Loading…
Loading…
Tender Value
₹6.1 Cr
EMD Value
₹12.2 L
Closing Date
16 Jul 2026, 2:00 pm
Executive Engineer
Office of the Executive Engineer Mechanical and Hospital Division Anantnag
SUPPLY, INSTALLATION, TESTING and COMMISSIONING OF 02 x 1000 LPM CAPACITY OXYGEN GENERATION PLANTS ALONG WITH ALLIED WORKS AT MMABM ASSOCIATED HOSPITAL GOVT. MEDICAL COLLEGE ANANTNAG
2026_PWDJK_313621_1
MHDA/TS/2026-27/08
Open Tender
Miscellaneous Works
120 days
MMABM AH GMC Anantnag
Refer NIT
10 documents required · 10 mandatory
₹5,000
Yes
Accounts Officer M and H Engg. Deptt. Kashmir
₹12.2 L
Yes
Mechanical and Hospitals Circle Srinagar
25 Jun 2026
25 Jun 2026
17 Jul 2026
25 Jun 2026
16 Jul 2026
26 Jun 2026
7 Jul 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Supply, Installation, Testing and Commissioning of 2x1000 LPM capacity Oxygen Generation Plant along with allied works including Comprehensive Maintenance Contract (CMC) for three (03) years post DLP/ Warranty period and the Operation of the Plant for three years after commissioning at MMABM associated Hospital, GMC Anantnag. | |||||
| 1.01 | Supply, Installation, Testing & Commissioning (SITC) of PSA technology based 1000 LPM Oxygen Concentrator Plant delivering 93 ± 3% oxygen purity, complete with main PSA oxygen generator, air compressors 02 nos, air dryers 02 nos, filtration system 02 nos, air & oxygen receiver tanks 02 nos. each , electrical panels. , MCCBs, UPS, ducting, cabling, piping and all allied accessories including necessary cable trays as per site requirement, strictly as per technical specifications, scope of work, standards and conditions laid down in Annexure C of the NIT, complete in all respects. | 2 | Jobs | 2,03,00,000 | ₹4,06,00,000 |
| 1.02 | Supply, installation, testing, and commissioning of 625 kVA capacity silent-type Diesel Generator Set, prime rated, 3-phase, 4-wire system, 415 V ±10%, 50 Hz, liquid-cooled (radiator type), turbocharged, water-cooled diesel engine with high-pressure fuel injection system (inline or rotary pump), 1500 RPM speed, 24V DC electric start with automatic start/stop via AMF panel, electronic governor with ±1% speed regulation, brushless, self-excited, self-regulated alternator conforming to IS:4722 / IEC:60034, insulation class H, power factor 0.8 lagging, efficiency ≥ 90%, enclosed in factory-fitted weatherproof acoustic canopy with sound level ≤ 75 dB(A) at 1 meter, including all associated cabling, earthing, foundation, and electrical works for DG backup to oxygen Supply systems, conforming to latest CPCB IV+ emission norms and relevant IS/IEC standards as per technical specifications, scope of work, standards and conditions laid down in Annexure C of the NIT, complete in all respects. | 1 | Job | 81,15,000 | ₹81,15,000 |
| 1.03 | Manifold system and Automatic oxygen changeover Panel: Supply, Installation, Testing and Commissioning of wall mounted 8x8 Oxygen manifold with fully automatic control system as per ISO: 13485 and ISO 9001 standards. It includes brass headers with connectors for 8 cylinders, pressure gauges (0-250 kg/cm2), regulators, alarm systems, non-return valves, pressure relief valves, leak detection alarms, copper pigtails, copper pipe paint, check valves and connection to oxygen plants and with existing system | 1 | Job | 1,80,000 | ₹1,80,000 |
| 1.04 | Supply, Installation, Testing and Commissioning of 400KVA servo-stabilizers.
The stabiliser should have following specifications:
a) Capacity: 400 KVA, 3-phase unbalanced type
b) Input: (90-265) V AC P-N; (156 - 460) V AC P.P
c) Output: 415 V ± 1% - phase to phase
d) Supply: 3 phase, 4 wires, 50Hz
e) Operation: Automatic
f) Duty cycle: Continuous
g) Transformer windings: Copper wound on CRGO laminations as per IS specifications.
h) Cooling: Oil cooled
i) Efficiency: Better than 98% at full load
j) Overload capacity: 15% for continuous 4 hours
k) Waveform distortions: Nil
l) High speed voltage correction: up to 8V to 20V per second
m) Protections: Under voltage, over voltage and Overload with time delay
Other features: LED indicators, Digital AC ammeter, AC voltmeter, Frequency meters, Phase Sequence meters, Single phase preventer, Stabilizer by-pass arrangement as per technical specifications, scope of work, standards and conditions laid down in Annexure C of the NIT, complete in all respects. | 2 | Jobs | 11,60,000 | ₹23,20,000 |
| 1.05 | Supply, Installation, Testing and Commissioning of 630 sq.mm single-core XLPE Steel Wire Armoured Aluminium cable from main sub-station to main electric panel. | 1,200 | Mtrs | 1,760 | ₹21,12,000 |
| 1.06 | Chemical earthing of all the equipment with GI earth pipe 2.5 mtr. Long 50 mm dia. Including accessories and providing masonry enclosure with cover plate having locking arrangements and watering pipe, trenching and filling with charcoal/coke and salt and along with shock proof rubber insulation mats | 10 | Nos | 14,690 | ₹1,46,900 |
| 1.07 | Providing and fixing of 50mmx6mm GI strip on surface or in recess for extending the earthing from earth electrode to controlling panel in one rim. | 160 | Mtrs | 144 | ₹23,040 |
| 1.08 | Design, Supply, Installation, Testing & Commissioning (DSITC) of 800A master control panel fabricated out of 16SWG sheets duly powder coated and having different compartment for housing of switchgears of different capacities, Changeover 630 A breaking capacity 50 K, copper bus bar, Coupler 630 A breaking capacity 50 K, ACB 800 A (02 No’s) breaking capacity 50 K, Emergency Stop etc. as per technical specifications, scope of work, standards and conditions laid down in Annexure C of the NIT, complete in all respects. | 1 | Job | 13,00,000 | ₹13,00,000 |
| 1.09 | Supply, Installation, Testing and Commissioning of Air Compressor Medical Air system along with allied works at MMABM Anantnag,.The Medical Air System should have pecifications as per the Technical Specifications laid down in annexure "C
Desiccant Air Dryer:
Heatless Regenerative Desiccant Dryer
80 CFM (to handle both compressors)
-40°C or better
Stainless steel/aluminium tower
Automatic cycling with purge valve
Pre & Post filters (1 micron particulate)
Carbon Tower (Odor Removal):
Activated Carbon Adsorption Tower
Matched with 80 CFM airflow
Air Receiver Tank:
Cylindrical Mild steel of 2062 grade, 6mm shell, 8mm dish ends
12 kg/cm² (working pressure, conforming to IS 2825)
Pressure gauge, manual drain, 10 kg/cm² safety valve
Primer + 2 coats of enamel paint
Capacity should not be less than 300 litres | 2 | Jobs | 3,00,000 | ₹6,00,000 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.56 MB
BOQ_1015271.xls
BOQ • 0.28 MB
Download all tender documents and submit your bid