Mr.Puneet Khanna (Head-Supply Chain Management)
Worley India Private Limited, New Energy House,RamakrishnaMandir Road, Kondivita, Andheri (East), Mumbai- 400 059, India
HV 6.6kV SWITCHGEAR MODIFICATION
2020_REFHQ_122391_1
44AC7500-00-ER-65-0001
Single
Electrical - Cables, Switchgear and Other Control Equipment
Supply
150 days
IOCL PANIPAT, INDIA
3 documents required · 3 mandatory
Exempted
18 Mar 2021
22 Aug 2020
25 Sept 2020
22 Aug 2020
24 Sept 2020
5 Sept 2020
HV 6.6kV Switchgear modification 51-HV-203,52-HV-203 54- HV-201 & HV-259 (Substation 51,52,54 & 29)
Extension panels for I. 51-HV-203 Switchgear panel (Qty:4 Nos.), II. 54-HV-201 Switchgear panel (Qty:1 No.) & III. HV-259 Switchgear panel (Qty:1 No.) Total for new motors 6 nos., each of 630A, 6.6kV, 50Hz, 25kA for 1 sec., 3 phase, 3wire, Single Front, Compartmentalized, drawout Type, Metal clad switchboard with enclosure protection of IP-4X (min.), Copper busbar with required hardware for integration with existing switchboards, Internal Arc tested as per IS/IEC 62271-200, ALFR for full short circuit current i.e. 25kA for a duration of 0.5 sec (min.) along with PRESSURE FLAP releasing Arc gases, Meters, Relays, Auxiliary relays, Protection, indication, alarms, Remote ECS/DCS/Annunciation panel with required hardware, software for interface (New or Modification of existing panel vendor to advise) with required interpanel wiring, looping with existing switchboard, associated terminal blocks and other applicable components, ECS interface panel (New or Modification of existing ECS interface panel) with associated interposing relay panel & other applicable components & accessories. Protection relay parametrization & testing kits at the time of testing & commissioning as required considering IEC61850 protocol to be arranged by vendor. Please refer single line diagram 44AC7500-00/E.01/0001/A4 for outgoing motor feeder details. Total no. of extension panels are 6 nos. on these 3 nos. of 6.6 kV Switchgears. + Third Party inspection, Start-up & Commissioning spares, Special tools & tackles
Modification of 15 nos. of existing motor feeder panels as shown below. I. 52-HV-203 Switchgear panel (14 Nos.) & II. 51-HV-203 Switchgear panel (1 No.) Total for modification 15 nos. motor feeders each of 630A, 6.6kV, 50Hz, 25kA for 1 sec., 3 phase, 3wire, Single Front, Compartmentalized, drawout Type, Metal clad switchboard with enclosure protection of IP-4X (min.), Copper busbar, Internal Arc tested panel to match with internal arcing requirement in line with existing panel, Replacement of Existing Meters, Relays with IEC 61850 protocol , Auxiliary relays, Protection & Metering CT , indication, alarms, Remote ECS/DCS/Annunciation panel (New or Modification of existing marshalling panel if applicable vendor to advise) with associated terminal blocks and other applicable components, ECS interface panel (New or Modification of existing ECS interface panel if applicable vendor to advise) with associated interposing relay panel & other applicable components etc., as applicable with all necessary accessories & components. Protection relay parametrization & testing kits at the time of testing & commissioning as required considering IEC61850 protocol to be arranged by vendor. Please refer single line diagram 44AC7500-00/E.01/0001/A4 for outgoing motor feeder details. Total no. of modification panels are 15 nos. on this 2 nos. of 6.6 kV Switchgear. + Third Party inspection, Start-up & Commissioning spares, Special tools & tackles
Description of Work / Item(s)
RECOMMENDED SPARES FOR TWO YEARS O&M – FOR SR NO 1.1 OF BOQ1
RECOMMENDED SPARES FOR TWO YEARS O&M – FOR SR NO 1.2 OF BOQ1
Description of Work / Item(s)
CHARGES FOR SITE SUPERVISION OF ERECTION,PRE-COMMISSIONING / COMMISSIONING & TRAINING OF ALL SUPPLIES AS PER MR. Refer Annexure-F of ITB for Terms & conditions for Site Supervision Services and Training for Indian bidders.
HV 6.6KV SWITCHGEAR MODIFICATION : Total 13 Mandays estimated for site Supervision of installation/ erection, testing and commissioning as listed at site as per instructions to bidder. FOR BOQ Sl.No.1.1 &1.2 Total : 13 Man-Days
Per diem charges (per person) for 8 hours work on normal working days.
Overtime rate / hour beyond normal 8 hours work on normal working days.
Overtime rate / hour for work on weekly off days/ holidays (as applicable to Refinery site).
HV 6.6KV SWITCHGEAR MODIFICATION : Total 5 Mandays estimated for Training as listed at site as per instructions to bidder. FOR BOQ Sl.No.1.1 &1.2 Total : 5 Man-Days
Charges of training for 3 man days at IOCL site for BOQ Sl.No.1.1 of BOQ1
Charges of training for 2 man days at IOCL site for BOQ Sl.No.1.2 of BOQ1
Description of Work / Item(s)
Schedule of rates for Addition / Deletion of accessories
Motor feeders
Vacuum circuit breaker
Current transformer
Core balance current transformer
Relay of each type main and auxiliary relay
Surge arrester
Meters of each type
Dummy panel
16 Port Ethernet switch
Modification of existing Motor feeder.
stage.html
html • 0.02 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .