Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Tender Value
₹97.1 L
EMD Value
₹1.7 L
Closing Date
28 Oct 2026, 5:00 pm
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
CWE AF SRINAGAR
CWE AF SRINAGAR
PROVN OF CERTAIN AIR RAID SHELTERS AT 1 WG AF STN SRINAGAR
2026_MES_790837_1
CWE(AF)SGR/SRG-30/2026-27
Open Tender
Civil Works
Lump-sum
180 days
GE AF SRINAGAR
Please refer Tender documents.
8 documents required · 8 mandatory
₹1,000
Yes
GE AF SRINAGAR
₹1.7 L
Yes
23 Sept 2026
23 Sept 2026
2 Nov 2026
23 Sept 2026
28 Oct 2026
22 Oct 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Sch 'A' Part-I (Building Works)
Provn of certain Air Raid Shelters permanenet specification of all as per drawing and directed by Engineer-in-Charge.
Note: Prepriced at par with SSR Part-II (2020) at Serial Page No 20 and contractor has to quote the estimated amount under Col 6 | 1 | Lumpsum | 12,71,300 | ₹12,71,300 |
| 2 | Sch 'A' Part-II (Sec-I) (Internal Electric Supply)
Note: Prepriced at par with SSR Part-II (2020) at Serial Page No 22 and contractor has to quote the estimated amount under Col 6 | 1 | Lumpsum | 6,21,649.7 | ₹6,21,649.7 |
| 3 | Sch 'A' Part-II (Sec-II) (Internal Electric Supply)
Note: This schedule is not pre priced by MES and the pre priced rate indicated as "Rs.0.00" under Col 5 signifies this fact only. | - | - | - | - |
| 4 | Supply & Fix Wall Mounted fan AC single phase 230 volts of size 300mm swap 1360 rev/min with blades and frame and louvers complete all as specified and directed. | 40 | Each | - | - |
| 5 | Sch 'A' Part-III ( Road, Path & Culvert)
Note:- Prepriced at par with SSR Part-II (2020) at Serial Page No 24 and contractor has to quote the estimated amount under Col 6 | 1 | Lumpsum | 4,99,222.52 | ₹4,99,222.52 |
| 6 | Sch 'A' Part-IV (Sec-I) ( External Electric Supply)
Note:- Prepriced at par with SSR Part-II (2020) at Serial Page No 26 and contractor has to quote the estimated amount under Col 6 | 1 | Lumpsum | 9,05,208 | ₹9,05,208 |
| 7 | Sch 'A' Part-IV (Sec-II) ( External Electric Supply)
Note:- This schedule is not pre priced by MES and the pre priced rate indicated as "Rs.0.00" under Col 5 signifies this fact only. | - | - | - | - |
| 8 | Suppl and laying unreinforced pre cast concerate cable cover confirming to IS: 5820 with minimum average breaking load capacity 200 KGs for unreinforced covers , class LV Type 1, flat size 250mmx 150mmx40mm complete all as specified and directed | 7,000 | Each | - | - |
| 9 | Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified LT feeder pillar box (KIOSK) out door type, floor mounted,compertmantalised suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, dust and vermin proof, made of 3.15mm CRCA MS sheet with digital Volt meter, Ammeter, with CTs ,Led lamps RYB for all incomers & outgoings MCCBs are to busbar spadles to fitted complete base frame of 50x50x6mm angle iron, powder coated, having front and rear openeable hinged double door shutters with aprons for cable entry and locking arrangement complete with following :- Incoming (a) MCCB 100 amps,4 pole, 25 KA , with adjustable thermal over load release 50 Hz, 415 volts grade - 01 Nos. (b) Bus bar electrolytic grade Aluminium and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 200 Amp,4 pole, not less than 75 cm long mounted on insulators 01 set | 5 | Each | - | - |
| 10 | Supply and fix Ligtning lightining conductor/Protection Rod with following specifications:-
a) Height of primary terminal = 1000mm
b) Diameter of Rod = 22-25 mm
c) Tip of Rod = Tapered tip/Sharp Edge
d) Scondary Terminal = Shall attached to bowl
e) Dimension of Bowl = 125 mm wide x 4mm thick
f) Direction = Facing the primary terminal on 4 sides
g) Electrolyte = Copper
h) Additional protection = Nickel plated tip for corrosion resistance & side flash capture
i) Confirmation = IEC 62305
j) Weight = 6.0 Kgs
k) Construction :- Protection system shall consist of one primary and four secondary air terminals. The Primary air terminal is a vertical conductive rod having a sharp tip at one end. The secondary air terminal (4 No) formed on a bowl shaped circular disc are fixed on vertical rods. further, the actual points of the secondary terminals are spaced and placed in such a way to receive the maximum side flashes. Work shall be excuted all as specified & directed by Engr-in-Charge.
l) ISO Certification = ISO 9001 : 2015
m) Current Capacity (Tested) = 40 Ka
n) Dia of SFCH (mm) = 125
o) Base Plate dimension (mm) = 150 x 150 x 6
Make:- Ashlok(Zeus)/Baron/Macmate | 5 | Each | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.48 MB
TENDER30.pdf
Tender Documents • 1.25 MB
SCHEDULES30.pdf
Additional Documents • 2.83 MB
DRAWING30.pdf
Additional Documents • 7.25 MB
BOQ_886571.xls
BOQ • 0.29 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .