 10/350 microsec(L-N)=25KA,In(L-N/N-E)=25/100KA at 8/20microsec, Imax(L-N/N-E)=65/130KA at 8/20microsec, voltage protection level(Up)<1.2KV, Response time (L-N/N-E)< 25ns/100ns, TOV withstand 120mts=438V, Short circuit withstand capacity(L-N/N-E)=50KA, Uw<4KV,Back up fuse 315A, Remote monitoring-yes with fault indication(3+1) protection
Supply and installation of DIN rail mounted Type 2 Three phase AC power line SPD tested as per IEC 61643 with following specification :- Uo=230V,Uc=260V(L-N), at 8/20microsec ,Imax(L-N/N-E)=50/65KA at 8/20microsec, voltage protection level (Up) <1.2KVIn(L-N/N-E)=20/40KA Response time(L-N/N-E) <25ns/100ns,TOV withstand 120mts,438V, short circuit withstand capacity (L-N/N-E)=25/50KA,Uw<2.5KV, Backup Fuse - 315A with remote monitoring & fault indication(3+1) protection
Supply and installation of DIN rail mounted Type 2+3 single phase AC power line SPD tested at 8/20microsec ,Imax(L-N/N-E)=50/65KA at 8/20microsec, voltage protection level (Up) <1.5KVas per IEC 61643 with following specification :- Uo=230V,Uc=260V(L-N), In(L-N/N-E)=20/40KA Response time(L-N/N-E) <25ns/100ns,TOV withstand 120mts,438V, short circuit withstand capacity (L-N/N-E)=25/50KA, Uw<1.5KV,Backup Fuse - 315A with remote monitoring & fault indication(1+1) protection
Supply and installation of Two port Surge Protection Device Type 3 shall have integrated EMI Filter tested as per IEC 61643-1. SPD should have visual failure indication with SPecifications as follow: Nominal voltage 230V AC and MCOV ≥ 275V , Voltage protection Level should be < 1000V, TOV withstand = 334 AC V for 5 Sec, Uoc= 6 KV, Max Load Current - 30A, Filetring < 70 dB@ 1Mhz,Thermal Protection -Yes, with fault indication
Supply and installation of Two port Surge Protection Device Type 3 tested as per IEC 61643-1. SPD should have visual failure indication with SPecifications as follow: Nominal voltage 230V AC and MCOV ≥ 275V , Voltage protection Level should be < 1000V, TOV withstand = 334 AC V for 5 Sec, Uoc= 6 KV, Max Load Current - 30A, Thermal Protection -Yes, with fault indication
cables 10 sqmm (Quantity mentioned is approximate, Billing should be as per actual measurement used during installation)
cables 6 sqmm (Quantity mentioned is approximate, Billing should be as per actual measurement used during installation)
cables 1.5 sqmm (Quantity mentioned is approximate, Billing should be as per actual measurement used during installation)
Box (Quantity mentioned is approximate, Billing should be as per actual measurement used during installation)
DIN Rail (Quantity mentioned is approximate, Billing should be as per actual measurement used during installation)
copper lug for 10sqmm cable (Quantity mentioned is approximate, Billing should be as per actual measurement used during installation)
copper lug for 6sqmm cable (Quantity mentioned is approximate, Billing should be as per actual measurement used during installation)
copper lug for 1.5sq.mm cable (Quantity mentioned is approximate, Billing should be as per actual measurement used during installation)
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .