Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹17.0 LAccepted-AOC 205 PARSHAV VIHAR PLOT NO 50 1 P EXTN PATPARGANJ DELHI 110092 | DELHI | EAST DELHI | DELHI | 110092 | L1 | Accepted-AOC Quoted L1 | |
| 2 | L2₹20.9 L+₹3.5 L (19.9%)Rejected-AOC 303 GHS 888 SECTOR 20 PANCHKULA 134116 HARYANA | PANCHKULA | PANCHKULA | HARYANA | 134116 | L2 | Rejected-AOC Quoted L2 | |
| 3 | L3₹21.5 L+₹4.1 L (23.4%)Rejected-AOC HYDERABAD TELANGANA 500076 INDIA UDYAM TS 02 0009467 | MEDCHAL MALKAJGIRI | TELANGANA | 500076 | L3 | Rejected-AOC Quoted L3 | |
| 4 | L4₹24.1 L+₹6.6 L (37.9%)Rejected-AOC 691 INDUSTRIAL AREA PHASE II CHANDIGARH 160 002 | CHANDIGARH | CHANDIGARH | CHANDIGARH | 160002 | L4 | Rejected-AOC Quoted L4 | |
| 5 | L5₹24.6 L+₹7.1 L (40.9%)Rejected-AOC RAM SHIV COLONY GALI NO 2 NAIKA CHATNAG ROAD JHUNSI PRAYAGRAJ UP 211019 | PRAYAGRAJ | UTTAR PRADESH | 211019 | L5 | Rejected-AOC Quoted L5 |
Tender Value
₹30 L
EMD Value
₹60,000
Closing Date
5 Jul 2023, 6:00 pmClosed
GE AF Chandigarh
GE AF Chandigarh PIN-160003 C/o 56AP
ROUTINE MAINTENANCE AND REPAIRS TO DG SETS AND OTHER ALLIED SERVICES AT VARIOUS E/M INSTALLATIONS AT AF STATION CHANDIGARH UNDER GE (AF) CHANDIGARH
2023_MES_601801_1
GE(AF)/CHD/T-19/2023-24
Open Tender
Electrical and Maintenance Works
Item Rate
274 days
Chandigarh
All as per NIT and Tender documents
10 documents required · 10 mandatory
₹500
GE AF Chandigarh
₹60,000
Yes
30 Aug 2023
7 Jun 2023
11 Jul 2023
7 Jun 2023
5 Jul 2023
21 Jun 2023
7 Jun 2023 - 13 Jun 2023
Amount
Servicing & maintenance of DG sets of capacity 15 KVA to 50 KVA through authorised representative of company to the entire satisfaction of Engineer-in-Charge complete as per following:- (i) Draining out engine/ lubrication oil, flushing and pouring new engine oil after repair of DG set including supply and replacement of oil pan/chamber gasket.(Engine oil shall be measured and paid under respective items). (ii) Supply and replacement of oil filter element. (iii) Supply and replacement of fuel filter element. (iv) Supply and replacement of element air cleaner/ filter. (v) General servicing of DG set by opening of tappet cover/top cover, tappet clearance setting with injector timing adjustment, re-fixing of tappet/top cover including supply and replacement of tappet cover packing set, shellac/bostic tube. (vi)Checking of auto programming & manual processing. (vii)Tightening of all electrical connection, AVR connections, alternator connection and Panel connections. (viii) Tightening of all the hoses, Fuel connections. (ix) Tightening/ adjustment of 'V' belts. (x) Cleaning of silencer muffler. (xi) Checking & adjustment of battery complete all as required. (xii) Testing of Engine on load for 30 Minutes.
All as per item No. 1.00 above but DG set of cepacity exceeding 50 KVA but not exceeding 100 KVA.
All as per item No. 1.00 above but DG set of cepacity exceeding 100 KVA but not exceeding 160 KVA.
All as per item No. 1.00 above but DG set of cepacity exceeding 160 KVA but not exceeding 250 KVA.
All as per item No. 1.00 above but DG set of cepacity exceeding 250 KVA but not exceeding 400 KVA.
Supply only lubricant oil (Engine oil) of viscosity grade SAE 20W/40for filling in DG set of any capacity installed at different locations in situ at site including draining out existing oil complete all as specified and directed.
Supply, install, connecting & commissioning 150AH, 12 Volts maintenance free, factory charged, ready to use battery including disconnecting and taking out existing battery complete all as specified and directed.
Supply, install, connecting & commissioning 180AH, 12 Volts maintenance free, factory charged, ready to use battery including disconnecting and taking out existing battery complete all as specified and directed.
Supply and fix in replacement automatic voltage regulator, 415volts, AC suitable for 20KVA to 100KVA DG set complete all as specified and directed.
Supply and fix in replacement automatic voltage regulator, 415 volts, AC suitable for 110KVA to 250KVA DG set complete all as specified and directed.
Supply and fix in replacement automatic voltage regulator, 415 volts, AC suitable for 300KVA to 400KVA DG set complete all as specified and directed.
M&L for rewinding of self-starter 12voltscomplete all as specified and directed.
M&L for rewinding of self-starter 24 volts including replacement of all required accessories for DG set of capacity 160 KVA to 400 KVA fixed in position & testing including dismantling & opening complete all as specified and directed.
Supply & replacement of battery leads of PVC insulated sheathed multi core copper conductor 25Sqmm (nominal area) heavy duty cable 1.5m long with copper lugs duly crimped & soldered in one side and battery terminal on other side complete all as specified and as directed.
Supply and filling engine coolant in radiators of DG sets as per Manufacturer's recommendations installed at different locations brought at site in sealed packets complete all as specified and directed. Make:- SERVO, GOLDEN CRUISER, SHEEL, TOTAL, BPL.
Supply and filling distilled water in batteries of DG sets at different locations, brought at site in 40 litre plastic sealed containers complete all as specified and directed.
Supply and replacement self starter 12 volts fixed in position and testing complete all as specified and directed. Make: LUCAS or equivalent.
Supply and replacement self starter 24 volts fixed in position and testing complete all as specified and directed. Make: LUCAS or equivalent.
Supply and fixing automatic transfer switch (ATS), 4 pole, 415 volts with inbuilt time delay with enclosures of rating 160 Amp including taking down old complete all as specified and directed. Make: Havells, L&T, Indo Asian, ABB
Supply and fixing automatic transfer switch (ATS), 4 pole, 415 volts with inbuilt time delay with enclosures of rating 200 Amp including taking down old complete all as specified and directed. Make: Havells, L&T, Indo Asian, ABB
S&F in replacement for power contactor 4 pole type 80/ 100 Amp including all accessories like auxiliary contacts etc. complete all as specified and directed. Make: L&T or equivalent.
S&F in replacement for power contactor 4 pole type 160 Amp including all accessories like auxiliary contacts etc. complete all as specified and directed. Make: L&T or equivalent.
S&F in replacement for power contactor 4 pole type 200/ 250 Amp including all accessories like auxiliary contacts etc. complete all as specified and directed. Make: L&T or equivalent as approved by GE.
S&F in replacement for power contactor 4 pole type 400 Amp including all accessories like auxiliary contacts etc. complete all as specified and directed. Make: L&T or equivalent as approved by GE.
S&F in replacement door hinges suitable for 63 KVA to 250 KVA DG set of existing type including welding and made to shape all as per specified and directed.
S&F in replacement V-belt complete all as specified and directed. Make: Fenner or equivalent as approved by GE.
S&F in replacement oil pressure gauge all as specified and directed.
S&F in replacement oil temperature gauge all as specified and directed.
S&F in replacement fuel gauge meter operated on 24V DC all as specified and directed.
S&F in replacement high temperature diesel hose pipe of 1000 PSI for connecting from diesel tank outlet to engine complete with banjo bolt & washer suitable for DG set of capacity upto 100 KVA all as specified and directed.
S&F in replacement high temperature diesel hose pipe of 1000 PSI for connecting from diesel tank outlet to engine complete with banjo bolt & washer suitable for DG set of capacity 125 to 250 KVA all as specified and directed.
M&L for dismantling of exhaust pipe of silencer, cleaning of silencer to remove carbon deposit inside exhaust pipe and refixing including replacement of worn out rubber gasket packing and nuts, bolts etc. complete all as specified and directed.
S&F coil suitable for MNX power contactor any size/ capacity all as specified and as directed. Make: L&T/ C&S/ Havells.
M&L for scraping out old paint from DG set of upto 160 KVA including chassis, radiator and exhaust pipe washing with caustic soda to wipe out greasy material and applying two coats of heat resistant paint using spray gun including writing SM/ MES No. of engine and the alternator with total alphabets not exceeding 20 No. with white signal paint complete all as specified and directed.
All as per item No 34.00 above but of capacity 200 to 320 KVA.
Supply and installation in replacement controller meter of DG sets suitable for 62.5/ 100 KVA alongwith the new display panel specifications complete all as directed.
Supply and fixing in replacement battery charger unit for 160 to 320 KVA DG Set suitable for 12 V 180 AH complete with 2m copper leads -02 Nos & brass clamps complete all as specified and directed.
M&L for taking out FIP from DG set, transportation to authorized service centre for overhauling and recalibration and refixing to DG set including replacement of spare parts such as delivery valves, plunger, 'O' rings spring etc. complete all as directed.
M&L cleaning of diesel tank of DG set of any capacity including replacement of worn out pipe line and measuring scale and fixing in original position and make it leak proof with necessary clamps complete all as specified and directed.
M&L for replacement of change over switch off load side operated of capacity 200 Amp complete all as specified.
M&L for replacement of change over switch on load front operated without enclosure of capacity 200 Amp complete all as specified.
Taking out unserviceable asbestos rope from the exhaust pipe, cleaning the exhaust pipe, supply and wrapping new asbestos rope of suitable size and wrapping with wire mesh and plastering with plaster of Paris/ white cement for smooth finishing including replacement of gasket and tightening of all nuts and bolts complete all as specified and directed by the Engineer-in-Charge.
Attending day to day complaints of the DG sets of various capacities including all major/ minor repairs as per the scope of the contract all as directed by Engineer-in-Charge. Notes: (a) The complaint shall be attended by the auth rep of the manufacturer by an experienced and professional mechanic. (b) The complaint shall be attended on the same day. (c) Non functioning of any DG set will be sole responsibility of the contractor and a penalty of Rs. 500/- for each hour of non running will be levied on the contractor. (d) The mechanic shall make a visit on all the generators on weekly basis.
Supply, laying, jointing and testing LT XLPE cable insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 95 sqmm 3½ core laid in trenches/ passing through GI tubing etc. including taking out existing LT XLPE cable complete as specified and directed.
Excavation in trenches in soft/ loose soil not exceeding 1.5 mtr wide and not exceeding 1.5 mtr in depth for foundation of pole, laying of cable etc. and getting out complete all as specified and directed.
Returning and filling in excavated soil in layer not exceeding 25cm thick in including spreading, levelling, watering and well ramming in soft/ loose soil complete all as specified and directed.
Removing excavated surplus soil to a distance not exceeding 50 mtrs and depositing where directed at a level not exceeding 1.5mtrs above the starting points complete all as specified and directed.
M&L for sand cushioning to cables with a layer of sand 8cm deep before laying the cable and 15cm depth after laying & stretching of cable) complete all as specified. Note: Punned thickness overall 18cm shall be measured & paid.
Supply and laying old size sub class ‘B’ bricks as in protection of cable laid dry flat perpendicular to direction of cable abutting each other complete all specified and directed.
M&L for cleaning of radiator fins of DG set of capacity 100 KVA to 160 KVA by blow pressurized air through radiator fins in reverse direction to the fan flow including internal cleaning by filling K-clean to remove contaminants like scale, oil, grease or unwanted materials; K-clean to be added in ratio 375ml for every 16 litre capacity of radiator and solution to be drained out after running of engine for minimum of 30 minutes and repeating the process till the contentious, scale are completely removed including filling the radiator with genuine coolant premix (Supply only of coolant to be measured and paid separately) including soldering/ welding work to radiator fins if found leaked including transportation to workshop and back complete all specified and directed.
All as per item No. 49.00 above but but radiator of DG set of capacity 200 KVA to 320 KVA.
M&L for taking out alternator assembly of DG set of capacity 100 KVA to 160 KVA with the help of puller and opening the cover of alternator assembly for varnishing the winding, cleaning the stator/ rotor assembly using tetra chloride solution to wash unwanted contents on the winding and applying two coats of ‘F’ class varnish in the winding of DG set, drying the same using heating arrangement or hot blower complete all as specified and directed.
M&L for isolating the main supply from the DG set of capacity 63 KVA to 125 KVA, dismantling the complete engine by taking out head, sump piston assembly, water sleeves, connecting rod, big end bearing, main end bearing, tapped assembly, inlet and outlet valves etc. including drainage out engine oil and keeping in container, Reassembly of engine after replacement of required accessories and testing the engine after making connection with alternator on load to the satisfaction of Engineers-in-Charge. Labour charges for replacement of new parts shall be deemed to be included in this item. However, supply of items required to be replaced will be paid separately. Parts where grinding, calibration or lapping is required at workshop will be measured and paid separately. Accessories required for overhauling of DG set shall be measured and paid separately.
M&L for decarburization of valve heads of DG of capacity 125 KVA and job making the surface free from carbon contents and lapping of inlet and outlet valve 12 No’s complete all as directed.
M&L for complete overhauling of fuel injecting pump of DG set of capacity 125 KVA and replacement of plungers, delivery valve and spring washer, cam shaft, pump, rack & pinion and testing the same after carrying out the job work from authorized workshop complete as specified and directed by Engineer-in-charge.
M&L for repair of injector nozzle of DG set of capacity 125 KVA and testing the injector assembly- 6 No. for proper delivery of the fuel including replacement of any parts like spring washers, plunger and barrel spring required complete as specified and directed by Engineer-in-charge.
Supply only the following parts for DG set of capacity 125 KVA:-
Liner assembly
Piston ring set
Gasket set complete for lower and upper parts
Water pump assembly
Thermo-state
Turbo charger repair kit
Fan belt
Diode assembly
Air Filler
Fuel filler
Oil filler
Hose pipe set
M&L for decarburization of valve heads of DG of capacity 100 KVA and job making the surface free from carbon contents and lapping of inlet and outlet valve 12 No’s complete all as directed.
M&L for complete overhauling of fuel injecting pump of DG set of capacity 100 KVA and replacement of plungers, delivery valve and spring washer, cam shaft, pump, rack & pinion and testing the same after carrying out the job work from authorized workshop complete as specified and directed by Engineer-in-charge.
M&L for repair of injector nozzle of DG set of capacity 100 KVA and testing the injector assembly- 6 No. for proper delivery of the fuel including replacement of any parts like spring washers, plunger and barrel spring required complete as specified and directed by Engineer-in-charge.
Supply only the following parts for DG set of capacity 100 KVA:-
Liner assembly
Piston ring set
Gasket set complete for lower and upper parts
Water pump assembly
Thermo-state
Turbo charger repair kit
Fan belt
Diode assembly
Air Filler
Fuel filler
Oil filler
Hose pipe set
M&L for decarburization of valve heads of DG of capacity 63 KVA and job making the surface free from carbon contents and lapping of inlet and outlet valve 12 No’s complete all as directed.
M&L for complete overhauling of fuel injecting pump of DG set of capacity 63 KVA and replacement of plungers, delivery valve and spring washer, cam shaft, pump, rack & pinion and testing the same after carrying out the job work from authorized workshop complete as specified and directed by Engineer-in-charge.
M&L for repair of injector nozzle of DG set of capacity 63 KVA and testing the injector assembly- 6 No. for proper delivery of the fuel including replacement of any parts like spring washers, plunger and barrel spring required complete as specified and directed by Engineer-in-charge.
Supply only the following parts for DG set of capacity 63 KVA:-
Liner assembly
Piston ring set
Gasket set complete for lower and upper parts
Water pump assembly
Thermo-state
Turbo charger repair kit
Fan belt
Diode assembly
Air Filler
Fuel filler
Oil filler
Hose pipe set
S&F in replacement all aluminium radiator suitable for DG set of capacity 125 KVA Make Kirlosakr complete including all fittings and fixtures including making connections and testing on load for 15 minutes complete as specified and directed by Engineer-in-charge.
M&L for repairing/ rewinding the alternator of DG Set 63 to 350 KVA complete with taking out unserviceable alternator with disconnecting the electrical connections and rewinding the burnt alternator with appropriate size of copper wire, leatherised rubber and opening the coil complete with vanishing the coils & making connections all as specified and directed by the Engineer-in-Charge.
R D Bansal
POWER TECH ENGINEERS
PARTAP ENGINEERING WORKS
TARA ENTERPRISES
M/s badrinath Traders
stage.html
html • 0.05 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .