Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹28.8 LAccepted-AOC | L1 | Accepted-AOC Accepted being lowest | |
| 2 | L2₹31.2 L+₹60,400 (1.97%)Rejected-Finance | L2 | Rejected-Finance Rejected being other than lowest | |
| 3 | L3₹31.6 L+₹95,085 (3.11%)Rejected-Finance | L3 | Rejected-Finance Rejected being other than lowest | |
| 4 | L4₹34.5 L+₹3.9 L (12.6%)Rejected-Finance | L4 | Rejected-Finance Rejected being other than lowest | |
| 5 | L5₹34.7 L+₹4.0 L (13.2%)Rejected-Finance | L5 | Rejected-Finance Rejected being other than lowest |
Tender Value
₹30 L
EMD Value
₹60,000
Closing Date
21 Mar 2020, 6:00 pmClosed
Lt Col Vipin Kumar Singh
GE (S) Ahmednagar, Military Engineer Services, Ahmednagar- 414002
Repair / maint to external water supply lines, pumping machinery including motors pumps, NRVS, control valves, control panel, stabilizers and certain misc E/M work at ACC and S area under GE (S) Ahmednagar
2020_MES_329765_1
8689/E8
Open Tender
Miscellaneous Works
Item Rate
270 days
AHMEDNAGAR
Class D cat a (ii)
8 documents required · 8 mandatory
₹500
Garrison Engineer (South) Ahmednagar
₹60,000
Yes
12 May 2020
28 Feb 2020
23 Mar 2020
28 Feb 2020
21 Mar 2020
14 Mar 2020
28 Feb 2020 - 6 Mar 2020
Amount
Excavation in trenches not exceeding 1.5M wide and not exceeding 1.5M in depth for laying pipe line, replacing sluice valve etc and getting out in any type of soil complete all as specified and directed.
Returning filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm in any type of soil including making good of disturbed bituminous road / hard standing all as specified and directed.
Removing excavated soil to a distance not exceeding 50 Mtrs and depositing where directed at a level not exceeding 1.5 Mtr above the starting point all as specified and directed.
Cutting the existing bituminous road / PCC hard standing upto 75 cm in depth, 60cm in width and getting out excavated materials making good the damaged portion after laying of pipes by returning, filling in including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick and PCC 1:2:4 type B1 using 20mm graded stone aggregate upto 30 cm depth from top of the road complete all as specified and directed.
Repairs / rectification of leakages of existing GI tubing laid in trenches, floors or on walls, roof by replacing new fittings such as union, sockets, nipples, tees, elbows, reducers etc including threading, cutting, jointing complete all as specified and directed for the following sizes:-
15 mm bore
20 mm bore
25 mm bore
40 mm bore
50 mm bore
Taking up or down steel water tubing and connections including cleaning, removing chalkings and refixing same with complete new GI fittings such as unions, sockets, nipples, tees, elbows, reducers etc on wall, floors, in trench etc complete all as specified and directed for the following sizes:-
15 mm bore
20 mm bore
25 mm bore
40 / 50 mm bore
80 mm bore
GI tubing medium grade laid in trenches / floors or fixed to wall in any length with screwed and socket joints together with all galvanised GI fitting such as sockets, bends, elbows, tees, reducers, unions, bushes etc including jointing materials and testing complete all as specified and directed for the following size.
15 mm bore
20 mm bore
25 mm bore
40 mm bore
50 mm bore
80 mm bore
Gun metal or Bronze globe, screwed both ends suitable for GI tubing with side way operating GI lever handle including taking down old unserviceable valve of any type / make all as specified and directed for the following size.
15 mm bore
20 mm bore
25 mm bore
40 mm bore
50 mm bore
Repairs / rectification of leakages of existing CI/DI Main joint with lead wool/Run lead/Rubber gasket joint/mechanical joint ,caulking/ nutbolt tight etc..including complete old burning out lead/rubber gasket/ nut bolts and including any type of excavation/returning filling (any type of soil strata) etc. and making good all disturbed area to match the surrounding all as specified and directed for the following sizes of cables:-
80 mm bore
100 mm bore
150 mm bore
200 mm bore
250 mm bore
300 mm bore
600 mm bore
Taking up or down CI/DI water mains (including all fittings) with spigot and socket ends lead joints including burning out joints and recovering lead complete all as specified and directed for following sizes of pipes:-
80 mm bore
100 mm bore
150 mm bore
200 mm bore
250 mm bore
300 mm bore
600 mm bore
Re laying CI/DI pipe lines in good condition including cleaning internally, cutting to reruired length and jointing complete all as specified and directed for the following sizes:-
80mm bore
100 mm bore
150 mm bore
200 mm bore
250 mm bore
300 mm bore
600 mm bore
Cast iron pipe with spigot and socket ends, centrifugally cast, class B, conforming to IS: 1536-1976, ISI marked, in any length laid in trenches including testing of the pipe line complete complete all as specified and directed for the following size.
80 mm bore
100 mm bore
150 mm bore
200 mm bore
250 mm bore
300 mm bore
600 mm bore
Styrene Butadiene rubber Gasket (IS: 5382) joint suitable for Spigot ends DI pipes complete and pressure testing all as specified and directed for the following sizes of pipes:-
80 mm bore
100 mm bore
150 mm bore
200 mm bore
250 mm bore
300 mm bore
600 mm bore
CI /DI fittings and specials such as Bends (any type, radius and angle), Tapers any type (straight, bend, increasing, decreasing or double socket etc.), Tee pieces single branch, "Y" junction, double branch, cross (all sockets or socket and spigot), Collars, Caps, Plugs, Connecting pieces one end flanged and other end socketed or spigot ends or all socketed / spigot ends etc complete all as specified and directed for the following sizes of pipes:-
80 to 150 mm bore
200 to 600 mm bore
Run lead joints suitable for spigot and socket ends complete and pressure testing all as specified and directed or the following sizes of pipes:-
100 mm bore
150 mm bore
200 mm bore
250 mm bore
300 mm bore
Drilling, tapping, cast iron water mains (in position) for branch connection of 15 mm internal dia of pipe complete all as specified and directed.
All as per serial item No. 16.00 here-in-before but GI pipe 20 mm internal dia
Taking out leaking sluice valves any pattern/any size for repair,replacing grafite grease gland rope,nuts,bolts,washers etc. and refixing in same position complete all as specified and directed.
Taking out sluice valves, re-faceing, re-grinding, repacking stuffing box of sluice valve spindle of any make any type including taking apart and reassembling, re-fixing, replacing nuts, bolts, washers, gland rope complete all as specified and directed for the following sizes of sluice valves:-
80 mm bore
100 mm bore
150 mm bore
200 mm bore
250 mm bore
300 mm bore
Sluice valve cast iron long body both ends flanged as per IS-14846 and drilled with stainless steel spindle iron wheel head and as per pressure rating PN 1.6, Class I, ISI Marked alongwith nuts, bolts, washers , gaskets etc. fixed complete in replacement after dismantling and taking out old unserviceable sluice valve from valve chamber / trenches complete all as specified and directed for the following sizes:- MAKE:- BIR/Kirloskar/Kartar/Leader
80 mm bore
100 mm bore
150 mm bore
200 mm bore
250 mm bore
300 mm bore
Non return valve cast iron body flanged end including neophrene ball and by pass arrangement complete including suitable flanges, nuts, bolts, washers and rubbber gaskets, fixed in replacement after dismantling and taking down old unserviceable valve complete all as specifibed and directed for following sizes:- MAKE:- BIR/Kirloskar/Kartar/Leader
80 mm bore
100 mm bore.
150 mm bore.
200 mm bore
300 mm bore
Cast iron foot valve complete suitable as per existing of the following sizes including taking down old unserviceable all as specified & directed. MAKE:- BIR/Kirloskar/Kartar/Leader
Mechanical joint having 2 Nos CI / DI sockets, 1No CI / DI collar and 2 Nos Styrene Butadiene Rubber Gaskets alongwith nuts, bolts, washers , gaskets etc. including cutting CI / DI pipe and reducing to required length for insertion in position of Mechanical Joint complete all as specified and directed for the following sizes:-.
80 mm bore
100 mm bore
150 mm bore
200 mm bore
250 mm bore
300 mm bore
Cst iron air release valves with two air outlets, 50mm-80mm bore and fixing up in cast iron water supply mains (including pipe) as in replacement complete all as specified and directed.
Cast iron pipe 200 mm bore both end flanged, heavy duty for under ground sump/OHT including nutsbolts ,rubber washers etc. duly painted with two coats of synthetic enamel paint over coat of zinc chromate primer complete all as specified and directed.
Taking down existing foot valves complete of any condition / size / type / make and refixing the same after repair /replacement of inlet pipe/Plate/rubber/nut bolts.etc. complete all as specified and directed.
Float valve 20 mm bore, high pressure of PTMT with epoxy coated aluminium rod & high density plastic ball screwed for Iron or CPVC pipe, ISI Marked, including taking down old unserviceable valve of any type / make complete all as specified and directed. Make : Pryag or equivalent as approved by GE.
Labour only for removing the water meter of any size and refixing the same after cleaning and minor repairs as required complete all as directed.
Cement concrete for coping / support to CI pipe line / headers / Junctions / bends, above or below ground 1:3:6, type C1 using 20 mm graded stone aggregate including necessry form work as required and finishing the exposed surface fair and even complete all as specified and directed.
Valve chambers of size 1500 mm x 1500 x 1500 mm with excavation in any type of soil including necessary rteturning filling and remaval of surplus soil,10 cm thick PCC 1:4:8, type D 2 in foundations, brick work in cement mortar 1:6 , cement concrete 1:2:4 type B1 as in floors 75 mm thickand coping 25 mm thick including necessary form work etc complete with internal plaster 15 mm thick from top in cement mortar 1:4 and supply and fix MS sheet cover 3.00 mm thick hinged at both ends to frame of MS angle iron 40 mm x 40 mm x 6 mm with locking arrangements complete duly painted steel surfaces with two coats of synthetic enamel paint over one coat of red oxide primer includingdemolition of existing valve chambers complete all as specified and directed.
All as per serial item No. 29 here-in-before but valve chamber of size 1100 mm x 1100 mm x 900 mm
All as per serial item No. 29 here-in-before but valve chamber of size 900 mm x 900 mm x 900 mm
Air termination, single pointed, copper rod 12 mm dia and 300 mm long complete including fixing and testing on OH Tank complete all as directed.
Aluminium strip 25 mm x 3.15 mm with saddles and fixing screws etc for roof conductors and down conductors above ground including testing on OH Tank as directed.
Digital Level Indicator Device operating on single phase supply,l direct display in 150 mm size digit system in CM of water level of over head tank /Under ground sump ensuring alarm while water fall or rise at predetermined limit. 1 minute auto off alarm. The entire unit must operate through a compact electronic circuit, which must ensure reliable operation at 230 volts +/- 5% with reliable in digit display and alarm at low and high level UG/over head tank. The circuit must be housed in MS /Steel CRC sheet powder coated box with nylon moulded connection strips. The level system must resistance transducer, which unaffected by corrosion and other contacts available in water. The product must be controlled by micro switch (should not be sensor system). The whole unit must electronically controlled and the upper level and lower level indicator must be highly sensitive MICRO SWITCH. The complete unit must be in two parts. Each complete part must be fitted in MSCRC sheet box separately. One must be installed at OHT and second at Pump Hose with proper powder coating points. For installation the unit, required all other supporting items must be provide (GI wire, PVC pipe etc) with testing.
Flexible copper cable of 1.5 sqmm size from over head tank /under ground sump to pump house to provide for connection the both units of digital level indicator device complete all as specified and directed.
Aviation obstruction LED light 15 W fitting weather proof IP 565 cast aluminium toughened clear, transparent, borosilicate hard glass endless neoprent gasket incl cable enty ET 19 mm at base including all fittings and accessories as required complete all as directed by Engr-in-Charge. Cat Part No BGAV 302 LED of Make Bajaj or equivalent in make Havells / Philips
MCCB 400 Amps, 4 pole, 50 Hz 415 Volts, adjustable type with rupturing capacity 36 KA fixed in replacement complete all as specified and directed. Make : L&T/C&S/ Schneider.
MCCB 200 Amps, 4 pole, 50 Hz 415 Volts, adjustable type with rupturing capacity 36 KA fixed in replacement complete all as specified and directed. Make : L&T/C&S/ Schneider.
MCCB 200 Amps, 3 pole, 50 Hz 415 Volts, adjustable type with rupturing capacity 36 KA fixed in replacement complete all as specified and directed. Make : L&T/C&S/ Schneider.
MCCB 125 Amps, 3 pole, 50 Hz 415 Volts, adjustable type with rupturing capacity 36 KA fixed in replacement complete all as specified and directed. Make : L&T/C&S/ Schneider.
MCCB 160 Amps, 3 pole, 50 Hz 415 Volts, adjustable type with rupturing capacity 36 KA fixed in replacement complete all as specified and directed. Make : L&T/C&S/ Schneider.
Push botton (Red and Green colour) switch of existing size and shape, fixed in replacement complete all as specifiedand as directed.
Galvanised iron strip 32 mm x 6 mm with saddles and fixing screws etc. for roof conductors and down conductors buried in ground complete all as specified and directed.
Repair/maintainance/servicing and checking thoroughly defective centrifugal pump set of capacities 100/90 HP DSM 5 by dismantling of pump set at site and checking inspection and replacement of unserviceable spares as required or as directed by Engr-in-Charge.
Repair/maintainance/servicing and checking thoroughly defective centrifugal pump set of capacities 25 HP by dismantling of pump set at site and checking inspection and replacement of unserviceable spares as required or as directed.
Repair/maintainance/servicing and checking thoroughly defective centrifugal pump set of capacities 60/75 HP DSM 100/36 by dismantling of pump set at site and checking inspection and replacement of unserviceable spares as required or as directed by Engr-in-Charge. Note for item No 44 & 46 :- (a) Spares shall be measured and paid separately under relevant items. (b) The work involves proper alignment after repairing testing, recommissioning the pump set to the entire satisfaction of Engr-in-Charge, Job should be carried out by the authorised persons.
FASD starter suitable for 100/90 HP electric motor including SPP , OLP relay ,timer of suitable range complete model ML-6 including removing old starter and reconnecting incomer and out going connections with proper lugs complete all as specified and diercted. Make : L&T/ S&S/BCH / Cromption.
FASD starter suitable for 60 to 75 HP electric motor including SPP , OLP relay ,timer of suitable range complete model ML-4 including removing old starter and reconnecting incomer and out going connections with proper lugs complete all as specified and directed. Make : L&T/ S&S/BCH
FASD starter suitable for 25 HP electric motor including SPP , OLP relay, timer of suitable range complete model ML-2 including removing old starter and reconnecting incomer and out going connection with proper lugs complete all as speciied and directed. Make : L&T/ S&S/BCH
Supply and replacement of the following spares for DSM 5 100/90 HP Pump set :-
Impeller CI stage -I
Impeller CI stage -II
Pump shaft C-40 including sleeves
Water retaining (Deflector) Ring DE/NDE
Spilt Linter Ring CI DE/NDE
Cartridge for bearing DE/NDE
Shaft Sleeve CI DE/NDE
Stuffing box bush (Throat) CI DE/NDE
Gland plate with gland packing CI
Set of gasket
Set of 'O' ring
Wear ring CI
All as per item No. 52 here-in-before but DSM 4 60/75 HP Pump Set :-
Impeller CI stage -I
Impeller CI stage -II
Pump shaft including sleeves
Water retaining (Deflector) Ring DE/NDE
Linter Ring CI DE/NDE
Cartridge for bearing DE/NDE
Shaft Sleeve CI DE/NDE
Stuffing box bush (Throat) CI DE/NDE
Gland plate with gland packing CI
Set of gasket
Set of 'O' ring
Wear ring CI
All as per item No. 52 here-in-before but 25 HP Pump Set :-
Impeller CI stage -I
Impeller CI stage -II
Pump shaft including sleeves
Water retaining (Deflector) Ring DE/NDE
Linter Ring CI DE/NDE
Cartridge for bearing DE/NDE
Shaft Sleeve CI DE/NDE
Stuffing box bush (Throat) CI DE/NDE
Gland plate with gland packing CI
Set of gasket
Set of 'O' ring
Wear ring CI
Dismantling and taking down unserviceable electric motor of 100/90 Hp capacity of Pump set. from foundation and transportation to workshop for repairing, opening and rewinding with new super enamelled copper insulated winding wire as per existing gauge of copper wire, winding with insulating material, varnishing heating etc and reassembling, transporting back to site of work e installing on existing foundation including proper alignment and testing complete all as specified and directed by Engr - in -charge. Note :- All disturbed surface shall be made good to match the souroundig
Dismantling and taking down unserviceable electric moto 60 capacity of Pump set. from foundation and transportation to workshop for repairing, opening and rewinding with new super enamelled copper insulated winding wire as per existing gauge of copper wire, winding with insulating material, varnishing heating etc and reassembling, transporting back to site of work e installing on existing foundation including proper alignment and testing complete all as specified and directed by Engr - in -charge. Note :- All disturbed surface shall be made good to match the souroundig
Dismantling and taking down unserviceable electric moto 75 capacity of Pump set. from foundation and transportation to workshop for repairing, opening and rewinding with new super enamelled copper insulated winding wire as per existing gauge of copper wire, winding with insulating material, varnishing heating etc and reassembling, transporting back to site of work e installing on existing foundation including proper alignment and testing complete all as specified and directed by Engr - in -charge. Note :- All disturbed surface shall be made good to match the souroundig
Dismantling and taking down unserviceable electric moto 25 capacity of Pump set. from foundation and transportation to workshop for repairing, opening and rewinding with new super enamelled copper insulated winding wire as per existing gauge of copper wire, winding with insulating material, varnishing heating etc and reassembling, transporting back to site of work e installing on existing foundation including proper alignment and testing complete all as specified and directed by Engr - in -charge. Note :- All disturbed surface shall be made good to match the souroundig
Contactor 3 Pole power contactor TYPE -MNX -45 conforming to IS/IEC 60947-4-1and IEC 6947-1 Amp rating 85 Amps (MNX45) along with Add on TOP2 NO+ 2 NC or Add on side, fixed in replacement in existing FASD starter complete all as specified and directed. Make :- L&T Cat No 907074 or equivalent in Make: Siemens, Crompton.
Supply and fix in repairs in existing FASD contactor 3Pole power contractor TYPE -MNX confirming to IS/IEC 60947-4-1and IEC 6947-1 Amp rating 85 Amps (MNX32) along with Add on TOP2 NO+ 2 NC or Add on side, fixed in replacement in existing FASD starter complete all as specified and directed. Make :- L&T Cat No ST- 907074 or equivalent in Make Siemens,Crompton
Contractor 3 Pole power contactor TYPE -MNX confirming to IS/IEC 60947-4-1and IEC 6947-1 Amp rating 85 Amps (MNX70) along with Add on TOP2 NO+ 2 NC or Add on side fixed in replacement in existing FASD starter complete all as specified and directed. Make :- L&T Cat No 907074 or equivalent in Make Siemens,Crompton
Spare contact kit and spare coil as per L&T Cat No SS-95311 and SS91258 or equivalent in Siemens/Cromption suitable for ML-4 starter as in replacement complete all as specified and directed.,
Spare contact kit and spare coil as per L&T Cat No SS-95313 and SS91258 or equivalent in Siemens/Cromption suitable for ML-6 starter as in replacement complete all as specified and directed.,
Taking out old unserviceable contactor ML-2 TP from panel board and supply and fix power contactor ML-2 TP 70 Amps capacity suitable for operation on 415 Volts 50 Hz AC supply complete all as specified and directed.
Taking out old unserviceable contactor ML-3 TP from panel board and supply and fix power contactor ML-3 TP 70 Amps capacity suitable for operation on 415 Volts 50 Hz AC supply complete including cables of existing size complete all as specified and directed.
Taking out old unserviceable contactor ML-4 TP from panel board and supply and fix power contactor ML-4TP 70 Amps capacity suitable for operation on 415 Volts 50 Hz AC supply complete all as specified and directed.
Taking out unserviceable contactor ML-6 TP from panel board and supply and fix power contactor ML-6 TP 70 Amps capacity suitable for operation on 415 Volts 50 Hz AC supply complete all as specified and directed.
Replacement of ball bearing of following sizes including taking out old unserviceable bearing complete all as specified and directed:-
Ball bearing 6307 (Single ball) Make : SKF/NBC
Ball bearing 6308 (Single ball) Make : SKF/NBC
Ball bearing 6309 (Single ball) Make : SKF/NBC
Ball bearing 6310 (Single ball) Make : SKF/NBC
Ball bearing 6311 (Single ball) Make : SKF/NBC
Ball bearing 6313 (Single ball) Make : SKF/NBC
Ball bearing 6314 (Single ball) Make : SKF/NBC
Ball bearing 6316 (Single ball) Make : SKF/NBC
Ball bearing 3309 (Double ball) Make : SKF/NBC
Ball bearing 3307 (Double ball) Make : SKF/NBC
Replacement of coupling bushes with studs of existing type and size suitable for 90/100 HP motor complete all as specified and directed.
Replacement of coupling bushes with studs of existing type and size suitable for 60/75 HP motor complete all as specified and directed.
Replacement of love-joy coupling, (including star bushes) made out of MS, complete suitable for 60/75 HP pump Set. Including Rubber star bush, metal filling existing Shaft of motor/ pump and re- grinding, making key slot etc and testing with zero level allingment complete all as specified and directed.
Replacement of love-joy coupling, (including star bushes) made out of MS, complete suitable for 100/90 HP pump Set. Including Rubber star bush, metal filling existing Shaft of motor/ pump and re- grinding, making key slot etc and testing with zero level allingment complete all as specified and directed.
Replacement of love-joy coupling, (including star bushes) made out of MS, complete suitable for 25/30 HP pump set. Including rubber star bush, metal filling existing shaft of motor/ pump and re- grinding, making key slot etc and testing with zero level allingment complete all as specified and directed.
Repairs of foundation of motor pump set of 100/90/75/60 HP by removing and taking out pump motor from foundation by unscrewing the nuts bolts and keeping away, cutting, welding and machining with flat iron or channel of 50 x 6 mm flat iron and channel MC 75 to MC 150 size as required for strengthing the foundation plate, cutting and replacing / shifting and welding at proper places on motor foundation, replacement of foundation nut bolts, washers, with accurate realignment of motor with pump to avoid vibration and smooth running of pump on full load, testing and commissioning complete all as directed.
Single phase preventor suitable for 100/90/75/60/25 HP Pump set starter 415/440 V 50 Hz , fixed in replacement complete all as directed.
ML6/ML4/ML2 stater timer of suitable/existing capacity for 100/90/75/60/25 HP Pump set starter 415/440 V 50 Hz , fixed in replacement complete all as directed.
Rubber matting 1100 Volts grade of size 2.0m x 1.0m x 10 mm thick conforming to IS, ISI marked duly tested by manufacturers, as in replacement complete all as directed.
Pressure gauge (complete set etc. GI bend pipe, nipples, operating switch / valve) of capacity 0-100 kg as per sample suitable for 25 to 100 HP pump set, fixed in replacement complete all as specified and directed.
On load change over switch 415 Volts in sheet metal enclosures three phase four pole 400 Amps capacity, fixed in replacement complete all as specified and directed. Make : Havells/ L &T/ Siemens
Repair / Servicing to voltage stabilizers 3 phase 4 wire system, 160 to 300 KVA by at site by opening carefully from top, taking out coils / connections, cleanig coils checking defective joints / soldering / jointing, re- assembling and testing on full load and making fully servicable including spray painting with supper enamelled paint of colour as directed by EIC, complete all as specified and directed.
Topping up / replacement of insulating oil of stabilizer chamber with new insulating / transformer oil upto the required level in any type and capacity of the voltage stabilizer complete all as directed by Engr-in-Charge. Note : Insulating / transforemer oil brought by the contractor at site must be in seal packed in drum having ISI mark as per IS-335 / 1983. Make : Savita / Asian.
Taking down carefully submersible pump 10 HP to 15 HP from well/borewell along with HDPE Pipe , cable , clamps and dismantaling opening and servicing , by replacing unserviceable parts such as impeller , bushing , thrust bearing waterseal / coupling etc , re- assembling , installing and testing complete all as directed by Engineer- in- Charge. Note : Spares required during servicing will be measured and paid separately
Thrust bearing suitable for 10 HP To 15 Hp including lathe machine work , fixed in replacement complete all as directed.
SS Coupling to connect DE and NDE ends of motor and pumps with locking Pins suitable for 10 to 15 HP motor, fixed in replacement complete all as directed.
SS Coupling / adopter suitable to connect HDPE pipe to pump outlet with MS Clips, fixed in replacement complete all as directed.
Copper flexible cable flat 3 core 1100 volts grade PVC Insulated 2.5 Sq mm including water proof joint , fixed in replacement complete all as directed. Make:- Havells/Polycab/Gloster
Dismantling and taking down unserviceable electric Sumersible pump 10-15HP Hp capacity Pump set. from well/borewell and transportation to and from for repairing and rewinding with existing size copper wire, winding with insulating material and warnishing heating etc and reassembly installing on existing foundation including proper alignment and testing complete all as specified and directed
DOL starter in sheet steel encloser WP 3 phase 440 volts 50Hz MU G -11 Model fixed to angle iron stand 1.00 mtr above ground level grouted 45 cm in grounf with PCC 1:2:4 type B1. fixed in replacement complete all as directed.
Repair / Servicing to ACB 3 phase, TP 415 V 400/600 Amp by replacing unserviceable spares like contacts, relays etc and other minor spares and testing complete all as directed.
Fan suitable for 25 HP to 100 HP induction motor as per existing , fixed in replacement complete all as directed.
Coupling protection / guard cover fabricated out of 3 mm thick MS sheet cover fixed flat iron 40 X 6 mm all around iron frame work with fixing arragement complete and duly painted with two coats of anticorrosive bituminous paint over a coat of anticorrosive bituminous primer complete all as specified and directed .
First aid Safety charts duly written with instructions as directed by JE/Engineer-in-charge and fixed all as diercted.
Replacement of Notice board of size 1500 mm x 1200 mm made of white laminated board having aluminium frame alround and two/four hooks on back/top for hanging complete all as directed.
Repair/ replace wall mounting lepose high grade metal first aid box with 2 keys, dimensions 30 cm x 25 cm x 7.5 cm complete all as specified and dircted. Note :-First aid kit shall contain medicines such as paracetamole , liquid detole,betadine, bandage and any other medicine as directed.
Replacement of LT Panel wiring with new wiring using new cables of same size as per makes given here-in-after including replacement of lugs, thimbles etc complete all as directed .
Earthing complete with galvanized steel earth plate electrode 60 cm X 60 cm X 6.3 mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of plate not less than 1.5 mtr below ground level connecting to the GI strip 32 x 6mm, by means nut bolt, nuts, check nuts and washer of the GI Earth wire protected by provision of GI light grade pipe 15 mm, GI light grade 20 mm bore pipe for watering perforated at bottom 1.75 mtr long placed on top edge of earth plate, common salt and charcoal filling, taste point made out of phosphorus bronze with fixing arrangement, funnel, wire mesh and earth work in hard/dense soil, returning filling in and removal of surplus soil to a distance not exceeding than 50 mtr, all as per electric plate No 3 of SSR Part I 2009 and connection to earth test point including testing complete all as specified and directed.
Replacement of LT Pannel CT coils as per exiting size and make complete all as directed.
Replacement of R Y B phase indicators complete set of make as per existing complete all as directed.
BHAVIN INFRA
AZAD SERVICES
Arihant Construction
OM SAI ASSOCIATES
MS. N.R. PENTA AND SONS
M/s Jeet Construction
United Enterprises
M/s Meher Construction
KAMINS CARE
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .