Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹13.9 CrAccepted-AOC | ₹13.9 Cr | L1 | Accepted-AOC Being the lowest tenderer L1 and reasonable |
| 2 | L2₹14.0 CrRejected-Finance NOT SPECIFIED | ₹14.0 Cr | L2 | Rejected-Finance Not being the lowest |
| 3 | L3₹14.1 CrRejected-Finance | ₹14.1 Cr | L3 | Rejected-Finance Not being the lowest |
| 4 | L4₹14.2 CrRejected-Finance | ₹14.2 Cr | L4 | Rejected-Finance Not being the lowest |
| 5 | L5₹17.8 CrRejected-Finance | ₹17.8 Cr | L5 | Rejected-Finance Not being the lowest |
Tender Value
₹12.5 Cr
EMD Value
₹9.5 L
Closing Date
21 Sept 2021, 6:00 pmClosed
Chief Engineer (Navy) Mumbai
HQ Chief Engineer (Navy) Mumbai, 26 Assaye Building, SBS Road, Colaba, Mumbai-05
RECONSTRUCTION OF CHARIOT HANGAR OF INS ABHIMANYU INCLUDING DEMOLITION AT NAVAL STATION KARANJA
2021_MES_459834_1
87881/E8
Open Tender
Civil Works
540 days
GE (P) NW Karanja
Please refer Tender documents.
8 documents required · 8 mandatory
₹3,000
GE (P) NW Karanja
₹9.5 L
Yes
HQ Chief Engineer (Navy) Mumbai
30 Sept 2021
15 Jul 2021
23 Sept 2021
15 Jul 2021
21 Sept 2021
7 Sept 2021
15 Jul 2021 - 24 Jul 2021
26 Jul 2021
Amount
SCHEDULE "A" Part - I (BUILDINGS & STRUCTURES WORKS) Total Amount B/F from Sch-'A' Part-I
SCHEDULE "A" PART-II (SITE CLEARANCE, AREA DEVELOPMENT, EXCAVATION & EARTHWORK) Total Amount B/F from Sch-'A' Part-II
SCHEDULE "A" PART-III (DEMOLITION / DISMANTLING) Total Amount B/F from Sch-'A' Part-III
SCHEDULE "A" PART-IV (INTERNAL WATER SUPPLY) Total Amount B/F from Sch-'A' Part-IV
SCHEDULE "A" PART-V (INTERNAL ELECTRICFICATION) Total Amount B/F from Sch-'A' Part-V
SCHEDULE "A" PART- VI (SEWAGE DISPOSAL) Total Amount B/F from Sch-'A' Part-VI
SCHEDULE "A" PART-VII (AREA DRAINAGE) Total Amount B/F from Sch-'A' Part-VII
SCHEDULE "A" PART-VIII (ROADS / PATHS / CULVERT) Total Amount B/F from Sch-'A' Part-VIII
SCHEDULE "A" PART-IX (EXTERNAL ELECTRIFICATION) Total Amount B/F from Sch-'A' Part-IX
SCHEDULE "A" PART-X (EXTERNAL WATER SUPPLY) Total Amount B/F from Sch-'A' Part-X
SCHEDULE "A" PART-XI (FIRE FIGHTING AND FIRE DETECTION CUM ALARM SYSTEM) Total Amount B/F from Sch-'A' Part-XI
SCHEDULE "A" PART-XII (FLAME PROOF FITTING) Total Amount B/F from Sch-'A' Part-XII
SCHEDULE "A" PART-XIII ( LIGHTNING PROTECTION ) Total Amount B/F from Sch-'A' Part-XIII
SCHEDULE "A" PART-XIV (AIR CONDITIONING ) Total Amount B/F from Sch-'A' Part-XIV
SCHEDULE "A" PART-XV ( DG SET ) Total Amount B/F from Sch-'A' Part-XV
SCHEDULE "A" PART-XVI ( CRANE ) Total Amount B/F from Sch-'A' Part-XVI
SCHEDULE "A" PART-XVII ( CONDUITS FOR LAN/ TELEPHONE SOCKET) Total Amount B/F from Sch-'A' Part-XVII
SCHEDULE "A" PART -XIX (MISCELLANEOUS ITEMS)
DEMOLITION / DISMANTLING
Dismantling and taking down UG cable complete all as specified and directed by Engr-in-charge of
70 Sqmm 3.5 core
35 Sqmm 3.5 core
25 Sqmm 3.5 core
16 Sqmm 4 core
Dismantling and taking down existing LT Panel complete all as specified and directed by Engr-in-charge
Dismantling and taking down switch fuse unit/MCCB DB/MCB DB of various sizes complete all as specified and directed by Engr-in-charge
Dismantling of existing AC plant 3 x 11 TR capacity including compressor, compressor motor, condenser, chiller pump set, AHU, cooling tower make up water tank, CI/GI pipe line any dia, control panel, ducting, iron frame structure etc. and serviceable items Compressor & Pump Motor transporting and depositing to AGE E/M Maintenance store yard all as specified & directed by Engr-in-charge including making good disturbed surfaces.
Dismantling and taking down existing 2.5 Ton EOT crane along with all accessories control panel, electric motor LT, electric motor CT, electric motor Hoist & gear box etc. and serviceable items electric motor LT, electric motor CT, electric motor Hoist transporting and depositing to AGE E/M Maintenance store yard all as specified & directed by Engr-in-charge including making good disturbed surfaces.
INTERNAL ELECTRIFICATION
Supply, installation, testing and commissioning of Pedestal panel wall mounted factory made, CPRI type tested, indoor cubical compartmental type of suitable size, conforming to IEC 61439-1 & 2 and IEC 61641, having double doors with locking arrangement, IP 43 protection made out of 2.0 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, cabelling, painting to all internal & external exposed steel surfaces with powder coating paint suitable for 3- Phase, 4 Wire system, 415 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length and size, including fixing lugs, bolts, screws, etc. complete all as specified and directed by engineer-in-charge. Make: L & T, Schneider, Siemens, ABB/ CPRI APPROVED Manufacturer
The Pedestal Panel shall comprise of the following: [A] BUSBAR CHAMBER [i] 01 Set (3L + N) of copper busbar of rated capacity 250 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection [B] INCOMING [i] 200 A, 415 V, Ics = 100% Icu = 50 kA, 50 Hz FP MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (Ready, Overload and pre-alarm & Overload), etc.- 01 Nos. [ii] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interrupts- 01 Nos. [iii] LED phase indicators (Red, Yellow, Blue)- 01 Set
[C] OUTGOING [i] 63 A, 415 V, Ics = 100% Icu = 50 kA, 50 Hz FP MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (Ready, Overload and pre-alarm & Overload), etc.- 02 Nos. [ii] 32 A, 10 kA, 415 V, 50 Hz TP MCB (c -curve)- 06 Nos [iii] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interrupts- 02 Nos.
Supply, installation, testing and commissioning of Pedestal panel wall mounted factory made, CPRI type tested, indoor cubical compartmental type of suitable size, conforming to IEC 61439-1 & 2 and IEC 61641, having double doors with locking arrangement, IP 43 protection made out of 2.0 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, cabelling, painting to all internal & external exposed steel surfaces with powder coating paint suitable for 3- Phase, 4 Wire system, 415 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length and size, including fixing lugs, bolts, screws, etc. complete all as specified and directed by engineer-in-charge. Make: L & T, Schneider, Siemens, ABB
The Pedestal Panel shall comprise of the following: [A] BUSBAR CHAMBER [i] 01 Set (3L + N) of copper busbar of rated capacity 250 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection [B] INCOMING [i] 200 A, 415 V, Ics = 100% Icu = 50 kA, 50 Hz FP MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (Ready, Overload and pre-alarm & Overload), etc.- 01 Nos. [ii] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interrupts- 01 Nos. [iii] LED phase indicators (Red, Yellow, Blue)- 01 Set
[C] OUTGOING [i] 63 A, 415 V, Ics = 100% Icu = 50 kA, 50 Hz FP MCCB, conforming to IEC 60947-2, having microprocessor based trip unit, adjustable overload setting (0.7 - 1 X In), adjustable short-circuit setting (5 - 10 X Ir), adjustable neutral protection (N, N/2, OFF), front indication LEDs (Ready, Overload and pre-alarm & Overload), etc.- 02 Nos. [ii] 32 A, 10 kA, 415 V, 50 Hz TP MCB (c -curve)- 02 Nos [iii] Automatic Star Delta starter for 63 Amps - 02 Nos [iv] Automatic Star Delta starter for 32 Amps - 02 Nos [v] Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interrupts- 04 Nos.
S & F of 4' batten light 34 watt suitable for surface / suspended mounting with steel housing, polycarbonate lens & optical cover, LED light having beam angle of light source 120˚, initial luminous flux 4000 lm, luminous efficacy not less than 100 lm/W, initial CCT 6500 K, initial CRI greater than 80, initial chromaticity <5, L70B50 50000 hr, IP 20 and IK 02 protection, surge protection level until 4 kV, power factor not less than 0.95 and built-in driver conforming to IS 15885 (Part 2/Sec 13): 2012 complete with electrical connection through 3 core PVC insulated copper conductor unarmoured cable of suitable size from ceiling rose to the light fitting as specified and directed by engineer-in-charge. Make: Philips BN308C LED40S-6500 L120 PSU WH or equivalent model of Havells, Wipro, Bajaj
S & F of 2' batten light 16 watt suitable for surface / suspended mounting with steel housing, polycarbonate lens & optical cover, LED light having beam angle of light source 120˚, initial luminous flux 2000 lm, luminous efficacy not less than 100 lm/W, initial CCT 6500 K, initial CRI greater than 80, initial chromaticity <5, L70B50 50000 hr, IP 20 and IK 02 protection, surge protection level until 4 kV, power factor not less than 0.95 and built-in driver conforming to IS 15885 (Part 2/Sec 13): 2012 complete with electrical connection through 3 core PVC insulated copper conductor unarmoured cable of suitable size from ceiling rose to the light fitting as specified and directed by engineer-in-charge. Make: Havells, Wipro, Bajaj, Philips or equivalent
S & F of square shape fully diffused recessed mounted 2' X 2' LED luminaire with, metallic CRCA housing & powder coated body, initial luminous flux 3600 lm, luminous efficacy not less than 110 lm/W, initial CCT 6500 K, initial CRI greater than 80, initial chromaticity <5, L70B50 50000 hr, IP 20 and IK 02 protection, power factor not less than 0.90 and built-in driver conforming to IS 15885 (Part 2/Sec 13): 2012 complete with electrical connection through 3 core PVC insulated copper conductor unarmoured cable of suitable size from ceiling rose to the light fitting as specified and directed by engineer-in-charge. Make: Philips RC380B LED 36S-6500 G4 L60 W60 PSU OD or equivalent model of Havells, Wipro, Bajaj
S & F 45 W LED street light having high efficiency long life LED module with SMD LED package mounted on MCPCB with high LED efficacy of ≥ 100 lumen/W, integral SMPS based constant current electronic LED driver with THD < 20%, surge voltage protection and other safety tests as per IS: 15885 (Part-2/Sec-13): 2012, IP 66 protection, high efficiency polycarbonate cover with integrated lens housed in pressure die-cast aluminium alloy heat sink for effective thermal management, sturdiness, excellent corrosion resistance, separate optical and control gear compartment & top opening for easy maintenance, suitable for side entry, pole mounting with bracket arm OD 35 mm to 42 mm including necessary electrical connection to the fixture with 3 core flexible Cu conductor cable of appropriate size and 1.5 m long bracket, having 40 mm diameter light grade GI pipe, including GI clamps, nuts, bolts & washers with two coats of synthetic enamel paint over a coat of red oxide primer complete in all respect as specified and directed by engineer-in-charge. Make: BAJAJ Cat-Part No. BAJAJ 169799 BRTFG 45W LED I or equivalent model of Havells, Philips or Wipro
S & F of Energy saving, environment friendly & robust highbay LED luminaire Saucer type with high efficacy suitable for ceiling Surface / Suspended 150 watt fitting complete Cat No.RADIOSOHB150WLED75760DBOPC of Make: Havells / BY415P LED145S CW WB FG PSU GR S2 of Make: Philips or equivalent as specified and directed by engineer-in-charge.
S & F BEE five star rated energy efficient high-speed ceiling fan having 1200 mm blade sweep, air-flow not less than 200 CMM, operating voltage 220-240 V and frequency 50 Hz, including a down rod of suitable size complete with electrical connection through 3 core PVC insulated copper conductor unarmoured cable of suitable size as specified and directed by engineer-in-charge. Make: Havells, Bajaj, Crompton, Usha
S & F energy efficient Non metallic exhaust fan (heavy duty) having blade sweep 300mm, air delivery not less than 850 CMH, suitable for 220-240 V, 50 Hz, 1-Ph AC supply, including electrical connection with 3 core flexible Cu conductor cable of appropriate size to the exhaust fan complete all as specified and directed by engineer-in-charge. Make: Crompton, Usha, Bajaj
S & F energy efficient metallic exhaust fan (heavy duty) having blade sweep 450mm, air delivery not less than 850 CMH, suitable for 220-240 V, 50 Hz, 1-Ph AC supply, including electrical connection with 3 core flexible Cu conductor cable of appropriate size to the exhaust fan complete all as specified and directed by engineer-in-charge. Make: Crompton, Usha, Bajaj
S & F Isolator for conforming to IS/IEC 60898-1-2002, having breaking capacity Icn = 10 kA, sliding bottom clamp, colour coded on/off indication on dolly, biconnect IP 20 protected lower terminals and sliding shutters, etc. complete as specified and directed by engineer-in-charge. Make: Legrand, Schneider, Siemens, ABB
63 Amp, 415 V, 50 Hz TPN
40 Amp, 415 V, 50 Hz SPN
S & F MCB for conforming to IS/IEC 60898-1-2002, having breaking capacity Icn = 10 kA, sliding bottom clamp, colour coded on/off indication on dolly, biconnect IP 20 protected lower terminals and sliding shutters, etc. complete as specified and directed by engineer-in-charge. Make: Legrand, Schneider, Siemens, ABB 6- 32 Amp, 230 V, 50 Hz SP MCB (c- curve)
INTERNAL WATER SUPPLY
S&F Angular stop cock 15 mm dia, quarter turn complete all as specified and directed by Engr-in-charge Make - Jaguar Model No CQT-23059 or equivalent in Crab Tree/Kohler brand.
S&F Chromium Plated flush valve/push cock for urinal 15mm DIA. Bore complete all as specified and directed by Engr-in-charge Make- Jaguar or equivalent PRS-073
S& F Overhead shower rose 80mm dia. Of ABS body chromium plated for fixing shower arm 15 mm size with bend of 45degree with flange complete all as specified and directed by Engr-in-charge
S&F two way bib cock 15 mm dia. complete all as specified and directed by Engr-in-charge Make - Jaguar Model No CQT-23041 or equivalent in Crab Tree/Kohler brand.
S&F Health faucet (ABS body) with 01 meter long PVC tube & wall hook complete all as specified and directed by Engr-in-charge Make - Jaguar Model No ALD-CHR- 583 or equivalent in Crab Tree/Kohler brand.
S&F Sink cock with swinging casted round shape spout (Wall mounted model) 20 mm dia, quarter turn complete all as specified and directed by Engr-in-charge
ELECTRIC OPERATED DOOR
(a) Over all dimension of door: (6000mm x 6000mm) + 5% (b) Wicket door of size: 1 m x 2.1 m (c) vision panel size: 240mm x 340mm (d) Shutter (door) material: Double Skin PUF insulated Galvanised Steel heavy duty strength at both side (inner & outer) Not less than 2.0mm thick with aluminium zinc alloy coating on both outer surface as corrosion resistance. (e ) Drive system (Electrical): Designed for a direct drive installation to the Shutter shaft. A worm gear with hollow shaft. An integrated safety brake. Integrated limit switch max turns 10. Motor overload safety factor. An electric motor: Capacity - 1.5 KW 3 Phase Power supply - 415 V, 50 Hz Duty rating (ED) S3-50% Torque - 650 Nm Output speed - 11 min Temperature -5°C/40°C Noise (dB) <70 Protection rate (IP) 54
(f) Emergency manual operation: The manual override devices (hand crank or hand chain override) when power cuts-off. (g) Digital Control Units: Integrated buttons in the front cover for UP, STOP and DOWN control. Display and keyboard for the programming of limit switches and managing of the functions. Note: (i) Contractor shall submit the detail drg, containing the frame, structure of door, shutter arrangement, mounting/erecting system, electrical operating system, layout of control cable and devices, complete technical specifications as per site requirement for approval of Accepting Officer before placing the order. (ii) The contractor shall intimate in writing for pre-dispatch inspection in the factory premises. The pre-dispatch inspecting shall be carried out in virgin condition of shutters.
CONDUIT FOR LAN/ TELEPHONE SOCKET
Supply and fixing Tele/Intercom socket /computer socket 1 modules type (LAN) outlet RJ 11 with shutter flush type ISI marked complete all as specified and directed by Engr-in-charge
S & F Metal flush mounting box 1 module complete all as specified and directed by Engr-in-charge
Supply& Fix mirror finish cover plate 1 Module complete all as specified and directed by Engr-in-charge
Supply and fixing Telephone Junction Box Size : 9.5 X 7.5 X 3.5 inches for 50 pair Telephone cable / LAN Cable etc. complete all as specified and directed by Engr-in-charge
AIR CONDITIONING
WATER-COOLED SCREW TYPE CHILLER UNIT (2W + 1S) Supply, installation, testing and commissioning of factory designed, pre-fabricated and floor-mounted AHRI certified screw type water-cooled chiller machine of nominal capacity 100 TR, complete with semi-hermetic screw compressors having single refrigerant circuits and automatic stepless capacity control, water-cooled S/T type condenser, S/T horizontal flooded type evaporator with carbon steel shell and seamless copper tubes with elastomeric insulation, suitable numbers of squirrel cage induction motors of appropriate rating with class 'B' insulation, unit mounted variable frequency drive (VFD) along with necessary drive arrangement, lubrication system as per manufacturer's design required for smooth and trouble-free operation of the chiller package, common base-frame, interconnected copper refrigerant piping along with elastomeric insulation, fittings, valves, expansion valves and accessories to interconnect compressor, condenser, chiller and expansion valve, microprocessor based control panel comprising of controls including sensors and equipped with a keyboard, LCD touchscreen access input system, protection and monitoring devices to perform control functions, wiring, vibration isolators, gauge panel, automatic safety controls, flow switch at evaporator and condenser connection ends and ozone friendly, CFC-HCFC free refrigerant complete all as specified and directed by the engineer-in-charge. Make: Voltas Model No. ACEGWFVXR1001MFHP2 or equivalent in Trane, York, Carrier or Bluestar
CHILLED WATER CIRCULATION PUMP (2W + 1S) Supply, installation, testing and commissioning of Monoblock, self-priming, single-stage centrifugal pump, capable of 17 LPS discharge at 20 MWC head, having cast iron casing, enclosed type dynamically balanced cast iron impeller, carbon steel pump shaft, gland packed sealing, deep groove ball bearings, etc. with TEFC squirrel cage induction motor having class 'B' insulation, IE3 efficiency, conforming to IS 12615: 2018 and suitable for operation on 3-Ph, 415 V±10%, 50 Hz AC supply, base plate, mounting channel frame, accessories and fittings, viz. pressure gauges, thermometers, drains, coupling, coupling guard, vibration isolation arrangement by means of spring / rubber type mounting duly insulated with FM approved highly- flexible, closed-cell thermal insulation of elastomeric foam based on synthetic rubber (NBR) of appropriate thickness laminated with 12 micron aluminium foil facing with reinforced glass scrim along with adhesives and other necessary accessories complete all as specified and directed by the engineer-in-charge. Make: Kirloskar KDI 830++ or Crompton, Mahindra NOTE: Necessary civil work viz. foundation for placement of pump and accessories shall be covered in the scope of work.
CONDENSER WATER PUMP (2W + 1S) Supply, installation, testing and commissioning of Monoblock, self-priming, single-stage centrifugal pump, capable of 25 LPS discharge at 14 MWC head, having cast iron casing, enclosed type dynamically balanced cast iron impeller, carbon steel pump shaft, gland packed sealing, deep groove ball bearings, etc. with TEFC squirrel cage induction motor having class 'B' insulation, IE3 efficiency, conforming to IS 12615: 2018 and suitable for operation on 3-Ph, 415 V±10%, 50 Hz AC supply, base plate, mounting channel frame, accessories and fittings, viz. pressure gauges, thermometers, drains, coupling, coupling guard, vibration isolation arrangement by means of spring / rubber type mounting complete all as specified and directed by the engineer-in-charge. Make: Kirloskar (KDI- 1030+) or Crompton, Mahindra NOTE: Necessary civil work viz. foundation for placement of pump and accessories shall be covered in the scope of work.
STAINLESS STEEL EXPANSION TANK S & F SS- 304 200 litre (for chilled water circuit) closed expansion tank with pressure rating to suit the system pressure and sized adequately to compensate for water expansion due to operating temperature variations, conforming to IS: 2825- 1969 for 'non-fired pressure vessels' complete with inter-connection piping, non-return valve, safety relief valve and pressure gauge, insulated with 50 mm thick elastomeric insulation and cladded with 26 gauge aluminium complete with accessories as specified and directed by the engineer-in-charge. Make: RAPID COOL, ANERGY, AEROSPIN
HDPE MAKE-UP WATER TANK S & F multi-layered HDPE make-up water tank of 45000 litre (3 X 15000) capacity made up of 100% virgin material, having 100% UV stabilized white outer layer, threaded lid, extra insert lid for protection against algae formation complete with inter-connection piping and non-return valve etc. complete all as specified INCLUDING Necessary PCC block staging ABOVE bottom of COOLING TOWER and directed by the engineer-in-charge. Make: SINTEX, POLYCON, ROTEX and KAVERI
M & L for 1.1 kV grade copper conductor, XLPE insulated armoured cable conforming to IS 7098 (Part 1): 1988, having stranded copper compact shaped conductors as per Cl. 2 of IS 8130: 1984, PVC inner sheath, single armouring of galvanised steel strip/wire and PVC Type ST-2 outer sheath conforming to IS 5831: 1984, including necessary clamping / dressing with cable ties and termination complete all as specified and directed by engineer-in-charge. Make: RR Kabel, Polycab, Havells
3.5 core, 50 mm² [for chillers]
3 core, 6 mm² [for cooling tower]
3 core, 4 mm² [for pump starter to motor terminals]
HVAC PANEL Supply, installation, commissioning and testing of factory made, CPRI type tested, indoor, cubical compartmental type "HVAC Panel" of suitable size, conforming to IEC 61439-1 &2, IEC 61641, having both sides openable with hinged double doors & locking arrangement and IP 42 protection made out of 2.0 mm thick mild steel CRCA sheet, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labelling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled (white) with letters figures and conventional skull and bones in signal red colour, suitable for 3- Phase 4 Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length & size, including fixing lugs, bolts, screws etc. complete with accessories as specified and directed by the engineer-in-charge. Make: Schneider, ABB, Siemens,L & T, Legrand Note: CPRI Approved panel manufacturer only certified by OEM channel partner
CONDENSER WATER PIPING: MS ERW CLASS- C PIPE Supply, laying / fixing, testing and commissioning of condenser water piping including necessary fittings viz. bends, tees, reducers, flanges, air purge valves, drain valves, structural support, necessary clamps, vibration isolators, etc. including painting and supporting / fixing the pipe in excavated trenches or on floor / wall / ceiling with clamps, hangers, angles, channels (using anchor fasteners) with necessary accessories complete all as specified and directed by the engineer-in-charge. Make: Tata, Jindal, Surya NOTES: [i] The pipe size 150 mm NB & below shall be MS 'C' class as per IS 1239 (Part- 1): 2004 & IS 1239 (Part- 2): 2011. [ii] The pipe size above 150 mm NB shall be welded black steel pipe heavy class as per IS 3589: 2001. [iii] Minimum thickness of MS sheet for pipe size above 150 mm NB and up to 350 mm NB shall be 6.35 mm and it shall be 7 mm for pipe size 400 mm NB and above.
Y- STRAINER Supply, installation, testing and commissioning of 150 mm NB cast steel bolted cover Y-type strainer with CCS body conforming to ASTM A- 216 Gr. WCB, AISI 304 screen with 1.2 mm diameter perforation, 40 kg/cm2 body test pressure & 20 kg/cm2 maximum working pressure and standard flange end conforming to BS 10 Table F / Class-150 with necessary accessories complete all as specified and directed by the engineer-in-charge. Make: Advance, Sant, Hindustan, Rapid Cool, Castle, Emerald
BUTTERFLY VALVE Supply, installation, testing and commissioning of 40 mm NB wafer type PN 1.6 rated short pattern CI butterfly valve having Gr. FG-200 CI body conforming to IS 210: 2009, seat having EPDM rubber lining, CF 8 stainless steel disc, AISI- 410 stainless steel stem, 2.4 MPa body test pressure & 1.6 MPa seat test pressure and standard flange end conforming to BS 10 Table D/E & ANSI B 16.1 CI- 125 with necessary accessories complete all as specified and directed by the engineer-in-charge. Make: Advance, Sant, Hindustan, L&T, Leader, Castle
NON-RETURN VALVE Supply, installation, testing and commissioning of 150 mm NB wafer type PN 1.6 rated swing check type multidoor reflux valve (NRV), designed & tested as per IS 5312 (Part- 2): 1986, suitable to handle clear water having turbidity up to 5000 PPM, having CI body, door and diaphragm, leaded tin bronze seat rings and flange drilling standard end connection, etc. with other necessary accessories complete all as specified and directed by the engineer-in-charge. Make: Advance, Sant, Hindustan, Audco, Leader, Castle
MANUAL BALANCING VALVE Supply, installation, testing and commissioning of 150 mm NB precise balancing, double regulation type cast iron balancing valve having FG 200 cast iron body conforming to IS 210: 2009, copper alloy trim, stainless steel 2 Cr. 13 stem, 2.4 MPa body test pressure & 1.6 MPa maximum working pressure and standard flange ends with necessary accessories complete all as specified and directed by the engineer-in-charge. Make: Advance, Sant, Hindustan, Castle
CHILLED WATER PIPING Supply, laying / fixing, testing and commissioning of chilled water circulation piping including necessary fittings viz. bends, tees, reducers, flanges, air purge valves, drain valves, structural support, necessary clamps, vibration isolators, etc. including painting and supporting / fixing the pipe in excavated trenches or on floor / wall / ceiling with clamps, hangers, angles, channels (using anchor fasteners) with necessary accessories duly insulated with FM approved highly- flexible, closed-cell thermal insulation of elastomeric foam based on synthetic rubber (NBR) of 19mm thick laminated with 12 micron aluminium foil facing with reinforced glass scrim along with adhesives and other necessary accessories complete all as specified and directed by engineer-in-charge. Make: Tata, Jindal, Surya for pipes & Armacell, K-Flex, Aeroflex for insulation NOTES: [i] The pipe size 150 mm NB & below shall be MS 'C' class as per IS 1239 (Part- 1): 2004 & IS 1239 (Part- 2): 2011. [ii] The pipe size above 150 mm NB shall be welded black steel pipe heavy class as per IS 3589: 2001. [iii] Minimum thickness of MS sheet for pipe size above 150 mm NB and up to 350 mm NB shall be 6.35 mm and it shall be 7 mm for pipe size 400 mm NB and above.
Y- STRAINER Supply, installation, testing and commissioning of cast steel bolted cover Y-type strainer with CCS body conforming to ASTM A- 216 Gr. WCB, AISI 304 screen with 1.2 mm diameter perforation, 40 kg/cm2 body test pressure & 20 kg/cm2 maximum working pressure and standard flange end conforming to BS 10 Table F / Class-150 duly insulated with FM approved highly- flexible, closed-cell thermal insulation of elastomeric foam based on synthetic rubber (NBR) of appropriate thickness laminated with 12 micron aluminium foil facing with reinforced glass scrim along with adhesives and other necessary accessories complete all as specified and directed by the engineer-in-charge. Make: Advance, Sant, Hindustan, Rapid Cool, Castle, Emerald for strainer & Armacell, K-Flex, Aeroflex for insulation
BUTTERFLY VALVE Supply, installation, testing and commissioning of wafer type PN 1.6 rated short pattern CI butterfly valve having Gr. FG-200 CI body conforming to IS 210: 2009, seat having EPDM rubber lining, CF 8 stainless steel disc, AISI- 410 stainless steel stem, 2.4 MPa body test pressure & 1.6 MPa seat test pressure and standard flange end conforming to BS 10 Table D/E & ANSI B 16.1 CI- 125 duly insulated with FM approved highly- flexible, closed-cell thermal insulation of elastomeric foam based on synthetic rubber (NBR) of appropriate thickness laminated with 12 micron aluminium foil facing with reinforced glass scrim along with adhesives and other necessary accessories complete all as specified and directed by the engineer-in-charge. Make: Advance, Sant, Hindustan, L&T, Leader, Castle for Butterfly valve & Armacell, K-Flex, Aeroflex for insulation
NON-RETURN VALVE Supply, installation, testing and commissioning of 100 mm NB wafer type PN 1.6 rated swing check type multidoor reflux valve (NRV), designed & tested as per IS 5312 (Part- 2): 1986, suitable to handle clear water having turbidity up to 5000 PPM, having CI body, door and diaphragm, leaded tin bronze seat rings and flange drilling standard end connection, etc. duly insulated with FM approved highly- flexible, closed-cell thermal insulation of elastomeric foam based on synthetic rubber (NBR) of appropriate thickness laminated with 12 micron aluminium foil facing with reinforced glass scrim along with adhesives and other necessary accessories complete all as specified and directed by engineer-in-charge. Make: Advance, Sant, Hindustan, Audco, Leader, Castle for Reflux valve (NRV) & Armacell, K-Flex, Aeroflex for insulation
3-WAY TEMPERATURE CONTROL VALVE Supply, installation, testing and commissioning of 125 mm NB electronic, self-balancing, pressure independent type dynamic balancing valve rated for minimum 25 bar working pressure with integrated 3-way modulating control valves in a single body and actuator capable of accepting up to 10 V DC and up to 20 mA electric signal and provide similar transduced feedback output to control system duly insulated with FM approved highly- flexible, closed-cell thermal insulation of elastomeric foam based on synthetic rubber (NBR) of appropriate thickness laminated with 12 micron aluminium foil facing with reinforced glass scrim along with adhesives and other necessary accessories complete all as specified and directed by the engineer-in-charge. Make: Honeywell, Danfoss, Advance, Rapid Control, Anergy for 3-Way Modulating Control valve & Armacell, K-Flex, Aeroflex for insulation NOTES:[i] Maximum close off pressure shall not be less than 6 bar for up to 50 mm valves. [ii] Maximum close off pressure shall not be less than 7 bar for 65 mm & above.
MANUAL BALANCING VALVE Supply, installation, testing and commissioning of precise balancing, double regulation type cast iron balancing valve having FG 200 cast iron body conforming to IS 210: 2009, copper alloy trim, stainless steel 2 Cr. 13 stem, 2.4 MPa body test pressure & 1.6 MPa maximum working pressure and standard flange ends duly insulated with FM approved highly- flexible, closed-cell thermal insulation of elastomeric foam based on synthetic rubber (NBR) of appropriate thickness laminated with 12 micron aluminium foil facing with reinforced glass scrim along with adhesives and other necessary accessories complete all as specified and directed by engineer-in-charge. Make: Advance, Sant, Hindustan, Castle for Balancing valve & Armacell, K-Flex, Aeroflex for insulation
BALL VALVE S & F of 20 mm NB SS 304 ball valve, having two piece design, SS 304 body & ball, PTFE seal/packing/gasket and screwed/socket weld end connection, etc. with accessories, etc. duly insulated with FM approved highly- flexible, closed-cell thermal insulation of elastomeric foam based on synthetic rubber (NBR) of appropriate thickness laminated with 12 micron aluminium foil facing with reinforced glass scrim along with adhesives and other necessary accessories complete all as specified and directed by engineer-in-charge. Make: Advance, Sant, Hindustan, Castle for Ball valve & Armacell, K-Flex, Aeroflex for insulation
DRAIN & INSTRUMENTATION PIPING-MS ERW CLASS- C PIPE-Supply, laying / fixing, testing and commissioning of MS ERW Class- C drain piping including necessary fittings viz. bends, tees, reducers, flanges, air purge valves, drain valves, structural support, necessary clamps, vibration isolators, etc. including painting and supporting / fixing the pipe in excavated trenches or on floor / wall / ceiling with clamps, hangers, angles, channels (using anchor fasteners) with necessary accessories complete all as specified and directed by the engineer-in-charge. Make: Tata, Jindal, Surya
BALL VALVE- S & F of SS 304 ball valve, having two piece design, SS 304 body & ball, PTFE seal/packing/gasket and screwed/socket weld end connection, etc. with accessories complete all as specified and directed by the engineer-in-charge. Make: Advance, Sant, Hindustan, Castle
AUTO AIR-VENT- Supply, installation, testing and commissioning of automatic air-vent valve with 20 mm end connections, brass OT 58 body and cover, polyacetal lever, high density expanded polyethylene float, EPDM rubber plug, stainless steel spring, polyamide cap etc. suitable for maximum operating pressure of 16 bar and maximum operating temperature 115 °C respectively, installed on all high points in the water piping system to automatically remove the trapped air complete all as specified and directed by the engineer-in-charge. Make: Advance, Sant, Hindustan, Castle, Anergy
TEMPERATURE GAUGE- S & F of 6" dual scale (°F/°C), lower mount (radial), bimetal thermometer having 0.5 NPT process connection, Grade A accuracy class as per ASME B40.200, stem diameter 6.35 mm, laminated safety glass window, stainless steel 304 case, steam, process connection & joint, aluminium dial & pointer, IP67 protection, scale range 0- 60 °C complete with accessories, etc. as specified and directed by the engineer-in-charge. Make: General, WIKA, TSI, H-Guru, FIEBIG
PRESSURE GAUGE- S & F of 4" bourdon tube pressure gauge conforming to EN 837-1, having copper alloy process connection & pressure element, plastic black pointer & case, plastic crystal-clear window, snap-fitted in case, accuracy class 2.5, scale range 0- 25 bar complete with accessories, etc. as specified and directed by the engineer-in-charge. Make: General, WIKA, TSI
Supply, installation, testing & commissioning of flameproof, foot-mounted (B3 construction), 3-Ph squirrel cage induction motor suitable for 415 V ± 10%, 50 Hz ± 5 % AC supply (combined variation ±10%), insulation class F, (for Blower of AHU) of 15 kW capacity, 35000 CFM with temperature rise limited to class B, degree of protection IP 55, duty 51, ambient temperature 45 ºC, conforming to IS 12615: 2011, IS/IEC 60079-1: 2007, IS 3682: 1966 gas group II A, II B complete all as specified and directed by the engineer-in-charge. Make: ABB, CG, Bharat Bijli
FIRE DAMPER- Supply, installation, testing and commissioning of 16 gauge GI fire damper, at least of 120 minutes fire-rating, spring activated on melting of fusible link having melting point 67.13° C complete with smoke detector / thermistor, fusible link etc. and actuator as required for operation, located in the SA / RA ducts, at all fire rated crossovers (shafts, walls, etc.). along with control panel (located in such a way that the reset can easily be done), interlocked with the building management system for the fire detection or HVAC to trip / close in the event of fire/smoke in the respective zone and tested as per ULL- 555 and certified by CBRI complete all as specified and directed by engineer-in-charge. Make: Ruskin Titus, Trox, Rola Star, Zeco, Airflow, Carrier, Airpro The fire dampers shall meet the following criteria: [a] Bare fire dampers with 400 mm sleeve [b] Control panel actuator, including electrical spring type actuator, remote indication of the fire damper position. [c] Interconnection wire for the fire detection & alarm system with the AHU and the smoke dampers [d] Sealing any openings around the sleeve of the fire dampers with approved fire sealant as per the specification & recommendations of the manufacturer.
Motorized, spring return type, combination fire and smoke damper
Control panel actuator, including electrical spring type actuator, remote indication of the fire damper position.
GALVANIZED STEEL SHEET (GSS) DUCTING-Supply, installation, balancing and commissioning of factory fabricated galvanized steel sheet metal (G.S.S.) round / rectangular ducting of following sheet thickness having zinc coating of 120 g/m² total on both sides and complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, volume control dampers, hangers, supports, etc. as per approved drawings and conforming to the latest edition of IS 655: 2006 & HVAC Duct Construction Standards - Metal and Flexible of SMACNA along with required scaffolding work to install the ducts at site complete all as specified and directed by engineer-in-charge. Make: Ruskin Titus, Trox, Rola Star, JSW, TATA NOTE: Each branch / terminal duct shall be fitted with volume control dampers for air balancing purpose. The rates thereof shall be deemed included.
22 G (MS angle flanges)
20 G (MS angle flanges)
18 G (MS angle flanges)
AIR TERMINALS S & F of supply / return / exhaust air diffusers / grilles / louvers of powder coated aluminium with aluminium volume control dampers with anti smudge ring & removable core complete all as specified and directed by the engineer-in-charge. Make: Ruskin Titus, Zeco, Rola Star, Airflow, Carrier, Airpro
AIR TERMINALS S & F of drum lovers, constructed with high quality extruded aluminium profiles, having drums of aluminium sheet and specially shaped aluminium profiles, blades of high quality extruded aluminium adjustable directional blades and opposed blade damper made with aluminium profiles of size 381 mm X 1584 mm, capable of delivering 2157 CFM @ 400 fpm neck velocity and 10 m throw @ 150 fpm terminal velocity complete all as specified and directed by the engineer-in-charge. Make: Ruskin Titus, Zeco, Rola Star, Airflow, Carrier, Airpro
THERMAL INSULATION- S & F of black flexible closed-cell elastomeric thermal insulation made of elastomeric foam based on synthetic rubber (NBR / PVC) with self pre-covered self-adhering, UV treated glass cloth of thickness 7 mm / 200 GSM, tested for maximum service temperature 100 ºC as per ASTM C411 & minimum service temperature -50 ºC as per ASTM C534, thermal conductivity λ ≤ 0.037 W/mK at mean temperature θm = 24 ºC as per ASTM C518 / C177, ASTM C335, water absorption by volume ≤ 0.2% as per ASTM C1763, fire spread index (FSI) & smoke development index (SDI) 25/50 as per ASTM E84, flammability HB, V-0 as per UL 94, fungi resistance as per ASTM G21, mould growth resistance as per ASTM E2180-18 / UL 181 and ozone resistance as per ASTM D 1149-18 along with adhesives and other necessary accessories complete all as specified and directed by the engineer-in-charge Make: Armacell, K-Flex, Aeroflex.
13 mm thick thermal insulation
19 mm thick thermal insulation
S & F of FM approved fibre-free, super-silent, microbe resistant, easy to apply 10 mm thick acoustic duct lining insulation of open cell elastomeric foam based on synthetic rubber tested for acoustic performance as per EN ISO 354, EN ISO 11654: 1997 & ASTM C 423, service temperature range -20- 85 ˚C as per EN 14706 & EN 14304, thermal conductivity λ ≤ 0.047 W/mK at mean temperature θm = 20 ˚C as per EN 12667, Class 1 surface spread of flame as per BS 476 7: 1997, flammability HB, V-0 as per UL- 94, anti-microbial behaviour (no fungal growth visible with the naked eye & no bacterial growth) as per EN ISO 846, air erosion resistance (no erosion, cracking or delamination at air velocity of 10000 FPM) as per ASTM C 1071- 05, density 140- 180 kg/m3 along with adhesives and other necessary accessories complete all as specified and directed by engineer-in-charge. Make: Armacell, K-Flex, Aeroflex
S & F of FM approved 25 mm thick dust and fibre free high performance mass loaded vinyl sound barrier mat of thermoplastic polymer compound free of lead, unrefined aromatic oils and bitumen for noise control and tested for acoustic performance as per ISO 10140-2, service temperature range -20- 65 ˚C, other fire class FMVSS 302 fire performance, having density 2400 to 2750 kg/m3 and tested as per ISO 845 & ASTM D1622, elongation MD/CD > 25% and tested as per ISO 37 along with adhesives and other necessary accessories complete all as specified and directed by engineer-in-charge. Make: Aracell, K-Flex, Aeroflex
M & L for low smoke zero halogen (LS0H) fire survival control cable of size 2 core, 2.5 mm² (for instrumentation)with circuit integrity, conforming to BS 7846 and rated for 600 V, having plain annealed stranded copper conductor with fire-resistant mica tapes covered by an extruded layer of cross-linked polyethylene, extruded layer of thermoplastic low smoke zero halogen (LS0H) compound, single layer of galvanized steel wires and thermoplastic LS0H compound sheath, suitable for operating temperature range -40 ˚C to +90 ˚C and minimum bending radius being 12 times the overall cable diameter, including laying, clamping, termination and ferruling complete all as specified and directed by engineer-in-charge. Make: Havells, Polycab, Finolex, RR Kabel
S & F of Indoor type wall mounted digital temperature cum %RH meter (Digital Thermo Hygrometer) complete with large LCD, English display having operating with 12/24H Max/Min temperature and humidity memory function range -50°C to 70°C Temperature accuracy 0.5 ºC and Humidity range 10% to 99% RH Humidity accuracy 5% RH Humidity resolution 1% RH Power source 1*AAA (1.5V) battery for AC Plant Room complete as specified and directed by engineer-in-charge. Make: Honeywell, HTC/Thermo-electric or equivalent
Water Softening Plant M&L for Water Softening Plant (FRP body) of Feed Flow Rate 1.2 Cubic Meter/Hour to remove the imparting impurities from water, hardness of water is effectively reduced by exchanging the Sodium ions. Automatic & manual operations including auto multiport valve, manual multiport valve and butterfly valve complete all as specified and directed. Make: Thermax / Ion Exchange
FIRE FIGHTING AND FIRE DETECTION CUM ALARM SYSTEM
Supply and fix Response indicator unit complete all as specified and directed by Engr-in-charge
Supply, installation, testing & commissioning of Repeater Panel with minimum 640 character LCD display with control keypad complete all as specified and directed by Engr-in-charge Approved Makes: Notifier/XLS-3000/IFC-JC/Fire Finder
S & F ,2 core x 1.5 Sqmm, Multistrand Copper, FRLS unarmoured cable, RED in Colour, laid in concealed conduit complete all as specified and directed by Engr-in-charge
M & L Terrace water Tank 5000 Ltr capacity complete all as specified and directed by Engr-in-charge
S & F branch pipe, conforming to IS 903: 1993, having 63 mm NB instantaneous gunmetal inlet, made threaded outlet, 15 mm NB long nozzle, suitable for inter connection to hose pipe coupling complete all as specified and directed by Engr-in-charge
Supplying and installing /Fixing of ISI mark fire extinguisher mechanical foam (AFFF) type of capacity 9 Ltrs manufactured out of CRCA plates of IS:513 grade conforming to IS :10204 and approved by TAC ,body coated with lead and tin alloy, having anti-corrosive treatment internally and externally by electrolytic deposition process, body tested at 25 Kg F/Cm,fire red epoxy polyester powder coated comprising of AFFF in concentration of 6% and CO2 gas cartridge jet range up to 6 mtr ,suitable for 'B' class fire ( Such as petrol, oils, fats, paints, organic solvents etc).Complete in all respect and as per IS :2190 and all as specified and directed by Engr-in-charge MAKE:-Cease fire/Fire age/New Tech
Supply ,installing , of ISI marked ABC stored pressure type fire extinguisher, capacity 4.5 Kg , portable type consisting of mild steel body as per IS :513, mild steel neck ring as per IS: 2052, brass valve, body test pressure upto 30 Kg F/Cm2 ,anti-corrosive treatment by epoxy polyester coating of 50 micron, jet length 2 mtr , jet range minimum 6 mtr minimum discharge 85 Ltrs/Minutes expelling agent dry nitrogen conforming to IS:13849 suitable for B and E class fire complete in all respect and all as specified and directed by Engr-in-charge Make:- Hindustan Fire protection/Cease fire/New tech.
Installing , of ISI marked Carbon dioxide type (CO2) fire extinguisher, capacity 4.5 Kg , portable type consisting of mild steel body as per IS :513, mild steel neck ring as per IS: 2052,body test pressure upto 250 Kg /Cm2 ,anti-corrosive treatment by epoxy polyester coating of 50 micron, jet range minimum 2.5 to 3 mtr , working pressure 60-65 kg / cm2 conforming to IS:2078 suitable for B and C class fire complete in all respect and all as specified and directed by Engr-in-charge Make:- Hindustan Fire protection/Cease fire/New tech.
UV&TRIPLE IR FLAME (RADIANT ENERGY ) DETECTOR -Detector detects multi spectral sensitivity of fire by using UV&IR sensors , clear line of sight visual range upto specific distance ) triple spectrum Design for long distance detection &excellent false alarm sensitivity to ensure no zone cross over detection high sensitivity combined with fast response time to ensure rapid and fast & accurate flame detection multiple output option for max flexibility and compatibility -(A)(3) relays for FLAME DETECTION Auxiliary and FAULT(b) 0-20ma stepped or 0-10v stepped (c )optical heart protocol for configuration setting (d) RS485 heat detector extension (optional) connectivity via LOT (optional) test lamp compatibility for safe test NOTE-item description includes complete installation test and commissioning wiring connection with the main panel or any items not mentioned but essentially required for the successful installing and commissioning of IR/UV detector is deemed to be included in the rate quoted
DG SET
Supply, installation, testing and commissioning of silent DG Set, conforming to IS: 10002- 1981, complete with Diesel Engine of suitable BHP & AC Brushless SPDP alternator, conforming to IS: 13364- 1992, mounted on a common base frame & coupled through a flexible coupling or close coupled complete with platform, AMF Panel, control panel having meters, sound-proof canopy, etc. of not less than 625 kVA/500KWe capacity conforming to the following specifications complete all as specified and directed. all as per CUMMINS model no. C625DSP or equivalent in Kirloskar / Greaves power / Caterpillar
[a] Engine: 6 cylinder, in-line, 4 stroke, radiator cooled engine, well designed air handling system with dry type, heavy duty, replaceable paper element air cleaner with restriction indicator, air to air aftercooling, optimised turbocharger for increased altitude, Inline fuel pump with class H electronic governing, spin on fuel filter, standard integral set-mounted radiator system, designed and tested for 50°C ambient temperature, full flow spin on lube oil filter, electrical starter motor with soft start engagement feature, battery charging alternator with 1 x 24 or 2 X 12 V DC dry type battery. [b] Alternator: Brushless type, screen protected, revolving field, self-excited alternator, conforming to IS/IEC 60034-1 3-phase reconnectable winding with 12 terminals brought out for connection, dedicated winding specially designed for single operation, impregnation on all wound components for better mechanical strength. [c] Control Panel: Manufactured with 2mm thick CRCA sheet and powder coated for weather-proof and long lasting finish. The control panel consists of the following parts: [i] Controller: Aluminium bus bars with suitable capacity with incoming/outgoing terminals [ii] Indicating lamps for ‘Load ON’ and ‘Set Running’ [iii] Instrument fuses duly wired and ferruled [iv] MCCB of suitable rating with overload and short circuit protections
[d] Microprocessor based generator set monitoring and control system including an intuitive operator interface that allows for complete generator set control as well as system metering, fault annunciation, configuration and diagnostics, LED backlit LCD display with tactile feel soft-switches & generator set status LED lamps, remote START-STOP [e] Digital Engine Metering: Oil pressure, engine temperature, starting battery voltage, engine running hours [f] AC Alternator Metering: L-L voltage and L-N voltage, current (phase and total), kVA (phase and total) and frequency [g] Engine Protection: Low lube oil pressure, high/low coolant temperature, battery over/under/weak volts, fail to crank/start, sensor failure, cranking lockout, low fuel level [h] AC Alternator Protection: Over/under voltage, over/under frequency, loss of AC sensing. [j] Data Logging: Engine hours, control hours and upto 5 recent fault codes [k] Configurable glow plug control [l] 24 V DC operation [m] Silencer: Critical grade silencer suitably optimized to meet stringent noise emission standards laid down by MoEF / CPCB-II Latest Norms [n] Mounting Arrangement: Engine and alternator are mounted on a common MS fabricated base frame with AVM pads. [o] Base frame with integral fuel tank is provided with drain plug, air vent, inlet and outlet connection, level indicator and provision for cleaning
CRANE
Design ,supply, install, testing and commissioning of indoor type NON FLAME PROOF EOT (electrically operated travelling) double girder over head crane of 10 Ton capacity, class II, M5 as per IS:3177 of 1999 and IS :807 of 2006 and other relevant Indian standards of latest versions having straight travel path, operating on 415 volts, 3phase, 50Hz, AC and with control voltage not exceeding 110 volts, AC through low voltage transformer with independent movable pendent supported by chain having lift of hook 8 mtr above floor level, span not exceeding 25m and rails (long travel length as per drawings 56.6m), double girder type main gantry girder, floor operated movable pendent control by means of push buttons independent of crab trolly position with Non flame proof protective panel with down shop lead, Non flame proof trailing cable complete with all accessorised/equipment duly epoxy painted complete all as stipulated in Annexure-'A' here in after as per OEM specifications, as shown on drawings and as directed. The make of crane shall be as approved by the Accepting Officer. The span mentioned is tentative exact span shall be measured at site before fabrication.
Non Flame proof EOT crane shall be provided with the following specifications and capable for electrically controlled movements: (i) Capacity of Crane : 10 Ton double box girder (ii) Clear span : 25 m approx. (iii) Bay length : 56.6m approx. (iv) Hook height : 8m approx. (v) Hoisting speed : Less than 3.00 / 0.60 mpm (vi)LT / CT speed : Less than 3.00 / 0.60 mpm (vii)Clearance from outer wall: 250 / 300mm (viii) Control; Pendent control, Non flame proof
NOTES:- (a) Unit rate quoted shall be deemed to include provision of electrical wiring of suitable size in rigid metallic conduits fixed on surfaces from main switch upto electrical control panels and provision of ISMC channel welded along with ISMB (gantry girder) and longitudinal travelling rail welded alongwith ISMC. (b) Clear span and bay length specified and shown on building are only indicative. The tenderer shall visit the site and as certain exact span and bay length before designing / execution. (c) Long travel girder rail is in the scope of building work. (d) Dimensions, capacities/sizes of equipment/ accessories mentioned on drawing are minimum to be provided. Prior approval of Accepting Officer shall be obtained for the detailed construction drg and Non flame proof electrical wiring diagram of EOT crane and contractor shall incorporate components wherever required and the rates quoted above shall deemed to inclusive of such provisions and its accessories before designing / execution. (e) Longitudinal / cross travel shall be limited to 250 / 300mm away from the wall on both ends. (f) The lowest bidder shall prepare Constructional drawing including specification as per the design and submit for Approval of Accepting Officer duly vetted by the nodal agencies such as NIT / IIT before acceptance of the tender. (g) Any technical clarifications regarding size, capacity, rating and specification and drawings may please be clarified by the bidder from the E-4 section of this office before the Bid is submitted, he should also visit the site where the crane are being installed before submitting the Bid.
Design, ,manufacturing, supply, erection, testing and commissioning of indoor type heavy duty hand operated traveling (HOT) overhead crane, capable of handling 10 metric tonnes (MT) main hoist with centre to centre clear span not exceeding 25 metres, single box girder type main gantry girder with necessary steel supporting structure and crab with clear hook height of 8 metres from the floor of corridor all as specified complete with all accessories/equipment and painted all as per OEM specification as approved by Engr-in-charge. HOT crane shall be provided with the following specifications and capable for Hand operating movements: (i) Longitudinal travel shall be limited to 250 / 300 mm away from the walls on both ends. (ii) HOT crane shall be provided with the following movements:- (iii) Capacity of crane : 10.0 Ton single girder (iv) Clear Span : 25 Mtr approx. (v) Bay length : 56.6.0 Mtr (vi) Hook height : 8 Mtr from the floor
FLAME PROOF FITTING
S&F flame proof LED tube light fitting 1 x 20 watt with bipin holders connector block etc complete with all accessories complete all as specified and directed by Engr-in-charge
S&F flame proof/ Exhaust fan 457 mm sweep Single phase 250 volt complete all as specified and directed by Engr-in-charge
EXTERNAL WATER SUPPLY
Cutting the existing water supply GI pipe line 100 mm dia and taking branch connection of 80 mm dia pipe by inserting Tee complete all as specified and directed by Engr-in-charge
M&L for construction of valve pit of size 900 cm x 900 cm x 900 mm internal dimensions complete all as specified and directed by Engr-in-charge
Supply and Fix monoblock pump set suitable for 415 v ,3 phase system having capacity 3 HP including suitable size of PCC platform as per OEM specification complete all as specified and directed by Engr-in-charge
EXTERNAL ELECTRICFICATION
Supply, laying HT XLPE insulated screened, earthed, PVC bedded, galvanized steel strip armoured, electric power cable (heavy duty) of size 3 core 120 sqmm with aluminium conductor suitable for 22kV grade as per relevant IS including latest amendment for IS ( ISI marked cable) testing, commissioning along with complete laid in trenches duct etc. all as specified and directed by Engr-in-charge
Supply, installation, testing and commissioning of 22kV, 630A, compact type out door VCB SF6 rated capacity of 40kA for 3 second with breaking capacity of 16kA for 3 second with self powered non-directional IDMT (Inverse definite minimum time) over current and earth fault relays (Micro processor based) to be installed with existing compact RMU in extension and to match the existing make and model (i) Cable box with cable cover interlock for front termination of the cable suitable upto 2 R x 3core 120sq.mm (XLPE) for VCB feeder. Cable door should be as per IP54 and manufacturer design and specification.
Supply, installation, testing, commissioning of energy efficient (level 2) 630 kVA, 22/0.433 kV, oil immersed, ONAN cooled, 3- Phase step-down distribution transformer indoor type suitable for 22 kV, 50 Hz distribution and conforming to IS: 1180 (Part- 1): 2014, including first filling of natural ester vegetable oil, conforming to IS: 16659- 2017, having dielectric breakdown strength ≥ 65 kV at 2.5mm gap, CRGO bolt-less prime grade core, M4 or better directly from reputed manufacturers like Nippon / Posco/ AK steels ensures high endurance of core HV & LV windings wound from super enamel covered electrolytic grade copper conductor with tapping on the HV winding for variation of HV voltage within range of ±2.5%, 5% and 7.5% in steps of 2.5%, corrugated tank, HV/LV cable boxes complete with all standard fittings/accessories and mounted on a platform as per manufacturer's recommendation as specified and directed. Make: ABB Ltd., Bangalore, Siemens Ltd., Mumbai, Bharat Bijlee Ltd, Mumbai, Crompton Greaves, Mumbai, Schneider, Alstom (GEC), M/s Kirloskar Electric, M/s EMCO, M/s BHEL, M/s Andrew Yule,M/s Indian Transformers and Electricals Pvt. Ltd. Gurgaon, VOLTAMP Transformer, M/S. URJA Techniques India Pvt. Ltd.
The transformer shall conform to the following specific parameters: [i] System Voltage: 22 kV [ii] Rated Voltage (HV/LV): 22 /0.433 kV [iii] Frequency: 50 Hz ±3% [iv] No. of Phases: 3 [v] Connection (HV/LV): Delta / Star (neutral brought out) [vi] Vector Group: Dyn-11 [vii] Type of Cooling: ONAN [viii] Audible Sound Level: < 75 dB [ix] Insulation Level: "(1) HV Peak Impulse Voltage: 75 kV (2) HV Power Frequency Voltage: 28 kV (3) LV Power Frequency Voltage: 2 kV [x] Impedance: 4.5% [xi] Maximum Losses: (1) at 50% loading: 5.05 kW (2) at 100% loading: 15 kW [xii] Cable Box Clearance: (1) HV: 127 mm Phase to Phase; 76 mm Phase to Earth (2) LV: 25 mm between Phase to Phase; 20 mm Phase to Earth" [xiii] Terminal Markings: (1) HV: 1U, 1V, 1W (2) LV: 2u, 2v, 2w, 2n [xiv] Off Circuit Tap Changer (OCTC): ±7.5% in steps of 2.5% The following standard fittings/accessories shall be provided along with the transformer: [i] Non-detachable rating & terminal marking plates [ii] Monogram plate [iii] Lifting lugs for main tank & top cover & jacking lugs [iv] Top filter valve [v] Drain cum bottom filter valve
[vi] Oil sampling valve [vii] Earthing terminals with lugs: 2 Nos. [viii] Storage & instruction plate [ix] Skid type under base [x] Bi-directional plain/flange rollers [xi] Detachable type radiators with top & bottom shut-off valve [xii] WTI & OTI with alarm & trip contact [xiii] Marshalling box [xiv] Magnetic Oil level gauge low oil level alarm contact NOTES: [i] The bidder shall furnish dimensional drawings of the items offered indicating all the fittings, dimensional tolerances, typical GADs of the windings with details of insulation at each point and core construction, etc. for approval . [ii] Contractor shall submit the technical drawing, Constructional drawings, safety features drawing etc for approval
Supply and fix cable jointing kit for 22 KV grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm.
Comprehensive Maintenance of AC
Comprehensive maintenance comprising of routine, preventive & breakdown maintenance of chilled water type central air conditioning plant of capacity 200 TR (2x 100 TR working + 1x 100 TR standby) installed comprising of all devices and accessories through out 12 months on all days including Sundays and holidays for a period of 03 years after expiry of defects liability period (i.e. 24 months after completion of all Phase II tests) all as specified and directed and as shown below:-
(a) 1 st year after expiry of defect liability period.
(b) 2 nd year after expiry of defect liability period.
(c) 3 rd year after expiry of defect liability period.
MANNING AND OPERATION OF AC PLANT Manning & operation of chilled water type central AC plant for a period of 60 ( sixty) months[ for three shifts of eight hours duration (0600 hrs to 1400 hrs, 1400 hrs to 2200 hrs and 2200 hrs to 0600 hrs)] for all days in a week including Sundays & holidays with all instruments and controls complete as specified as under and as directed by Engineer-in-charge.
(a) First (11 months after completion)
(b) Second (11 months after completion of Phase (a) above)
(c) Third (11 months after completion of Phase (b) above)
(d) Fourth (11 months after completion of Phase (c) above)
(e) Fifth (11 months after completion of Phase (d) above)
(f) Sixth (05 months after completion of Phase (e) above)
United Sales Corporation
Nexus Infratech
DAS Offshore Engg. Pvt. Ltd.
B D Raizada Projects Pvt Ltd
UBC Engineers Pvt Ltd
Hariom Projects Pvt Ltd
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid