| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹23.1 LAccepted-AOC | L1 | Accepted-AOC LOWEST QUOTED BIDDER | |
| 2 | L2₹25.8 L+₹1.9 L (7.92%)Rejected-Finance | L2 | Rejected-Finance NOT THE LOWEST QUOTED BIDDER | |
| 3 | L3₹29.4 L+₹5.5 L (23.1%)Rejected-Finance NO 133 RASHTRAPATHI ROAD SECUNDERABAD 500 003 | SECUNDERABAD | HYDERABAD | TELANGANA | 500003 | L3 | Rejected-Finance NOT THE LOWEST QUOTED BIDDER |
Tender Value
₹29 L
EMD Value
₹58,000
Closing Date
20 Dec 2022, 6:00 pmClosed
CWE AF SECUNDERABAD
CWE AF SECUNDERABAD BOWENPALLY POST SECUNDERABAD 500011
REPAIRS AND MAINTENANCE TO LT ELECTRIC SUPPLY / LT PANEL BOARDS AND CONNECTED WORKS AT AF STATION HAKIMPET
2022_MES_563202_1
84703/E8
Open Tender
Civil Works - Others
Item Rate
180 days
GE AF HAKIMPET
AS PER NIT
9 documents required · 9 mandatory
₹500
GE AF HAKIMPET
₹58,000
Yes
22 Dec 2022
15 Nov 2022
22 Dec 2022
15 Nov 2022
20 Dec 2022
6 Dec 2022
15 Nov 2022 - 30 Nov 2022
Amount
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m depth and getting in hard/dense soil for laying of cables/ for erection of poles/ for stay assembly etc complete all as specified and as directed.
Boaring / drilling (horizontally ) of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 80 mm dia suitable for 0.4 mpa working pressure. complete all as specified and as directed.
Supply and spread clean dry river sand in trenches for cushioning of cable complete all as specified and as directed. (Note :- Punned down thickness only shall be measured for the purpose of payment)
Supply and laying sub class 'B' bricks laid dry and flat old size across the length of cable for protection of cable complete all as specified and as directed.
Returning, filling in trenches including spreading, levelling, watering and well ramming in layers not exceeding 25 cm complete all as specified and as directed.
Removing surplus excavated material to a distance not exc 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and as directed.
Material and labour for 80 mm dia bore tubes, 'light grade' galvanised, with all fitting and fixed complete to walls/ poles or laid in trenches/ floors for cable protection complete all as specified and as directed.
Description all as per Ser item No. 7 here-in-before but of size 50 mm dia GI pipe light grade complete all as specified and as directed.
Description all as per Ser item No. 7 here-in-before but of size 40 mm dia GI pipe light grade complete all as specified and as directed.
Supply & fixing in replacement of LT PVC insulated, heavy duty aluminium conductor multi stranded, served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape underground cable of 16 Sqmm, 2 core in trenches or fixed on pole/wall or drawn through pipes including suitable size Lugs and Glands etc complete all as specified and as directed.
Description all as per Ser item No. 10 here-in-before but of size 16 Sqmm, 4 core complete all as specified and as directed.
Supply & fixing in replacement of LT XLPE insulated strip armoured multi stranded aluminium underground cable of 25 Sqmm, 4 core in trenches or fixed on pole / wall or drawn through pipes including suitable size Lugs and Glands etc complete all as specified and as directed.
Description all as per Ser item No. 12 here-in-before but of size 35 Sqmm, 3.5 core complete all as specified and as directed.
Description all as per Ser item No 12 here-in-before but of size 50 Sqmm, 3.5 core complete all as specified and as directed.
Description all as per Ser item No 12 here-in-before but of size 70 Sqmm, 3.5 core complete all as specified and as directed.
Description all as per Ser item No 12 here-in-before but of size 95 Sqmm, 3.5 core complete all as specified and as directed.
Description all as per Ser item No 12 here-in-before but of size 120 Sqmm, 3.5 core complete all as specified and as directed.
Description all as per Ser item No 12 here-in-before but of size 150 Sqmm, 3.5 core complete all as specified and as directed.
Dismantling & taking out LT burnt cable ends of any size from transformer / LT panel / LT feeder pillar / street light pole box / trenches any type / size, for repair/making suitable for reconnection to cable, providing lugs to burnt end of cables, preparing fresh terminals and reconnection, fixing the removed portion of cable with transformer/in trenches/along pole/ panel/feeder pillar box, including excavation of loop & refilling complete using old bricks and sand returning filling the excavated soil complete all as specified and as directed.
Demolition for cement concrete/road in ground floor and paving n. exc 15 cm thickness below or above ground level including removal of rubbish to a distance exc 1.50 Km and n.exc 5.00 Km etc complete all as specified and as directed.
M & L for 50 mm thick PCC 1:2:4 type B1 (using 20 mm graded stone aggregate) as in floor finishing even and smooth with using extra cement and making impression of expanded metal, whilst concrete is green over 100 mm thick PCC (1:4:8) type D-2(using 40 mm graded stone aggregate) with and including to make the road surface making good as per existing surface etc complete all as specified and as directed.
Repair of earth pit including required excavation ,earth work and PCC work to make good damaged /disturbed surfaces of earth pit chamber & making new pit cover of RCC 1:2:4 type B1 using 20 mm graded stone aggregate reinforced and lifting handle on RCC cover with 8 mm bars at 150 mm centre to centre both ways or PVC readymade available in market with prior approval of Engr In Charge, incl supply & fixing of wire mess and funnel including re-connection of earth wire/strip with panel/transformer using GI nut, bolts washer complete all as specified and as directed.
Supply, fixing ( in replacement ) of LT Panel cubical types, connecting to electrical system & testing for out door use, made out of 3.0 mm thick CRCA sheet CPRI approved factory made, totaly enclosed of size not less than Box size - 600 mm x 550 mm x 300mm and supported with 4 Nos MS Angle, lugs , duly painted with two coats of powder coated paint over one coat of red oxide primer effectively PVC gaket & sealed for vermi proof and dust proof and mounted on PCC blocks double door type with locking arragement with handle at front and openable at front &back both side with required hinges heavy duty, compartemtalised suitably including provision for tapping incoming & outgoing electric connections with suitable size of aluminium lugs glands and comprising of the following accessories :-
(a) High conductivity aluminium bus bar of size - 500 mm x 40 mm x 5 mm (RYB) for phase and 1 No for neutral mounted on DMC support with heat shrink sleeve-1 Set. ,
(b) Phase indication lamp, LED type(Set of 3)
(c) Grouting of panel including earth work as required & PCC (1:3:6) type D-2 using 20 mm gradeded stone 2x PCC block of size, 500 mm x 300 mm x 100 mm & plastering with (1:4) cement sand etc complete all as directed.
Description all as per Ser Item No 23 above but with Aluminium Bus bar strip of size - 500 mm x 50 mm x 8 mm (Box size - 800 mm x 550 x 300 mm) complete all as specified and as directed.
Supply, fixing ( in replacement ), of LT Panel cubical type,connecting to electrical system & testing for out door use, made out of 3 mm thick CRCA sheet CPRI approved factory made, totaly enclosed of size not less than 900 mm x 600 mm x 400 mm and supported with 4 Nos MS Angle, lugs , duly painted with two coats of powder coated paint over one coat of red oxide primer effectively PVC gaket & sealed for vermi proof and dust proof and mounted on PCC blocks double door type with locking arragement with handle at front and openable at front &back both side with required hinges heavy duty, compartemtalised suitably including provision for tapping incoming & outgoing electric connections with suitable size of aluminium lugs glands and comprising of the following accessories :-
(a) High conductivity aluminium busbar of size - 50 mm x 820 mm x 8 mm) 4 Nos of 400 amps rating (RYB) for phase and 1 No for neutral mounted on DMC support with heat shrink sleeve-1 Set. ,
(b) Phase indication lamp, LED type (Set of 3)
(c) MCCB 4 Pole 200 Amp 415 volt ,36 KA breaking capacity microprocessure based - 01 Nos
(d) MCCB 4 pole 100Amps 16KA -03 Nos as a outgoing
(e) Grouting of panel including earth work as required & PCC (1:3:6) type D-2 using 20 mm gradeded stone , 2x PCC block of size, 500mm x 300 mm x 100 mm & plastering with (1:4) cement sand etc complete all as directed.
Note :- Panel Board Drawing will be approved by accepting officer before placing order to manufacturer.
Material and Labour for inspecting and servicing of Oil cooled / air cooled Servo controlled voltage stabilizer of following capacities installed at various locations within Air Force Station Hakimpet by cleaning the complete unit with suitable cleaning agent and checking the serviceability state of all the switchgears/ components such as variacs, ECC box, stepper motors, RC networks, control PCB, Carbon Brushes, sensing transformers, synchronising motor, drive gears etc complete and replacing the defective spare parts and testing for proper fuctioning complete all as specified and as directed . Note :- Supply and replacement of Components / spare parts will be measured and and paid separately under relevant items of Schedule 'A', however the the cost of suitable wires, lugs, nuts, bolts and washers required for control wiring shall be included in quoted rate.
a) Up to 15 KVA, 240/415 V, 50 Hz of any phases
b) 20 KVA to 30 KVA, 415 V, 50 Hz, Three phase
c) 30 to 50 KVA, 415 V, 50 Hz, Three phase
d) 60 to 75 KVA, 415 V, 50 Hz, Three phase
e) 100 to 125 KVA, 415 V, 50 Hz, Three phase
f) 160 - 300 KVA, 415 V, 50 Hz, Three phase
Supply only AC stepper motor of capacity 3Kg / CM suitable for servo controlled voltage stabilizer complete all as specified and as directed.. Make : - Servomax / Servocon / SCAN power stabilizer
Supply only AC stepper motor of capacity 10Kg/CM suitable for servo controlled voltage stabilizer complete all as specified and as directed. Make :- Servomax / Servocon / SCAN power stabilizer
Supply only motor gear and variac shaft gear set suitable for servo controlled voltage stabilizer complete all as specified and as directed.
Supply only RC Network 3Kg / CM to 10 Kg / CM suitable for servo controlled voltage stabilizer complete all as specified and as directed.
Supply only sensing transformer with triac board complete all as specified and as directed.
Supply only control PCB with wiring complete all as specified and as directed.
Supply only voltmeter 0 to 500 V of existing type suitable for existing servo controlled voltage stabilizer complete all as specified and as directed.
Supply only limit switches suitable for existing servo controlled voltage stabilizer complete all as specified and as directed.
Supply only POT meters suitable for existing servo controlled voltage stabilizer complete all as specified and as directed.
Supply only carbon brushes of various capacity suitable for existing servo controlled voltage stabilizer complete all as specified and as directed.
Supply only VARIAC of rating upto 15 A suitable for existing servo controlled voltage stabilizer complete all as specified and as directed.
Supply only VARIAC of rating above 20 A and upto 35 A suitable for existing servo controlled voltage stabilizer complete all as specified and as directed.
Supply only ECC box suitable for existing servo controlled voltage stabilizer complete all as specified and as directed.
Material and labour for Filtration / dehydration of transformer oil of oil cooled servo voltage stabilizer of various capacities installed at various locations within Air Force Station Hakimpet with mobile type filtration plant to achieve di-electric strength of 30 KV for 1 minute at 2.5mm gap as per relevant IS including testing and recording the values of dielectric strength of oil before and after filtration at site with transformer oil testing machine complete all as specified and as directed.
Supply and Topping up of transformer oil into the body of servo controlled voltage stabilizer having di-electric strength of 40 KV for 1 minute at 2.5mm gap as per relevant IS complete all as specified and as directed.
Cutting / pruning of tree branches along /around over head LT line at places within a radius of 2 mtr from furthest conductor and removing from site complete all as specified and as directed.
Supply and fixing post top lantern LED type 20 watt 230 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp including provision of mounting pole of suitable Dia & Height complete all as specified and as directed.
Supply and fix Switch flame proof rotary type with termination box in LM6, 16A, single pole 250V including taking down existing unserviceable flame proof switch complete all as specified and as directed.
M&L for Earthing complete with galvanized steel earth plate electrode 600 mm x 600 mm x 6 mm thick buried directly in ground earth pit not less than 2.25 mtr deep below normal ground level with top edge of the plate not less than 1.5 mtr below ground level connected to galvanized iron or steel earth lead strip 32x6 mm size upto 7.5 mtr long in single length by mean of nut/bolt and washer of galvanized iron or steel as shown in electrical plate no 5 of SSR part I including necessary excavation in hard/dense soil and earth work GI pipe 20mm dia mediumj grade for watering and GI 15mm dia light grade pipe for protection of GI earth wire etc, PCC chamber with PCC cover in cement concrete 1:2:4 Type B1(20mm graded aggregate), funnel, wire mesh, charcoal dust, salt etc, connected to LT panel board as indicated including testing complete all as specified and as directed.
M&L for Earth continuity GI strip 32 mm X 6 mm with saddles and fixing screws etc fixed to wall on batten/porcelain insulator or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing including breazing at each necesasry joints etc complete all as specified and as directed.
M&L for replacement of earth continuity copper strip 20 mm X 3 mm with saddles and fixing screws etc fixed to wall on batten/porcelain insulator or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing including breazing at each necesasry joints etc complete all as specified and as directed.
Checking, identifying the defect /faulty point of LT UG cable of any size using Conventional Cable fault locator machine or by mannual excavation and taking out bricks from the trench upto fault point along cable route and re-laying the same using old bricks / sand including returning filling and making good surface after rectification of defect complete all as specified and as directed.
Material and labour for cable jointing kit for 1100 Volts grade cable for straight through joint (Heat Shrink system) complete with jointing material and accessories suitable for 3.5/4 core XLPE/PVC insulated armoured aluminium conductor cable of size 240/300 sqmm complete all as specified and as directed.. (Make :- Birla 3M / M Seal / Raychem RPG / Densons).
Description all as per item No. 49 here-in-before but of size 120 sqmm to 185 sqmm. , 3.5/4 core complete all as specified and as directed.
Description all as per Ser item No. 49 here-in-before but of size 3.5/4 core, 70 sqmm to 95 sqmm. complete all as specified and as directed.
Description all as per Ser item No 49 here-in-before but of size 3.5/4 core, 25 sqmm to 50 sqmmcomplete all as specified and as directed.
Material and Labour for inspecting and servicing of APFC panel of capacity from 55 KVAR to 75 KVAR installed at various locations within Air Force Station Hakimpet by cleaning the complete panel with suitable cleaning agent and checking the serviceability state of all the switchgears/ components such as Capacitors, Relays, Contactors, MCCBs, control MCBs, fuse cut outs, meters, auto/manual switches/ push buttons, indications lamps, control wiring etc complete and replacing the defective spare parts and testing for proper fuctioning complete all as specified and as directed. Note :- Supply and replacement of Components / spare parts will be measured and and paid separately under relevant items of Schedule 'A', however the the cost of suitable wires, lugs, nuts, bolts and washers required for panel wiring shall be included in quoted rate.
Supply and replace heavy duty contactor with built in auxiliary contact suitable for capacitor of rating upto 12.5 KVAR, 415 V, 3 Ph, 50 Hz of existing type complete all as specified and as directed.
Supply and replace heavy duty contactor with built in auxiliary contact suitable for capacitor of rating above 12.5 KVAR and upto 25 KVAR, 415 V, 3 Ph, 50 Hz of existing type complete all as specified and as directed.
Supply and replace 12 stage APFC relay, 415 V, 3 Ph, 50 Hz of existing model complete all as specified and as directed.
Supply and replace heavy duty power capacitors of rating 1 KVAR to 2 KVAR, 440 Volts, 3 Ph, 50 Hz of existing type/ model complete all as specified and as directed.
Supply and replace heavy duty power capacitors of rating 4 KVAR to 5 KVAR, 440 Volts, 3 Ph, 50 Hz of existing type/ model complete all as specified and as directed.
Supply and replace heavy duty power capacitors of rating 10 KVAR, 440 Volts, 3 Ph, 50 Hz of existing type/ model complete all as specified and as directed.
Supply and replace heavy duty power capacitors of rating 12.5 KVAR, 440 Volts, 3 Ph, 50 Hz of existing type/ model complete all as specified and as directed.
Supply and replace heavy duty power capacitors of rating 15 KVAR, 440 Volts, 3 Ph, 50 Hz of existing type/ model complete all as specified and as directed.
Supply and replace Current transformer of ratio 200/5A, CL-I, 10 VA for measuring purpose complete all as specified and as directed.
Supply and replace LED type pilot light indication lamps for R, Y, B phases complete all as specified and as directed.
Supply and replace illuminated push buttons for ON/OFF purpose (Red and Green) of existing size mounted on front door of panel complete all as specified and as directed.
Supply and replace on delay timer of existing type suitable for APFC panel complete all as specified and as directed.
Supply and replace auto/ manual rotary switch, 230V, 50 Hz of existing type complete all as specified and as directed.
Supply and replace axial flow ventilation fan to work on 230 V, 1 ph, AC supply of existing size/ model complete all as specified and as directed.
Supply and replace MCB SP 6-32 A, 10 KA, 'C' curve complete all as specified and as directed.
Supply and replace glass fuse with fuse blow indicator,6 A, 230 V, 50 Hz complete all as specified and as directed.
Supply and replace glass fuse with fuse blow indicator,200 A, 230 V, 50 Hz complete all as specified and as directed.
Supply and replace auxiliary contactor for AC control std coil voltage 230 to 415 Volts, 50Hz of any type complete as per existing capicity complete all as specified and as directed.
Modifiaction of LT Panel by adding the Bus Bar of Size (300 Amp capacity) with the length of 400 mm and shape as required at the site with cutting, drilling, welding of Panel sheet for holding the bus bar with spacer , nut Bolt and other neceessary items complete all as specified and as directed.
M&L for surface excavation over the areas around the poles/feeder piller boxes/ sub stations not exceeding 15cm depth including cleaning the bushes and vegetation and leveling incl removal of surplus soil in hard/ dense soil. complete all as specified and as directed. Note :- This Job may be repeated on the same location after three months
Material and labour for ACSR conductor and proper stringing for required tension and sag including binding with new aluminium binding wire of suitable size including taking down old ACSR conductor complete all as specified and as directed.
S&F( in replacement) Pole box three phase of size 297x 250 x 130 mm made out of 2 mm MS sheet factory made with inbuilt locking arrangement, out door type , fix to pole with suitable MS clamp comprising of alluminium busbar 16 Amp 04 Nos fixe on epoxy insulated pole and MCB 6 Amp 10 kA 240 volt complete all as specified and as directed.
Disconnecting of OH line of ACSR Conductor / GI earthing wire, opening of binding wires, jumper connections any size and restringing, tightening of conductor with suitable line vice, replacing all worn out jumper connection with suitable conductor, re-tightening and straightening all cross arms, insulators, clamps etc including replacement of all wornout nut bolts and washers complete all as specified and as directed.
Material and labour in replacement of Shackle Type, Porcelain, vitreous, white, brown or green insulator including galvanised mild steel straps, washers, insulator bolts, washers and nuts for working pressure 1100 volts of size 75 mm height and 90 mm dia complete all as specified and as directed. (Make :- Jaipuria Bros / WS / Mysore Porcelain).
Material and labour in replacement of Pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 100mm height, 65mm dia for 1100 volts grade complete all as specified and as directed. (Make : - Jaipuria Bros / WS / Mysore Porcelain).
Supply and fix in replacement of rigid PVC LT line spacers spiral/bolted type as per IS:1445-1977 suitable for 2 wires complete all as specified and as directed.
Description all as per item No.80 here-in-before but suitable for 4 wires complete all as specified and as directed.
Repairing / overhauling of existing indoor/outdoor type LT panel board/bus bar /any size/type fixed on building wall / PCC block incl cleaning with compressed air, tightening of all electric connection to the bus bar, providing bus bar, insulator of suitable size & switch gears , refixing of loosed doors with proper fixing & locking arrangement &necessary welding work as required and replacement of wornout/ burnt/rusted/ loose lugs , door lock, nut bolt,hing, washers,internal wiring with suitable size (minimum 1.5 sqmm) of PVC copper conductor wire ,repair to plaster work as require at site and including disconnection of all cable/ sub main from the bus bar and insulating the neked portion of Al conductor and re-connect the same after repair of panel and proper connection of main earth wire/lead with panel body using lugs complete all as specified and as directed.
M& L for reparing door of existing LT panel / feeder pillar box with locking arrangement & gasketed made of CRCA sheet 2.0 mm thick including hinge and welding work complete all as specified and as directed.
Material and labour in replacement of Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size including applying two coats of aluminium paint over a coat of red oxide primer complete all as specified and as directed.
Material and labour in replacement of Stay assembly with 16 mm dia stay rod and all accessories as shown in electrical plate No. 1 complete all as specified and as directed.
Digging & taking out old steel tubular pole 9/11 mtr long carefully from foundation for re-use, shifting and re-fixing / re-errecting at other location within Hakimpet area complete all as specified and as directed for the following :-
(a) Excavation in post hole not exceeding 1.5 Mtr wide & 2 Mtr deep for pole foundation & getting out in soft loose soil, returning, filling in the excavated soil after fixing the pole in foundation, ramming earth around in layers n.exc 25 cm thick and disposal of surplus soil to a distance n.exc 50 metres.
(b) M&L for Providing PCC 1:4:8, type D2 ( using 40 mm graded stone aggregate) in foundation 600mm x 600mm x 1500 mm (planting depth) for concrete encasing the pole upto GL all as specified and directed.
(c) M&L for Providing PCC 1:3:6, type C2 (using 20 mm graded stone aggregate) for plinth block /Collar above GL, 300 mm high and 450x450 mm size and plastering with 1:4 PCC complete all as specified.
(d) M&L for Painting of pole externally with one coats of black bituminous paint (upto planting depth) and above plinth block/ concrete collar with two coats of aluminium paint over a coat of red oxide primer including preparation of surfaces including painting of 30 cm wide black bands 3 Nos with synthetic enamel paint in alternate layers upto the height of 1.5 Mtr above plinth block.
S&F in replacement of steel tubular electric pole, swaged type, welded (9 metre long) complete with CI base plate, bolts, nuts & screws all as specified type 410 Sp-31 complete all as specified and as directed.
M&L for preparation of old painted surfaces of LT 8.5/ 9.0 m height steel tubular/ ISMB poles by scrubing sand paper alongwith all pole fittings such as cross arms, clamps, nuts & bolts etc and applying paint as follows:- (i) One coat of aluminium paint on all exposed surfaces of pole, cross arms, clamps, nuts & bolts etc, leaving in 1m from ground level. (ii) One coats of synthetic enamel paint of approved colour upto 1.0m height from GL including coping. (iii) Writing pole number in white letters on black background with synthetic enamel paint complete all as specified and directed by Engineer-in-Charge.
M&L for preparation of old painted surfaces of LT 8.5 / 9.0 m height PCC poles by scrubing sand paper alongwith all pole fittings such as cross arms, clamps, nuts & bolts etc and applying paint as follows:- (i) One coat of aluminium paint on all steel sections such as cross arms, clamps, nuts & bolts etc, leaving in 1m from ground level. (ii) One coat of synthetic enamel paint of approved colour upto 1.0m height from GL including coping. (iii) One coat of Cement base paint on balance portion of PCC pole. (iv) Writing pole number in white letters on black background with synthetic enamel paint complete all as specified and directed by Engineer-in-Charge.
Takingdown old existing outdoor LT panel board of any description and Supply, installation, testing and commissioning of oudoor type cubicle panel board of size not less than 1100 mm x 600 mm x 400 mm suitable for 3 phase 4 wire, 50 Hz supply system CPRI approved factory fabricated made out of 3 mm thick CRCA sheet for outer shell and 2 mm thick for inner shell with front and rear openable double lief doors with locking arrangement complete with powder coat painting and suitable packing material for IP- 43 degree of protection and confirming to IS:8623-1993 and including 50mmx50mmx6mm angle iron base frame of suitable size for mounting the panel board at a height of 450mm from GL and grouted on PCC foundation complete all as specified and directed by Engineer-in-Charge. The size of panel board shall be suitable for accommodating and including provision of following switchgears complete:-
(a) Aluminium bus bar of capacity 600 Amp with heat shrinkable coloured PVC sleeve insulation mounted on suitable insulators for 3 phases and half of the capacity for neutral - 01 Set (b) MCCB, 400 Amps, 4 Pole,35 KA microprocessor based(Make:Havells/Indoasian/L&T/Standard).-01No.(incoming). (c) MCCB, 250 Amps, 4 Pole, 25 KA microprocessor based - (Make: Havells/indoashian/L&T/Standard). -02 Nos. (Outgoing) (d) MCCB 160 Amps, 4 Pole, 25 KA microprocessor based (Make: Havells/indoashian/L&T/Standard). - 03 Nos. (Outgoing)
Supply and install LT Panel out door double door front and rear openable type made out of CRCA 3 mm thick sheet and angle iron of size 40 x 40 x 4 mm thick complete including locking arrangement,proper mounting of feeder pillar legs of size not less than 800x500x400 mm on cement concrete foundation including painting with 2 coats of synthetic enamel grey paint complete comprising following including taking down of old LT panel board : Note :- Old Retrieved serviceable MCCBs will be deposited to AGE E/M Store. (a) Aluminium bus bar of capacity 300 Amps- 1 set 3 Nos phase, 1 No neutral (b) MCCB 200 Amps capacity 415 V,25KA 4P microprocessor based (Incoming) (c) MCCB 100 Amps capacity 415 V,16 KA 4P- 01 nos microprocessor based (out going) (d) MCCB 63 Amps capacity 415 V,16 KA 4P- 02 nos microprocessor based (out going)
Material and Labour for spray painting with two coats of enamel paint surfaces of any description of approved colour over one coat of red oxide metal primer after scraping thoroughly the existing corroded metal surfaces of the LT panel at installed position complete all as specified and as directed.
Supply and fix Off load changeover rotory type switch 250Amps, 4 Pole, in sheet steel enclosure including taking down existing unserviceable changeover switch complete all as specified and as directed.(Make :- Havells/Indoashian/L&T/Standard))
Supply and fix On load changeover rotory type switch 200 Amps, 4 Pole , suitable for LT Panel including taking down existing unserviceable changeover switch complete all as specified and as directed.(Make :- Havells / Indo asian / L&T / Standard))
Description all as per Ser item No. 94 here-in-before but of capacity 100 Amps complete all as specified and as directed.
M&L MCCB 4 Pole, current rating 250 Amp, microprocessor based, thermal setting adjustable 70%-100% breaking capacity 25kA at 415V,50Hz. Including both side spreader complete all as specified and as directed.
Description all as per Ser item No.96 here-in-before but of capacity 160 Amps, 36 KA. complete all as specified and as directed.
Description all as per Ser item No. 96 here-in-before but of capacity 25-100 Amps, 1 6KA complete all as specified and as directed.
M&L MCCB 3 Pole, current rating 400 Amp, microprocessor based, thermal setting adjustable 70%-100% breaking capacity 36kA at 415V,50Hz Including both side spreader complete all as specified and as directed.
M&L MCCB 3 Pole, current rating 350 Amp, microprocessor based, thermal setting adjustable 70%-100% breaking capacity 35kA at 415V,50Hz Including both side spreader complete all as specified and as directed.
Surface excavation not exc 30 Cm deep and averaging 15 cm deep and getting out in hard / dense soil complete all as specified and as directed.
M&L for hard core of broken stone of guage n.exc 63 mm deposited spread and leveled in layres , water and rammed true surface in Pathway / hard standing to transformer / DG set/LT Panel complete all as specified and as directed.
M&L for 50 mm thick PCC , 1:3:6 type C- 2 mix using 40 mm graded stone aggregate laid in floors.foundation, sub base etc and cement concrete surface finished even and smooth without using extra cement complete all as specified and as directed.
M&L for 25 mm thick PCC , 1:2;4 type B1 using 20 mm graded stone aggregate as in copings etc including necessary formwork and exposed surface of concrete shall be finished even and smooth without using extra cement complete all as specified and as directed
M&L for glass dividing strips 3 mm thick & 38 mm width inserted in position and confirming to design complete all as specified and as directed.
Material and labour for repair of chemical earth pit by using liquid chemical earthing solution (not less than 10 Kg) and mixing with water and filling into the chemical earth pit to achieve the result less than 01 Ohm complete all as specified and as directed.
M&L for in replacement of porcelain vitreous white seperators and fixing screws etc . to be refixing alongwith the pole and wall with existing copper strip complete all as specified and as directed.
M&L for dismanteling of damaged / cracked PCC of existing earth pit and prepare the new Earth pit using PCC 1:2:4 type B-1 mix using 20 mm graded stone aggregate alongwith the cover with suitable handle complete all as specified and as directed.
SRI SAI RAM ENTERPRISES
THE DECAN ENGINEERING AND REFRIGERATION COMPANY
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .