| 1 | L1₹1.2 CrAccepted-AOC | ₹1.2 Cr | L1 | Accepted-AOC Being L1 and Reasonable |
| 2 | L2₹1.2 Cr+₹98,700 (0.83%)Rejected-Finance 1ST FLOOR PRABHA SHOPPING COMPLEX OLD PAHARGAON DOLLYGUNJ PORT BLAIR SOUTH ANDAMAN ANDAMAN NICOBAR 744103 UDYAM AN 01 0000143 | SOUTH ANDAMANS | ANDAMAN AND NICOBAR ISLANDS | 744103 | ₹1.2 Cr+₹98,700 (0.83%) | L2 | Rejected-Finance Not being L1 |
| 3 | L3₹1.5 Cr+₹28.1 L (23.7%)Rejected-Finance | ₹1.5 Cr+₹28.1 L (23.7%) | L3 | Rejected-Finance Not being L1 |
Tender Value
₹1.4 Cr
EMD Value
₹2.2 L
Closing Date
20 Nov 2023, 6:00 pmClosed
Col Arvind Bhakuni, CWE Port Blair
COMMANDER WORKS ENGINEER, MILITARY ENGINEER SERVICES, MINNIEBAY, JUNGLIGHAT-PO, PORT BLAIR 744103
Provn of Fuel Bunkering Facility under GE P North Hutbay
2023_MES_622395_1
81058 E8 Provn of Fuel Bunkering
Open Tender
Civil Works
Lump-sum
365 days
HUTBAY
As per NIT
8 documents required · 8 mandatory
₹1,000
GE (P) NORTH
₹2.2 L
Yes
12 Jan 2024
9 Oct 2023
27 Nov 2023
9 Oct 2023
20 Nov 2023
6 Nov 2023
10 Oct 2023 - 23 Oct 2023
Amount
SCHEDUEL 'A' PART- I TO XI NOTES: Schedule ‘A’ Part- I to X are prepriced by MES under Ser No. 1.00 to 10.00. Bidders shall insert their lump sum amount in the Green coloured field under Col-6 only.
Lump sum price worked out by the tenderer for "Building/Structures" as listed in Schedule 'A' Part-I
Lump sum price worked out by the tenderer for "Excavation, Earth work, site clearance and Land Development" as listed in Schedule 'A' Part-II
Lump sum price worked out by the tenderer for "Internal Water Supply" as listed in Schedule ‘A’ Part-III
Lump sum price worked out by the tenderer for "Internal Electrification" as listed in Schedule ‘A’ Part-IV
Lump sum price worked out by the tenderer for "External Water Supply" as listed in Schedule ‘A’ Part-V
Lump sum price worked out by the tenderer for "External Electrification" as listed in Schedule ‘A’ Part-VI
Lump sum price worked out by the tenderer for "Road, Hard standing, Path" as listed in Schedule ‘A’ Part-VII
Lump sum price worked out by the tenderer for "Sewage Disposal" as listed in Schedule ‘A’ Part-VIII
Lump sum price worked out by the tenderer for "Compound Wall" as listed in Schedule ‘A’ Part-IX
Lump sum price worked out by the tenderer for "Lightening Protection" as listed in Schedule ‘A’ Part-X
Subtotal
NOTE: Schedule ‘A’ Part - XI is not prepriced by MES and prepriced rate indicated as 0.00 under Col.5 signifies this fact only. Bidder shall insert their rates in Green colour filled under Col-6.
SCHEDULE `A' PART - XI (MISC ITEMS)
External Electrification
Supply and Fixing of Flameproof LED street light fitting of 30W, IP66 protection of Cast Aluminum alloy material and Heat and Impact resistance toughen 'A' clear glass having Anti corrosive epoxy powder coated finish, fixing on street light pole with the suitable size of GI tube and clamps, bolts & nuts etc. complete with all accessories pre wired and including connecting up with three core flexible copper conductor cable with suitable size all as specified and as directed.
Supply & Fix HDGI Octagonal pole 7 Meter height having top dia 70 mm and bottom dia 130 mm and thickness 3 mm, single Arm bracket made of 40NB GI Pipe, 4 Nos 'J' type foundation bolts of dia 16 mm and 450 mm long with base plate, HT sheet alongwith base plate 200X200X12mm Note - PCC/RCC foundation will be measured seperately under respective items
Excavation in post holes not exceeding 0.5 Cum for erection of poles, removing the excevated materials to distance not exceeding 50 meter and providing PCC bed and RCC foundation as per following including form work (i) PCC BED - 450 mm X 450 mm X 100 mm (ii) RCC Column - 400 mm X 400 mm X 1300 mm, M20 Design, using 6 Nos 12 mm Steel Bar
Supply, install, test, commissioning LT panel board (CPRI Approved) cubical out door type, factory fabricated made out of 3 mm thick CRCA sheet & suitable size to accomodate all acessories/fittings, compartmentalized in construction with TPN bus bar of rating not less than 1.5 times of rated capacity of incomer MCCB and out going feeder, (a) MCCB Four Pole 100 Amps, 415 Volts 25 KA - 2 Nos (Incoming for AED Supply & Incoming for DG Supply) (b) Change Over Switch four 100 Amps, four Pole - 1 Nos (c) MCCB Three Pole 63 Amps, 415 Volts 25 KA - 1 Nos (IOCL) (d) MCB TPN 20 Amps, 415 Volts - 4 Nos( Gaurd Post, High Mast & Secutiry Light, Spare) (e) Time switches astro type 440 V three phase of 20 Amp rating with contactor - 1 Set (f) RYB Panel Indicators - 3 Nos (g) Three Phase tri vector Energy meter - 1 No
Supply & installation of Galvanized steel high mast lighting system of 12.5 meter in two section confirming to BSEN 10025, 3 mm section thickness, top dia 150 mm, bottom dia 360 mm, with 2/3 wire rope system of motor operated lowering & lifting of lights, necessary electric control panel & Trailing as per the OEM specifications and its accessories to suitable for loading 04 nos 70w LED Lights (againest Item No 14), including foundation bolts and RCC/PCC foundation as per OEM recommendations all as specified and as directed.
Supply and fix LED Flood light 70 W IP 65, pressurer die cast alluminium housing with toughend glass, fixing arrangements on the high mast all as specified and as directed. Confirming to cat No LFL-70-CDL/60-M of crompton or equivallent in Bajaj/ Philips. (For fixing on High Mast)
DG Set
Supply, install , testing and commissioning of approved OEM factory,assembled diesel generator set of totally enclosed and sound proof (with acoustic enclosure) of capacity - 40 KVA, 3 phase, 4 wire, 415 volts, 1500 RPM, AC power supply with power factor 0.8, coupled directly to alternator mounted on common base plate complete with fuel tank, battery and standared accessories and fittings confirming to engine as per IS:10001/ 10002 and Alternator as per IS: 13364 complete with relay panel and switch gears for automatic starting on main failure, control panel, vibration pads, PCC foundation complete all as specified and directed. The genset shall conform to CPCB norms for noise and emission limits and including the following :-
(a) Alternator:- Standard design alternator rated at 40 KVA net output at site after considering all derating factors, site conditions and at power factor 0.8, AC 3 phase, 4 wire 415 volts, 50 cycles, 1500 RPM, self excited, self regulated, screen protected, drip proof IP-23 enclosure, brushless design, insulating class H, voltage regulation +/- 1% operated voltage from no load to full load and shall be in position to generate supply with frequency regulation within +/- 3% tolerance, revolving field type. (b) DIESEL ENGINE :- Adequate capacity diesel engine suitable to above alternator, to drive independently above alternator and after considering derating as per site conditions directly coupled to alternator multicylinder,multistrocke, direct injection cold starting, 1500 RPM, with an overload cap of 10% for 1 hour in any 12 hours continuous running complete with standard accessories all as specified and requied for safe running anf opeation with accessories shall be as under :-
(i) Flywheel (ii) Air cleaner wet/dry type (iii) Fuel Filter (iv) Fuel Injection system incl. injection pump, solenoid switch, nozzle as per manufacturer's specifications (v) Lubricating oil filter (vi) Lubricating oil pump (vii) Turbocharger (viii) 12 volts staring system consisting of batteries of capacity as recommended by manufacturer, battery connections with copper leads and with lugs of adequate size, initial charging of batteries, battery charger/generator with regulator starter motor, starter gear (ix) Exhaust silencer complete with exhaust pipe of suitable dia. (x) Microprocessor control electronic metering and module for indication of battery voltage, oil pressure, engine RPM, hour meter and protection against low oil pressure and over speed of engine including electronic governing. (xi) Battery charging system with suitable capacitybattery charger complete with necessary connecting leads etc all as directed
(xii) Cooling (xiii) Fuel Hoses (xiv) Inbuilt fuel tank of 10 h\Hrs run of full load capacity of DG set. (xv) Air intake system (xvi)Common base frame of sturdy design suitable for antivibration mounting and permanent concrete foundation for mounting engine and alternator as per manufacturer's instructions. (xvii) Extension of exhaust silencer complete with exhaust pipe of suitable dia from out side canopy to out side of building /shedall covered with glass wool wrapped with aluminium foil f 28 SWG adequate to create draft for safe exhaust without without transering vibrations to buildings/walls, flxible exhaust pipe complete.
(ix) O/L relay. (x) CTs set of 3 - 1 set. (xi) Load on DG Indicator - 1 No. (xii) Load on Mains Indicator - 1 No. (xiii) Mains ON Indicator - 1 No (xiv) DG On Indicator - 1 No. (xv) Digital Multifunctional meter 01 Nos. (xvi) Supply and lay control cable LT 1100 volt PVC insulated armoured heavy duty copper conductor of suitable size multicore from DG set to AMF panel. (xvii) Any other components/parts as per manufacturer instructions and as directed by GE required for entire completion of the item.
Earthing complete with galvanized steel earth plate electrode 60cm x 60cm x 6mm thick, buried directly in ground (earth pit not less than 2.25m deep below ground level) with top edge of earth plate not less than 1.5m below normal ground level, including provision of GI earth strip 32x6 mm as earthing lead connected by means of bolts, nuts, check nuts and washers of galvanized iron or steel, provision of 40mm dia GI pipe medium grade for GI strip protection connected from earth plate electrode to main switch board, provision of 20mm dia GI pipe medium grade for watering arrangement and PCC 1:3:6 type C1 chamber, MS funnel, wire gauge, 50mm thick RCC 1:2:4 type B1 for earth pit cover with 6 Nos x 8 mm dia high strength deformed steel TMT bars on both ways, including necessary excavation in any type of soil, returning, filling in, removal of surplus soil to a distance n.exc. 50m, provision of charcoal and salt complete all as shown in electrical plate No.3 of Schedule Part-I 2009 all as specified and as directed.
Subtotal
Island Agency
N Rathinam
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.06 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .