CWE Allahabad
HQ CWE New Cantt Allahabad
PROVN OF 400 KVA AND 200 KVA STANDBY PORTABLE TRANSFORMER (OUT DOORS) AT NEW CANTT ALLAHABAD UNDER GE (WEST) ALLAHABAD.
2021_MES_411047_1
81577/W/E8
Open Tender
Civil Works
Item Rate
120 days
Allahabad
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
GE (West) Allahabad
₹28,040
Yes
22 Mar 2021
9 Jan 2021
17 Feb 2021
10 Jan 2021
15 Feb 2021
1 Feb 2021
Amount
Supply, fixing, commisioning and testing of Outdoor type trolley mounted Transformer 400 KVA capacity, step down with dual ratio on HT side 11/0.433 KV at NO load, 3 phase, 4wire 50 Hz AC double wound core type copper wound, oil immersed, air naturally cooled with extarnal cooling tubes, transformer delta connection on HV side and star connection on LV side in accordence with vector symbol DyN-II with neutral brought out on secondary side and having tapping in step of 2.5 %, 5%, and 7.5% to be changed by means of hand operated off load tap changing gear arrangement including first fill of transformer oil as per IS-335 and including all fitting / accesories as specified in SSR Part -I and IS -1180 Part I/2014 (revised) BEE Star rated energy saving . Transformer should have cable box on LT side and brass bushing on HT side , oil temperature guage, dehydrating breather with first fill of dehydrating silica gel, oil conservator tank, explosion vent, rating and terminal marking plate, oil level guage, oil drain and filter valve, independent earth point and neutral fittings, earth terminal at bodybase, voltage regulation should be as per IS and limil of temp rise after contineous full load run as specified in SSR part-I and IS -1180 Part I (revised) shall be suitably adjusted to suit the maximum ambient temp prevailing at site all as specified comprising with the following specifications: -
(i) Cable box on LV & HV side consisting of 03 Nos porcelain bushing with bushing brass rods and nut bolts. (ii) Oil conservator with filter type drain valve and oil level gauage. (iii) Two earthing terminal on tank body to facilitate fixing of GI strip. (iv) Vapour pressure based dial type anolog thermometer having range0-120 degree centegrate with maximum temperature indicator needle of temperature guage. (v) Rating plate with terminal plate. (vi) Oil level guage. (vii) Oil drain filter valve. (viii) Oil filling port on top cover with plug. (ix) Air release valve/plug. (x) 4 Nos plain solid cast steel detachable rollers. (xi) Shut off valve between conservator and bucholz relay. (xii) First fill of transformer oil of 60 KV dielectric strength. (xiii) Inspection cover. (xiv) Lifting lugs and jack lifting pad support. (xv) Explosion vent with double diaphram and sight glass. Note :- The transformer shall be suitable for fixing on trolley and rate for fixing of transformer in existing trolley deemed to be included in unit rate.
Supply and laying XLPE insulated , screened ,pvc bedded galvanised steel strip or wire armoured electric power cable (heavy duty) with alluminium conductor 11000 volt grade having cross section area of 95 Sq mm 3 core "E" grade complete all as specified and directed.
Supply and laying XLPE insulated , screened ,pvc bedded galvanised steel strip or wire armoured electric power cable (heavy duty) with alluminium conductor 11000 volt grade having cross section area of 120 Sq mm 3 core "E" grade complete all as specified and directed.
Supply, fixing ,commisioning and testing of Outdoor type trolley mounted Transformer 200 KVA capacity , step down with dual ratio on HT side 11/0.433 KV at NO load, 3 phase, 4wire 50 Hz AC double wound core type copper wound, oil immersed, air naturally cooled with extarnal cooling tubes, transformer delta connection on HV side and star connection on LV side in accordence with vector symbol DyN-II with neutral brought out on secondary side and having tapping in step of 2.5 %, 5%, and 7.5% to be changed by means of hand operated off load tap changing gear arrangement including first fill of transformer oil as per IS-335 and including all fitting / accesories as specified in SSR Part -I and IS -1180 Part I (revised) BEE Star rated energy saving . Transformer should have cable box on LT side and brass bushing on HT side , oil temperature guage, dehydrating breather with first fill of dehydrating silica gel, oil conservator tank, explosion vent, rating and terminal marking plate, oil level guage, oil drain and filter valve, independent earth point and neutral fittings, earth terminal at bodybase, voltage regulation should be as per IS and limil of temp rise after contineous full load run as specified in SSR part-I and IS -1180 Part I (revised) shall be suitably adjusted to suit the maximum ambient temp prevailing at site all as specified comprising with the following specifications: -
(i) Cable box on LV & HV side consing of 03 Nos porcelain bushing with bushing brass rods and nut bolts. (ii) Oil conservator with filter type drain valve and oil level gauage. (iii) Two earthing terminal on tank body to facilitate fixing of GI strip. (iv) Vapour pressure based dial type anolog thermometer having range0-120 degree centegrate with maximum temperature indicator needle of temperature guage. (v) Rating plate with terminal plate. (vi) Oil level guage. (vii) Oil drain filter valve. (viii) Oil filling port on top cover with plug. (ix) Air release valve/plug. (x) 4 Nos plain solid cast steel detachable rollers. (xi) Shut off valve between conservator and bucholz relay. (xii) First fill of transformer oil of 60 KV dielectric strength. (xiii) Inspection cover. (xiv) Lifting lugs and jack lifting pad support. (xv) Explosion vent with double diaphram and sight glass. Note :- The transformer shall be suitable for fixing on trolley and rate for fixing of transformer in existing trolley deemed to be included in unit rate.
M&L Cable jointing kit for 11 KV cable for end termination heat shrink type joint with jointing material and accessories suitable for XLPE armoured aluminium conductor cable of following size:-
Size 95 sqmm, 3 core outdoor type.
Size 120 sqmm, 3 core outdoor type
Diamond Electric Co.
Titco Electricals
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .