Executive Engineer STD Sopore
Amargarh
Augmentation of Receiving Station Hyhama from 1x10 MVA to 2x10 MVA under UT Capex
2026_PDD_327595_1
STDS/23 of 2026-27
Open Tender
Electrical Works
Turn-key
120 days
Hyhama
Please refer Tender documents.
5 documents required · 5 mandatory
₹2,003
Executive Engineer STD Sopore
₹1.8 L
8 Oct 2026
8 Oct 2026
4 Nov 2026
8 Oct 2026
2 Nov 2026
13 Oct 2026
8 Oct 2026 - 13 Oct 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Supply, Installation, Testing and Commissioning of | |||||
| 1.01 | Installation, testing and successful commissioning of 10 MVA Power Transformer including loading at ECSD Pampore, handling, Carriage upto site/ Unloading /Dragging /Assembling at site including insurance during transit (Complete Job) to Receiving Station ( Power Transformer to be provided by the Department) | 1 | Job | - | - |
| 1.02 | Supply, Carriage upto site (including Loading/Unloading),Installation,Testing & Commissioning of 33 kV VCB (36 kV, 1250A, 26.2 kA, Outdoor Type of reputed make as per approved drawings/standards | 1 | Set | - | - |
| 1.03 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 33 kV Isolator with Earthing Blade (36KV,800A,Outdoor,3 poles,25 KA) of reputed make as per approved drawings/standards (01 Set = 03 Number) | 1 | Set | - | - |
| 1.04 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 33 kV Isolator without Earthing Blade (36KV,800A,Outdoor,3 poles,25 KA) of reputed make as per approved drawings/standards (01 Set = 03 Number) | 1 | Set | - | - |
| 1.05 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 33 KV Current Transformer (33 KV, 1Φ, 2 Ratio 3 Core, Outdoor Type ; 300-150/5-5A) of reputed make including supply and fixing of suitable CT Clamps as per approved drawings/standards | 3 | No | - | - |
| 1.06 | Supply, Carriage upto site (including Loading/Unloading),Testing of 11kV/ 110 V, Three phase epoxy resin cast Voltage Transformer with rated burden 15VA per phase and accuracy class 0.5 (reputed make) | 3 | No | - | - |
| 1.07 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 33 kV Lightening Arrestors (33 kV, 10kA, Station class, ZnO, Polymer) gap less (1 No. per Φ) of reputed make as per approved drawings/standards | 12 | No | - | - |
| 1.08 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 33 kV C&R Panel along with O/C, E/F,REF and differential relays (IEC61850), mimic diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port | 1 | No | - | - |
| 1.09 | Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 33 kV 10 kN Post Insulator Polymer 36kV,235kV Impulse, creepage distance 1224m of reputed make as per approved drawings/standards | 3 | No | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.22 MB
BOQ_1108292.xls
BOQ • 0.39 MB
SBD23.pdf
Tender Documents • 1.71 MB
Drawing.pdf
Tender Documents • 38.49 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .