Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.3 LAccepted-AOC | L1 | Accepted-AOC L1 bidder | |
| 2 | L2₹9.5 L+₹19,807 (2.14%)Rejected-Finance | L2 | Rejected-Finance Rejected_Fin | |
| 3 | L3₹9.9 L+₹62,915 (6.79%)Rejected-Finance | L3 | Rejected-Finance Rejected_Fin | |
| 4 | L4₹10.4 L+₹1.1 L (11.9%)Rejected-Finance 86 TOLLYGUNGE CIRCULAR ROAD KOLKATA WEST BENGAL 700053 | KOLKATA | KOLKATA | WEST BENGAL | 700053 | L4 | Rejected-Finance Rejected_Fin |
Tender Value
₹11.5 L
EMD Value
₹23,061
Closing Date
22 Oct 2024, 12:00 pmClosed
EE_II, Kol. South Health El. Divn.,P.W.Dte.
75 D H Road Kidderpore Kol_23
Urgent Replacement of 3 nos Ductable Split AC at Central Block (Third Floor) of Extended SNCU (Minor OT) and SITC of new Air- Conditioning Machines along with necessary Electrical Works releted to AC installation works in CSS-SITC of AC M/chs
2024_WBPWD_757113_1
WBPWD/EE-II/KSHED/Q63/24-25
Open Tender
A/C ORG
Item Rate
30 days
Kolkata
Please refer Tender documents.
3 documents required · 3 mandatory
₹23,061
O/o Exe. Engr., Kol. South Health El. Divn., PWDte
4 Apr 2025
24 Sept 2024
24 Oct 2024
24 Sept 2024
22 Oct 2024
3 Oct 2024
1 Oct 2024
Amount
Supply, installation, testing and commissioning of 5.5Tr Microprocessor based Air cooled Ductable Split Unit in compliance with latest QCO guideless complete with highly efficient Single Scroll Compressor suitable for operate on eco-friendly refrigerant R-407C/R-410A , Copper condenser coil, unit mounted starter panel complete with all accessories suitable for operate on 415V +/- 5%, 50Hz, 3ph AC Supply (As per direction of E.I.C). MAKE: VOLTAS/MITSUBISHI/O GENERAL/DAIKIN. .
SupplyInstallation Testing & Commissioning of 1.5 ton Split type room Air conditioner fitted with Power saver rotary compressure having turbo cooling capacity 5400Wt suitable for operate on 230V +/-510%, 50HZ Single phase AC Supply having features model (Auto/Cool/fan/Dry) air flow (horizontal louver/Verticle swing) sleep mode timer off/on anti freeze thermostat bio/active carbon/dust air filter with star rating 3 star. [Make O-General/Voltas/Mistshubishi Electric /Daikin)).
SITC of duct fabricated with 22 SWG galvanised Ducting GI sheet complete with necessary MS supports as required & turning vanes etc complete as per IS 655 ( Make : Sail/TATA)
Thermal Duct Insulation with 13 mm thickness with fire retendent Al foil faced closed nitrul rubber insulation on duct with necessary pesting.(Make - Acoflex / Araflex / Supreme)
Acoustic lining of duct work with 12mm thick having density 48 Kg /mtr³ rigid board inside with 300 fiberglass RP tissue & 36 G Al purforated sheet with necessary accessories initialy fastened, covered. Acoustic lining shall be rigid board.(Make - Twiga)
REFRIGERANT PIPING : Installation and commissioning of hard/soft copper refrigerant piping, complete with fittings, elbows, bends, supporting arrangement on walls for Ductable /Concealed split AC :
22.2mm OD with minimum thickness 0.9mm with 9mm thick Nitrile insulation .(Make: Rajko/Royku/Mandev)
12.7mm OD with minimum thickness 0.8mm with 9mm thick nitrile insulation (Make: Rajko/Royku/Mandev)
15.88 mm OD with minimum thickness 0.9mm with 9mm thick Nitrile insulation .(Make: Rajko/Royku/Mandev)
6.35mm OD with minimum thickness 0.9mm with 9mm thick Nitrile insulation .(Make: Rajko/Royku/Mandev)
DIFFUSERS: S/F Al powder coated diffuser with VCD for supply/Return air Make : Dynacraft/Premier/Ravister)
Supply and installation of motorized fire damper incl acuator control panel and all other requried accessories (Make:Systemair / Dynacraft / Premier / Air enterprise/Caryaire / Airmaster.
DRAIN PIPING :-Supply & laying of 1" dia.drain Water piping work out of UPVC/ HDPE hard pipes (Supreme, ISI Marked) incl. fitting , accessories bends, elbows, tees, flanges, tapings, etc. insulated with 9mm. Thick nitrile rubber tube insulation.
Supplying & Fixing of fire proof Canvass Connection with necessary fixing accessaries as required.
Electrical Cabling : Supply ,installation ,testing and commissioning of control cabling of 4Core 1.5Sqmm 1.1kV grade PVC insulated copper cable between ODU and IDU(Make-Finolex/ Polycab/Gloster/Havells) .
Supply ,installation ,testing and commissioning of control cabling of 4Core 2.5Sqmm 1.1kV grade PVC insulated copper cable between ODU and IDU(Make-Finolex/ Polycab/Gloster/Havells) .
Supply installation of VI pad for ODU Unit
Supply and Charging of R-410A Refrigerant.
FRAME WORK: Supply, fabrication & fixing of 2 nos. M.S 'U' Channel of 6mm thick of size (75mm x 40mm x 40mm) of 1m length for making platform for installation of outdoor unit incl. drilling 2 nos. hole in each channel for all outdoor units including making necessary arrangement as per site condition as per direction of EIC.
Supplying,fitting & fixing in position suspended false ceiling with frame work of aluminium hollow section of size 50mm X 25mm (2.0mm thickness) combined with aluminium corners of size 38mm X 25mm, suspended by aluminium hollow tube section of size 38mm X 25mm having size of 600mm X 600mm ceiling with aluminium composit panels (ACP) - Interior grade of thickness 3.0mm comprising of proctective film, polyester coating, primer, aluminium coil, adhesive film, polyethylene core again with one layer adhesive film, aluminium bottom coating and finally service coating as per manufacturer's specification finished with aluminium screw and silicon sealent complete in all respect including all incidental charges etc. as per direction of Engineer-in-charge.
Insulation of drop celing by 10mm Nitrile rubber sheet (Accoflex / A-flex) with necssary pasting by best quality adhishive as per direction of EIC
Making Trap door for maintenance of Indoor Unit with lockable gate.
Lifting charges for indoor & outdoor units after making scaffolding arrangement as required
TERMS & CONDITIONS :- The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them. Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/ submission of bill. If any refurbished material is supplied and installed, penal action will be taken as per existing rules
Defect Liabibility Period 1 (One) year
Make & model of each and every material to be approved by EIC
TRANSTECH (BID ID -5699423)
NEXAIR TECHNOLOGIES PVT LTD (BID ID -5689013)
Lyric International (BID ID -5703506)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .