| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | H3₹66.5 LAccepted-AOC 3 4 JEEVAN DEEP BUILDING 10 PARLIAMENT STREET NEW DELHI 1 PH 011 43573493 9899713006 | ₹66.5 L Quoted ₹58.9 L | H3 | Accepted-AOC L1 bidder |
| 2 | H1₹67.2 LRejected-Finance 19 LAKE TEMPLE ROAD KOLKATA 700029 | KOLKATA | WEST BENGAL | 700029 | ₹67.2 L | H1 | Rejected-Finance L3 Bidder |
| 3 | H2₹62.7 LRejected-Finance VASANTASAKHA PLAZA NEAR NAVLE BRIDGE NEXT TO DANGAT CERAMIC HOUSE NARHE PUNE 411 041 | PUNE | MAHARASHTRA | 411041 | ₹62.7 L | H2 | Rejected-Finance L2 Bidder |
| 4 | Rejected-Technical | - | - | Rejected-Technical Not submitted all the documents required as per NIT |
| Sl No | Description | Qty | Unit | SNOWMEX ENGINEERS LIMITED H3 | Virtus Techno H2 | SHINRYO SUVIDHA ENGINEERS INDIA PVT. LTD. H1 |
|---|---|---|---|---|---|---|
| 1.00SH-I: Electrical Works | ||||||
| 2.00 | Supply, installation, testing and commissioning of FRP/ GRP (Glass reinforced polystyrene) induced draft based Single cell rectangular shape induced draft counter flow type cooling towers for airconditioning system. Each tower shall be complete with basin, casing distribution system, filling fills, hot deep galvanised (HDG) supportors, GI ladders, motor (IP55 protection) suitable for 415 ± 10% volts, 3 phase power supply, 50 Hz and high efficiency (IE-4) moter, isolators provision at cooling tower enclosed in weather proof panel, Emergency Stop Switch, sump temperature sensors complete as per specification as required.
Cooling Towers system shall be selected on the basis of ambient wet bulb 82.94 degree F and actual capacity as follows:
Nominal Capacity : 387.8 TR (Heat rejection - 11,61,753 kcal/hr)
Water flow rate : 1218 USGPM
Water temp. in : 37 °C
Water temp. out : 32 °C
Note: Selection of Moter shall be as per AAI approval. | 4 | Job | 7,95,000 ₹31.8 L | 8,46,000 ₹33.8 L | 8,72,025 ₹34.9 L |
| 3.00 | Supply, Installation, Testing and Commissioning of Centrifugal Split Casing Pump with bronze and corro coating factory assembled on a common base duly aligned with electric motor (efficiency IE4) for recirculation of water for the central air conditioning system. The pump motor shall be suitable for 415 + 10% volts, 50 Hz, 3 phase power supply including base plate, vibration isolation pad, rubber expanasion bellow, mechanical seals, drain connection remote start stop push buttons etc. complete as required including providing and laying in position cement concrete 1:2:4 (1 Cement : 2 Coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump including form work etc. as required
Condenser Water Pump Motor specification as follows :
Water flow rate : 1218 USGPM each
Head : Minimum 20 Mtr.
Pump Efficiency : Minimum 75%
Note: Selection of Moter and pumps shall be as per AAI approval. | 4 | Job | 3,25,000 ₹13 L | 2,80,297.2 ₹11.2 L | 3,75,375 ₹15.0 L |
| 4.00Supply fixing, testing and commissioning of condenser water pipes of following sizes of MS ‘C’ class along with necessary clamps, vibration isolators and fittings such as bends,tees etc. but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect. | ||||||
| 5.00 | 250 mm dia MS pipes ('C' Class) | 18 | Mtr. | 5,976 ₹1.1 L | 3,180 ₹57,240 | 4,704.7 ₹84,684.60 |
| 6.00 | 125 mm dia MS pipes ('C' Class) | 14 | Mtr. | 50 ₹700 | 1,980 ₹27,720 | 2,524.67 ₹35,345.38 |
| 7.00 | 100 mm dia MS pipes ('C' Class) | 32 | Mtr. | 1,428 ₹45,696 | 1,458 ₹46,656 | 1,430.9 ₹45,788.80 |
| 8.00 | 50 mm dia MS pipes ('C' Class) | 15 | Mtr. | 980 ₹14,700 | 1,020 ₹15,300 | 754.75 ₹11,321.25 |
| 9.00SITC of Cast Iron BUTTERFLY VALVE (MANUAL) with C I body SS disc nitrile sheet & O - ring & PN 16 pressure rating as specified. | ||||||
| 10.00 | 250 mm dia Valves. | 5 | Nos. | 28,500 ₹1.4 L | 17,892 ₹89,460 | 21,469.83 ₹1.1 L |
Tender Value
₹66.5 L
EMD Value
₹2.0 L
Closing Date
12 Dec 2025, 6:00 pmClosed
AGM (E-E)
Engineering Electrical Department, S. V. Airport, Raipur.
Replacement of Cooling Towers of HVAC System at S. V. Airport, Raipur.
2025_AAI_256261_1
AAI/RPR/AGM/EE/CW/25-26/ENIT-2
Open Tender
Electrical Works
180 days
S. V. Airport
As per NIT criteria.
8 documents required · 8 mandatory
₹1,180
₹2.0 L
6 Mar 2026
21 Nov 2025
15 Dec 2025
21 Nov 2025
12 Dec 2025
21 Nov 2025
21 Nov 2025 - 28 Nov 2025
SH-I: Electrical Works
Supply fixing, testing and commissioning of condenser water pipes of following sizes of MS ‘C’ class along with necessary clamps, vibration isolators and fittings such as bends,tees etc. but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect.
250 mm dia MS pipes ('C' Class)
125 mm dia MS pipes ('C' Class)
100 mm dia MS pipes ('C' Class)
50 mm dia MS pipes ('C' Class)
SITC of Cast Iron BUTTERFLY VALVE (MANUAL) with C I body SS disc nitrile sheet & O - ring & PN 16 pressure rating as specified.
250 mm dia Valves.
125 mm dia Valves.
100 mm dia Valves.
50 mm dia Valves.
BALANCING VALVE WITH BUILT IN MEASURING FACILITY with C I body flanged construction with EPDM coated disc with long pitch with protected out pipe insulation & PN 16 pressure rating for chilled / hot water circulation as specified. 250 mm dia Valves.
SITC of Y - STRAINER of Ductile CI Body flanged ends with stainless steel strainer for chilled / hot water circulation including insulation as specified. 250 mm dia strainers.
Supply of 3 core X 25 Sq.mm. size of 1.1kv grade multicore aluminium conductor XLPE insulated and PVC sheathed armoured cable as per IS : 7098:1988 with upto date amendments.
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of size Upto 35 sq. mm (clamped with 1mm thick saddle) on wall surface as required.
Supplying and making end termination with brass compression gland and aluminum lugs for 3 core, 25 Sq.mm. size of PVC insulated and PVC sheathed / XLPE aluminum conductor cable of 1.1 KV grade as required.
Supplying and installing of perforated Hot Dipped Galvanised Iron cable tray "cable tray" of size 150 mm width X 50 mm depth X 1.6 mm thickness with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.
Supplying and installing of perforated Hot Dipped Galvanised Iron cable tray “bends" (galvanisation not less than 50 microns) of 150 mm width X 50 mm depth X 1.6 mm thickness with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.
Supplying and installing of perforated Hot Dipped Galvanised Iron cable tray “Tee” (galvanisation not less than 50 microns) of 150 mm width X 50 mm depth X 1.6 mm thickness size with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.
Supplying and installing of perforated Hot Dipped Galvanised Iron cable tray “Cross member” (galvanisation not less than 50 microns) of 150 mm width X 50 mm depth X 1.6 mm thickness with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
Demolishing HVAC cooling Tower manually/ by mechanical means including stacking of metallic items and disposal of unserviceable material within 50 metres lead as per direction of Engineer - incharge.
SH-II: Civil Work
Centering and shuttering including strutting, propping etc. and removal of form for a) Lintels, beams, plinth beams, girders, bressumers and cantilevers
Centering and shuttering including strutting, propping etc. and removal of form for a) Columns, Pillars, Piers, Abutments, Posts and Struts
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete above plinth level. a) Thermo-Mechanically Treated bars (Fe-500D)
Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana /Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate /retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement. All works above plinth level Upto floor V level. a) Concrete of M25 grade with minimum cement content of 330 kg /cum.
Add for using extra cement in the items of design mix over and above the specified cement content therein.
Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete.
Drilling suitable holes in reinforced or plain cement concrete with power driven drill machine to a depth as per Drawing/manufacturer's specification in RCC beams, lintels, columns and slabs to introduce steel bars for sunshades/balconies including fixing the steel bars in position using epoxy resin anchor grout of Hilti HIT-HY 200-RV3 Adhesive anchor or equivalent approved make but excluding the cost of reinforcement, all complete as per direction of Engineer-In-Charge. From 12 mm upto and including 25 mm dia
Demolishing R.C.C. work manually/ by mechanical means including stacking of steel bars and disposal of unserviceable material within 50 metres lead as per direction of Engineer - incharge.
Preparation and submission of structural design/drawing for Base of Cooling Tower along with three copy of drawings, soft copy, hard copy of Design/drawings etc all complete including duly vetting from Govt. Engineering College/NIT/IIT .
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.55 MB
TenderDocument.pdf
Tender Documents • 10.82 MB
BOQ_295557.xls
BOQ • 0.31 MB
Download all tender documents and submit your bid