Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance SANAT NAGAR SRINAGAR PIN 190005 J K | SRINAGAR | JAMMU AND KASHMIR | 190005 | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
| 4 | Admitted-Finance | Admitted-Finance |
| 5 | Admitted-Finance | Admitted-Finance |
Tender Value
₹69.3 L
EMD Value
₹1.4 L
Closing Date
2 Feb 2023, 2:00 pmClosed
Ex.Engineer Mechanical Division Kargil
Office of the Executive Engineer Mechanical Division Kargil, Opposite Indian Oil Depot, TCP Kurbathang Kargil (194103)
Design, Supply, Installation, Testing and Commissioning of Diesel Fired Boiler Central Heating system for PHC Panikhar Kargil
2023_PWD_8980_1
MDK/e-NIT/83 of 2022-23
Open Tender
Machineries/ Mechanical Engg Items
Turn-key
90 days
Panikhar
Please refer Tender documents.
10 documents required · 10 mandatory
₹1,000
Payable To Executive Engineer Mechanical Kargil
₹1.4 L
Kargil
28 Feb 2023
25 Jan 2023
3 Feb 2023
25 Jan 2023
2 Feb 2023
25 Jan 2023
28 Jan 2023
Amount
SITC of HSD/LDO fired Horizontal fire tube HWG of capacity 02Lac Kcal/hr fitted with control panel, all boiler mounting / accessories and chimney fabricated out of 1MM MS /CGI sheet 6Mtr height with cowl and Dia as per HWG = 01 set
(a)SITC of brine circulation monobloc pump with mechanical seal of Discharge 13LPS at 5Mtr, 3 phase 415V, 50Hz = 2 Nos (b)SITC of brine feeding monobloc pump 200-230V, 50Hz 1HP = 01 Nos
SITC of Day oil tank 500 ltr capacity HDPE triple layer insulated with 25mm thick nitrile foam with 26 Gauge aluminium cladding and mounted on a suitable iron stand
SITC of Expansion tank 200 ltr capacity HDPE triple layer insulated with 25mm thick nitrile foam with 26 Gauge aluminium cladding and mounted on a suitable iron stand
SITC of steel panel radiator conforming tomEN442 standards of type 22; fitted with supply and return valves of following sizes:
b. 900 X 400 MM (column type)
SITC of Heavy Duty MS class C pipe insulated with 25mm nitrile foam with26SWG aluminium cladding for external pipes and with heat proof enamel paint for interior pipes along with all fittings like bends, TEE supports etc.
SITC of following flow control Valves: Butterfly valve 3" Dia = 2Nos Butterfly valve 2" Dia = 8Nos Butterfly Valve1½" Dia = 2Nos Ball Valve 1" Dia = 2 Nos Ball Valve ¾" Dia = 4
SITC of Heavy Duty PPR pipe insulated with 25mm nitrile foam with26SWG aluminium cladding for external pipes only along with all fittings like bends, TEE supports etc.
32mm Dia
25mm Dia
Providing and filling of coolent IOC Servo cool plus
SITC of Electric control panel fitted with all components like MCCB, Bus Barr, indivdual switches for all pumps / HWG etc . The job also includes fitting of 01 Change over switch 100Amp.
SITC of servo voltage stabilizer of 20KVA filled with recommended oil upto full capacity. Input 270-470V, output 415±1%
Providing and Fitting of 3-Ph. 25kVA DG Set with 120sq.mm cable of length 30m , complete earthing accessories.
Earthing for various equipments inside the boiler room using copper plate electrode of size 500 x 500 x 3mm placed in 1000 x 1000 x 1800 mm pit filled with charcoal and salt by copper strip
SITC of 10KL underground MS Tank as per IOC specifications including all earth/civil works.
Construction of Boiler Room & Operators Room:
(a)Boiler room of size 15' x 20' x Ht 13', RCC Framed Structure with concrete block and 125mm thick RCC with one Door, One window and Rolling Shutter of Size 10' x 10' (b)Operators Room of size 12' x 13' with one kitchen of size 6' x 8' and one bath room of size 5' x 7'
BHAT ENGINEERING WORKS
THERMOTECH ENTERPRISES
NIGHTINGALE TRADING ENTERPRISES
M/S HIGHLAND ENGINEERING
ECO HVAC SOLUTIONS
NATIONAL ENGINEERING
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .