SM(E-E), GAYA AIRPORT GAYA
SM(E-E), GAYA AIRPORT GAYA
Modification of existing Terminal Building and replacement of false ceiling at Gaya Airport. SH Fire Hydrants and Sprinkler Works.
2026_AAI_290840_1
AAI/ER/GAYA/SM(E-E)/e-NIT-08
Open Tender
Electrical Works
Works
180 days
GAYA AIRPORT GAYA
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,180
₹4.4 L
17 Sept 2026
17 Sept 2026
10 Oct 2026
18 Sept 2026
9 Oct 2026
18 Sept 2026
18 Sept 2026 - 25 Sept 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Designing of complete fire hydrant and sprinkler system including equipment sizing, preparation of shop drawings, coordinated service drawings, submission of NOC from State Govt Authorities complete as required as per NBC/IS norms with up to date amendments. | 1 | job | 263 | ₹263 |
| 2 | Supplying, installation, testing and commissioning of Electric driven Main Fire Pump conforming to IS 12469: 2019 suitable for automatic operation and consisting of following, complete in all respects, as required :
(a) Horizontal type, multistage, centrifugal, split casing pump of cast iron body & bronze impeller with stainless steel shaft, mechanical seal as required.
(b) Suitable HP Squirrel cage induction motor,TEFC, synchronous speed 1500 RPM, suitable for operation on 415 volts, 3 phase 50 Hz, AC supply with IP 55 protection for enclosure,horizontal foot mounted type with Class-'F' insulation, conforming to IS-12615: 2018.
(c) M.S. fabricated Common base plate, coupling,coupling guard, foundation bolts etc. as required.
(d)Suitable cement concrete foundation duly plastered with anti vibration pads.
2280 lpm at 70 m Head | 2 | job | 263 | ₹526 |
| 3 | (a) Supplying, installation, testing and commissioning of diesel engine driven main fire pump conforming to IS 12469: 2019 suitable for automatic operation and consisting of following, complete in all respects, as required : (Diesel Driven Pump)
(b) Horizontal type, multistage, centrifugal pump of cast of iron body and bronze impeller with stainless steel shaft, mechanical seal as required.
(c) Suitable HP, 1500 RPM water cooled with radiator, diesel engine conforming to relevant IS standard complete with auto starting mechanism, 12/24 volts electric starting equipment,diesel tank,exhaust pipe extended upto 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour etc. as required.
(d) M.S fabricated, common base plate, coupling, coupling guard, foundation bolts etc. as required.
(e) Suitable cement concrete foundation duly plastered and with anti vibration pads.
2280 lpm at 70 m Head | 1 | job | 263 | ₹263 |
| 4 | (a) Supplying, installation, testing and commissioning of electric driven pressurisation pump conforming to IS 12469: 2019 suitable for automatic operation and consisting of following, complete in all respects, as required : (Jockey Pump)
(b) Horizontal type, multistage, centrifugal pump of cast iron body and bronze impeller with stainless steel shaft, mechanical seal as required.
(c) Suitable HP squirell cage induction motor TEFC type suitable for operation on 415 volts, 3 phase 50 Hz AC supply with IP 55 class of protection for enclosure, horizontal foot mounted type with Class- 'F' insulation, conforming to IS-12615: 2018.
(d) M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required.
(e) Suitable cement concrete foundation duly plastered and with anti vibration pads.
180 lpm at 70 m Head | 2 | Job | 263 | ₹526 |
| 5 | Fabrication, supplying, Installation testing & commissioning of Electrical control panel of type tested assemblies as per IEC 61439 of cubical construction, floor mounted type, fabricated out of 2mm thick CRCA sheet, compartmentalised with hinged lockable doors, dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable alley, inter-connection with suitable size copper conductor cable/solid copper strip, having switchgears and accessories,mountings and internal wiring, earth terminals,numbering etc. complete in all respect, suitable for main fire pump, pressurisation pump & diesel pump set complete as per CPWD specification with following in coming and Outgoings, suitable for operation on 415V, 3 phase, 50Hz Ac Supply with enclosure protection class IP 42 as required :
Incomings
400A, 50kA 4 Pole MCCB, Ics=100% Icu Rating Digital Voltmeter 0-500V with selector switch Ammeter (0-800 A) with selector swtich & CTs etc. LED type RYB phase indicating lamps, ON, OFF, trip indicating lamps
Set of Copper Bus Bar 500 Amps
Outgoings(Note : All outgoing feeders for pumps should have digital Ammeter with selector switches, and LED type ON, OFF, trip indicating lamps)
Main Fire Pump
200 Amp, 50kA TPN MCCB, Ics=100% Icu, with fully automatic Star/Delta starter suitable for 75 hp pump with overload protection, current sensing type single phase preventor complete with all accessories and internal wiring required for automatic operation, selector switch for local/remote, Auto/manual/OFF operation. - 2 sets
Jockey Pump
100 Amp, 50kA TPN MCCB, Ics=100% Icu, with Suitable HP fully automatic Star/Delta starter with overload protection, current sensing type single phase preventor complete with all acceessories and internal wiring required for automatic operation, selector switch for local/remote, Auto/manual/OFF operation. - 2 sets
Diesel Engine Control
Control for diesel engine comprising -
Automatic/Manual selctor switch & 3 attempts starting device, timers and relays as required, push buttons, start/stop in manual mode Indicating lamp for high/ Low Lub. Oil pressure, High Water Temp and Engine on indication Battery charger suitbale for 12V/24 V DC with boost and trickle selector switch, 0-30 V DC volt meter, and 0-20 A DC Ammeter.
All standard relays and accessories for automatic operation of diesel engine.
System Controller
Designing, Supply, Installation, Testing and commissioning of system controller to control operation of main electric fire pump, diesel pump,Pressurization pump, Terrace pump in sequence as per specification consisting of relays, timers.
Sensors, annunciation window for fault indication,complete as per specification | 1 | Job | 263 | ₹263 |
| 6 | Providing laying, testing & commissioning of 'C' class heavy duty MS Pipe conforming to IS 1239/Class -II of IS: 3589 i/c fittings like elbows,tees, flanges, tapers, nuts bolts, gaskets etc. in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coaltar/asphalt tape as per IS 10221,refilling the trench etc. of following sizes complete as required. | - | - | 263 | - |
| 6.1 | 150 mm dia | 500 | m | 263 | ₹1,31,500 |
| 7 | Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 1239/Class -II of IS: 3589 including Welding, fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. and fixing the pipe on the wall/ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as required : | - | - | 263 | - |
| 7.1 | 25 mm dia | 1,500 | m | 263 | ₹3,94,500 |
| 7.2 | 32 mm dia | 500 | m | 263 | ₹1,31,500 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.48 MB
TENDERDOCFFS.pdf
Tender Documents • 8.69 MB
BOQ_339680.xls
BOQ • 0.50 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .