Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance NO 68 ANJANEYA TEMPLE CROSS OPP M S RAMAIAH HOSPITAL NEW BEL ROAD BANGALORE 560 094 | BENGALURU URBAN | KARNATAKA | 560094 | Admitted-Finance |
| 2 | Admitted-Finance 606 80 FEET ROAD 7TH BLOCK 2ND PHASE BANASHANKARI 3RD STAGE BANGALORE 560 085 | BENGALURU URBAN | KARNATAKA | 560085 | Admitted-Finance |
| 3 | Admitted-Finance NO 12 5TH B CROSS SHARADAMBA NAGAR M E S ROAD BANGALORE 560013 | BANGALORE | BANGALORE | KARNATAKA | 560013 | Admitted-Finance |
| 4 | Admitted-Finance | Admitted-Finance |
Tender Value
₹20 L
EMD Value
₹40,000
Closing Date
12 Nov 2020, 6:00 pmClosed
CWE ARMY BANGALORE
HQ CWE ARMY BANGALORE 101 Dickenson Road Bangalore 560042
REPAIR / MAINTENANCE /REWINDING OF TRANSFORMER, HT SWITCH GEARS, CSS AND ALL OTHER HT CONNECTED WORKS UNDER GE (NORTH) BANGALORE
2020_MES_367037_3
86003
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
BANGALORE
AS PER TENDER
7 documents required · 7 mandatory
₹500
GE (NORTH) BANGALORE
₹40,000
Yes
HQ CWE ARMY BANGALORE
21 Nov 2020
22 Oct 2020
14 Nov 2020
22 Oct 2020
12 Nov 2020
29 Oct 2020
22 Oct 2020 - 26 Oct 2020
26 Oct 2020
Amount
Taking down defective transformers of any size and capacity including disconnecting electric connection LT/HT side from two pole structure, from platform or from indoor sub station transporting it to the workshop for repairs testing/commissioning and reinstallation after repairs as and when directed including making electric connection on HT/LT side complete all as directed.
Strip opening of transformer 315 to 500 KVA, 11 KV/440 volts indoor/outdoor of any make/type after unscrewing nuts/bolts, washers and taking down other connected accessories, such as temp gauge/breather, conservator tank for rewinding of HT/LT coils ( Payment of repairs replacement of parts, rewinding of coils and filtration of oil shall be measured and paid for separately under relevant item of schedule complete all as directed.
All as per serial item No 2 above but of capacity 200 KVA to 250 KVA
All as per serial item No 2 above but of capacity 100 KVA to 160 KVA
Supply and replacement of HT coils made out of super enamelled copper winding wire for transformer capacity 100 KVA to 500 KVA complete all as directed. Note:- Mode of rewinding/gauge of winding wire shall be maintained as per the manufacturers design
Supply and replacement of LT coil of copper strip duly insulated/cotton covered/varnished as per the standard design complete all as directed. Note:- Mode of rewinding/gauge of winding wire shall be maintained as per the manufacturers design
Reconditioning of LT coils by removing old insulation, covering with super enamelled varnish, cotton tape etc complete all as directed.
Filtration & Dehydration of transformers oil by attending each transformers, HT OCB, LT OCB, HT VL switches etc through on line filtration equipment to with stand minimum dielectric strength 40 KV for 1 min at 2.5 mm gap and flash at 60 KV without disturbing/switching off system complete all as directed.
Supply and topping up of fresh transformer oil on transformer/OCBs having lower level of oil, leveling upto desired level having dielectric strength not less than 45 KV confirming to relevant IS complete all as directed.
Decanning of existing burnt transformer oil, washing the tank with petrol / spirit and refilling new transformer oil confirming to relevant IS complete upto desired level, oil dielectric strength 45- 50KV confirming to relevant IS complete all as directed.
Preparing the surface of the transformers for painting by cleaning thoroughly the surface for removing dirt, grease, oil, scales etc and spray painting with a coat of heat resistant synthetic enamel paint of suitable/specified colour as directed including painting/writing the SM and MES No on the transformer with white paint complete all as directed for the following capacities:-
(a) Transformer 500 KVA to 315 KVA.
(b) Transformer 250 KVA to 200 KVA.
(c) Transformer 160 KVA to 100 KVA.
Preparing the surface of LT panel at site for painting by cleaning and scrubbing throughly the surafce for removing dirts, grease, oil scale etc and painting with approved synthetic enamel paint complete all as directed
Preparing the surface of fencing, including post XPM, gate, pillars, other fittings for painting by cleaning and scrubbing throughly the surafce for removing dirts, rust deposition, oil, paint etc and painting with approved synthetic enamel paint complete all as directed
Replacement of tap changing device for 100 KVA to 500 KVA transformer complete all as directed.
Earthing complete with galvanized steel earth plate electrode 60 cm x 60 cm x 6mm thick buried directly in ground vertically to a depth not less than 2.25 metre below ground level with top edge of earth plate at a depth not less than 1.5 metre connected to galvanized strip 32x6 mm as earth lead up to 20 metre long by meaxns of nuts, bolts, thimbles, check nuts and washers etc made of galvanized iron connected to earthing test point all as shown in electrical plate No 3 of SSR Part-I 2010 and as specified or indicated and testing on completion including earth work and excavation in any type of soil PCC (1:3:6) type C1 chamber, pre cost slab 40mm thick in cement concrete (1:2:4) type B1 with 8 mm dia MS bars reinforced at 10 cm centre to centre both ways including funnel with watering pipe wire mesh and lugs, including test point complete all as directed. Note :- (i) Earthing strip and protection pipe to a length of 7.5 m is deemed to be included in the rate. (ii) The unit rate deemed to include taking down old earthing.
Replacement of worn out rubbersied cork sheet gasket form top cover and HT/LT connection side of transformer of any Make/Capacity and providing the new synthetic rubberised cork sheet on top cover and HT/LT connection both side & servicing of defective HT/LT bushes with brass spindle, nuts, bolts, washers insulation complete all as directed. Note :- (i) New nut and bolts with washer for top cover as per existing size is deemed to be included in the rate of this item. (ii) The unit rate deemed to include drain out transformer oil storing the same in suitable container to be provided by the contractor and refilling the same after necessary repair. (iii) Supply only HT/LT bushes shall be measured and paid separately
Supply only HT bushes with brass spindle with hexagonal brass nut 02 Nos and washers for the transformer of any capacity complete all as directed.
Supply only LT bushes with brass spindle with hexagonal brass nut 02 Nos and washers for the transformer of any capacity complete all as directed.
Replacement of temperature gauge for recording observation of temperature of transformer oil complete all as directed.
Replacement of gate valve brass 20mm ISI marked with iron wheel complete all as directed Note:- Make shall be same as that of replaced one.
Painting to cross arms "V" type with one coat of aluminum paint on 11 KV HT pole on distribution system after thoroughly cleaning the surfaces including cross arm clamps, pin insulators clamps, insulators pins, bolt nuts etc complete all as directed.
one coat of aluminum paint to angle iron channel both side and GI protection pipe of any type on two/four pole of 11 KV distribution system after thoroughly cleaning the surfaces including clamps complete all as directed.
Trimming /cutting tree branches with clearing space upto 2 meter from the over head conductor system all around for HT distribution system (two times in the currency of the contract)complete all as directed Note :- Measured each span as distance pole to pole
Trimming /cutting tree branches with clearing space upto 2 meter from two/four pole structure of sub station over head conductor system all around for HT distribution system (two times in the currency of the contract) complete all as directed
Stay assembly using stay rod not less than 20 mm accessories all as shown in plate No. 1 of SSR Part-I (loop type insulator, stay clamps, excavation and PCC shall be measured separately). complete all as directed
Loop type insulator, vitreous porcelain, brown Large size, with overall dimensions 140mm, clearance of hole 25.5mm complete all as directed
Galvanised stay wire of 7/4mm dia for stay assembly complete all as directed
Taking down transformer of any Make/capacity by disconnecting HT/LT connection and shifting from one location to another location with the help of chain pulley/crane and re-connecting to HT/LT connection at new location complete all as directed
Replacement of Breather assembly as per existing sizes with silica gel for absorbing moisture complete all as directed
Silica gel blue, chemical grade, crystal, type A for transformer breather complete all as directed
GI strip of sizes 32 x 6 mm fixed on walls/poles / shafts/pipes, etc including taking down existing strip complete all as directed.
ACSR (Aluminium conductor steel reinforced) conductor of any size of on poles including binding wire of appropriate size complete all as directed.
Out door type triple pole switch air brake (gange operated) each pole consisting of galvanised steel base HT insulators as per BSS/ISS, non ferrous knife and spring loaded contact, arcing horn mechanically operated , horizontal/vertical type mounted on insulator and steel frame complete, current rating up to 400 Amps.complete all as directed
Lightening arresters expulsion type complete with all fittings transmission class discharge capacity 65 Kilo Amps suitable for 11000 volts grade as in repairs complete all as directed
11 KV, Bottle type HT fuse of capacity 40 Amp for CSS in repairs complete all as directed
Replacement of male and female contact made out of brass copper alloy suitable for gang operated device 11 KV 200 Amps/400 Amps complete all as specified and directed.
Disc type insulator porcelain vitreous 145 mm high and 255 mm dia ball and socket type white or brown single disc assembly for tension clamps for conductors working pressure 11000 volts in repairs complete all as directed
Pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 150mm height, 150mm dia for 11000 volts grade in repairs complete all as directed
Iron work of any type including cross arms, supports, bracing MS clamps etc made out of MS channel/ angle iron/ flat iron/ round section of any size and bolts, nuts and washers including painting with two coats of aluminium paint over a coat of red oxide primer in repairs complete all as directed
Cable jointing kit for 11 KV (earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sq mm in repairs complete all as directed
Cable jointing kit for 11 KV (earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sq mm to 185 sqmm in repairs complete all as directed
Cable jointing kit for 11 KV (earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sq mm in repairs complete all as directed
Cable jointing kit for 11 KV (earthed) grade cable for outdoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sq mm to 185 sqmm in repairs complete all as directed
Cable jointing kit for 11 KV (earthed) grade cable straight through joint heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sq mm in repairs complete all as directed.
Cable jointing kit for 11 KV (earthed) grade cable straight through joint heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sq mm to 185 sqmm in repairs complete all as directed. Note for item No.40 to 45:- Excavation, earth work, sand , PCC cover, shall be measured and paid separately under respective items.
Servicing of HT 11 KV CSS of any capacity including replacing of burnt out cable lugs, terminals and cleaning with air blower and calibration of any capacity of relay complete all as directed
Cable finding cable fault in HT cables any sizes complete all as directed.
Servicing of existing GOD with replacement with GI nuts bolts, washers and lugs etc. as per site requirement including necessary greasing and cleaning with petroleum jelly complete all as directed .
Excavation in trenches in hard/dense soil not exc 1.5 metre wide and not exc 1.5mtr in depth for laying of cables/pole foundation complete all as directed.
Excavation in trenches in hard/dense soil not exc 1.5 metre wide and exc 1.5m deep but not exc 3 metre in deep for pole foundation complete all as directed.
Returning, filling in trenches including spreading leveling watering and well ramming in layers with hard/dense soil not exc 25 cm thick in each layer complete all as directed.
Removing excavated soil to a distance n.exc 50m and deposition where directed at a level not exc 1.5 metre above the starting point complete all as directed.
Sand cushioning to under ground cable in layers (8 cm before laying the cable and 15 cm after laying the cable in trenches for cable protection complete all as directed. Note : Punned / completed thickness shall be measure for payment purpose.
Supplying and laying reinforced precast concrete cable cover, class HV, type 1 flat, size 300mmx l80mm x 40mm complete all as directed.
Supply laying, commissioning & testing cable HT UG cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cable (heave duty) with aluminium conductor, 11000 Volts grade of size 95 Sqmm 3 core suitable for 11 KV(E) system laid in trenches/ducts/encased in GI pipe/fixed to pole complete all as directed. Note :- (i) Excavation earth work sand PCC cover, GI pipe shall be measured and paid separately under respective items
Supply laying, commissioning & testing cable HT UG cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cable (heave duty) with aluminium conductor, 11000 Volts grade of size 185 Sqmm 3 core suitable for 11 KV(E) system laid in trenches/ducts/encased in GI pipe/fixed to pole complete all as specified and directed. Note :- (i) Excavation earth work sand PCC cover, GI pipe shall be measured and paid separately under respective items
Supply and erect Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-55 (11.0 metres long) complete all as directed. Note : Earth work, excavation, cross arms, PCC foundation and PCC coping shall be measured and paid seperately.
Plain cement concrete 1:3:6, type C1, using 20 mm graded stone aggregate for coping including necessary form work complete complete all as directed
Plain cement concrete 1:4:8, type D2, using 40 mm graded stone aggregate for foundation of poles, stay assembly etc., complete complete all as directed
Dismantling HT cable of both side from two pole structure and HT panel and servicing of HT panel by meggering of cable with a help of HT megger, cleaning of HT panel chamber with the help of air blower, replacement of burnt lugs & calibration of relay 01 (incomer) + 04 (outgoing) connected nuts bolts washers etc at 2 PARA complete all as directed:- Note:- Fixing of all items as mentioned below is included in the quoted rate of this item and supply only rate shall be measured and paid separately under respective items
(a) Supply only 11 KV Barrel fuse 60 Amps capacity complete complete all as directed.
(b) Supply only of NHP201699R1 Bushing 400 Series bolted type 11 KV complete complete all as directed. Make : ABB
(c) Supply only of NHP402076P15 C Ring 75X6 Bushing 400 Series Bolts complete complete all as directed. Make : ABB
(d) Supply only SF6 Gas cylinder 9 Kgs Article No:- SWT-431336-P2 complete as directed. Make : ABB
(e) Supply only 2REA024265POOO1 Reducer stud for cable bushing complete all as directed. Make : ABB
(f) Supply only PTMVT120702-01 24 KV VP IS Cord complete all as directed. Make : ABB
(g) Supply only Terminal protector silcab (Reychem) for 11 KV IVYN303050-060 complete all as directed.
in replacement of XPM net of size 4 mm dia GI wire 4 feet width complete with fixing around the platform of transformer structure complete including painting with two coat of aluminum paint over a coat of primer complete over mild steel members all as directed
GI tubing light grade 80 mm bore with all fitting laid in trenches/walls/Roads /pole for cable protection complete complete all as directed
Lucky Enterprises
Shanthi Construction
SREE VARU ELECTRICALS
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .