| 1 | L1₹1.6 CrAccepted-AOC ERODE 638 152 | ERODE | TAMIL NADU | 638152 | ₹1.6 Cr | L1 | Accepted-AOC Accepted |
| 2 | L2₹1.7 Cr+₹8.2 L (5.01%)Rejected-Finance 9 A PONGALIVALASU KODUMUDI POST ERODE 638 151 | KARUR | TAMIL NADU | 638151 | ₹1.7 Cr+₹8.2 L (5.01%) | L2 | Rejected-Finance Reject |
| 3 | Rejected-Technical COIMBATORE COIMBATORE TAMIL NADU | - | - | Rejected-Technical Not Satisfied |
| Sl No | Description | Qty | Unit | Sri Balaji Constructions | VRR CONSTRUCTION |
|---|---|---|---|---|---|
| 1.00VARIABLE REFRIGERANT FLOW OUTDOOR UNITS (VRF ODU): Supply Installation,Testing & Commissioning of modular type Variable Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor units suitable for cooling and heating,having all hermetically sealed inverter type Scroll Compressor(s),minimum two compressors for above 14HP modules, microprocessor based Controller, top discharge type condensing unit(s), with R410A Refrigerant, vibration isolators, with suitable foundation etc. complete as required.The unit shall deliver the rated capacity at AHRI Conditions and work even at 50°C ambient temperature without tripping.The unit shall be suitable to work on 400V+/10%, 3Phase, 50Hz AC power supply. The unit shall be filled with first charge of the refrigerant and ready for use as required.The COP at AHRI conditions shall not be less than 3.1 and IEER not less than 6.5 . | |||||
| 2.00A. Casette Unit | |||||
| 3.00 | 26.0 HP M-2026 | 4 | Nos | 26,03,580 ₹30,72,224.4 | 24,79,200 ₹29,25,456 Lowest |
| 4.00 | 10.0 HP M-2034 | 1 | Nos | 2,62,290 ₹3,09,502.2 | 2,49,760 ₹2,94,716.8 Lowest |
| 5.00CEILING MOUNTING TYPE CASSETTE UNITS (REGULAR): Supply, installation, testing and commissioning of the following capacity, ceiling mounting type, Variable Refrigerant Flow cassette Unit consisting of Thermo plastic Cabinet, Dynamically balanced centrifugal blowers, fan motors, fresh air port, Direct Expansion type cooling coil, Insulated drain tray, Prefilters, Electronic Refrigerant Flow Control valve, connection / branching kit, additional refrigerant charging, Room temperature sensor & Cordless remote controller, Infra red sensor, Control module self-diagnostic features, Inbuilt condensate drain pump, necessary supports as per the specification and drawings. The VRF System shall use R410A as refrigerant. NOTE: Indicated Cooling & airflow Capacities of IDUs are the minimum requirement to meet the Designed indoor Conditions for the out door peak Weather Conditions as noted on the drawings and specification. The HVAC Vendor is responsible to make the selection of suitable indoor units from their available product range to meet both TR & airflow rate and considering capacity loss due to pipe length and level difference between VRF IDUs & VRF ODUs and Indoor/Outdoor design conditions etc. | |||||
| 6.00a. Indoor 4 Way Casette Unit | |||||
| 7.00a. Indoor 4 Way Casette Unit | |||||
| 8.00 | 1.0 TR | 12 | Nos | 5,58,180 ₹6,58,652.4 | 5,31,540 ₹6,27,217.2 Lowest |
| 9.00 | 1.5 TR | 8 | Nos | 4,04,880 ₹4,77,758.4 | 3,85,520 ₹4,54,913.6 Lowest |
| 10.00 | 2.0 TR | 7 | Nos | 3,68,235 ₹4,34,517.3 | 3,50,350 ₹4,13,413 Lowest |
Tender Value
₹2.0 Cr
EMD Value
₹2.0 L
Closing Date
11 Aug 2025, 3:00 pmClosed
THE COMMISSIONER TAMBARAM CORPORATION
TCMC Main Office
Supply and installation of HVAC in New Corporation office Building at Third Floor in Tambaram City Municipal Corporation
2025_DMA_589343_6
340/2025/E1/Z4
Open Tender
Civil Works
Works
90 days
TCMC Main Office
Please refer Tender documents.
3 documents required · 3 mandatory
₹10,000
₹2.0 L
11 Nov 2025
5 Aug 2025
11 Aug 2025
5 Aug 2025
11 Aug 2025
5 Aug 2025
VARIABLE REFRIGERANT FLOW OUTDOOR UNITS (VRF ODU): Supply Installation,Testing & Commissioning of modular type Variable Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor units suitable for cooling and heating,having all hermetically sealed inverter type Scroll Compressor(s),minimum two compressors for above 14HP modules, microprocessor based Controller, top discharge type condensing unit(s), with R410A Refrigerant, vibration isolators, with suitable foundation etc. complete as required.The unit shall deliver the rated capacity at AHRI Conditions and work even at 50°C ambient temperature without tripping.The unit shall be suitable to work on 400V+/10%, 3Phase, 50Hz AC power supply. The unit shall be filled with first charge of the refrigerant and ready for use as required.The COP at AHRI conditions shall not be less than 3.1 and IEER not less than 6.5 .
A. Casette Unit
a. Indoor 4 Way Casette Unit
a. Indoor 4 Way Casette Unit
B. Ductable Unit
Total Indoor Ductable Unit
SECTION- B : REFRIGERANT PIPING AND PVC CONDESATE PIPING
6.4 mm dia with 19 mm thick insulation
Liquid Delivery Line-Compressor to Evaporator Coil
9.5 mm dia with 19 mm thick insulation
Liquid Delivery Line
12.7 mm dia with 19 mm thick insulation
Liquid and Gas Delivery Line ( For Indoor to Outdoor)
15.9 mm dia with 19 mm thick insulation
Liquid and Gas Delivery Line ( For Indoor to Outdoor)
19.1 mm dia with 19 mm thick insulation
Liquid and Gas Delivery Line ( For Indoor to Outdoor)
22.2 mm dia with 19 mm thick insulation
Liquid and Gas Delivery Line ( For Indoor to Outdoor)
24.5 mm dia with 19 mm thick insulation
Liquid and Gas Delivery Line
28.6 mm dia with 19 mm thick insulation
Liquid and Gas Delivery Line
31.75 mm dia with 19 mm thick insulation
Liquid and Gas Delivery Line
34.9 mm dia with 19 mm thick insulation
Liquid and Gas Delivery Line
38.1 mm dia with 19 mm thick insulation
Liquid and Gas Delivery Line
42.0 mm dia with 19 mm thick insulation
Liquid and Gas Delivery Line
44.45 mm dia with 19 mm thick insulation
Liquid and Gas Delivery Line
PVC CONDENSATE PIPING: Supply,installation,Testing & Commissioning of Heavy duty PVC pipes of following sizes; with 9mm thick Aluminium Foil faced Nitrile Rubber Insulation
Water drain pipe line (1” PVC Pipe)
25mm Dia for All Floors DATA-A-I
32mm Dia for All Floors DATA-A-ii
Supply and laying of 2 core 1.5 sq.mm. armoured copper cable for control wiring to the Terrace Pump Motor with runs of 14 SWG TC wire for earthing, providing in wall with suitable size GI clamps, screws, wooden plug, end termination by using suitable size cable glands, copper sockets and etc., as directed by the Departmental Officers.SD M-0786
For Communication Purpose
Supply and filling of R410A Refrigerant Gas
Filling of Refrigerant Gas i.e Each HP Need 0.5kg/HP M-2046
Testing of Nitrogen Pressure in Coolant Pipes By maintaining it by hold for certain Periods
Nitrogen Pressure Testing
FACTORY MADE RECTANGULAR GI DUCTING : Supply, installation, testing and commissioning of factory made lock-forming quality rectangular GI ducting, complying with IS: 277 and having 120 GSM coating classification. The price include the cost of necessory accessories & supports (like TDF flanges, ms angle flanges, neoprene gaskets, threaded rod, corner saddles, guide vanes as per SMACNA standards, joints, labelling etc..
Supply, Fabrication and erection of fabricated ducting made up of GI Sheets of 24 Gauge thickness M-2006
Supply, Fabrication and erection of fabricated ducting made up of GI sheets of 22 Gauge thickness M-2007
SUPPLY AIR ROUND DIFFUSER: Supply, installation, testing and balancing of aluminum powder coated circular / square diffuser with collar damper as per approved shop drawings and with standard flange size.
300mm Dia M-2009
ROUND DISC VALVE:
Supply, fixing and testing of Al. powder coated Round disc Valve of 150 mm dia for Toilet Exhaust with damper.
COLLAR DAMPER
Supply, installation, testing and commissioning of aluminium collar damper to be mounted for grilles & diffusers.
FIRE RETARDANT CANVASS
Supply, installation, testing and commissioning of fire-retardant canvss, with GI matching flanges, with a provision of operable zip. The entire assembly shall be fabricated at factory.
MS SUPPORT WORK
Supply, fabrication and installation of mild steel support work for support works as per the drawing , other than for duct, pipe and equipment supporting. The supports should be duly painted using two coats of primer and two coats of black enamel paint. DATA-E
SECTION – D : INSULATIONS
DUCT THERMAL INSULATION :
Providing and fixing of External Wall Thermal Insulation using extruded polystyrene rigid foam ship-lap edged, three dimensional closed cell structure Insulation board of required thickness over the plastered/ precast/ Masonry/ levelled brick wall, complying with ASTM C 578 type VI, Chlorofluoro carbons & Hydro chlorofluoro carbons Free, having K (thermal conductivity) value of 0.0289 W/m.K or less as per ASTM C 518, compressive strength of ≥ 350 kPa at 10% deflection listed as per ASTM D 1621, density not less than 34kg/cum as per ASTM D 1622, water absorption ≤ 0.3% by volume as per ASTM C - 272, oxygen index of 24 as per ASTM D 2863,Fire retardant property as per DIN 4102, Part 1 of class B2 and fixed with cementitious adhesive and fasteners, Level the surface using Glass fiber mesh with Polymer modified cementitious mortar/adhesives. The Protection profile in edges/ corners, etc., complete complying with standard specification.
9mm – U value of0.58W/M2k
DUCT ACOUSTIC INSULATION :
Design, Manufacture, Supply, Installation, Testing, and Commissioning of Open cell Nitrile rubber for Acoustics , of Class-1 with Ultrafresh Antimicrobial protection as per ASTM G21, ASTM G22, UL-181 and E2180 , FM Global, Density 140-180Kg / m3, UL94 approved (HBF, HF 1 & HF 2) in accordance to UL 94,1996.Thermal conductivity 0.047 W / MK at 20 Deg C, Air Erosion Resistance test Confirming to ASTM Standard C 1071-05 (section 12.7). For application use Low Voc Adhesive. thickness as per specification. [ for duct linear=15mm thk ] Note - if the adhesive is not self adhiesive type then the glue should be used with the same manufacturer.
10mm Thick in Double Height Council Hall Y Axis and X Axis
SECTION – E : FANS
CABINET FRESH FAN/INLINE EXHAUST FAN:
Supply, installation, testing and commissioning of Ventilation fan cabinet type units. The unit shall be 0.6mm GIS construction, belt driven centrifugal fan, High efficiency motor, spring vibration isolator for fan and motor, Fire retardant canvass connections, with acoustic enclosure for fan & noise level not exceed 65 dBA at 1.5m distance,weatherproof type, internal power and control wiring, GI base frame complete as per specifications as required. Fan motor shall be suitable for 415±10% volts, 50Hz, 3 phase AC supply & & 230V, 1 phase, 50Hz AC supply.
Air Qty: 2210 CFM, ESP: 15mmWC
Air Qty: 600 CFM, ESP: 15mmWC
Air Qty: 435 CFM, ESP: 15mmWC
Supply and fixing of Refnet joint M-2060
Supply of Y-Joints
Supply and fixing of Twinning Joints M-2060
AC Twinning Joints
HVAC PANEL - THIRD FLOOR
THIRD FLOOR: Supply, Loading,transportation Unloading, Storing, Shifting to Installation, Testing & Commissioning of LT Switch board ( PHE PANEL )cubicle type, complete as required as per Main SLD & M V PANEL ANNEXURE. NOTE - AS PER SLD
Supply, Loading,transportation Unloading, Storing, Shifting to Installation, Testing & Commissioning of LT Switch board cubicle type, complete as required as per Site Condition
INCOMER : 250A 4P 36kA MCCB - 1 No 250/5A CT ELR - 1 Set ON OFF TRIP - 1 SET MFM - 1 SET RYB - I SET OUTGOING: 63A TPN MCCB with Star-Delta Starter - 5 No' s 32A TPN MCCB with Star-Delta Starter - 4 No' s All interconnection cables and accessories
Supply and Laying of 3 1/2 x 25 sq.mm. PVC armoured LTUG cable in suitable size HDPE pipe in a trench to be excavated at a depth of 0.75 metre and refilling the earth to make good. SD-659
SSB-1 to ACDB-1
Supply and Laying of 4 x 16 sq.mm. PVC armoured LTUG cable in suitable size HDPE pipe in a trench to be excavated at a depth of 0.75 metre and refilling the earth to make good. SD-658
SSB-1 to PDB-1
Supply and Laying of 4 x 10 sq.mm. PVC armoured LTUG cable in suitable size HDPE pipe in a trench to be excavated at a depth of 0.75 metre and refilling the earth to make good. SD-657
LT Panel to FF HVAC Panel
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .