| 1 | 34809084520_245KVTERM CONNECTOR SINGLE ZEBRA ACSR CB | 1. Terminal connector to suit single Zebra ACSR on CB (HA)
2. Max. System Voltage:245kV
3. Continuous Rating:800 A(Max. Temp. Rise 35 deg C above 50 deg C ambient)
4. Short Time Rating:40kA for 3 Sec
5. Reference Drawing:- Attached Sample Drg.1
Detailed Technical specifications as per attached Annexure-1.
Drawing approval has to be obtained from NALCO before manufacturing. | 15 | EA | arbind.singh | 180 |
| 2 | 34809084530_245KVTERM CONNECTOR SINGLE ZEBRA ACSR IL | 1. Terminal connector to suit single Zebra ACSR on Isolator (HA)
2. Max. System Voltage:245kV
3. Continuous Rating:800 A(Max. Temp. Rise 35 deg C above 50 deg C ambient)
4. Short Time Rating:40kA for 3 Sec
5. Reference Drawing:- Attached Sample Drg.2
Detailed Technical specifications as per attached Annexure-2.
Drawing approval has to be obtained from NALCO before manufacturing. | 30 | EA | arbind.singh | 180 |
| 3 | 34809084540_245KVTERM CONNECTOR SINGLEZEBRA ACSR CVT | 1. Terminal connector to suit single Zebra ACSR on CVT (HA)
2. Max. System Voltage:245kV
3. Nominal
4. Short Time Rating:40kA for 3 Sec
5. Reference Drawing:- Attached Sample Drg.3
Detailed Technical specifications as per attached Annexure-3
Drawing approval has to be obtained from NALCO before manufacturing. | 10 | EA | arbind.singh | 180 |
| 4 | 34809084550_245KVTERM CONNECTOR SINGLE ZEBRA ACSR CT | 1. Terminal connector to suit single Zebra ACSR on CT (HA)
2. Max. System Voltage:245kV
3. Continuous Rating:800 A(Max. Temp. Rise 35 deg C above 50 deg C ambient)
4. Short Time Rating:40kA for 3 Sec
5. Reference Drawing:- Attached Sample Drg.4
Detailed Technical specifications as per attached Annexure-4
Drawing approval has to be obtained from NALCO before manufacturing. | 20 | EA | arbind.singh | 180 |
| 5 | 34809084560_245KVTERM CONNECTOR SINGLEZEBRA ACSR TRF | 1. Terminal connector to suit single Zebra ACSR on Transformer Bushing (HA)
2. Max. System Voltage:245kV
3. Continuous Rating:800 A(Max. Temp. Rise 35 deg C above 50 deg C ambient)
4. Short Time Rating:40kA for 3 Sec
5. Reference Drawing:- Attached Sample Drg.5
Detailed Technical specifications as per attached Annexure-5
Drawing approval has to be obtained from NALCO before manufacturing. | 9 | EA | arbind.singh | 180 |
| 6 | 34809084570_245KVTHRU CONNECTOR BPI SINGLEZEBRA ACSR | 1. Through type connector on BPI to suit single Zebra ACSR (HA)
2. Max. System Voltage:245kV
3. Corona extinction Voltage:156kV (rms)
4. Reference Drawing:- Attached Sample Drg.6
Detailed Technical specifications as per attached Annexure-6
Drawing approval has to be obtained from NALCO before manufacturing. | 10 | EA | arbind.singh | 180 |
| 7 | 34809084580_245KVTEE CONNECTOR SINGLE ZEBRA ACSR | 1. Tee connector to suit single Zebra ACSR to single Zebra ACSR
2. Max. System Voltage:245kV
3. Continuous Rating:800 A(Max. Temp. Rise 35 deg C above 50 deg C ambient)
4. Short Time Rating:40kA for 3 Sec
5. Reference Drawing:- Attached Sample Drg.7
Detailed Technical specifications as per attached Annexure-7
Drawing approval has to be obtained from NALCO before manufacturing. | 25 | EA | arbind.singh | 180 |
| 8 | 34809084590_145KV225MM FLEXI SPACER CLAMP TWIN ZEBRA | 1. Flexible type spacer clamp for twin Zebra ACSR at 225 mm spacing
2. Max. System Voltage:145kV
3. Short Time Rating:20kA for 3 Sec
4. Conductor Slip Strength: 250kg
5. Compression Strength: 1500kg
6. Tensile Strength: 750kg
7. Reference Drawing:- Attached Sample Drg.8
Detailed Technical specifications as per attached Annexure-8
Drawing approval has to be obtained from NALCO before manufacturing. | 30 | EA | arbind.singh | 180 |
| 9 | 34809084600_145KVTEE CONNECTOR 4IPS AITUBE TWINZEBRA | 1. Tee connector to suit 4" IPS AL tube to twin Zebra ACSR
2. Max. System Voltage:145kV
3. Continuous Rating:1600 A(Max. Temp. Rise 35 deg C above 50 deg C ambient)
4. Short Time Rating:20kA for 3 Sec
5. Reference Drawing:- Attached Sample Drg.9
Detailed Technical specifications as per attached Annexure-9
Drawing approval has to be obtained from NALCO before manufacturing. | 6 | EA | arbind.singh | 180 |
| 10 | 34809084610_145KVTERM CONNECTOR TWIN ZEBRA ACSR CVT | 1. Terminal connector to suit twin Zebra ACSR on CVT (HA/VA)
2. Max. System Voltage:145kV
3. Continuous Rating:Nominal
4. Short Time Rating:20kA for 3 Sec
5. Reference Drawing:- Attached Sample Drg.10
Detailed Technical specifications as per attached Annexure-10
Drawing approval has to be obtained from NALCO before manufacturing. | 6 | EA | arbind.singh | 180 |