Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹19.8 LAccepted-AOC | ₹19.8 L Quoted ₹20.5 L | L1 | Accepted-AOC Lowest Bidder |
| 2 | L2₹22.0 L+₹1.5 L (7.51%)Rejected-Finance 179 URBAN ESTATE RAM TIRATH ROAD NR GURUDAWARA DARSHAN SINGH AMRITSAR PUNJAB 143001 | AMRITSAR | PUNJAB | 143001 | ₹22.0 L+₹1.5 L (7.51%) | L2 | Rejected-Finance Other than lowest bidder |
| 3 | L3₹25.2 L+₹4.7 L (23.1%)Rejected-Finance | ₹25.2 L+₹4.7 L (23.1%) | L3 | Rejected-Finance Other than lowest bidder |
Tender Value
₹20 L
EMD Value
₹40,000
Closing Date
23 Nov 2019, 6:00 pmClosed
GE (AF) Jammu
GE (AF) Jammu Air Force Station Jammu
REPAIR/MAINT TO UNSV LT UG CABLES, PANEL BOARDS FEEDER PILLAR AND ALLIED WORKS AT DOMESTIC AREA AT AF STATION JAMMU
2019_MES_281373_2
CA No GE/AFJ-40/2019-20
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE (AF) Jammu
As per tender documents and as per policy in vogue
8 documents required · 8 mandatory
₹500
GE AF Jammu
₹40,000
Yes
22 Jan 2020
21 Oct 2019
25 Nov 2019
21 Oct 2019
23 Nov 2019
7 Nov 2019
Amount
Supply and laying & testing UG cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (Heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10 sq mm, 2 core, complete including disconnecting and taking out old existing unserviceable cable all as specified and directed by Engr-in-Charge.
Supply and laying & testing UG cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (Heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 sq mm, 4 core, complete including disconnecting and taking out old existing unserviceable cable all as specified and directed by Engr-in-Charge.
Supply and laying & testing UG cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (Heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 sq mm, 4 core, complete including disconnecting and taking out old existing unserviceable cable all as specified and directed by Engr-in-Charge.
Supply and laying & testing UG cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (Heavy duty) 1100 Volts grade with stranded aluminium conductor of size 50 sq mm, 3.5 core, complete including disconnecting and taking out old existing unserviceable cable all as specified and directed by Engr-in-Charge.
Supply and laying & testing UG cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (Heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95 sq mm, 3.5 core, complete including disconnecting and taking out old existing unserviceable cable all as specified and directed by Engr-in-Charge.
Supply and laying & testing UG cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (Heavy duty) 1100 Volts grade with stranded aluminium conductor of size 150 sq mm, 3.5 core, complete including disconnecting and taking out old existing unserviceable cable all as specified and directed by Engr-in-Charge.
Supply and laying & testing UG cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (Heavy duty) 1100 Volts grade with stranded aluminium conductor of size 185 sq mm, 3.5 core, complete including disconnecting and taking out old existing unserviceable cable all as specified and directed by Engr-in-Charge.
Supply and laying & testing UG cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (Heavy duty) 1100 Volts grade with stranded aluminium conductor of size 240 sq mm, 3.5 core, complete including disconnecting and taking out old existing unserviceable cable all as specified and directed by Engr-in-Charge.
Taking out of old serviceable/unserviceable PVC under ground LT cable of any size and type fixed on pole, wll or laid in floors, trenches, across road crossing, etc. including taking out cable covers of precast PCC/RCC slab or brick covers, etc., including setting a side serviceable materials in safe costody for reuse and or unserviceable materials shifting to store complete all as specified and as directed. Note: (i) Dismantling of clamps, nuts, bolts, etc., taking out of GI pipe in cable protection shall be measured and paid separately under respective item of this schedule. (ii) Cost for making good the disturbed ground surfaces of floors/walls in cement mortar 1:3 shall deemed to be included in the unit rate quoted. However cost for making good the disturbed surfaces of roads with PCC and hard core filling is out of scope of this work and shall be measured and paid separetely under respective item of this schedule.
Relaying only of serviceable LT under ground cable of any size and any type in trenches, floors, across road crossing or fixed on poles, walls, or passing through pipe, cable obtained from ser item No 9.00 here-in-before complete all as specified and as directed by the Engineer-in-Charge. NOTE: Handling of under groucn cable to working site as ordered shll be carried out by the firm and rate for the same is to be deemed in overall rates quoted by the tenderer under this item.
Relaying only of serviceable bricks/PCC slab cover obtained from item No 9.00 here-in-before for cable protection cover laid width wise along length of cable complete all as specified and as directed by the Engineer-in-Charge.
Supply, install and erect in true vertical position (or to be fixed in an inclined position as strut pole) steel tubular swaged poles complete with MS base plate of 6 mm thick of size 300 mm x 300 mm, finial taper plug, pole cap, bolts, nuts and washers and screwed pole made out of FRW MS tubing conforming to IS-2713 (Part-II) 1980 type 410-SP-31 (9 meters long) pole including drilling of holes of required size and Nos for fixing of cross arms, painting with one coat of red oxide primer and two coats of aluminium paint for exposed surfaces and two coats of black bituminous paint for portion embeded in concrete, incl taking down carefully old deterioiated RCC/steel pole etc complete all as specified and directed.
S & F Stay assembly complete with accessories as shown in electrical plate No 1 incl GI Adjustable Stay Rod of 20 mm Dia, GI Stay wire of size 7/4 mm incl stay clamps, loop type insulator, excavation in any strata including taking down old unserviceable stay assembly all as specified and directed
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth and getting out in any type of soil for laying of LT UG cables, foundation of poles, etc. complete. Note:- The Rate quoted deemed to including cutting and removal of PSP Sheets wherever occured during excavation and the same shall be staged at desired location as directed at site which will be handed over to the appropriate authority as directed by Engineer-in-Charge
Excavation in trenches not exceeding 1.5m wide and exceeding 1.5m but not exceeding 3.0m in depth and getting out in any type of soil for laying of LT UG cables, foundation of poles, etc. complete. Note:- The Rate quoted deemed to including cutting and removal of PSP Sheets wherever occured during excavation and the same shall be staged at desired location as directed at site which will be handed over to the appropriate authority as directed by Engineer-in-Charge
Returning, filling in, including spreading levelling, watering and well ramming in layers not exceeding 25 cm thick in hard dense soil
Removing excavated material not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point
Dry coarse sand as cushioning to under ground cable provided with layer of 8 cms deep before laying the cable and 15 cms deep after laying and stretching the cable, punned to 18 cm thick complete all as specified and as directed by Engr-in-Charge. NOTE: Only punned thickness shall be measured for payment purpose.
Sub class 'B' old size bricks well burnt as covering to under ground cables , laid dry, flat over the cables on sand cushioning with width equal to length of the brick as mechanical protection to cable, complete all as specified and directed.
Plain cement concrete 1:4:8 type D2 using 40mm graded stone aggregate for foundation and mass concrete of poles complete all as specified and as directed.
PCC 1:3:6 type C1 using 20 mm graded stone aggregate for coping of poles/plinth blocks of HT poles etc incl fair finishing the exposed surfaces even and smooth without using extra cement including necessary form work complete all as specified & directed.
Boring/drilling horizontelly under the road/hard standing from one end to another end of road, having width not exceeding 6 mtr of road/hard standing and not exc 1 mtr below road level without damaging the road/hard standing, for providing 150mm dia of MS/GI pipe for laying/protection of cable through pipe ,complete all as specified and directed by Engr-in-charge.NOTE: Pipe will be measured and paid separately
M & L for Cutting through existing road surfaces i.e. black top surfacing, WBM, soling, earth formation, etc, and making trench of minimum 500mm wide 100cm in depth along the cross section of road for laying of pipes or UG cables, including returning filing in, well ramming & removal of surplus spoil to a distance not exc. 50 mtrs & repairs to road surfaces to match with existing specifications of earth formation, soling, WBM and black top surfacing after laying the pipes/cable etc. all as specified & directed.
M&L for ACSR conductor on HT/LT poles of any type of conductor as required at site including binding and jointing to insulator with suitable size of binding aluminium wire for connectors, jumpers, etc. complete including taking out old unserviceable ACSR conductor from overhead line all as specified and directed.
Material and labour for Pin type, porcelain, vitreous, white brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 50 mm height, 65 mm dia for 1100 Volts grade
Material and labour for shackle type porcelain vitreous white, brown or green insulator incl GI mild steel strip, washer, insulator bolts, washers and nut for working pressure 1100 volts section of strips 31 x 5 mm bolt dia 14 mm max dia 115 mm height 100 mm on poles upto 9 metre long incl taking down old unserviceable one.
Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat one under coat and one finishing coat of aluminium paint, including taking down old broken steel complete all as specified and directed by Engr-in-Charge.
Anti-climbing device spikes type fabricated out of M.S. bars (round,square and flat) including nuts, bolts, washers and welding in two halves made to shape to suit the cross section of the pole and duly painted with synthetic enamel aluminium/smooke grey paint over a coat of primer and entire satisfaction of Engnr-in-Charge complete including taking down of old broken anti climbing device all as specified and directed .
Supplying, laying and spreading (thickness as directed by Engineer-in-Charge) dry/loose coarse aggregates (granite, trap, Basalt), grading I, 90 to 40 mm or grading 2, 63 to 40 mm size, including well ramming, under 2/4 pole structure including cleaning and uprooting the wild grass and other vegitation, complete all as per direction by Engineer-in-charge.
Brick work with old size sub class 'B' bricks, straight or curved on plan exc 6 m mean radius built in cement mortar 1:6, complete including demolition old broken brick work all as specified and as directed by Engr-in-Charge.
Rendering 10 mm thick on fair faces of brick work or concrete surfaces, finished even and smooth (without using extra cement) on walls in cement mortar 1:6, complete all as specified and directed by Engr-in-charge.
M&L for three coat of white washing on new undecorated plastered surface including preparation of walls surfaces complete all as specified.
Supply and Fixing GI tubing light grade 40mm dia along the wall/in trenches/in duct/in culvert/road crossing and including provisioning of suitable mild steel flat iron clamps and bolts, nuts and double washers etc for holding of GI pipe alongwith poles including taking out old broken Gi pipes, complete all as specified and as directed by Engr-in-Charge.
Supply and Fixing GI tubing light grade 50mm dia along the wall/in trenches/in duct/in culvert/road crossing and including provisioning of suitable mild steel flat iron clamps and bolts, nuts and double washers etc for holding of GI pipe alongwith poles including taking out old broken Gi pipes, complete all as specified and as directed by Engr-in-Charge.
Supply and Fixing GI tubing light grade 80mm dia along the wall/in trenches/in duct/in culvert/road crossing and including provisioning of suitable mild steel flat iron clamps and bolts, nuts and double washers etc for holding of GI pipe alongwith poles including taking out old broken Gi pipes, complete all as specified and as directed by Engr-in-Charge.
Supply and fixing in repairs ISI mark aluminium thimbles suitable for under ground LT cables of sizes 16 Sqmm including cutting of exsting burn/ dammaged cable after disconnecting from exsting position, extending the cable from cable loop including neccesory earth work and reconnecting the same.
Supply and fixing in repairs ISI mark aluminium thimbles suitable for under ground LT cables of sizes 25 Sqmm including cutting of exsting burn/dammaged cable after disconnecting from exsting position, extending the cable from cable loop including neccesory earth work and reconnecting the same.
Supply and fixing in repairs ISI mark aluminium thimbles suitable for under ground LT cables of sizes 35 Sqmm including cutting of exsting burn/dammaged cable after disconnecting from exsting position, extending the cable from cable loop including neccesory earth work and reconnecting the same.
Supply and fixing in repairs ISI mark aluminium thimbles suitable for under ground LT cables of sizes 50 Sqmm including cutting of exsting burn/dammaged cable after disconnecting from exsting position, extending the cable from cable loop including neccesory earth work and reconnecting the same.
Supply and fixing in repairs ISI mark aluminium thimbles suitable for under ground LT cables of sizes 70 Sqmm including cutting of exsting burn/dammaged cable after disconnecting from exsting position, extending the cable from cable loop including neccesory earth work and reconnecting the same.
Supply and fixing in repairs ISI mark aluminium thimbles suitable for under ground LT cables of sizes 95 Sqmm including cutting of exsting burn/dammaged cable after disconnecting from exsting position, extending the cable from cable loop including neccesory earth work and reconnecting the same.
Supply and fixing in repairs ISI mark aluminium thimbles suitable for under ground LT cables of sizes 120 Sqmm including cutting of exsting burn/dammaged cable after disconnecting from exsting position, extending the cable from cable loop including neccesory earth work and reconnecting the same.
Supply and fixing in repairs ISI mark aluminium thimbles suitable for under ground LT cables of sizes 185 Sqmm including cutting of exsting burn/dammaged cable after disconnecting from exsting position, extending the cable from cable loop including neccesory earth work and reconnecting the same.
Supply and fixing in repairs ISI mark aluminium thimbles suitable for under ground LT cables of sizes 240 Sqmm including cutting of exsting burn/dammaged cable after disconnecting from exsting position, extending the cable from cable loop including neccesory earth work and reconnecting the same.
Supply and fixing in repairs ISI mark aluminium thimbles suitable for under ground LT cables of sizes 400 Sqmm including cutting of exsting burn/dammaged cable after disconnecting from exsting position, extending the cable from cable loop including neccesory earth work and reconnecting the same.
Supply and fixing fixed in repairs cable Junction Boxes with terminals` IP 66 "halogen free and weather proof” for outdoor installation (with metric knockouts for cable entry - Black Colour) Cable Size 16/25 Sqmm, Box Dimensions-200 x160 x 98, Catalog No-KF 9255(hensel) complete taking out of loop of cable from ground by neccessary earth work all as spcefied and directed by Engr-in- charge. Make- Hensel/Dowells
Supply and fixing in repairs PVC cable end terminal box outdoor type, 140 x 140 X 95 mm, PVC door, Sintex type , provision for cable incoming and outgoing from bottom, comprising of one MCB SPN 6-32 Amps (of Make: Legrand/Schneider/L&T), cable glands suitable size and one porcelein connector four way complete fixed on wall/pole. Make- Sintex of equivalent.
Supplying and fixing multi stranded 10 sqmm, 1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections one twin core cable flat or circular, fixed in repairs, complete all as specified and directed by Engineer-in-Charge.
Supplying and fixing multi stranded 16 sqmm, 1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections one twin core cable flat or circular, fixed in repairs, complete all as specified and directed by Engineer-in-Charge.
Supply and Fixing Change over switch On load 315 Amps 4 pole with sheet metal enclosure, fixed in repairs complete all as specified and directed. Make: Indoasian Cat Part No ICASO320 or equal approved in Siemens/Havells/Legrand.
Supply and Fixing MCCB 400 Amps 4 pole 36 KA with thermal magnetic release, fixed in repairs complete all as specified and directed. Make: Legrand (DPX³) Cat Part No 4220 07 or equal approved in Siemens (3VL)/Schneider (NSX)/L&T (D-Sine)
Supply and Fixing MCCB 320 Amps 4 pole 36 KA with thermal magnetic release, fixed in repairs complete all as specified and directed. Make: Legrand (DPX³) Cat Part No 4220 06 or equal approved in Siemens (3VL)/Schneider (NSX)/L&T (D-Sine)
Supply and Fixing MCCB 250 Amps 4 pole 25 KA with adjustable thermal and fixed magnetic setting, fixed in repairs complete all as specified and directed. Make: Legrand (DPX³) Cat Part No 4202 19 or equal approved in Siemens (3VL)/Schneider (NSX)/L&T (D-Sine)
Supply and Fixing MCCB 200 Amps 4 pole 25 KA with adjustable thermal and fixed magnetic setting, fixed in repairs complete all as specified and directed. Make: Legrand (DPX³) Cat Part No 4202 18 or equal approved in Siemens (3VL)/Schneider (NSX)/L&T (D-Sine)
Supply and Fixing MCCB 100 Amps 4 pole 25 KA with adjustable thermal and fixed magnetic setting, fixed in repairs complete all as specified and directed. Make: Legrand (DPX³) Cat Part No 4202 15 or equal approved in Siemens (3VL)/Schneider (NSX)/L&T (D-Sine)
Supply and fixing MCB TPN, 20 to 32 Amps, 415 V,AC complete all as specified and as directed by Engineer-in-Charge. Make: Cat part No 4086 78 to 4086 80 of Legrand (DX³) or equal approved in Schneider (Acti -9)/ Siemens (Betagard-5SL4)
Supply and fixing MCB TPN, 40 to 63 Amps, 415 V,AC complete all as specified and as directed by Engineer-in-Charge. Make: Cat part No 4086 81 to 4086 83 of Legrand (DX³) or equal approved in Schneider (Acti -9)/ Siemens (Betagard-5SL4)
Supply and fixing MCB SPN 6 to 32 Amps, 230 V,AC complete all as specified and as directed by Engineer-in-Charge. Make: Cat part No 4086 9 to 4086 17 of Legrand (DX³) or equal approved in Schneider (Acti -9)/ Siemens (Betagard-5SL4)
Supply and fixing MCB SPN 40 Amps, 230 V,AC complete all as specified and as directed by Engineer-in-Charge. Make: Cat part No 4086 18 of Legrand (DX³) or equal approved in Schneider (Acti -9)/ Siemens (Betagard-5SL4)
Preparation of old painted surface of HT steel tubular poles above the top of PCC coping. Painting of pole from top of coping to a height of 1.5mtr (bottom portion of pole) with two coats of synthetic enamel paint (Make-DULUX/ Superlac (Shalimar)/ Apcolite (Asian)/ Nerolac/ Luxol (Berger) in black and yellow alternate strip and painting the rest portion of pole of (approx length 9 mtr) including painting of cross arms/clamps etc complete with two coats of synthetic enamal aluminium paint (Make-Asian (Apex)/ Berger (Weather Coat) /Shalimar (Ist quality)/ Nerolac (Ist India) and to the entire satisfaction of Engineer-in-Charge complete all as specified and directed
Preparation of old painted surface of LT steel tubular poles above the top of PCC coping. Painting of pole from top of coping to a height of 1.5mtr (bottom portion of pole) with two coats of synthetic enamel paint (Make-DULUX / Superlac (Shalimar) / Apcolite (Asian) / Nerolac/ Luxol (Berger) in black and yellow alternate strip and painting the rest portion of pole of (approx length 7 mtr)including painting of cross arms/clamps etc complete with two coats of synthetic enamel aluminium paint (Make-Asian (Apex) /Berger (Weather Coat) / Shalimar (Ist quality) /Nerolac (Ist India) and to the entire satisfaction of Engineer-in-Charge complete all as specified and directed
Preparation of old cement based painted surfaces of RCC pole 9 mitres long by complete removal of existing treatment and painting with two coats of exterior emulsion weather proof paint of approved make and colour all as specified and to the entire satisfaction of Engineer-in-Charge complete all as specified and directed
Material and labour for fault detection in damaged under ground cables using cable fault detector/locater, vehicle mounted to accuracy of 2 mitres for various locations inside Air Force Station for under ground cables of any size upto 240 sqmm including excavation and earthwork in any type of soil having trench size 4 x 2 x 0.60m to visually inspect/ repair the damaged cable when and whre detected complete all as specified and directed by Engineer-in-Charge. NOTE: cable fault shall be located with use of cable fault locator machine as and when required with minimum possible time to reduce the downtime. If fault is not attended/located within 24 hours, recovery will be made at Rs 4000.00/Day from the date of such occurance.
Cable jointing kit for 1100 Volt (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 4 core XLPE armoured aluminium conductor cable of size 10 sqmm to 35 sqmm fixed in repairs,complete all as specified and directed by Engineer-in-Charge. Make: 3M/Denson/M-Seal
Cable jointing kit for 1100 Volt (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 4 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm fixed in repairs,complete all as specified and directed by Engineer-in-Charge. Make: 3M/Denson/M-Seal
Cable jointing kit for 1100 Volt (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 4 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm fixed in repairs,complete all as specified and directed by Engineer-in-Charge. Make: 3M/Denson/M-Seal
Cable jointing kit for 1100 Volt (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 4 core XLPE armoured aluminium conductor cable of size 240 sqmm to 300 sqmm fixed in repairs,complete all as specified and directed by Engineer-in-Charge. Make: 3M/Denson/M-Seal
Supply, installation , commissioning and testing LT panel in replacement of size 60 cm x 60 cm x 25 cm, outdoor cubical type floor mounted factory made of CPRI approved factory, totally enclosed vermin proof with front and rear opening with IP-54 protection as per IS - 8623 duly powder coated , fabricated out of 2.5 mm thick mild steel sheet mounted on frame of mild steel angle iron 60 cm x 60 cm x 6mm and , 45 cm above ground level duly supported with mild steel angle iron struts 60 cm x 60 cm x 6mm thick and embedded in PCC foundation in PCC 1:2:4, type B-1 , using 20 mm graded crushed stone aggregate , with suitable 415 Volt, 3 phase, four wire copper bus bar of rating capacity 400 Amps duly drilled holes for connections, R-Y-B-N insulated with different colour code and sleeved mounted on insulators complete prewired and cable connection with copper conductor wire upto copper bus bars including all incoming and outgoing cable connections with suitable size of copper lugs/ gland including supply and fixing of MCCB four pole, 415V, 250 Amp. 25KA-01No.(In comming) (Make:Legrand/L&T/ Schneider) including taking out old unserviceable, complete all as specified and directed by Engr - in- Charge
Supply, installation, commissioning and testing of LT feeder pillar, compartmentalised design of sie not less than 70 x 70 x 25 cm suitable for 440 volts 3 phase 4 wire system made out of 2.5mnm CRCA sheet powder coated having gasketed front two hinged doors with locking arrangement including bottom and top detachable gland plate complete with suitable size of rust proof nuts, bolts and washers, etc. with mounted accessories including the following components fixed in repairs,complete all as specified and directed by Engineer-in-Charge. (a) Four 30cm long copper bus bars 400 Amps mounted on epoxy insulators provided with rust proof nuts, bolts and washers. (b) LED indicating lamps - Set of three (Red, yellow, Blue)
M & L for Repair of LT Panel indoor/outdoor type of any size and capacity including welding, replacement of hinges, replacement of locking arrangement with new, L Drops hooks, etc. including PVC insulation on bus bar complete all as specified and directed by Engineer-in-Charge
M & L for Preparation of Old painted surfaces of LT Panel of any size by scraping of old paint of rusted portion and applying painting with one coat of aluminium paint complete all as specified.
Cleaning of under growth at substation . Cleaning should be carried out as & when required or when directed by Engr- in-Charge. Undergrowth at any point of time should not be more than 3 to 4 cm. A fine of Rs 1000.00 per month per substation will be deducted if undergrowth found grown beyond permissible height complete all as directed by Engr-in-Charge.
M&L for clearing of Grass Shrubs and other growing by uprooting in switchyards and installations upto 10 cms in girth at various locatins as directed
Material and labour for earth continuity conductor or main earthing lead using 4 mm dia galvanised iron or steel wire fixed to wall on batten or recess or chases or burried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required including taking down old wire complete all as specified and directed by Engineer-in-Charge.
Material and labour for earth continuity conductor or main earthing lead using 25 x 4mm galvanised steel strip fixed to wall on batten or recess or chases or burried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation, etc. as required including porcelain insulator saddle at the spacing nort exceeding 400mm including taking down old strip complete all as specified and directed by Engineer-in-Charge.
Material and labour for earth continuity conductor or main earthing lead using 32 x 6mm galvanised steel strip fixed to wall on batten or recess or chases or burried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation, etc. as required including porcelain insulator saddle at the spacing nort exceeding 400mm including taking down old strip complete all as specified and directed by Engineer-in-Charge.
Material and labour for earth continuity conductor or main earthing lead using 20 x 3.15 mm copper strip fixed to wall on batten or recess or chases or burried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation, etc. as required including porcelain insulator saddle at the spacing not exceeding 400mm including taking down old strip complete all as specified and directed by Engineer-in-Charge.
Earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6.0mm thick buried directly in ground, (Earth pit not less than 2.25 mtr deep below ground level) with top edge of plate not less than 1.5 mtr below normal ground level, connected to and including 4 mm dia galvanised earth lead wire by means of bolts, nuts, check nuts and washers of galvanised standard iron or steel all as specified or indicated in electrical plate no 3 of MES Part-I, including testing on completion including the material and labour of the following :-
(a) Excavation and earth work for drilling hole for electrode in any type of soil.
(b) PCC pit in cement concrete 1:2:4 type B-1.
(c) Precast RCC cover with suitable handle 40 mm thick in PCC 1:2:4 type B-1, reinforced with welded steel wire fabric weighing not less than 1.87 Kg/Sqm.
(d) Funnel with watering pipe of GI 20 mm nominal bore medium grade and copper lugs etc all as specified.
(e) 15 mm nominal bore light grade GI protection pipe 5 mtr long for protection of earthing lead from mechanical injury or tempering.
(f) Requisite quantity of common salt and charcoal.
(g) Testing of earthing.
Note : (a) On testing after completion of earthing, if the desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk and cost to the entire satisfaction of the Engineer-in-Charge. (b) The contractor shall quote his rate considering taking down cost of existing unserviceable earthing.
Earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6.0mm thick buried directly in ground, (Earth pit not less than 2.25 mtr deep below ground level) with top edge of plate not less than 1.5 mtr below normal ground level, connected to and including 32 x 6 mm galvanised earth strip by means of bolts, nuts, check nuts and washers of galvanised standard iron or steel all as specified or indicated in electrical plate no 3 of MES Part-I, including testing on completion including the material and labour of the following :-
(a) Excavation and earth work for drilling hole for electrode in any type of soil.
(b) PCC pit in cement concrete 1:2:4 type B-1.
(c) Precast RCC cover with suitable handle 40 mm thick in PCC 1:2:4 type B-1, reinforced with welded steel wire fabric weighing not less than 1.87 Kg/Sqm.
(d) Funnel with watering pipe of GI 20 mm nominal bore medium grade and copper lugs etc all as specified.
(e) 40 mm nominal bore light grade GI protection pipe 5 mtr long for protection of earthing lead from mechanical injury or tempering.
(f) Requisite quantity of common salt and charcoal.
(g) Testing of earthing.
Note : (a) On testing after completion of earthing, if the desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk and cost to the entire satisfaction of the Engineer-in-Charge. (b) The contractor shall quote his rate considering taking down cost of existing unserviceable earthing.
Material & labour for Earthing using Copper earth plate electrode of size 60cm X 60cm X3.15mm thick burried directly in ground vertically at a depth not less than 2.25 mtr below normal ground level with top edge of earth plate at a depth not less than 1.5 mtr below normal ground level, earth plate surrounded from all sides by 15 cm thick and packed layer of charcoal dust and common salt filling in alternate layers including refilling with good earth as specified and electrode connections by using Copper strip of size 20x3mm by means of bolts, nuts, check nuts and washers made of copper/brass and provision of GI pipe medium grade 40 mm dia for protection of earthing lead and 20mm dia for watering arrangement including funnel, wire mesh, CI pit cover and PCC chamber pit with PCC 1:2:4 type B-2 (including necessary excavation and earth work disposal of surplus soil to a distance not exceeding 50 mtr all as specified and shown on plate No 5 of SSR Part-I 2009.
(a) Excavation and earth work for drilling hole for electrode in any type of soil.
(b) PCC pit in cement concrete 1:2:4 type B-1.
(c) Precast RCC cover with suitable handle 40mm thick in PCC 1:2:4 type B-1, reinforced with welded steel wire fabric weighing not less than 1.87 Kg/Sqm.
(d) Funnel with watering pipe of GI 20 mm nominal bore medium grade and copper lugs etc all as specified.
(e) 40 mm nominal bore light grade GI protection pipe 5 mtr long for protection of earthing lead from mechanical injury or tempering.
(f) Requisite quantity of common salt and charcoal.
(g) Testing of earthing.
Note : (a) On testing after completion of earthing, if the desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk and cost to the entire satisfaction of the Engineer-in-Charge. (b) The contractor shall quote his rate considering taking down cost of existing unserviceable earthing.
Supply and fixing in repairs illuminated push button projecting head, red/green colour, 240 volts AC, complete all as specified and as directed. Make: Cat part No EGO3PDL of L&T or equal approved in HPL/ABB/Schnieder
Supply and fixing in repairs LED indicating lamp for LT panel board, Red/Yellow/Blue, surface mounted devices LED technology low power consumption <0.6W, low voltage glow protection (LVGP), SIL 240A-240V AC complete all as specified and as directed. Make: L&T/HPL/ABB/Schnieder
Supply and fixing in repairs aluminium bus bar suitable for any size and any capacity LT panel board complete all as specified and as directed.
Supply and fixing in repairs copper bus bar suitable for any size and any capacity LT panel board complete all as specified and as directed.
SCHEDULE 'A' PART-II (Schedule of credit) Credit amount of Rs (Refer schedule of credit) for retrieved material mentioned in Sch 'A' Part-II of Tender documents in PDF form will be deducted offline during acceptance of tender of lowest bidder.
Note: (1) The repair has to carried out as and when required basis and accordingly site will be available in piecemeal wise and as directed by Enginer-in-Charge in the Air Force station area
Mahajan Construction Co
M/s Mohan lal
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .