Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹16.7 LAccepted-AOC NO 3 WD BUILDING JP AGARWALLA ROAD BHARALUMUKH KAMRUP ASSAM 781009 UDYAM AS 03 0009483 | KAMRUP METRO | ASSAM | 781009 | L1 | Accepted-AOC Lowest bidder | |
| 2 | L2₹21.3 L+₹2.4 L (13.0%)Rejected-Finance | L2 | Rejected-Finance Unsuccessful bidder |
Tender Value
₹18.0 L
EMD Value
₹35,960
Closing Date
12 Feb 2022, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE Tezpur
HQ CWE TEZPUR PO DEKARGAON DIST SONITPUR PIN 784501 (ASSAM)
REPAIR/REPLACEMENT OF HT DISTRIBUTION SYSTEM AND ALLIED WORKS AT RANGIA, CHANGSARI, TAMULPUR, DARRANGA AND HATTIGOR STN UNDER GE RANGIA
2022_MES_499994_2
CWE/TEZ(R)/T-30 of 21-22
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE Rangia
as per tender docus
8 documents required · 8 mandatory
₹500
GE Rangia
₹35,960
Yes
26 Feb 2022
29 Jan 2022
14 Feb 2022
29 Jan 2022
12 Feb 2022
29 Jan 2022
75 days
Amount
Disconnecting all in coming and outgoing cables, removing the transformer from the platform / two pole structure / floor and loading it in the vehicle carefully using crane and transporting it to the contractor's workshop, carry out the required repairs and transport the transformer back to the site , install it, reconnect all the incoming and out going cables by properly crimping using lugs of suitable size lugs, taping the bushes / bus bars, using insulation tape and testing complete of following capacity all as directed by Engr-in-Charge
(a) 11/0.433 KV, 63 KVA, Distribution transformer
(b) 11/0.433 KV, 100 to 250 KVA Distribution transformer
(c) 11/0.433 KV, 400 to 500 KVA Distribution transformer
Note:- (i) Gasket set, LT/HT side ceramic bushing, spindle for HT/LT side , rewinding,dehydration of oil shall be measured and paid separately in respective items. (ii) Contractor shall open the transformer/ dismentling of core and winding in presence of Eng in Charge. Eng in Charge shall examine the transformer for cause of fault, damage to the parts, burnt winding and prepare fault / inspection report. Accordingly after carrying out the repair before shifting the transformer to site all the necessary test to be done at factory/ workshop in presence of Engineer in Charge. Test report to be perpared before and after carrying out repair and to be produce at the time of claiming the payment.
Draining out all the transformer oil ,dismantling and inspection of transformer core and winding including taking out burnt out winding/insulation of LV / HV strips/coils , Reassembling of core and winding after replacement of burnt winding and insulation, drying out in vacuum chamber till specified IR values are obtained and providing new insulation materials, gasket, nuts , bolts, checking of leakages and rectifying the same by welding etc and replacement of silica gel for transofomer of following capacity all as directed by Engr-in-Charge :- Note: (i) S&F of all materials required such as winding, LV/HV bushes, Silica gel breather etc will be measured and paid for separately under relevant item as mentioned below. (iii) Repair / replacement of all other minior parts if found un servicable/ worn out during repair shall be replace by contractor and cost of same is deemed to included in unit rate of above item. No extra payment shall be made for this.
(a) 11/0.433 KV, 63 KVA Distribution transformer
(b) 11/0.433 KV, 100 to 250 KVA Distribution transformer
(c) 11/0.433 KV, 400 to 500 KVA Distribution transformer
NOTE :_ (i) Cost of transformer oil cleaning after draining out and after hosting down of core and winding shall be deemed include in the rate Quoted (ii) Gasket set, LT/HT side ceramic bushing, spindle for HT/LT side and are horn surge arrester for replacement shall be measured and paid under relevant item.
Material and labour for rewinding of burnt winding coil of HV and LV limbs of 11/0.433 KV distribution transformer of capcity up to 500 KVA using new copper wire/strip of appropriate size and gauge , number of turns etc as per existing size of core & winding including insulating materials (double insulation), including heating , baking and varnishing of transformer coils complete all as specified and directed by EIC.
Taking out old u/s breather and Supply and replace silica gel breather , made up of aluminium TOP, Powder coated, Transaparent Centre Portion made of Polycarbonate of size, Nitirle rubber O ring connection1/2 " BSP or 3/4 " thread, filled with new Silica Gel Blue (including silica gel crystal) suitable for transformer of capacity as mentioned below of approved make complete all as specified and directed
(a) 25 to 75 KVA Distribution transformer
(b) 100 to 250 KVA Distribution transformer
(c) 300 to 500 KVA Distribution transformer
Supply and fix brass spindle for terminal on HT side threaded complete with nut, washers etc of suitable dia for transformer of following capacity :-
(a) 25 to 63 KVA Distribution transformer
(b) 100 to 250 KVA Distribution transformer
(c) 300 to 500 KVA Distribution transformer
All as per item No 5 here-in-before but for LT side of transformer of following capacity :-
(a) 25 to 63 KVA Distribution transformer
(b) 100 to 250 KVA Distribution transformer
(c) 300 to 500 KVA Distribution transformer
Supply and fix ceramic bushing and Gasket on LT side of transformer of following capacities (Make : Mysore Potteries/BHEL/ :-
(a) 25 to 75 KVA Distribution transformer
(b) 100 to 250 KVA Distribution transformer
(c) 300 to 500 KVA Distribution transformer
All as per item No 7 above, but on HT side of transformer of following capacites :-
(a) 25 to 75 KVA Distribution transformer
(b) 100 to 250 KVA Distribution transformer
(c) 300 to 500 KVA Distribution transformer
Supply and fixing in replacement of complete gasket (Cock sheet) 6 mm thick complete of capacity of following transformer including conical rubber bush:-
(a) 25 to 75 KVA Distribution transformer
(b) 100 to 250 KVA Distribution transformer
(c) 300 to 500 KVA Distribution transformer
M&L in repair for Filteration and dehydration of HV grade transformer oil of distribution transformer of out door/ indoor type of 11/.433 KV, 25 KVA to 500 KVA and min three cycle to achive die elctric strength of 40 KV to 60KV for 1 Minute at 4 mm gap as per relevent IS with portable filteration plant, testing the oil for die elctric strength, break down voltage before filteration and after filteration complete all as specified and directed by EIC. Note : Filteration to be done by Dehydration machine till the desired level of dielectric strength of tranformer oil comes to 60 KV . (ii) The contractor will test the dielectric strength of oil of each Tranformer & voltage stabilizer before starting dehydration & filteration and after completion of dehydration & filteration process and he will submit a record of same. (iii) Each sample of oil will be tested with a transformer oil test machine at site in presence of concerned JE's/Engr-in-charge and test result will be submitted accordingly). (iv) Centrifugal machine with all T&P and Testing Machine , oil required shall be arranged by contractor. (v) Oil required for topping up the transformer oil will be measured and paid seperately in relvent item.
Supply and pouring of new transformer oil to achieve a di-electric strength up to 60 KV in 4 mm gap conform to IS-335-1983 with sealed barral contains each 210 litre Make : Sabita/Golf/Power/Trans oil. Note : Transformer oil shall be bring in sealed barrel having proper test certificate from manufacturer. Contractor shall submit the test certificate of oil before fill/ top up in transformer.
M & L for Painting of transformer after cleaning the body surface of transformer by rubbing with emery Paper to remove oil stains, dust etc and applying one coat of snthetic enamel paint by spray paint incl writing SM No/MES No , capacity of transformer of following capacity all as directed by Engr-in-Charge
(a) 25 to 75 KVA Distribution transformer
(b) 100 to 250 KVA Distribution transformer
(c) 300 to 500 KVA Distribution transformer
Shifting Transformer of 25 to 500 KVA from one Sub Station to another after disconnection of LT & HT Side Connections, Installation, Commissioning and connecting LT & HT Side Connections, complete all as specified and as directed.
M&L for earthing complete with galvanized steel earth plate electrode 60cm x 60cm x 6mm thick burried directly in ground (earth pit not less than 2.25m deep below ground level) with top edge of the plate not less than 1.5m below normal ground level, connected to galvanised iron earth strip of 32 x 6 mm by means of bolts, nuts, checknuts and washers of galvanised iron or steel, GI earth wire protected by 15mm bore light grade GI pipe and other end connected to earthing test point or main switch board as directed including funnel with watering pipe of 20mm bore light grade GI, wire mesh, charcoal or coke and common salt in alternate layer of 15cm compacted thickness all around the earth electrode PCC (1:3:6) type C-1 earth pit, cast iron cover and frame, including necessary excavation and earth work and necessary testing complete all as specified and directed and shown on electrical plate No 3 of MES Schedule Part I
Supply and fixing in repair earthing lead of GI strip 32 x 6 mm all as specified and directed.
M&L Broken Stone or Boulders Hardcore of Gauge not exc. 63 mm, deposited, spread and levelled in layers not exc. 150mm thick, watered and rammed to a True Surface, complete all as specified and as directed.
Dismantling fancing wire mesh,any type incl all as specifed and directed..
Supply and fixing Chain Link Fencing of any Mesh or Cages with 3.15 mm dia Mild Steel Galvanised Wire, lapped, Straining and Binding with including Mild Steel Wire (annealed) not less than 0.9 mm dia, complete all as specified and as directed.
Dismantling of insulator of any type and size from existing poles after opening nuts, bolts and removing from site all as directed.
Dismantling of old unserviceable PCC pole / Studs of any size including all necessary demolition of concrete foundation, excavation, earth work as required complete all as specified and dircected.
Supply, erecting and fixing in true vertical position, steel tubular swaged pole (410 SP – 55), 11 mtr long, complete with cast iron base plate, pole cap / finial taper plug, bolts, nuts and washers, welded reduced section and longitudnal weld through out entire length of pole including painted with two coats of black bituminous paint externally upto planting depth and remaining exterior portion of pole shall be provided with one coat of red oxide primer and two coats of aluminium paint all the metallic surfaces complete all as specified and directed by Engineer-in-Charge. Make : Calcutta/Jindal/Bansal
M&L for Lightning arresters expulsion type complete with all fittings, transmission class, discharge capacity 65 kilo amp for 11000 V complete all as specified and directed.
Dismantling of old unserviceable stay assembly including stay wire complete with necessary demolation of concrete excavation and earth work as reqd and removing the same form site complete all as specifed and as directed by Engineer in Charge
Supply any fix Stay assembly of size 20 mm dia complete with accessories as shown in electrical plate No. 1 including stay clamps complete all as specifed and as directed by Engineer in Charge. Note : (loop type insulator, excavation and concrete measured separately)
Supply and fixing loop type insulator of large size for stay wire , with overall dimensions 140 mm, clearance of hole 25.5 mm complete as directed by Engineer in Charge.
Supply and fixing Galvanised stay strand of size 7/3.15 mm complete as directed by Engineer in Charge.
M & L for Danger notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for LT, 25x20cm size all as directed
M &L for Triple pole, mechanically operated gang operated device, mounted on insulator and steel frame, with operating mechanism worked from ground level, for current rating upto 200 amps for 11000 volts complete all as specified and directed
M & L for air break switch ( drout out fuse ) suitable for 11000 volts of current rating 200 amps complete all as specified and directed.
Servicing, calibration, trouble shooting, repairing & adjusting of over current relay, earthfault relay, spring, spring charge mechanism, closed coil, trip coil including connected accessories, Power pack, master control relay, HRC fuse, NC contactor, HT fuse, LED indicator, annuceator, hooter, thermostate, cleaning all contacts with CRC spray of 11 KV VCB panel of 630 Amps, 50 Hz by qualified technical personnel to make functional in all respect including identifying the defective parts including replacement of defective parts complete all as specified. Note:- Spare parts shall be paid under relevant item as "Supply only". Make of VCB : CG/Schneider/AREVA Note : (i) All testing equipment and test kit required for calibration to be arrange and brought by contractor. (ii) Test report to be prepare for all VCB`s sepeartely and in presence of Eng in Charge and to be submitted by contractor before claiming the bill. (iii) Calibration of relays and meters to done in presence of JE / Eng in Charge and fuctionality to be check and shown to Eng in Charge up to entire satisfaction.
Supply only Releasing /closing coil 110 V DC pares suitable for 11 KV HT VCB of maximum short circuit rating 1.8 KA, 400 A 250 MVA all as directed.
Supply only Motor Charge spring mechanism with all necessary coils suitable for 110 DC (SPMX-500 FORM-AM Make CG)
Supply only Power pack with cell unit ,230 V incoming and 110 V DC out put for supply of relay complete all as specified and directed. Make: Alan/Gogate electro system
Supply only master trip relay of 24 V DC for 11 KV HT VCB of maximum short circuit rating 1.8 KA,400 A,250 MVA all as directed.
Supply only thermostat 52 degree to 90 degree for 11 KV HT VCB of maximum short circuit rating 1.8 KA,400 A,250 MVA all as directed.
Supply only annuceator MLD-02 with hooter for 11 KV HT VCB of maximum short circuit rating 1.8 KA, 400 A, 250 MVA all as directed.
Supply only HRC fuse 6 to 10 Amp for 11 KV HT VCB of maximum short circuit rating 1.8 KA 400 A, 250 MVA all as directed. Make Bussmann
Supply only HT fuse 1 Amp for 11 KV HT VCB of maximum short circuit rating 1.8 KA,400 A, 250 MVA all as directed. Make Bussmann
Supply only R-Y-B healthy indication lamp complete all as specified as directed.
M & L for Cutting vegetation and surface dressing not exceeding 15 cm deep including removing the materials to a distance not-exc 60 mtr complete all as specified and directed. (Note :- Due heavy vegitation growth the ittem shall be executed twice/ thrice as per requirement basis in each installation . However unit rate to be quoted by the tendered for single operation only)
Supplying and laying synthetic Rubber insulated mats 2.5 mm thick for voltage upto 11 kv for electrical purpose E73as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m complete all as specified.
Supply only hand gloves of good quolity ISI marked 15 KV . Make : Jaipuria brothers
Excavation in trenches in any type of soil not exceeding 1.5 mtr wide and n.exe 1.5 mtr depth including getting out all as specified and directed.
Excavation in trenches not exceeding 1.5 mtr wide and exc 1.5 mtr in depth but not exceeding 3.0 mtr in depth and getting out in any type of soil for laying cables, erection of poles complete all as specified.
Returning filling in including spreading, leveling ,and well ramming, in layers not exceeding 25 cm each layer of any kind of soil all as specified and directed.
Removing surplus excavated material from site not exceeding 50 mtrs from starting point and depositing where directed at level not exceeding 1.5 mtr above the starting point all as specified and directed.
M&L PCC 1:3:6 type C2 using 40 mm graded stone aggregates, as in foundation filling, mass concrete, complete all as specified and as directed.
M&L for plain cement concrete 1:2:4 type B-1 using 20 mm graded stone aggregate for coping around poles , including necessary form work finishing even and smooth without using extra cement , all as specified and directed.
M&L for plain cement concrete 1:4:8 type D-2 using 40mm graded stone aggregate in base / foundtion of Steel/PCC poles/struts as specified including necessary form work all as specified and directed.
NOTES: 1. The amount of schedule of credit shall be deducted from the total of this BOQ for arriving at contract sum. 2. The rates for RCC/PCC shall deemed to include the cost of formwork, shuttering etc., required for complete and proper execution of the item. Refer Schedule "A" notes for details.
Purbanchal Construction Co
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .