| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹37.5 LAccepted-AOC 6 RAILWAY STATION ROAD ONKAR INDUSTRIES GULAMALI PURA BAHRAICH UTTAR PRADESH 271801 | BAHRAICH | UTTAR PRADESH | 271801 | L-1 | Accepted-AOC Being L-1 | |
| 2 | L-2₹40.7 L+₹3.2 L (8.49%)Rejected-Finance NEAR MES FILTER PLANT SANGOOR UDHAMPUR J K 182101 | UDHAMPUR | UDHAMPUR | J K | 182101 | L-2 | Rejected-Finance Other than L-1 |
Tender Value
₹38.3 L
EMD Value
₹76,560
Closing Date
6 Nov 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Sh A K Dubey IDSE SE CWE
Military Engineer Services, Commander Works Engineer, Udhampur, PO - Garhi, Udhampur-182121
Addn Altn to the Electrical Distribution System at CPH under GE Utility Udhampur
2021_MES_478992_1
CWE/U(U)-62/2021-22
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Udhampur
7 documents required · 7 mandatory
₹500
GE U Udhampur
₹76,560
Yes
12 Nov 2021
30 Sept 2021
8 Nov 2021
30 Sept 2021
6 Nov 2021
25 Oct 2021
60 days
Amount
Supply, installation, testing and commissioning of indoor type vaccum circuit breaker (Incommer Panel ) 11 KV, 800 Amp, 3 Phase, 3 wire, 50 Hz, having a rupturing capacity of 350 MVA at 11 KV, 26.3 KA breaking capacity for 3 sec, totally enclosed with extended Copper bus bar of 800 Amps for each phase, metal clad, indoor extensible type, flush front, horizontal isolation horizantal draw out type with Electrical and Mechnical interlock and automatic safety shutter gear incl padlocking arrangement, isolation plugs, assembly of 3 vaccum interrupters (Should be VCB manufacturer's own make), with each pole individually encapsulated by epoxy insulations to make it dust proof and self-aligning finger type isolating contacts. Truck having integral racking with necessary interlocks (for insertion and removing of VCB), manual and automatic motar charged independent spring closing/triping, trip free opearting mechanism with closing and triping push buttons and mechnical breaker including all protection, indication Operation, monitoring and control and accessories as per the specification. (a) Power pack (230V AC to 110V DC - 1 No ) (b) Closing & triping coil of VCB should be of continious rating to achieve minimal failure. (c) Resin cast type CT having Ratio :400-200A/1-1 A, Core1: 5P20, 5VA; Core 2: 0.5, 5VA (for metering )
Item No 1 (contd......) (k) LR & TNC Switch. (l) Indication lamp- CB ON/OFF, Spring charge, auto trip, TCS healthy etc. (m) Spec heaters. (n) Castel lock for all fedder, interlock between incomer and buscoupler. NOTE :- (i) Factory testing of equipment shall be carried out by an officer detailed by the Accepting officer at the factory premises. Contracto shall facilitate the charges for testing officer (Tro/ Fro including loadging / boarding ) all the testing arrangements with the manufactures at no extra cost. (ii) 3 Sets of Literature,Maintenance Manual,Operatig tools required for the operations shall be supplied alongwith VCB's and rates are included in above items.
Supply, installation, testing and commissioning of indoor type vaccum circuit breaker (Bus coupler Panel including attachment Bus riser ) 11 KV, 800 Amp, 3 Phase, 3 wire, 50 Hz, having a rupturing capacity of 350 MVA at 11 KV, 26.3 KA breaking capacity for 3 sec, totally enclosed with extended Copper bus bar of 800 Ampsfor each phase, metal clad, indoor extensible type, flush front, horizontal isolation horizantal draw out type with Electrical and Mechnical interlock and automatic safety shutter gear incl padlocking arrangement, isolation plugs, assembly of 3 vaccum interrupters(Should be VCB manufacturer's own make), with each pole individually encapsulated by epoxy insulations to make it dust proof and self-aligning finger type isolating contacts.Truck having integral racking with necessary interlocks (for insertion and removing of VCB), manual and automatic motar charged independent spring closing/triping , trip free opearting mechanism with closing and triping push buttons and mechnical breaker including all protection, indication Operation, monitoring and control and accessories as per the specification. (a) Power pack (230V AC to 110V DC - 1 No ) (b) Closing & triping coil of VCB should be of continious rating to achieve minimal failure. (c) Resin cast type CT having Ratio : 400-200A/1-1 A, Core1: 5P20, 5VA; Core 2: 0.5, 5VA(for Bus coupler)
Item No 4 (contd......) NOTE :- (i) Factory testing of equipment shall be carried out by an officer detailed by the Accepting officer at the factory premises. Contracto shall facilitate the charges for testing officer (Tro/ Fro including loadging / boarding ) all the testing arrangements with the manufactures at no extra cost. (ii) 3 Sets of Literature,Maintenance Manual,Operatig tools required for the operations shall be supplied alongwith VCB's and rates are included in above items.
Supply, installation, testing and commissioning of indoor type vaccum circuit breaker (outgoing Panel ) 11 KV, 630 Amp, 3 Phase, 3 wire, 50 Hz, having a rupturing capacity of 350 MVA at 11 KV, 26.3 KA breaking capacity for 3 sec, totally enclosed with extended Copper bus bar of 800 Ampsfor each phase, metal clad, indoor extensible type, flush front, horizontal isolation horizantal draw out type with Electrical and Mechnical interlock and automatic safety shutter gear incl padlocking arrangement, isolation plugs, assembly of 3 vaccum interrupters (Should be VCB manufacturer's own make), with each pole individually encapsulated by epoxy insulations to make it dust proof and self-aligning finger type isolating contacts .Truck having integral racking with necessary interlocks (for insertion and removing of VCB), manual and automatic motar charged independent spring closing/triping,
Item No 7 (contd......) (h) Multifunction meter of Acc class 0.5, having facility to see KW, KVA, KVR ,PF, KWH, KVARH, KVAH, A, V etc. (i) Master trip relay. (j) Trip circuit supervision relay ( feature of numerical relay) (k) LR & TNC Switch. (l) Indication lamp- CB ON/OFF, Spring charge, auto trip, TCS healthy etc. (m) Space heaters. (n) all fedder, interlock between incomer and buscoupler. NOTE :- (i) Factory testing of equipment shall be carried out by an officer detailed by the Accepting officer at the factory premises. Contracto shall facilitate the charges for testing officer (Tro/ Fro including loadging / boarding ) all the testing arrangements with the manufactures at no extra cost. (ii) 3 Sets of Literature,Maintenance Manual,Operatig tools required for the operations shall be supplied alongwith VCB's and rates are included in above items.
Supply lay test and commissiong for XLPE insulated, armoured, aluminium conductor cable, 11000 volts grade, heavy duty, cross sectional area 120sq mm ,3 core, laid in trenches/ducts/through pipe complete all as specified and directed.
Cable jointing kit for 11 KV grade cable for out door termination heat shrinkable type joint complete with jointing material and acessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120sq.mm
M&L for providing earthing with Copper earth plate electrode 600 x 600 x 6 mm buried directly in ground (earth pit not less than 2.25 M deep below ground level) with top edge of the earth plate not less than 1.5 M below ground level connected to Copper strip 32 x 6mm thick for earthing lead fixed by means of nuts,bolt,washers etc connected to earth test point complete all as specified in electrical plate No 3 of SSR-2009 part 1, including necessary excavation and earth work in any type of soil, comman salt, charcoal dust, 40 mm dia light grade GI pipe for protection to earth lead, GI water pipe 20mm dia with funnel &wire mesh, PCC pit with CI cover and frame etc complete all as specified and directed by Engr-in-Charge. Note: - (i) All the joints shall be made with welding to get proper conductivity. (ii) On testing after completion of earthing, if desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk & cost to the entire satisfaction of Engineer-in-charge.
FANGALIA TRADERS
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .