Loading…
Loading…
Tender Value
₹72.7 L
EMD Value
₹1.5 L
Closing Date
14 Jul 2026, 6:00 pm4d left
Unit Head
Senior Deputy General Manager RIICO EPIP Sitapura
Remaining electrification and fire safety work in plug and play building EPIP Sitapura, Jaipur
2026_RIICO_571704_1
18/EPIP Sitapura/2026-27/1015/1
Open Tender
Electrical Works
120 days
plug and play building EPIP Sitapura
Please refer Tender documents.
4 documents required · 4 mandatory
₹2,360
RIICO Ltd
₹1.5 L
29 Jun 2026
29 Jun 2026
15 Jul 2026
29 Jun 2026
14 Jul 2026
29 Jun 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | SITC of UL 10th edition / EN54 / VDS certified Automatic Floating Sensitivity type Analog addressable Multi criteria (two optical/Smoke sensor to reduce false alarm) detector with mounting base & LED etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . | 420 | Each | 3,104 | ₹13,03,680 |
| 2 | SITC of UL 10th edition / EN54 / VDS certified Addressable type fault isolator with base for isolating shorted, dewired and loose circuits between two successive fault, isolators with automatic resetting arrangement etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . | 22 | Each | 2,726 | ₹59,972 |
| 3 | SITC of UL 10th edition / EN54 / VDS certified Addessable Manual Call point (MCP) with LED / FIRE Indication Etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . | 24 | Each | 3,509 | ₹84,216 |
| 4 | SITC of UL 10th edition / EN54 / VDS certified Addressable sounder with strobe light, Loop Powered / Direct powered from FACP with sound level 90 dB and programmable from the panel etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . | 24 | Each | 8,128 | ₹1,95,072 |
| 5 | SITC of Response Indicator for indicating the activation of the Remotely located Detector for Addressable type Detectors Etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . | 45 | Each | 269 | ₹12,105 |
| 6 | SITC of UL 10th edition / EN54 / VDS certified Microprocessor based inteligent, Analogue addressable,modular, expandable networkable loop Fire Alarm Control Panel with each loop capacity of min 125 detectors per loop with total of 125 detectors & devices with Loop length up to 1 KM as per NFPA 72 approval. The Panel shall be able to give pin point location of addressable units via the address code for each unit. The Panel shall also be able to automatically switch off all control switches when-ever any Alarm is triggered. . The panel shall have 230 + 5 % volts power supply, Automatic battery charger 24V, sealed lead acid maintanence free battries sufficient for 24 hours normal working and then be capable of operating the system for 30 minutes during emergency condtion. Loop interface cards, communication module, LCD/LED unit to indicate Fire / Fault Signal of individual unit, inbuilt networking port(both RS485&Ethernet),Serial port for printer,two supervisory inputs,two position key switch and USB port for programming.including the cost of all accessories Etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR ., 2 - Loop Panel | 1 | Each | 2,96,858 | ₹2,96,858 |
| 7 | SITC of UL 10th edition / EN54 / VDS certified Microprocessor based inteligent, Analogue addressable,modular, expandable networkable loop Fire Alarm Control Panel with each loop capacity of min 125 detectors per loop with total of 125 detectors & devices with Loop length up to 1 KM as per NFPA 72 approval. The Panel shall be able to give pin point location of addressable units via the address code for each unit. The Panel shall also be able to automatically switch off all control switches when-ever any Alarm is triggered. . The panel shall have 230 + 5 % volts power supply, Automatic battery charger 24V, sealed lead acid maintanence free battries sufficient for 24 hours normal working and then be capable of operating the system for 30 minutes during emergency condtion. Loop interface cards, communication module, LCD/LED unit to indicate Fire / Fault Signal of individual unit, inbuilt networking port(both RS485&Ethernet),Serial port for printer,two supervisory inputs,two position key switch and USB port for programming.including the cost of all accessories Etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR ., Add Extra for per Loop expansion beyond Two Loop | 2 | Per Loop | 67,462 | ₹1,34,924 |
| 8 | SITC of UL 10th edition / EN54 / VDS certified Active Repeater Panel for Fire Alarm System with inbuilt networking port (both RS485 & Ethernet),Serial port for printer,two supervisory inputs,two position key switch and USB port for programming. The Repeater Panel shall allow users to acknowledge, reset,silence, program, view hisory events.etc (All functions similar to main panel)The user interface of the repeater panel shall be same as the Main Controller with menu driven user interface with smart search.including the cost of all accessories Etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . | 1 | Each | 80,967 | ₹80,967 |
| 9 | Supplying and drawing Fire Resistant flexible / stranded bare copper conductor, PVC / XLPE insulated, overall aluminium mylar tape shielded ATC drain wire and outer PVC sheathed industrial Instrumentation (shielded)cables voltage grade 300/500 V as per BS /EN 50288-7 in existing surface or recessed PVC/ MS conduit/casing capping / Cable tray / Open Duct making connections, testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for cables. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR ., 2 x 1.5 Sq.mm Armoured With Outer Sheath in Red Color | 3,520 | Mtr | 158 | ₹5,56,160 |
| 10 | SProviding & Laying P.V.C. / XLPE insulated & P.V.C. sheathed Armoured Copper cable confirming to IS:1554 P-I / IS :7098 P - I of 1.1 KV with electrolytic grade Copper made of copper rods confirming to IS 613-1964, of purity >99.7 %, round / flat strip armouring, Inner / outer sheath confirming to IS:5831 in existing RCC / Hume / Stoneware / PVC pipe/ open duct/cable trench / Cable tray(with cable tie) including testing etc. as required of following size. OEM must have it's own in house NABL accrediated Laboratory for testing procedure as per IS:10810 For additional technical parameters of product / work refer Annexure 'A' attached with this BSR, 1.5 Sq. mm, 6 core | 950 | mtr | 223 | ₹2,11,850 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.06 MB
BOQ_1017296.xls
BOQ • 0.60 MB
Specialtermsandconditionsfire.pdf
Other Document • 0.24 MB
Tenderdocument01.pdf
Tender Documents • 0.21 MB
Download all tender documents and submit your bid