Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹23.0 LAccepted-AOC 2ND FLOOR PLOT NO 338 UDHYOG VIHAR PHASE IV GURUGRAM 122015 HARYANA | GURUGRAM | HARYANA | 122015 | L1 | Accepted-AOC L1 | |
| 2 | L2₹24.1 L+₹57,110 (2.43%)Rejected-Finance 11 26 BHAGWANPURA KISHANGARH CHANDIGARH | L2 | Rejected-Finance L2 | |
| 3 | L3₹24.7 L+₹1.1 L (4.83%)Rejected-Finance 209 210 AGGARWAL TOWER PLOT NO 2 SECTOR 5 ROHINI NORTH WEST DELHI DELHI 110085 | DELHI | NORTH WEST DELHI | DELHI | 110085 | L3 | Rejected-Finance L3 | |
| 4 | Not Admitted-Fee/PreQual/Technical C O SH JITENDER CHAUHAN 542 L MODEL TOWN PANIPAT HARYANA 132103 | PANIPAT | PANIPAT | HARYANA | 132103 | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
₹21.2 L
EMD Value
₹42,500
Closing Date
12 Jun 2024, 5:30 pmClosed
NAVIN KUMAR
ED - Gurgaon
Construction of Auditorium at Ballabgarh. (Pdg. Fire Alarm and PA system only)
2024_HRY_372939_1
20248C5F0CA2 78A0 473F BE37 4D496214A6B8664BAR
Open Tender
Electrical Works
Works
30 days
Faridabad (MC)
2 documents required · 2 mandatory
₹1,000
₹42,500
Yes
9 Jan 2025
5 Jun 2024
13 Jun 2024
5 Jun 2024
12 Jun 2024
5 Jun 2024
5 Jun 2024 - 6 Jun 2024
Amount
SITC of Micro processor based 2 wire fault tolerant, networkable type fire alarm / detection control panel ( having nos. of 2 loops to suit minimum 20% extra over the nos. of fire detectors. The panel shall be able to give location of all fire / fault conditions of addressable units via the address codes. Further, the panel must be able to automatically switch ON/OFF respective control module when ever any alarm is triggered. The panel shall have rectifier, loop cards, minimum 160 character L C D unit/ 5.7’’TFT to indicate Fire / Fault Signal with address and analog output, external/inbuilt printer to log all fire or fault events complete in all respects. The Panel Shall be sheet Steel power coated, sealed to IP30. The Panel shall have 20 Zones with individual LED Indicators, expandable to 80LED Indicators. The Panel shall have 3 Serial Ports. The panel shall have a built in power supply and battery charger along with maintenance free 24 AH,2 x 12 volt SMF lead acid batteries capable of running for a minimum of 24 hours with battery charger complete as required. And conforming to BS5839 standards and Duly Approved by EN 54/UL/VDS/ as per specifications complete in all respect up to the entire satisfaction of Engineer-in – charge of work Makes : Bosch FPA 1000/ Siemens cerberus/ GST 200 (EN)
Supply Installation Testing & Commissioning of Celling Mount Speaker with Plastic Mount or without mount as per site requirement for operation 6 Watts Make Honeywell/ BOSCH/Henrich
Supply Installation Testing & Commissioning of addressable multisensor detector with a combination of Optical and Thermal including mounting base, auto addressing feauture as required. Detetctor should have 2 as per NFPA 72 style 7 wiring requirements (one for incoming and one for outgoing line) for maintaining operational availability of all elements in the loop in the event of a short circuit and to meet style 7 requirements. High resistance to electromagnetic effects in accordance with EFSG agreement EFSG/F/97/005 .Detector should monitor Electromagnetic interference and report to the panel - current and average values. EMC safety for detector shall be 50 V/m. Shall be EN54/ VDs/UL certification. (Detectors without Inbuilt Isolators may be considered with an additional Isolator Module after 20 devices) Make: Bosch / Siemens Cerberus / GST
Supply, Installation, Testing & commissioning of addressable Heat detector with fixed and rate of raise feature including mounting base with LED etc. complete as required. Each Detector should have 2 as per NFPA 72 style 7 wiring requirements (one for incoming and one for outgoing line) for maintaining operational availability of all elements in the loop in the event of a short circuit and to meet style 7 requirements. High resistance to electromagnetic effects in accordance with EFSG agreement EFSG/F/97/005 .Detector should monitor Electromagnetic interference and report to the panel - current and average values. EMC safety for detector shall be 50 V/m. Shall be EN54/ VDs/UL certification. (Detectors without Inbuilt Isolators may be considered with an additional Isolator Module per detector) Make: Bosch / Siemens Cerberus / GST
Supply Installation Testing & Commissioning of intelligent Analog Addressable type Manual Call Point having Surface or flush mounting option fully compliat to EN 54 having Rotary Decade switches for addressing with back box for mounting as required conforming to BS5839 standards and duly approved by EN54/UL/VDS required to complete the job in all respect up to the entire satisfaction of Engineer – in Charge of work. Make: Bosch / Siemens Cerberus / GST
Supply Installation Testing & Commissioning of Addressable Loop powered sounder with strobe / flasher complete with mounting base as required conforming to BS5839 standards and duly approved by EN54/UL/VDS required to complete the job in all respect up to the entire satisfaction of Engineer – in Charge of work. Make: Bosch / Siemens Cerberus / GST
Supply Installation Testing & Commissioning of Analog Addressable type Active Repeater fire alarm panel with Backlit LCD Display, having controls for reset, mute, Accept, Silence alarms and self test conforming to BS5839 standards and Duly approved by EN54/UN54/VDS with all labour and material required to complete the job in all respect up to the entire satisfaction of Engineer – in Charge of work. Make: Bosch / Siemens Cerberus / GST
Supply Installation Testing & Commissioning of Glow Type EXIT Sign Board photo luminescent of size 300 mm x 250 mm x 1.5 mm rigid sheet signage containing Zink Sulphate as bare chemical class – 1 material PSPA fixed on 3 mm acrylic sheet on both side showing marking (running man, Arrow and Exit) and hanged with the ceiling with chain and fastener including cost of labour & material required to complete the job in all respect up to the entire satisfaction of Engineer-in-Charge of work Make : Giolite/Pearl/ Devi
Supply Installation Testing & Commissioning of Addressable Monitor Module for monitoring of a line with EOL resistor/ Potential free contact/ voltage monitoring shall be EN54/UL/VDS approved. (In case of 2 monitoring features in one module (points) each point shall be consider separately for payment). Make: Bosch / Siemens Cerberus / GST
Supply Installation Testing & Commissioning of Addressable Control Relay Module with flexible network structures with a maximun switching current of 1A @ 30V DC. Shall be EN54/UL/VDS Certification Make: Bosch / Siemens Cerberus / GST
Supply Installation Testing & Commissioning of UL/EN54/LPCB listed and FM Approved Line Isolator for Isolating the section of circuit in case of short in the addressable Loop wiring Make: Bosch / Siemens Cerberus / GST
Supply Installation Testing & Commissioning of minimum 1000 Mtr. Range Siren provided at the roof of the building with separate power suppl, relay etc.with all accessories required to complete the job in all respect up to the entire satisfaction of engineer incharge. Make: National/Kheraj
Supply and erection of FIRE EXTINGUISHERS duly hang on wall with necessary hook complete in all respect (Make: Safex/Minimax/ Ceasefire) ABC Dry power type fire Extinguishers of 6 kg. capacity
Co2 type fire extinguishers of 4.5 Kg capacity
Supply & erection of PVC Insulated and PVC round sheathed multi core annealed bare copper conductor industrial flexible cables for voltage grade 1100 Volts conforming to IS: 694:2010 complete in all respect upto the entire satisfaction of Engineer in charge of the work 2 core PVC round sheathed copper size 1.5 sq mm
Supply and erection of PVC conduit pipe ISI marked (Medium) recessed in wall /ceiling etc. including cost of PVC bends, inspection box and all other material required to complete the job in all respect to the entire satisfaction of Engineer-in-Charge of work. (As per HSR 2021 item no. 23.7.6.2) 25 mm dia
Supply and erection of On-Line- UPS rating 6.0KVA, indicative backup time 100 minutes with isolation transformer suitable for single phase AC input & single phase AC output, floor mounted type complete in all respect upto the entire satisfaction of Engineer in charge of the work. Make Microtek/ Emerson / Eaton/ APC
Supply and erection of 12 volt 42Ah SMF battery complete in all respect upto the entire satisfaction of Engineer in charge of the work. Make Exide/ Amaron/ Luminious
Supply and erection of 16 mm angle MS stand of 55 kg. weight of dimension 40mm (L) x 50mm (H) x10 mm (W) duly painted used to accomodate 16 nos.12 volt 42Ah SMF batteries complete in all respect upto the entire satisfaction of Engineer in charge of the work.
SITC of addressable beam detector with short circuit isolator (inbuilt or separate) complete with emitter and receiver including connections with remote test features etc. as required to complete the job in all respect upto the entire satisfaction of Engineer in charge of the work. Make : GST/ Honeywell/ Siemens cerberus
SITC of 22U Rack for wall/floor mounting of Equipment with drawer shelves and wiring channels to accommodate AV system equipment and accessories as mentioned in the BOQ above and including all connections and terminations as required fabricated from minimum 2 mm thick CRCA sheet including power coating after surface treatment complete as required complete in all respect upto the entire satisfaction of Engineer in charge of the work. Make : Rittel/Valrack/Commscope/D-link/Hive Network
Supply Installation Testing & Commissioning of of Booster amplifier 480 watt frequency response : 60 Hz to 15 khz (plus 1/3 db), Inputs : XLR and phone jack, input 1, Input 24, IMpendence : 20 Kg, SEnsitivity : 1 V balanced, S/N : ) 85 dB complete as required complete in all respect upto the entire satisfaction of Engineer in charge of the work. Make : Bosch/ Heinrich/ Honeywell
SITC of Cabinet Speaker max Power - 9 W, Rated power (PHC) - 6W (6-3-1.5), sound pressure level at rate power / 1 w, 9at1kHz, 1m) (at 1 kHz 1m) - 96dB/90 dB, Effective frequency range (-10 dB) - 200 - 15000 Hz, Opening angle (at 1 kHz/ 4 kHz, - 6 dB), In degrees - 150/70, rated voltage - 100 v, rated impedance - 1667 complete as required complete in all respect upto the entire satisfaction of Engineer in charge of the work. Make : Bosch/ Heinrich/ Honeywell
AVNET Solutions
Hytek Turnkey Projects Pvt. Ltd.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .