Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹26.7 LAccepted-AOC | L1 | Accepted-AOC The lowest bidder | |
| 2 | L2₹29.1 L+₹1.8 L (6.55%)Rejected-AOC 158 ARATH BAZAR KASAULI 173204 HP | KASAULI | SOLAN | HIMACHAL PRADESH | 173204 | L2 | Rejected-AOC Other than the lowest bidder |
Tender Value
₹25 L
EMD Value
₹50,000
Closing Date
16 Oct 2023, 6:00 pmClosed
GE (I) JUTOGH
GE (I) JUTOGH, JUTOGH CANTT SHIMLA (HP) - 171008
REPAIR AND MAINTENANCE OF CENTRAL HEATING PLANT AND FIRE FIGHTING SYSTEM ALONG WITH CONNECTED ITEMS AT MH SANJAULI UNDER GE (I) JUTOGH
2023_MES_619583_1
GE(I)/JUT-72 OF 2023-24
Open Tender
Civil Works
Item Rate
330 days
SANJAULI
CLASS E CATEGORY c (i)
7 documents required · 7 mandatory
₹500
GE (I) JUTOGH
₹50,000
Yes
14 Nov 2023
19 Sept 2023
18 Oct 2023
19 Sept 2023
16 Oct 2023
3 Oct 2023
19 Sept 2023 - 25 Sept 2023
Amount
Servicing of Hot Water Generators (AMW-03) and Steam Boiler Stematic (SG-01) including periodical servicing of each boiler at every month and overhauling of each boiler twice in a year with necessary minor repairs required if any for trouble free functioning comprising the maintenance work such as arresting of oil/fuel/water leakage if any ,cleaning the boiler to maximize its efficiency should remove the debris and residue from the combustion chamber (fire box) as well checking all the electrical connections , checking of oil/water pressure and oil/water level, temperature, RPM, in put voltage , replacement of the rubber bush, checking electrical parameters of the starter and circulator pumps , checking of Heat exchanger,Expansion tank,Burner,backflow valve, supply line and return lines etc complete including replacement of the unserviceable parts parts during servicing if required of the followings:-
Note:- (i) Unserviceable parts will be measured and paid separately. (ii) Servicing will be carried out through rep of M/s Micromeg Enterprises Pvt Ltd or any authorised agency of OEM or as directed by Engr-in-Charge. (iii) Servicing will be carried out at every month or whenever required or as directed by Engr-In-Charge within 48 hrs of requirement otherwise recovery per day shall be made against the repective item at the rate quoated by the contractor.
Servicing of Hot Water Generator of capacity 3 Lakh Kilo Cal complete all as specified and directed. Make :-Thermax
Overhualing of Hot Water Generator of capacity 3 Lakh Kilo Cal complete all as specified and directed. Make :-Thermax
Servicing of Steam Boiler Stematic of cap 100 kg/ hr complete all as specified and directed. Make:Thermax
Overhualing of Steam Boiler Stematic of cap 100 kg /hr complete all as specified and directed. Make Thermax
Supply only following spare Parts for Hot Water Generator of cap 3 lakh kilo cal complete all as specified and directed. Make:- Thermax
Nozzle 5.5 GPH 60 DEG Pt. No. P22NM20210
Sequence controller LOA24, Pt. No.-P21BSP0010
Photocell QRB1,Pt.No. P22BE10040
Fuel Pump,Pt.No. P21RSP1280
Electrode Assembly,Pt.No.P21BSP0320
Fuel Diesel Filter as per sample
Metallic fuel pipe from filter to FIP as per sample
Supply only following spare Parts for Steam Boiler Stematic of cap 100kg/hr complete all as specified and directed. Make:- Thermax
Nozzle 1.25 GHP,60 DEG. Pt.No. P22NM10370
Sequence controler,LOA24 Pt.No.P21BSP0010
Photocell QRB1A,Pt.No. P22BE10040
Electrode,Pt No. P21BSP0200
Gland washer,Pt.No.P01RDS0690
Valve seat assembly,P01RDS0320
Supply only followings spare parts :-
Indicator lamps DC filament type 10 W 12 V
Push button with contact element 5A.
Servicing of Hot water pump set supply including repairs if any for trouble free functioning comprising the maintenance work such as arresting oil /fuel leakage if any ,greasing of the bearing, cleaning/ checking of bush, coupling , adjusting the alligment, vibrations with checking all the electrical connections , oil level , starter complete all as specified and directed for the following Pump sets.:-
Servicing of Hot water pump set 10 HP , 21 Mtr head complete all as specified and directed.
Supply only 20w40 grade complete all as specified and directed.
Suuply only Pressure gauge 0- 10 kg/ cm2 of dial size 100mm with fixing accessories complete all as specified and directed.
Servicing of fire fighting Panel and fire alarm network system at every three months or as required complete comprising for checking/ tighteting of connections for Hose reel,Hydrant valve,smoke detector, alarm panels, Hooter, MCP, Fire pumps (Hydrant & sprinkler , Jockey pump set, Diesel pump set, fire control alarm panel) to provide services by professional technician of fire safety norms of the systems,including replacement of unseviceable parts like sprinker, Smoke detectors , control wire etc complete all as specified and directed. Note:- (i) Unserviceable parts will be measured and paid separatetly, however minor items likes clamps, tapes & T&P will be provided by contractor without any extra cost . (ii) Servicing will be carried out through rep of M/s A K Fire Engineering or any authorised agency or as directed by Engr-in-Charge. (iii) In case of any urgency of related to Fire work, the complaint will be attended with in 24 Hrs or as directed by Engr-In-Charge otherwise recovery per day shall be made against the item with the rate of quoated by the contractor.
Servicing of Air Handling Unit (AHU) & HVAC unit (OT's) & Fan Coil Unit (FCU) comprising checking of AHU's/ FCU's Motors, Fan belt, Thermostate, humidistate, dampers,starter, blower fan, Actuator, pressure gauge , control wiring etc for each AHU's/ FCU's and including cleaning of filters with minor repairs as per site if any for trouble free functioning comprising the maintenance work such as arresting any leakage of water from pipe line ,Air from ducts, greasing/ oiling of electrical drives, bush/ bearing as well as checking/ tightening of all the electrical connections , temperature, RPM, in put voltage , vibration, allignment, Heat exchanger , , Actuator/ valves, cleaning of Y- strainer by draning out of water from pipe line , to remove any particles from inside of supply/ return pipe lines etc and making trouble free complete all as specified and directed of followings:- Note:- Spare parts will be paid seperately. Note:- (i) Unserviceable parts replaced will be measured and paid separatetly. (ii) Servicing will be carried out through rep of M/s AVONAIRE SOLUTIONS or any authorised agency or as directed by Engr-in-Charge.
Servicing of Air Handling Unit (AHU) of cap 5000 CFM complete all as specified and directed. Make:- Savier complete all as specified
Servicing of Air Handling Unit (AHU) of 3000 CFM cap Make:- LLoyed complete all as specified
Servicing of Fan Coil Unit (FCU) of 500 CFM cap Make:- Carrier complete all as specified
Servicing of HVAC unit comprising checking of compressor, controls such as pressure cut outs, cooling coil, blower motor, checking/ arresting of gas leakage if any incl necessary charge of gas etc of 8.5TR cap Make:- Carrier complete all as specified
Supply only followings spare parts :-
Digital type Thermostate 230 V AC suitable for FCU as per sample : Make- Honeywell or equivalent.
Digital type Thermostate 230V AC suitable for AHU as per sample complete all as specified and directed. Make- Honeywell or equivalent.
Actuator 230V AC for motorised valve suitable for FCU as per sample complete all as specified and directed. Make- Honeywell or equivalent.
Actuator 230V AC for motorised valve suitable for AHU as per sample complete all as specified and directed. Make- Honeywell or equivalent.
Pre Filter 10 Micron for AHU size 700x600x25mm box type complete as per sample complete all as specified and directed.
Fine Microvee Filter 5 Micron Flange type size 600x600x150mm complete as per sample complete all as specified and directed.
M&L for Danger notice board/plate of 1.6mm thick mild steel sheet , vitreous enameled white with letters, figures , and conventional skull and bone in signal red colour and fixed with MS clamps bolts approved size for LT 20cmx15 cm complete all as specified and directed. Note:-Old u/s item will be deposited to E/M store yard.
Material and labour for synthetic insulating mat of thickness not less than 2.5 mm size 2.0 mtr X 1.0 mtr suitable for system voltage 11 kV and break down voltage 45 kV confirming IS 15652 : 2006 incl fixing on floor with adhesive complete all as specified and directed. Note:-Old u/s item will be deposited to E/M store yard.
Supply and connecting of Pure Sine wave Automatic Inverter is equiped with fan for cooling,Power active switch, MCB protection and bypass switch which keeps supplying output from grid even in case of inverter faults, emergency power off,LCD display, charging current not less than 16A, efficiency 95 %, suitable for 24 Volts batteries (2 nos batteries, 12 volts and 150 AH each) Input 240 Volts, 50 Hz, output power not less than 1400 Watt , 240 vots AC alongwith standard accessories complete all as specified and directed. Note:- Battery will be paid seperately.
Supply and connecting Maintenance free battery 12 volt 150 AH minimum warranty of 18 Months including statndard accessories complete all as speciied and directed. Note:-Old u/s item will be deposited to E/M store yard.
Calibration/setting of protection devices, Relays with all protection function (overcurrent, Earth fault protection), tripping test of Over current and earth fault realay through primary and secondary injection machine, testing of Auxiliary relay, tripping test through all respected relays and provide report from authorised service dealer/center/representative complete all as specified and directed. Note. (i) All equipments, tools , labour, incl in the quoted rates. (ii) Contractor will provide company authorised dealer/service centre / representative test report of calibration of relay. (iii) Unserviceable part or items shall be replaced, measured and paid separately under relevent item.
S&F tape wound Current transformer of ratio 1000/5A, line voltage 415 V, class 1.0/5P10, 50 Hz, size and model as suitable as existing CTs installed at 1100 Volt protection/metering system system at Substation complete all as specified and directed. Note:-Old u/s item will be deposited to E/M store yard.
Supply and fixing of combined over current and earth fault numerical relay with input current 1A/5A and auxiliary voltage 24 V DC incl complete installation in LT Panel, complete connections and testing as per instruction from OEM all as specified and directed by Engr in Charge. Make: CG, ABB, L&T, C&S or Siemens. Note :(i) Relay will be fixed in existing panel incl cutting , welding, drilling or any other suitable means or will be fixed in separate cabinet without any extra cost to department (ii) All type of wires required for proper connection will be provided by contractor without any extra cost to department. (iii) Proper functioning and testing will be carried out without any extra cost to department.Note:-Old u/s item will be deposited to E/M store yard.
Supply and fixing of Master tripping relay of auxillery vaoltage 24 V DC incl complete installation in panel, with connections and testing as per instruction from OEM all as specified and directed by Engr in Charge. Make: CG, ABB, L&T, C&S or Siemens. Note :(i) Relay will be fixed in existing panel incl cutting , welding, drilling or any other suitable means or will be fixed in separate cabinet without any extra cost to department (ii) All type of wires required for proper connection will be provided by contractor without any extra cost to department. (iii) Proper functioning and testing will be carried out without any extra cost to department. Note:-Old u/s item will be deposited to E/M store yard.
Supply and fixing of Engine control relay (EC-2) as per existing for Auto Start/Stop DG set with auxillery vaoltage 24 V DC or 230 Volt AC incl complete installation in panel, with connections and testing as per instruction from OEM all as specified and directed by Engr in Charge. Make: C&S , CG, ABB or Siemens. Note :(i) Relay will be fixed in existing panel incl cutting , welding, drilling or any other suitable means or will be fixed in separate cabinet without any extra cost to department (ii) All type of wires required for proper connection will be provided by contractor without any extra cost to department. (iii) Proper functioning and testing will be carried out without any extra cost to department.
Supply and fixing power pack for relay operation in ACB Panel, inlet voltage 230-240 Volts AC and output 24 Volt DC incl connections complete all as specified and directed. Note:-Old u/s item will be deposited to E/M store yard.
Supply and fixing change over switches 4 pole 400 Amps , 415 volts in sheet metal enclosure incl fixing on wall/LT panel/any other surface using nut/bolts/Anchor fastners and dismantling and taking down old unser switch/MCB/MCCB/DB as available on site any type any size complete all as specified and directed. Note:-Old u/s item will be deposited to E/M store yard.
Supply and fixing single phase preventor ( sequence controller) for 3 phase 415V comprising MCCB 4 pole 200 Amps , 415 volts, with contactor 4 pole 160 Amp and suitable connected accessories with enclosure incl fixing on wall/LT panel/any other surface using nut/bolts/fastners complete all as specified and directed. Note:-Old u/s item will be deposited to E/M store yard.
Supply and fixing ACB 4 pole , 415 V, Manual drawout type of rated current 630 Apms , Icu =50 kA, Ics =100% Icu , rated short time withstand current for 1 sec Icw=50 kA @ 415 Volts, horizontal/vertical type complete accessories and connection with setting of tripping parameters complete all as specified and directed. Note:-Old u/s item will be deposited to E/M store yard.
Supply and fixing contactors of capacity 200 Amps 4 Pole, rated insulation voltage 1100 Volts, rated operational voltage 415 volts, rated impulse withstand voltage 8kV, with inbuilt auxiliary contacts , frequency 50 Hz, coil voltage 240/415 Volts , dimension as per existing incl connections complete all as specified and directed. Make: L&T, Havells, Schneider, C&S or equivalent. Note:-Old u/s item will be deposited to E/M store yard.
Supply,fixing,installing,testing and commissioning of end suction type insulated Hot Water Pump set capacity of 20 HP,head 45 mtr,discharge range of 1100 LPM) 1100 volts ,power 15 KW, single stage (for hot water pumping application) in cast iron body,bronze impeller complete with mechanical seals including TEFC squirrel cage induction motor base plate,mounting on suitable size MS channel frame with all fixing accessories and fittings with suitable size of PCC foundation as per site condition i.e. mechanical seal,pressure gauges,thermometers, drains,coupling, coupling guard,vibration isolation arrangement by means of spring/rubber typecomplete all as specified and directed. Make:- Bharat Bijlee, Kirloskar, Crompton. Note:- Old unserviceable pumping set shall be deposited to MES store yard
Supply,fixing,testing and commissioning of ERW type M.S. "C" class 80 mm dia for Hot water pipe confirming to IS 1239 complete with bends,reducers,tees,supports including PUF insulation 40mm thick with aluminium clading with all fixing accessories complete all as specified and directed. Note:-Old u/s item will be deposited to E/M store yard.
Supply,fixing,testing and commissioning of ERW type M.S. "C" class 100 mm dia for Hot water pipe confirming to IS 1239 complete with bends,reducers,tees,supports including PUF insulation 40mm thick with aluminium clading with all fixing accessories complete all as specified and directed. Note:-Old u/s item will be deposited to E/M store yard.
Supply,installing,testing and commissioning of Butterfly valve size of 100 mm dia duly insulated complete with companion flanges,nuts,bolts,gaskets etc, as specified,having cast iron body,seat of black nitrile rubber,nylon coated S.G. iron disc PTFE coated SS (AISI 410) shaft, complete with companion flanges,nuts,bolts,gaskets,etc as required. Note:-Old u/s item will be deposited to E/M store yard.
Supply,installing,testing and commissioning of Butterfly valve size of 80 mm dia duly insulated complete with companion flanges,nuts,bolts,gaskets etc, as specified,having cast iron body,seat of black nitrile rubber,nylon coated S.G. iron disc PTFE coated SS (AISI 410) shaft, complete with companion flanges,nuts,bolts,gaskets,etc as required complete all as specified and directed. Note:-Old u/s item will be deposited to E/M store yard.
Supply,installation,testing and commissioning of suction guide having C.I body,CI cover, Y type-SS/CI strainer,start up filter of fine brass mesh and MS/CI guide vans for water pump with flanges,nuts-bolts gaskets etc,for 100 mm dia pipecomplete all as specified and directed. Note:-Old u/s item will be deposited to E/M store yard.
Supply,installation,testing and commissioning of suction guide having C.I body,CI cover,Non Return Valve (NRV) with flanges,nuts-bolts gaskets etc,for 80 mm dia pipe complete all as specified and directed. Note:-Old u/s item will be deposited to E/M store yard.
S&F Star Delta Starter suitable for 20HP,415V pump set including contactor, relay, single phase preventor, suitable ammeter incl control wiring etc with MCCB 4 pole 63 Amp 415 V as incommer complete all as specified and directed. Note:-Old u/s item will be deposited to E/M store yard.
Supply, fix and testing of Photoelectric Multi Sensor Smoke Detector including taking out old unserviceable smoke detector all as specified by Engineer in Charge. Note:- Old unserviceable smoke detector shall be deposited to MES store yard
Supply, fix and testing of water sprinkler for fire protection system including taking out old unserviceable water sprinkler all as specified by Engineer in Charge. Note:- Old unserviceable water sprinkler shall be deposited to MES store yard
Supply, fix and testing of response indicator after detecting firer including taking out old unserviceable response indicator all as specified by Engineer in Charge. Note:- Old unserviceable response indicator shall be deposited to MES store yard
Pankaj Traders
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .