Executive Engineer (E)
BSNL ED PB
Providing Earthing, Lightning arrestor and aviation light for various BTS under phase IX.2 project, Port Blair (Phase-IV)
2023_BSNL_173256_1
42/ED/PB/2023-24, dated. 04.11.2023
Open Tender
Electrical Works
Item Rate
90 days
Port Blair
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
Yes
Accounts Officer Cash
₹9,918
Yes
16 Nov 2023
4 Nov 2023
16 Nov 2023
4 Nov 2023
15 Nov 2023
4 Nov 2023
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories with 25 Kg bentonite compound as required.
Earthing with Galvanized Iron Earthing Electrode, 1 Metre Length and 40mm diametre, Contains 1 metre of GI Strip 40mm Size, Electrode filled with bentonite clay, and filling the pit with 25 Kg bentonite compound, etc, providing masonry enclosure with cover plate, complete as required. (As per RDSO specification)
Providing masonry enclosure with cover plate having locking arrangement and 20mm dia GI watering pipe of 2.7 metre long for earthing pit, etc as required.
Providing and fixing of lightning conductor finial, made of 25 mm dia 300mm long, G.I. tube, having single prong at top, with 85mm dia 6mm thick G.I. base plate including holes etc. complete as required
Jointing copper / G.I. tape (with another copper/ G I tape, base of the finial or any other metallic object) by riveting / nut bolting/ sweating and soldering etc as required.
Providing and fixing G.I. tape 25 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required. (For horizontal run)
Providing and fixing G.I. tape 25 mm X 3 mm thick on parapet or surface of wall for lightning conductor complete as required. (For vertical run)
Providing and fixing testing joint, made of 25 mm X 3 mm thick G.I. strip, 125 mm long, with 4 nos. of G.I. bolts, nuts, chuck nuts and spring washers etc. complete as required.
Providing and fixing 25 mm X 6 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
Providing and fixing 25 mm X 6 mm G.I. strip on surface or in recess for connections etc. as required
SITC of LED type aviation light made of cast aluminum base, comprising of dome shaped, thick clear glass cover, cylindrical shaped, consist of LED lamps to give a light intensity not less than 10 candelas i/c S/F of power pack, with photo sensor for switching on and off, pdg necessary MS frame & tube for fixing the fitting on top of the tower, connection etc complete as reqd. (Make: BSNL approved make)
Supplying of PVC insulated and sheathed armoured 2 core 1.5 sq.mm copper conductor 1.1 KV grade cable and laying the same on surface or in recess as reqd.(BSNL approved make).
Supplying and making end termination with brass compression gland for PVC insulated and sheathed copper conductor cable of 1.1 KV grade of size 2 core 1.5 sq.mm as reqd.
K. M. ENTERPRISE
stage.html
html • 0.02 MB
finance_189790.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .