| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹147.5 CrAccepted-AOC PLAT NO 943 54TH STREET T V S COLONY ANNANAGAR WEST EXTENSION CHENNAI PIN 600 101 | CHENNAI | CHENNAI | TAMIL NADU | 600101 | ₹147.5 Cr | 1 | Accepted-AOC L1 tenderer |
Tender Value
Refer Docs
EMD Value
₹36.5 L
Closing Date
9 Mar 2022, 3:00 pmClosed
SE (C and M)
CMWSSB, 3rd Floor, Commissionerate of Municipal Administration, Urban Administrative Building, Santhome High Road, MRC Nagar, Raja Annamalaipuram ,Chennai 600 028
Providing comprehensive underground sewerage scheme to Madipakkam (Division 187 and 188), Area XIV (Perungudi) in Chennai City.
2022_CMWSS_222381_1
CNT/SEW/NCB/AMRUT2/001/2021-22
Open Tender
Civil Works
900 days
Chennai
Please refer Tender documents.
5 documents required · 5 mandatory
₹0
₹36.5 L
Office of SE (C and M)
9 Sept 2022
4 Feb 2022
10 Mar 2022
4 Feb 2022
9 Mar 2022
23 Feb 2022
16 Feb 2022
Amount
BILL NO 1. Providing Collection System, Pumping main, Pipes & Specials in Wells and allied works
Supply, delivery, laying and jointing of Double wall corrugated /structured wall plastic polyethylene/polypropylene pipes DWC PE or PP of class SN-8 with non-smooth external Annular Corrugated and Smooth Internal Surfaces in Standard lengths with online coupler and spigot type confirming to IS 16098 (Part-2) 2013 / EN: 13476-3 (latest revision) including elastomeric sealing ring gasket suitable for DWC PE or PP pipes conforming to IS: 5382 (latest revision), freight,insurance, loading into the truck and transporting to the stores / site.. etc including earth work excavation in hard stiff clay,stiff black cotton,hard red earth, shales, muram, gravel, stoney earth and earth mixed with small size boulders and hard gravelly soil, depositing the earth on banks with initial lead of 10m and lowering into trenches, aligning and testing of DWC PE or PP pipes, watering and ramming to consolidation, etc., complete
295/250mm OD/ID DWC PE or PP Pipe
at 1.0m deep
at 1.5m deep
at 2.0m deep
358/300mm OD/ID DWC PE or PP pipe
at 1.5m deep
at 2.0m deep
Supply, delivery, laying and jointing of Double wall corrugated /structured wall plastic polyethylene/polypropylene pipes DWC PE or PP of class SN-8 with non-smooth external Annular Corrugated and Smooth Internal Surfaces in Standard lengths with online coupler and spigot type confirming to IS 16098 (Part-2) 2013 / EN: 13476-3 (latest revision) including elastomeric sealing ring gasket suitable for DWC PE or PP pipes conforming to IS: 5382 (latest revision), freight,insurance, loading into the truck and transporting to the stores / site.. etc including earth work excavation in hard stiff clay,stiff black cotton,hard red earth, shales, muram, gravel, stoney earth and earth mixed with small size boulders and hard gravelly soil, depositing the earth on banks with initial lead of 10m and lowering into trenches, aligning and testing of DWC PE or PP pipes, watering and ramming to consolidation including timbering the trenches for depths 2.5m and above, pumping out subsoil water etc., complete.
295/250mm OD/ID DWC PE or PP Pipe
at 2.5m deep
at 3.0m deep
358/300mm OD/ID DWC PE or PP pipe
at 2.5m deep
at 3.0m deep
Supply, delivery of CI socket spigot pipes of LA class including rubber gaskets as per the latest revision of IS 1536, laying, jointing and testing CI pipes (LA class) including earth work excavation for trenches in hard stiff clay, black cotton, hard red earth, shales, murams, gravel, stoney earth and earth mixed with small size boulders and hard gravelly soil, depositing the earth on banks with initial lead of 10m and initial lift of 2m, lowering the pipes in to the trenches, aligning, making rubber joints, testing CI pipes, refilling the trenches with excavated soil, watering and ramming to consolidation, disposal of surplus earth including timbering the trenches for the depths up to 2.0m and above, pumping out sub soil water etc., complete. (For Gravity Sewers)
450mm dia CI pipe
at 1.5m deep
at 2.0m deep
Supply, delivery of CI socket spigot pipes of LA class including rubber gaskets as per the latest revision of IS 1536, laying, jointing and testing CI pipes (LA class) including earth work excavation for trenches in hard stiff clay, black cotton, hard red earth, shales, murams, gravel, stoney earth and earth mixed with small size boulders and hard gravelly soil, depositing the earth on banks with initial lead of 10m and initial lift of 2m, lowering the pipes in to the trenches, aligning, making rubber joints, testing CI pipes, refilling the trenches with excavated soil, watering and ramming to consolidation, disposal of surplus earth including timbering the trenches for the depths of 2.5m and above, pumping out sub soil water etc., complete. (For Gravity Sewers)
250mm dia CI pipe
at 3.5m deep
at 4.0m deep
at 4.5 m deep
300mm dia CI pipe
at 3.5m deep
at 4.0m deep
at 4.5 m deep
at 5.0 m deep
at 5.5 m deep
at 6.0 m deep
350mm dia CI pipe
at 2.5m deep
at 3.0m deep
at 3.5m deep
at 4.0m deep
at 4.5 m deep
400mm dia CI pipe
at 3.0m deep
at 3.5m deep
at 4.0m deep
at 4.5 m deep
450mm dia CI pipe
at 2.5m deep
at 3.0m deep
at 3.5m deep
at 4.0m deep
at 4.5 m deep
at 5.0 m deep
at 5.5 m deep
500mm dia CI pipe
at 4.5 m deep
at 5.0 m deep
at 5.5 m deep
600mm dia CI pipe
at 3.5m deep
at 4.0m deep
at 5.0 m deep
700mm dia CI pipe
at 4.0 m deep
at 4.5 m deep
at 5.5 m deep
Supply delivery of CI Socket spigot pipes including rubber gaskets as per the latest revision of IS 1536,laying and jointing including earth work excavation for trenches in hard stiff clay, black cotton, hard red earth, shales, murams, gravel, stoney earth and earth mixed with small size boulders depositing the earth on banks with initial lead of 10m and initial lift of 2m, lowering pipes in to the trenches, aligning, making rubber joints, refilling the trenches with excavated soil, watering and ramming to consolidation, disposal of surplus earth,pumping out sub soil water etc.complete (For pumping main)
200mm dia CI LA class pipe at 1.5m depth
250mm dia CI LA class pipe at 1.5m depth
300mm dia CI A class pipe at 1.5m depth
450mm dia CI A class pipe at 1.5m depth
600mm dia CI A class pipe at 2.0m depth
750mm dia CI A class pipe at 2.0m depth
Cement concrete 1:3:6 using 40mm gauge hard broken stone jelly for PCC works SRC including laying in layers of not more than 15cm thick,compacting, curing etc complete for encasing and end concrete.
Construction of MachineHole using Sulphate Resistant Cement at various depths to invert including earthwork excavation as per SS 20B, laying cement concrete in C.M. 1:3:6 using 40mm B.G.jelly for foundation, sinking well kerb below G.L. for 4.5m depth and above, pumping, timbering charges for 2.5m depth and above, stock brick work in C.M. 1:3, for 23cm thick wall and over 23cm thick wall, plastering interior with C.M. 1:3, 20mm thick and exterior with C.M. 1:3, 12mm thick, laying plain cement concrete 1:3:6 using 12.0mm to 20mm B.G.jelly fixing the frame, providing C.I. steps, manhole cover and frame, benching and channelling including refilling the trench with excavated earth and disposal of surplus earth etc. complete for the following sizes for each MachineHole
at 1.0m deep
at 1.5m deep
Construction of Precast circular RCC MachineHole using sulphate resistant cement with M30 design mix concrete including earthwork excavation as per SS20B including timbering and pumping charges(for 2.5m depth and above), supplying & filling sand for bedding, providing plain cement concrete 1:1.5:3 using 20mm hard broken stone jelly for foundation, providing base units of 1m height (base slab and sidewall),riser unit (without corbel) of varying heights to suit the various depth requirements and roof slab including cost of steel reinforcement, cost of fabricating the steel mould using MS sheet and ISA angles including material and labour cost, providing CI steps, fixing FRC MachineHole frame and door, benching and channelling, refilling with excavated earth and disposal of surplus earth, joining of precast units by grouting with CM1:1 and polyurethane based water proofing compound 1% (by weight of cement ) at shear key and protruded bars- grout holes locations, cost of conveyance and erection charges of precast MachineHole at the required position as directed by the engineer at site including testing the manhole with water for 48 hours to check water tightness and rectifying the defects if any for the following size and depths:
1200mm dia Circular MachineHole for Sewers (upto 450mm dia)
at 2.0m deep
at 2.5m deep
Construction of RCC MachineHole using sulphate resistant cement with M30 design mix concrete including earthwork excavation as per SS20B , providing point edge to well kerb for sinking using ISA 150x75x10mm weighing at 16.9kg/m, sinking well kerb below 2.0m from G.L. or by open excavation for various depth as per site conditions with M30 mix for side wall, raft and roof slab, including cost of steel reinforcement , including bailing and pumping out water, formwork, plugging the bottom with PCC 1:3:6 using 40mm hard broken granite jelly, laying plain cement concrete 1:3:6 using 12mm to 20mm hard broken granite jelly for fixing the frame, fixing FRC manhole cover and frame, providing CI steps, ,benching and channelling including refilling the trenches with excavated earth and disposal of earth etc., including testing the manhole with water for 48 hours to check water tightness and rectifying the defects if any complete for the following size of Machinehole
1200mm dia Circular MachineHole for Sewers (upto 450mm dia)
at 3.0m deep
at 3.5m deep
at 4.0m deep
at 4.5m deep
at 5.0m deep
at 5.5m deep
at 6.0m deep
1500mm dia Circular MachineHole for Sewers (500mm dia & above)
at 3.5m deep
at 4.0m deep
at 4.5m deep
at 5.5m deep
Supplying and fixing 150mm dia MS Ventilating columns 6.0m length with CI Base for Ventilating column, Wire Cowl, Supplying, Laying, Jointing and Testing of 150mm dia stoneware pipe to a length of 6m for each column with 100mm SW stopper including cost of joining materials such as cement, sand and spun yarn with necessary civil works for construction of Masonry Pillars, earthwork excavation, refilling etc., complete.
Providing Iron Barricading of size 2.50 m width and 1.75 m height using 40x40x4 mm angle for outer frame supports, 25 x 25 x 3 mm angle for inner frame supports and 20 gauge thickness MS sheet for name board (as per drawing) including cutting, welding, fabrication charges and one coat of primer and 2 coats of enamel paint of approved quality, writing "METRO WATER" & work detail/ caution sign, providing necessary interlocking arrangements with adjoining units, fixing danger flags, danger lights, reflectors, fixing stickers etc, including watching during night and placing the barricading units as directed at the sites
Cutting Asphaltic Road
Non Bus route
Bus route- GCC
Bus route- SH/NH
Cutting Cement Concrete Road
Cutting CI Pipes
200mm dia CI pipe
250mm dia CI pipe
300mm dia CI pipe
350mm dia CI pipe
400mm dia CI pipe
450mm dia CI pipe
500mm dia CI pipe
600mm dia CI pipe
700mm dia CI pipe
750mm dia CI pipe
Cutting DWC PE Pipes
295/250mm OD/ID DWC PE or PP Pipe
358/300mm OD/ID DWC PE or PP pipe
Providing House service connection: Supplying, laying jointing and testing UPVC pipe including earthwork excavation for trenches in hard stiff clay, stiff black cotton, hard red earth, shales, murams, gravel, stoney earth and earth mixed with small size boulders and hard gravelly soil, depositing the earth on banks with initial lead of 10m. lowering the pipes into the trenches, aligning, refilling the trenches with excavated earth in layers of not more than 23cm thick watering, ramming to consolidation and disposal of surplus earth etc., complete
110mm dia upto a depth of 1.0m
160mm dia upto a depth of 1.5m
Supplying and fixing drop pipes with 'U' clamps etc. complete (inside MachineHoles) at required level as type design cutting, jointing and filleting as per specification etc. complete.
DWC pipe - 250mm dia
CI pipe - 450mm dia
Supplying and filling with stone dust for bedding for a thickness of 10cm and back fill envelope for a thickness of 150mm above the crown of the pipe for DWC PE pipes including ramming, consolidation etc., complete
Refilling with excavated soils (other than sand) complying with standard specifications for filling in foundations and basement.(for DWC PE or PP pipe length)
Disposal of surplus earth (for DWC PE or PP pipe length)
Inspection Chamber for HSC : Construction of inspection chambers of following sizes with earth work excavation for foundation, 23cm thick concrete bed using 40mm brick jelly concrete in C.M. 1:4:10 for foundation, brick work in C.M. 1:6 for chamber, plastering with C.M. 1:3,12mm thick, benching, channelling, supplying and fixing 45x45cm medium weight L.S. cover and frame, etc., complete
a) Supply, conveying and fixing CI specials as per the latest revision of IS 1538 including with ISI markings on it including earthwork excavation, lowering into the trenches, aligning, refilling the trenches with excavated soil, watering and ramming to consolidation, etc.
750mm D/Soc CI 90o Bend
750mm D/Soc CI 45o Bend
750mm D/Soc CI 22.5o Bend
600mm D/Soc CI 90o Bend
600mm D/Soc CI 45o Bend
600mm D/Soc CI 22.5o Bend
450mm D/Soc CI 90o Bend
450mm D/Soc CI 45o Bend
450mm D/Soc CI 22.5o Bend
300mm D/Soc CI 90o Bend
300mm D/Soc CI 45o Bend
250mm D/Soc CI 90o Bend
250mm D/Soc CI 45o Bend
250mm D/Soc CI 22.5o Bend
200mm D/Soc CI 90o Bend
200mm D/Soc CI 45o Bend
200mm D/Soc CI 22.5o Bend
750 mm F/Spi Tail Piece
750 mm F/Soc Tail Piece
600 mm F/Spi Tail Piece
600 mm F/Soc Tail Piece
500 mm F/Spi Tail Piece
500 mm F/Soc Tail Piece
450 mm F/Spi Tail Piece
450 mm F/Soc Tail Piece
400 mm F/Spi Tail Piece
400 mm F/Soc Tail Piece
350 mm F/Soc Tail Piece
300 mm F/Spi Tail Piece
300 mm F/Soc Tail Piece
250 mm F/Spi Tail Piece
250 mm F/Soc Tail Piece
200 mm F/Spi Tail Piece
200 mm F/Soc Tail Piece
150 mm F/Soc Tail Piece
500 mm collars
400 mm collars
350 mm collars
300 mm collars
250 mm collars
200 mm collars
150 mm collars
750mm x 600 mm D/S taper
600mm x 400 mm D/S taper
600mm x 500 mm D/S taper
450mm x 350 mm D/S taper
350mm x 300 mm D/S taper
750mm x 700 mm CI D/F taper
750mm x 600 mm CI D/F taper
700mm x 500 mm CI D/F taper
600mm x 500 mm CI D/F taper
600mm x 400 mm CI D/F taper
500mm x 350 mm CI D/F taper
450mm x 400 mm CI D/F taper
450mm x 300 mm CI D/F taper
400mm x 300 mm CI D/F taper
400mm x 250 mm CI D/F taper
350mm x 300mm CI D/F taper
300mm x 250 mm CI D/F taper
300mm x 200 mm CI D/F taper
300mm x 150 mm CI D/F taper
250mm x 200 mm CI D/F taper
250mm x 125 mm CI D/F taper
200mm x 100 mm CI D/F taper
150mm x 100mm CI D/F Taper
150mm x 80mm CI D/F Taper
100mm x 80mm CI D/F Taper
750 x 400 mm CI A/S tee
600 x 350 mm CI A/S tee
450 x 250 mm CI A/S tee
300 x 200 mm CI A/S tee
250 x 150 mm CI A/S tee
200 x 150 mm CI A/S tee
750 mm x 150 mm D/Soc/Fl Tee
600 mm x 150 mm D/Soc/Fl Tee
450 mm x 100 mm D/Soc/Fl Tee
300 mm x 80 mm D/Soc/Fl Tee
250 mm x 80 mm D/Soc/Fl Tee
200 mm x 80 mm D/Soc/Fl Tee
750mm x 500 mm A/F Radial Tee
600mm x 400 mm A/F Radial Tee
450 x 300 mm A/F Radial tee
250 x 150mm A/F tee
300 x 150 mm A/F Radial Tee
200 x 100 mm A/F radial tee
750 mm D/F 90o Duck Foot Bend
600 mm D/F 90o Duck Foot Bend
450 mm D/F 90o Duck Foot Bend
400 mm D/F 90o Duck Foot Bend
350 mm D/F 90o Duck Foot Bend
300 mm D/F 90o Duck Foot Bend
250 mm D/F 90o Duck Foot Bend
200 mm D/F 90o Duck Foot Bend
150 mm D/F 90o Duck Foot Bend
100 mm D/F 90o Duck Foot Bend
80 mm D/F 90o Duck Foot Bend
750 mm dia D/F CI 90o Bend
600 mm dia D/F CI 90o Bend
400 mm dia D/F CI 90o Bend
b)Supply, conveying and fixing CI specials as per the latest revision of IS 1538 including with ISI markings on it including earthwork excavation, lowering into the trenches, aligning, refilling the trenches with excavated soil, watering and ramming to consolidation, etc.
450 mm dia D/F CI 90o Bend
350 mm dia D/F CI 90o Bend
300 mm dia D/F CI 90o Bend
250 mm dia D/F CI 90o Bend
200 mm dia D/F CI 90o Bend
150 mm dia D/F CI 90o bend
100 mm dia D/F CI 90o bend
750mm dia CI Blank flange
600mm dia CI Blank flange
450mm dia CI Blank flange
300mm dia CI Blank flange
250 mm dia CI blank flange
200mm dia CI blank Flange
200mm CI Bell Mouth
250mm CI Bell Mouth
300mm CI Bell Mouth
450mm CI Bell Mouth
600mm CI Bell Mouth
750mm CI Bell Mouth
500mm 1.0m cut pipe
400mm 1.0m cut pipe
400mm 2.0m cut pipe
350mm 2.0m cut pipe
300mm 1.0m cut pipe
200mm 1.0m cut pipe
200mm 2.0m cut pipe
250mm 1.0m cut pipe
250mm 2.0m cut pipe
150mm 2.0m cut pipe
Supply, conveying and fixing following CI pipes as per latest revision of IS 1536 with ISI markings on it excluding earthwork excavation
750 mm D/F C.I pipe - 1.5m long
750 mm D/F C.I pipe - 0.5m long
600 mm D/F C.I pipe - 0.5m long
450 mm D/F C.I pipe - 0.5m long
400 mm D/F C.I pipe - 0.5m long
400 mm D/F C.I pipe - 1.6m long
400 mm D/F C.I pipe - 2.0m long
400 mm D/F C.I pipe - 4m long
350 mm D/F C.I pipe - 1.0m long
350 mm D/F C.I pipe - 1.4m long
350 mm D/F C.I pipe - 1.5m long
350 mm D/F C.I pipe - 2.0m long
350 mm D/F C.I pipe - 3.0m long
350 mm D/F C.I pipe - 3.5m long
350 mm D/F C.I pipe - 0.5m long
300 mm D/F C.I pipe - 0.5m long
300 mm D/F C.I pipe - 3.0m long
300 mm D/F C.I pipe - 1.5m long
250 mm D/F C.I pipe - 0.5m long
250 mm D/F C.I pipe - 1.0m long
250 mm D/F C.I pipe - 1.5m long
250 mm D/F C.I pipe - 2.0m long
250 mm D/F C.I pipe - 2.5m long
250 mm D/F C.I pipe - 3.0m long
200 mm D/F C.I pipe - 0.5m long
200 mm D/F C.I pipe - 2.0m long
150 mm D/F C.I pipe - 0.5m long
150 mm D/F C.I pipe - 0.6m long
150 mm D/F C.I pipe - 1.5m long
150 mm D/F C.I pipe - 2.0m long
150 mm D/F C.I pipe - 2.5m long
150 mm D/F C.I pipe - 3.0m long
125 mm D/F Pipe -0.5mlong
125 mm D/F Pipe -1.25mlong
100 mm D/F C.I pipe - 0.4m long
100 mm D/F C.I pipe - 0.5m long
100mm dia D/F CI Pipe -1.0m long
100 mm D/F C.I pipe - 1.5m long
100 mm D/F C.I pipe - 2.0m long
100mm dia D/F CI Pipe -2.5m long
100mm dia D/F CI Pipe -3.0m long
From Desilting pump to silt pit - 100mm dia D/F CI Pipe -0.5m length
From Desilting pump to silt pit - 100mm dia D/F CI Pipe -1.0m length
From Desilting pump to silt pit - 100mm dia D/F CI Pipe -2.0m length
From Desilting pump to silt pit - 100 mm dia D/F CI bend 90o bend
From Desilting pump to silt pit - 100 mm D/F 90o Duck Foot Bend
Supplying and laying 100 mm dia CI D/F pipe - 1m as per latest revision of IS 1536 with ISI markings on it length including earthwork excavation in all kinds of soil, including refilling the excavated earth etc. complete.
Supplying and laying 100 mm dia CI D/F pipe - 2m as per latest revision of IS 1536 with ISI markings on it length including earthwork excavation in all kinds of soil, including refilling the excavated earth etc. complete.
Supplying, laying , jointing and testing 110 mm dia UPVC pipes SN8-SDR 34(S 16.5) AS PER IS 15328/2003 pipe including earthwork excavation for trenches in hard stiff clay, stiff black cotton, hard red earth, shales, muram, gravel, stoney earth and earth mixed with small size boulders and hard gravelly soil depositing the earth on banks with initial lead of 10m , lowering the pipes into the trenches, aligning, refilling the trenches with excavated earth in layers of not more than 23 cm thick watering , ramming to consolidation , depositing the surplus earth, etc. complete at an average depth of 1.50m.
Supplying and delivery at site, conveying and fixing the CI sluice valves as per IS 14846/2000 PN 1 with ISI marking including loading, transportation charges and stacking etc complete as per specifications
500mm DN Sluice valve
400mm DN Sluice valve
350mm DN Sluice valve
300mm DN Sluice valve
250mm DN Sluice valve
200mm DN Sluice valve
150mm DN Sluice valve
100mm DN Sluice valve
80mm DN Sluice valve
Supplying and delivery at site, conveying and fixing the CI D/F Reflux valves as per IS 5312/Part I /84 with Bye-pass arrangements with ISI marking including loading, transportation charges and stacking etc complete as per specifications
350mm DN Non-return Valve
300mm DN Non-return Valve
250mm DN Non-return Valve
150mm DN Non-return Valve
100mm DN Non-return Valve
Supplying and delivery at site, conveying and fixing the CI double air valve as per IS14845/2000 with ISI marking including loading, transportation charges and stacking etc complete as per specifications
150mm Double Air valve
100mm Double Air valve
80mm Double Air valve
Jointing the CI specials with molten lead and yarn including caulking the joints and testing to the required pressure with water. (Including cost of Jointing materials)
Jointing the double flanged pipes and specials with rubber insertion to the required specifications with M.S bolts and nuts, and testing the pipes to the required pressure including cost of joining materials etc complete
Testing of M.S./C.I./P.V.C./D.I pipes with hydraulic testing equipment by filling with water(including cost of water @ Rs.60/KL) and testing to recommended pressure in convenient stetches and attending the bursts if any occured during the test, excluding the cost of pipes, including other incidental and operational charges, etc., complete for following diameters of pipes
750mm dia
600mm dia
450mm dia
300mm dia
250mm dia
200mm dia
Providing thrust blocks with Plain Cement Concrete in 1:3:6 with 40mm HBG for the pumping main including the cost of shuttering, cost of reinforcement ,compaction, curing etc. complete.
750mm D/Soc CI 90o Bend
750mm D/Soc CI 45o Bend
750mm D/Soc CI 22.5o Bend
600mm D/Soc CI 90o Bend
600mm D/Soc CI 45o Bend
600mm D/Soc CI 22.5o Bend
450mm D/Soc CI 90o Bend
450mm D/Soc CI 45o Bend
450mm D/Soc CI 22.5o Bend
300mm D/Soc CI 90o Bend
300mm D/Soc CI 45o Bend
250mm D/Soc CI 90o Bend
250mm D/Soc CI 45o Bend
250mm D/Soc CI 22.5o Bend
200mm D/Soc CI 90o Bend
200mm D/Soc CI 45o Bend
200mm D/Soc CI 22.5o Bend
Electromagnetic Flow Meter conforming to ISO 17025 Standard shall be a velocity sensing Electromagnetic type, microprocessor based signal converter, sealed housing, flanged tube meter for 1.0 Mpa working pressure, manufactured to highest standard available for mag-meters, equipped with minimum six digit digital totalizers, reading in units of kiloliters and shall be accurate within 0.5% of Measured value, shall operate within a range of 0.3m/sec to 4 m/sec and be constructed as follows:Meter tube (Sensor) shall be fabricated from stainless steel tube and use class PN10 flat face carbon street flanges in accordance with IS 1538. These flanges shall be welded to the flow tube. The internal and external of the meter tube shall be blasted to near white and lined with hard rubber /Polyurethane/PTFE preferably by SBR or EPDM. Meter tube shall have a constant nominal inside diameter offering no obstruction to the flow. The accuracy should be inclusive of linearity, hysteresis, repeatability, temperature and pressure effects.
Coil Housing shall be fabricated from stainless steel/SS304/Die cast Aluminium/Carbon Steel with Anticorrosive paint for corrosion resistance and welded to the tube providing a completely sealed environment for all coils, electrode connections and wiring harness capable of submerged or buried operation. Signal Converter shall be pulsed DC coilexcitation type with auto zeroing. The signal converter shall be remotely mounted away from the meter. The converter shall indicate direction of flow and provide a flow rate indication and a total of flow volume for both forward and reverse directions. The converter shall provide an isolated 4-20 mA output into minimum 500-ohm load and a frequency output of a maximum of 0-10 KHZ and a scaled pulse output. The microprocessor based signal converter shall have a self-diagnostic test mode and a backlit display that continuously displays “Rate of Flow” and “Total Volume.”Converter shall be supplied with a programmable low flow drop out and empty pipe zero return. The signal converter housing should be die-cast aluminium with glass window. The converter cum transmitter should be fully programmable form the front facia. The programming should be user friendly, self- prompting menu driven. Flow meter test calibration certificate should be provided with life cycle test certificate from FCRI/NABL accredited lab.
100mm dia
125mm dia
150mm dia
250mmdia
350mm dia
400mmdia
BILL NO: 2 Construction of Screen Well, Suction Well, Valve Chamber, Grit Chamber, Pump House, Rainwater Harvesting Structures,Water Supply and Sanitary Items, R.C.C Sump, Compound Wall, Air valve Chamber, Sluice valve Chamber, Scour valve Chamber, Discharge Chamber, Dismantling of existing Structure and Approach road
Earth work excavation in hard stiff clay, stiff black cotton, hard red earth, shales, murum, gravel, stoney earth or earth mixed with small size boulders and hard gravely soil as per SS20B with initial lead of 10m and lift of 2m etc. complete.
For Open excavation 0- 2 m depth
From 2.0 m to 3.0 m below GL
For trenches & foundation a) 0 - 2 m depth
From 2.0 m to 3.0 m below GL
Earthwork excavating and depositing on bank with an initial lead of 10 metres and initial lift of 2 metres by wedging chiselling and trimming to proper shape where blasting is prohibited. etc. complete.
For 2 to 3 m depth
For 3 to 4 m depth
For 4 to 5 m depth
For 5 to 6 m depth
For 6 to 7 m depth
For 7 to 8 m depth
Supplying and filling crushed stone sand (M sand) for foundation and basement including watering, consolidating, ramming etc. complete.
Providing form work with centering for soffits of reinforced cement concrete slabs or plain surfaces including strutting
From 1.0m above ground level to 3.0m below ground level (Curved Surface)
upto 3m high (below & above)
3m to 4m below GL
4m to 5m below GL
5m to 6m below GL
6m to 7m below GL
7m to 8m below GL
3m to 4m high
4m to 5m high
5m to 6m high
4m to 5m above invert level
5m to 6m above invert level(bottom of top slab)
5m to 6m below GL (bed for pump)
6m to 7m below GL (bed for pump)
7m to 8m below GL (bottom of top slab)
7m to 8m below GL (bed for pump)
6 to 7m above invert level (bottom of top slab)
8m to 9m below GL (bed for pump)
Cement concrete 1:3:6 using Crushed stone sand (M-sand) and 40mm gauge hard broken stone jelly for plain cement concrete works including laying in layers of not more than 15cm thick including ramming curing, etc., complete
upto 1.5m from G.L
1.5m to 4.5m depth
Cement concrete 1:2:4 using Crushed stone sand (M-sand) and 20mm gauge hard broken stone jelly for plain concrete works including laying ramming curing, etc., complete.
upto 1.5m below or above G.L
1.5m to 4.5m depth below G.L
Cement concrete 1:2:4 using Crushed stone sand (M-sand) and 20mm gauge hard broken stone jelly & SRC for plain concrete works including laying ramming curing, etc., complete.
Up to 1.5m Below & 1.0m above ground level
1.5m to 4.5m depth below G.L
4.5m to 9m depth below G.L
Cement concrete 1:3:6 using Crushed stone sand (M-sand) and 12-20mm gauge hard broken stone jelly for plain cement concrete works including laying in layers of not more than 15cm thick including ramming curing, etc., complete
1.5m to 4.5m depth above G.L
Cement concrete 1:3:6 using Crushed stone sand (M-sand) and 40mm gauge hard broken stone jelly & SRC for plain cement concrete works including laying in layers of not more than 15cm thick including ramming curing, etc., complete
4.5m to 9m depth below G.L
Providing and laying in position machine batched, machine mixed and machine vibrated design mix cement concrete of M25 grade for reinforced cement concrete structural elements under controlled water cement ratio with plasticiser using Crushed stone sand (M-sand) and 20mm and down graded machine broken granite stone jelly excluding the cost of centering and shuttering and reinforcement but including curing, fixing, fan clamps etc., as per standard specification and as directed by the Board officers complete.
upto 1.5m below G.L
1.5 m to 4.5m below G.L
upto 1.5m above G.L
1.5 m to 4.5m above G.L
4.5 m to 9.0m above G.L
Providing and laying in position machine batched, machine mixed and machine vibrated design mix cement concrete of M25 grade using SRC and M sand for reinforced cement concrete structural elements under controlled water cement ratio with plasticiser using 20mm and down graded machine broken granite stone jelly excluding the cost of centering and shuttering and reinforcement but including curing, fixing, fan clamps etc., as per standard specification and as directed by the Board officers complete
upto 1.5m below G.L
1.5 m to 4.5m below G.L
upto 1.5m above G.L
1.5 m to 4.5m above G.L
Providing and laying in position machine batched machine mixed and machine vibrated design mix. Sulphate resistance cement concrete M30 grade (River sand) for reinforced cement concrete using SRC structural elements under controlled water cement ratio with plasticiser using 20mm and down graded machine broken granite stone jelly excluding the cost of centering and shuttering and reinforcement but including curing, Mixer, vibrator, etc. as per standard specification and as directed at site
Up to 1.5m Below ground level & 1m above GL
From 1.5m to 4.5m Below ground level
From 4.5m to 9.0m Below ground level
Beyond 9.0m Below ground level
Providing and laying in position machine batched, machine mixed and machine vibrated design mix cement concrete of M30 grade with (River sand) for reinforced cement concrete structural elements under controlled water cement ratio with plasticiser using 20mm and down graded machine broken granite stone jelly excluding the cost of centering and shuttering and reinforcement but including curing, fixingetc., as per standard specification and as directed
Up to 1.5m Below ground level & 1m above GL
From 1.5m to 4.5m Below ground level
Providing point edge to well kerb using ISA 200x150x16 mm of weight 42.20 kg/m
Sinking well below water level including all incidental charges using special tools and plants such as air compressor, helmet etc., complete and including baling out water.
7.5m dia well
First depth of 2m
Second depth of 2m
Third depth of 2m
Fourth depth of 2m
6.5m dia well
First depth of 2m
Second depth of 2m
Third depth of 2m
Fourth depth of 2m
Fifth depth of 2m
5 m dia well
First depth of 2m
Second depth of 2m
Third depth of 2m
Fourth depth of 2m
3 m dia well
First depth of 2m
Second depth of 2m
Third depth of 2m
Fourth depth of 2m
2.5 m dia well
First depth of 2m
Second depth of 2m
Third depth of 2m
Plugging the bottom of the well using C.C 1:3:6 using 40mm gauge hard broken stone jelly with 10% extra cement for plain cement concrete works including laying in layers of not more than 15cm thick including ramming curing etc complete
4.5m to 9.0m depth
9.0m to 13.0m depth
Supplying and fabricating CRS/Thermo Mechanically Treated High Corrosion Resistance bars manufactured by Primary steel producers/Integrated Steel Plants as per IS:1786-2008,including fixing with binding wires, assembling and laying in position for all RCC works
Stock brick work with II class bricks in cement mortar 1:5 (Crushed stone sand (M-sand)) for 23 cm thick wall including curing etc. complete
Up to 1.5m above ground level
From 1.5 to 4.5m above GL
Stock brick work with II class bricks in C.M. 1:4 (Crushed stone sand (M-sand)) for 23 cm thick wall including curing etc.complete
Up to 1.5m below & above ground level
Ground floor
From 1.5 to 4.5m below GL
Stock brick work in cement mortor 1:4 using second class bricks including curring etc. complete for 11cm thick wall.
Supplying and fixing 0.43 cu.m. of broken glass pieces on the coping of the compound wall with C.M. 1:3, 20mm thick including curing, etc., complete as directed
Supplying and fixing barbed wire fencing over the proposed compound wall with ‘L’ angle iron 50 x 50 x 6mm & 1.45m posts bent to shape at 2.5m centres with 6 rows of barbed wire and also in a zig zag manner at 25cm c.c. connecting all the rows with barbed wire will be of 2 ply and 12 gauge or other approved size including drilling hole in ‘L’ iron posts and fixing the posts in cement concrete 1:2:4 of size 15x15x45cm etc as directed
20mm thick sand faced cement plaster on wall upto hight 10 meters above ground level consisting of 12mm thick backing coat of CM 1:3 ( 1 cement : 3 sand ) and 8mm thick finishing coat of CM 1:1 ( 1 cement : 1 sand ) etc complete
Plastering with C.M.1:3 for 20mm thick including curing etc complete.
Plastering with C.M.1:3 using Sulphate resistant cement for 20mm thick including curing etc complete.(well inner)
Plastering with C.M.1:3 for 12mm (SRC) thick including curing etc complete.
Plastering with C.M 1:3 for 12mm thick including curing etc. complete
Special ceiling plastering for RCC slabs, and beams in CM 1:3 using Crushed stone sand (M-sand) – 10mm thick including hacking and curing, etc., complete
Flooring with 100mm thick base cement concrete 1:4:10 using 40mm gauge brick jelly including laying ramming, curing, etc., complete.
Granolithic flooring 25mm thick with cement concrete 1;2:4 using 3-10mm chips and top surface rendered smooth with cement including thread lining and 25mm dia G.I. pipe of necessary length for water outlet curing, etc. complete
Paving Hydraulic Pressed Cement Double Charged Vitrified Tiles of size 800 x 800 x 10mm finished thickness with small Verona or Indian Marble Chips (other than Salem Magnasite) with CM 1:3, 20mm thick and painted with same colour Cement including polishing with power polisher to a high degree of polish so as to be perfectly smooth and glossy with GREY colour
Dadooing walls with glazed tiles of sizes 15cmx15cmx6mm thick laid in CM 1;2, 10mm thick and pointing with white cement using 0.4 Kg/m2 including finishing the joint and pointing flush with tile surface, etc., complete.
Terrace flooring with two course of flat tiles of 15cmx15cmx12mm using CM 1:3 mixed with crude oil 10% by weight of cement and pointed with same oiled mortar
Weathering course Concrete with broken brick jelly 20mm gauge in pure slacked lime over R.C.C. roof slab in the proportion of 32:12 ½ (No sand to be used )well beaten with wooden beaters to the required depth of 80mm thick and giving required slope and thickness to roof as required, etc., complete.
Supplying and erecting rolling shutters of 76mm 18 gauge of galvanised steel sheet with push and pull or self coiling type operated by pulling hook with top cover including locking arrangements and fixed in position inside or outside, etc., complete and painting with priming coat of redoxide without lock. (payment will be made by only for the actual opening of the shutters are rolled up wherever the shutters are to be fixed)
Maufacturing supplying and fixing in position Anodised Alu. Natural colour mat finish with openable type window of size 1.2m x 1.3m with extruded Alu. Sections with two panels of size (Frame - 38 x 33 x21 x 2.4mm @ 0.615 Kg/m, Shutter: Bottom, Top - 38.5 x 33 x 24.5 x 3 & 4mm @ 0.706 Kg/m, Interlocking vertical - 59 x 33 x 25 x 2.5mm @ 1.135 Kg/m) with necessary accessaries such as rubber beadings best quality of lock handle hinges,stays and fixing 4 mm thick plain / frosted/ pin headed glass including cost of all materials labour for electrical consumption required for drilling holes in RCC columns, beams, masonry wherever necessary with power drill to the extent required and made good to the original conditions after fixing as directed by the Board officers.The Al.Surfaces is to be anodised with matt finish usder electrically condition in accordance with ISI1868/1962 specification for an average anodic film thick of not less than 15 microns. (All materials should be got approved by the Site Engineer before fixing in position)
Supplying, fabricating and fixing in position of Alumi.Anod.natural colour matt finish door (of single leaf of size 2.1m x 1.0m) half glazed and half PLB board using 12 mm thick PLB board and 5.5 mm thick glazed door using rectangular Alu.Box section of size (Frame : Section - 101.60 x 44.45 x 3.18 mm @ 2.399 Kg/m, Shutter : Top, Middle, Vertical style- 50 x 44.45 x 2.5mm @ 1.292 Kg/m, Bottom - 100 x 44.45 x2.5mm @ 1.974 Kg/m) with necessary accessories such as rubber beading, Al. Clips, Best double action floor springs, Aluminium Handles on both sides,floor stopper,Tower bolt, Locks and glass including all materials,Labour, power consemption charges required for fabrication if necessary chipping, dismantling making necessary holes in RCC Coloums, Beams or Masonry wherever necessary with power drill to the extent required and made good to the original conditions after fixing etc.,complete. The Alumi. surface must be anodised with matt finish under electrically controlled condition in accordance with IS specification 1868 / 1962 of Anodic filthickness of not less than 15 Microns (Fifteen) for all sections.All the materials should be got approved by the Site Engineer before fixing as directed.
Solid PVC door shutters using 19 Gauge 19mm MS square tubes for styles and outer frames.15mm MS Square tubes for top, lock and bottom rails. The steel tubes shall be covered with 5mm thick solid PVC sheets. Shutter using 5mm thick solid PVC sheets for panelling shall rigidly fixed in position including necessary furniture and fittings. The overall size of styles shall be 50mm x 30mm. The overall size of top rail, Lock rail and bottom rail shall be 75mm x 30mm. The overall size of frames shall be 50mm x 45mm, with suitable rabate for housing the shutter. a. Solid panel PVC door with frame
Supplying and fixing in position of aluminium anodised colour matt finish Louvered Ventilator. The outer frame will be 62x38x2mm @ 1.17 Kg / m and the louvers with moving arrangements will be made with Alu. Channel of size 60x30x4 mm @ 1.27 kg /m with necessary glass pans for louvers 4mm thick Al. Clips, including all materials, labour & power consumption charges required for fabrication if necessary chipping dismantling making holes in RCC columns,beams or masonry wherever necessary with power drill to the extent required and make good to the original conditions after fixing etc., complete. The Aluminium surface is to be anodised with matt finish under electrically controlled condition in accordance with ISI specification 1868/1962 of anodic film thickness of not less than 15 microns (fifteen) for all sections. All the materials should be got approved by the Site Engineer before fixing in position as directed.
Supplying and fixing M.S. grills for window and gate including one coat of primer with red lead etc. complete as directed.
Supplying and fabricating and erection of iron gate with grill works of required size as per direction at site with G.I pipes of 50 mm and specials at all sides and 40x40x6mm angles as bracing on which 2 No.of m.s sheet of 16 gauge of size 2x2.50m each is welded as two halves fixing letter ''METROWATER' including one coat of primer with red lead etc.compete as directed including fixing wicket gate of size 0.75x2.m with M.S.grill work
Refilling with excavated soil ( other than sand) complying with standard specifications for filling in foundations & basement
Disposal of surplus earth
Supplying river sand for filling in the RWH pit
Supplying and fixing C.I.steps.
Colour washing two coats over one coat white washing
White washing three coats ( Ceiling)
Painting two coats with superior quality of ready mixed paints of chocholate colour, light green or grey colour or any other approved colour over painting with primary coat (red lead) on new iron work.
Providing and fixing 160 mm dia PVC Rainwater downfall pipe from roof to the RWH chamber for collecting the water (2 m horizontal distance from RWH pit)
Providing and fixing 75mm dia Nahani trap (floor trap) with brass gratings
Providing 75 mm dia PVC pipe from Nahani floor trap to the RWH chamber for collecting the rain water and tap water.
Supplying and fixing of stainless steel ladder consisting of side support and foot rest made up of 18 SWG ,304 Grade stainless steel with stainless steel welded joints.The width of the ladder is 45cms.
Precast slab 100mm thk in Cement Concrete 1:2:4 using Crushed stone sand (M-sand) and 12 to 20mm gauge hard broken stone jelly for reinforced cement concrete works including cost of steel, centering, shuttering and cost of steel reinforcement and including laying in position, compacting, curing, finishing,as per drawings,or as directed etc., complete.
Supply and erection of Cast Iron single faced manually operated rising type penstock of following dia conforming to relevant IS with IS markings on it, having cast iron door and frame with Gunmetal seating, spindle made of Stainless steel, CI head stock with gear arrangment and hand wheel fitted in well
700mm dia @5.5m depth
700mm dia @7.5m depth
700mm dia @7.0m depth
500mm dia @6.0m depth
400mm dia @ 5.5m depth
350mm dia @ 6.5m depth
300mm dia @ 6.0m depth
300mm dia @ 5.5m depth
250mm dia @ 5.0m depth
Supply and installation of SS open mesh flooring of grade 316 with 25x6mm thick flats for outer frame and 25x3mm SS and 12x3mm SS flats spaced at 30mm and 60mm respectively forming a mesh on the surface of the well .
Supplying and fixing SS screen of grade 316. The screen shall be fabricated out of stainless steel flats of 50 x 10mm. The outer frame also shall be of 50 x 10mm fixed inside the well for seating the screen. The screen shall be so fabricated that the inclined portion of the screen is fixed and the horizontal portion of the screen is a removable one for lifting the pump for maintenance purpose.
Supply and fixing ISMB 600mm of 122kg/m for 11m on column over suction well
Supply and fixing ISMB 600mm of 122kg/m for 12m on column over suction well
Supply and fixing ISMB 300mm of 42.2kg/m for 6.5m on column over suction well
Supply and fixing ISMB 300mm of 42.2kg/m for 5.5m on column over suction well
Supply and fixing ISMB 300mm of 42.2kg/m for 5.5m on column over screen/grit well
Supply and fixing ISMB 400mm of 66.3kg/m for 8m on column over suction well
Supply and fixing ISMB 400mm of 66.3kg/m for 9.5m on column over suction well
Supply and fixing ISMB 300mm of 42.2 kg/m for 5m length
Erecting pulley block of 2Tonne capacity with a 3m chain including additional chain length of 8m facilitate for horizontal movement on the beam etc complete
Erecting pulley block of 2Tonne capacity with a 3m chain including additional chain length of 11m facilitate for horizontal movement on the beam etc complete
Erecting pulley block of 2Tonne capacity with a 3m chain including additional chain length of 7m facilitate for horizontal movement on the beam etc complete
Erecting pulley block of 2Tonne capacity with a 3m chain including additional chain length of 9m facilitate for horizontal movement on the beam etc complete
Erecting pulley block of 1Tonne capacity with a 3m chain including additional chain length of 6m facilitate for horizontal movement on the beam etc complete
Erecting pulley block of 1Tonne capacity with a 3m chain including additional chain length of 7m facilitate for horizontal movement on the beam etc complete
Erecting pulley block of 1Tonne capacity with a 3m chain including additional chain length of 9m facilitate for horizontal movement on the beam etc complete
Painting with superior quality ready mixed paint of chocolate, light green, grey or any other approved colour over ISMB (for new iron work two coats).
Providing and fixing colour glazed European water closet with rose wood seatings (Black) low level flushing tank with fittings, etc., complete.
Providing and fixing 100 mm dia CI soil or vent pipe
Providing and fixing 50 mm dia CI soil or vent pipe bend without door arrangement for bathroom
Providing and fixing 100mm dia CI soil or vent pipe bend without door arrangements
Providing and fixing 50 mm dia CI soil or vent pipe for bathroom
Providing and fixing 15 x 10 cm SW gully trap with CI gratings in BJ concrete in CM 1:4:10 with silt pit diaphragm arrangements etc., complete.
Supplying, laying , jointing and testing 100mm dia SW pipe including earthwork excavation for trenches in hard stiff clay, stiff black cotton, hard red earth, shales, muram, gravel, stoney earth and earth mixed with small size boulders and hard gravelly soil depositing the earth on banks with initial lead of 10m , lowering the pipes into the trenches, aligning, refilling the trenches with excavated earth in layers of not more than 23 cm thick watering, ramming to consolidation, disposal of the surplus earth, etc. complete at an average depth of 2.0m.
Construction of inspection chambers of following sizes with earth work excavation for foundation, 23cm thick concrete bed using 40mm brick jelly concrete in C.M. 1:4:10 for foundation, brick work in C.M. 1:6 for chamber, plastering with C.M. 1:3,12mm thick, benching, channelling, supplying and fixing 45x45cm medium weight L.S. cover and frame, etc., complete for a. 60cm x 60cm x 75cm
Supplying and fixing 55cm x 40cm colour glazed wash basin with lead and brass connections, C.P. Pillar Tap and other fittings, etc., complete
Supplying and fixing best mirror of size 60cmx45cm of 6mm thick with plywood back including necessary fittings, etc., complete
Supplying and fixing C.P towel rails 45cmx 20mm
Supplying GI pipes and specials of size 25mm dia including cutting, threading and jointing with necessary specials including carting the materials, fixing to wall with necessary clamps and screws, making holes in roof, repacking the same with necessary brickwork and plastering wherever necessary with scaffolding etc., complete
Supplying and fixing 25 mm GM Gate Valve
Supplying and fixing 25 mm GM foot Valve
Supplying and fixing 20mm C.P Screw down Tap
Supply and delivery of domestic pumpset (centrifugal monobloc pumpset of capacity 100lpm and 20m head with ISI mark as per IS 9079/1989-1HP) including necessary electrical works etc., complete.
Supply and delivery and fixing of HDPE tank 500 litres capacity as per IS 12701 / 1996 including loading, unloading, transportation and labour charges for fixing of the GI pipes and specials for pipe connection works including cutting, threading and fixing charges as directed at site etc.,
Supply and delivery and fixing of HDPE tank 1000 litres capacity as per IS 12701 / 1996 including loading, unloading, transportation and labour charges for fixing of the GI pipes and specials for pipe connection works including cutting, threading and fixing charges as directed at site etc.,
Supplying and fixing in position Cement based hydruali-cally pressed Anti-Skid tiles (pattern design) 20 mmthick in cement mortar 1:3 , 20 mm thick & pointed with same colour of cement etc.,complete.
Laying CC1:2:4 for RCC sun shade works using 20mm HBG jelly 80mm thick at wall end and 50mm thick at free end and projecting 600mm from wall face moulded along with RCC lintels and tailed into full thickness of wall where there no lintels excluding cost of steel reinforcement but including shuttering, compacting, curing and finishing etc. complete.
Supplying hard broken granite stone jelly I.S.S 40 mm for filling
Supplying hard broken granite stone jelly I.S.S 20 mm for filling )
Supply of PVC slotted pipe, 160 mm dia
Supply of PVC end cap 160 mm dia
Drilling of bore well of size 16" dia in sedimentayr formation using hand boresets including insertion of casing pipes suppling and packing of pebbels and conveyance of hand boreset including loading and unloading
Providing and fixing FRC cover and frame of size 60 x 60cm including necessary masonry work and plastering, etc., complete
Construction of 80mm Double Air Valve chamber for 100mm to 350mm dia.pipeline including providing and fixing FRC cover and frame of size 60 x 60cm for size 1.2 x 0.9 x 1.8 m
Construction of 100mm Double Air Valve chamber for 400mm to 500mm dia.pipeline including providing and fixing FRC cover and frame of size 60 x 60cm for size 1.5 x 1.2 x 2.3 m
Construction of 150mm Double Air Valve chamber for above 600mm dia.pipeline including providing and fixing FRC cover and frame of size 60 x 60cm for size 1.5 x 1.2 x 2.3 m
Construction of Rising Main Discharge chambers of following sizes with earth work excavation for foundation, 23cm thick concrete bed using 40mm brick jelly concrete in C.M. 1:4:10 for foundation, brick work in C.M. 1:6 for chamber, plastering with C.M. 1:3,12mm thick, benching, channelling, supplying and fixing 45x45cm medium weight L.S. cover and frame, etc., complete
Construction of water meter Chamber in second class brick work in CM 1:4 proportion with 12mm thick outside plastering and 20 mm thick inside plastering in CM 1:3 proportion, RCC cover slab in CC 1:2:4 proportion using 20 mm jelly, chamber foundation and bed block in PCC 1:3:6 proportion using 40 mm jelly including cost of reinforcement and labour charges,earth work excavation,sand filling,refilling and disposal of surplus earth ,fixing CI steps, etc. complete and including providing and fixing L.S cover and frame of size 60cmx60cm including necessary masonry work and plastering etc complete as directed by the Engineer at site as per specification of sizeas mentioned below 1.5 m x 1 m x 1.5 m- 80mm dia to 125mm dia
Construction of water meter Chamber in second class brick work in CM 1:4 proportion with 12mm thick outside plastering and 20 mm thick inside plastering in CM 1:3 proportion, RCC cover slab in CC 1:2:4 proportion using 20 mm jelly, chamber foundation and bed block in PCC 1:3:6 proportion using 40 mm jelly including cost of reinforcement and labour charges,earth work excavation,sand filling,refilling and disposal of surplus earth ,fixing CI steps, etc. complete and including providing and fixing L.S cover and frame of size 60cmx60cm including necessary masonry work and plastering etc complete as directed by the Engineer at site as per specification of sizeas mentioned below 1.5 m x 1.2 m x 1.5 m for 150-200mm Dia
Construction of water meter Chamber in second class brick work in CM 1:4 proportion with 12mm thick outside plastering and 20 mm thick inside plastering in CM 1:3 proportion, RCC cover slab in CC 1:2:4 proportion using 20 mm jelly, chamber foundation and bed block in PCC 1:3:6 proportion using 40 mm jelly including cost of reinforcement and labour charges,earth work excavation,sand filling,refilling and disposal of surplus earth ,fixing CI steps, etc. complete and including providing and fixing L.S cover and frame of size 60cmx60cm including necessary masonry work and plastering etc complete as directed by the Engineer at site as per specification of sizeas mentioned below 1.75 m x 1.5 m x 2 m for 250-300mm Dia
Construction of water meter Chamber in second class brick work in CM 1:4 proportion with 12mm thick outside plastering and 20 mm thick inside plastering in CM 1:3 proportion, RCC cover slab in CC 1:2:4 proportion using 20 mm jelly, chamber foundation and bed block in PCC 1:3:6 proportion using 40 mm jelly including cost of reinforcement and labour charges,earth work excavation,sand filling,refilling and disposal of surplus earth ,fixing CI steps, etc. complete and including providing and fixing L.S cover and frame of size 60cmx60cm including necessary masonry work and plastering etc complete as directed by the Engineer at site as per specification of sizeas mentioned below 1.90 m x 1.75 m x 2 m for 350-450mm Dia
Providing and fixing gardening items on site as directed - Spider Lilly
Providing and fixing planting plants and shrubs on compound wall as directed
Painting with two coats of ready mixed plastic emulsion paint first class quality and of approved colour over a priming coat including thorough scrapping clean removal of dirt, etc., complete and including necessaary plaster of paris, putty, etc., wherever required.
Clearing heavy jungle
R.C.C. approach road at SPS site: Construction of R.C.C. approach road (3mt. wide) including clearance of site, required excavation, granular sub-base layer (300mm thk.) with C.C. M-10 of Dry Lean Concrete (150mm thk.) and M-30 grade of C.C. (100mm thk.) as per mix desing and applicable MORTH standards including joints, reinforcement of 10mm dia. at 230mm c/c both way, other material, labour charges etc. as directed by engineer incharge.
Band course work flat 10mm to 12mm thick and 50mm deep with C.M. 1:3 (Crushed stone sand (M-sand) including curing, etc., complete as directed
Supplying and fixing PVC water bar, 150 mm wide for construction joint
Using Electrically operated Breaker machine for demolishing and breaking the Concrete debris of OHT
Using JCB for levelling and loading for removal of concrete
Transporting the Broken concrete debris to near by SPS location
Removing the EB main switch box,meter and allied works for reuse a)Electrician Category II
Barrication all around the OHT from top to bottom upto 10m using Green net cloth with scaffholding
Labour for cleaning,watering the structures frequently (to avoid dust)diverting the trafficc oneither side of the street
Dismantle and remove the GI pipes and specials,Dispaly Board and other allied works including neatly stacking the materials from the OHT site a)Plumber Category I
b)Mazdoor Category I
Providing Iron Barricading of size 2.50 m width and 1.75 m height using 40x40x4 mm angle for outer frame supports, 25 x 25 x 3 mm angle for inner frame supports and 20 gauge thickness MS sheet for name board (as per drawing) including cutting, welding, fabrication charges and one coat of primer and 2 coats of enamel paint of approved quality, writing "METRO WATER" & work detail/ caution sign, providing necessary interlocking arrangements with adjoining units, fixing danger flags, danger lights, reflectors, fixing stickers etc, including watching during night and placing the barricading units as directed at the sites.
BILL NO:3 Supply, delivery, erection & commissioning of electrically driven non clog submersible sewage pumpsets with allied electrical works for sewage pumping stations
Supply, delivery, erection, testing and commissioning of non-clog submersible sewage pumpset with following duty point, including required capacity 3 Ph, 415 V, AC, 50 Hz, Electrical Motor with suitable weather proof cable (Copper ) of total length of 35 m, control panel, Pedestal Coupling, guide wire / suitable guide pipe of length 10m, M.S.(GLVD) lifting chain of length 10m, necessary level controlling probes with sufficient length of armoured copper LTUG cable to connect the probe from the junction box to the control panel, fasteners including laying of pump cable under ground with suitable conduit and clamping on walls in trays and incidental civil works etc.complete.
788 lpm against a total head of 11 m (LS-01)
1107 lpm against a total head of 11 m (LS-02)
691 lpm against a total head of 9 m (LS-03)
396 lpm against a total head of 8 m (LS-04)
6349 lpm against a total head of 18 m (SPS-01)
1185 lpm against a total head of 9 m (SPS-03)
4139 lpm against a total head of 12 m (SPS-04)
2123 lpm against a total head of 12 m (SPS-05)
Supply, delivery, erection, testing and commissioning of electrically driven non-clog sewage submersible Grit pumpset including agitator arrangements, with the following duty point, including required capacity 3 Ph, 415 V, AC, 50Hz Electrical Motor with suitable weather-proof cable (copper ) of total length 25 m, control panel, Skirtbase, Flanged Elbow, lifting chain M.S.(GLVD) of length 10m, necessary level controlling probes with sufficient length of armoured copper LTUG cable to connect the probe from the junction box to the control panel, fasteners including laying of pump cable under ground with suitable conduit and clamping on walls in trays and incidental civil works etc.complete.
Grit Pump - 500 lpm against a total head of 9 m
Supply, delivery, erection, testing and commissioning of following sizes of power shunt capacitor for power factor improvement, suitable to operate on 415V, 3Ph,50Hz A/C supply, on suitable angle iron frame-works (37.5 mm x 37.5 mm x 6.24mm ) at a height of 0.25m from the ground, including earthing and incidental civil works etc., complete.
Supplying and fixing of following capacity Triple Pole fuse carrier in MS Sheet steel encloure with provision for accommodating the TNEB meter including earthing etc., complete.
Supplying and fixing of following capacity Triple Pole SFU with HRC fuses on suitable angle iron frame with earth connection only.
Capacity of M.V. Panel - 32 Amps (LS-01, LS-02, LS-03, LS-04) 32 A FP(SN) MCCB 25 kA (for EB) - 1 No 16 A TP MCCB 25 kA for Sew. Pump - 2 Nos 16A TPMCCB25kA (forSew. Pumpcap.)-2Nos
Capacity of M.V. Panel - 32 Amps (SPS-03) 32 A FP(SN) MCCB 25 kA (for EB) - 1 No 16 A TP MCCB 25 kA for Sew. Pump - 2 Nos 16A TPMCCB25kA (forSew. Pumpcap.)-2Nos
Capacity of M.V. Panel - 400 Amps (SPS-01) 350 A FP(SN) MCCB 50 kA (for EB) 200 A FP(SN) MCCB 35 kA (for DG) 120 A TP MCCB 35 kA for Pump 1 20 A TP MCCB 35 kA for Grit Pump 63 A TP MCCB 35kA (for Pump 1 cap.) 16 A TP MCCB 25kA (for Grit Pump cap.) 63 A TP MCCB 35kA (for PLC Panel) 32 A TPN MCB 10kA (for LDB & PLC)
Capacity of M.V. Panel - 200 Amps (SPS-04) 200 A FP(SN) MCCB 25 kA (for EB) 63 A FP(SN) MCCB 25 kA (for DG) 50 A TP MCCB 25 kA for Pump 1 20 A TP MCCB 25 kA for Grit Pump 63 A TP MCCB 25kA (for Pump 1 cap.) 16 A TP MCCB 25kA (for Grit Pump cap.) 63 A TP MCCB 35kA (for PLC Panel) 32 A TPN MCB 10kA (for LDB & PLC)
Capacity of M.V. Panel - 100 Amps (SPS-05) 100 A FP(SN) MCCB 25 kA (for EB) 63 A FP(SN) MCCB 25 kA (for DG) 32 A TP MCCB 25 kA for Pump 1 20 A TP MCCB 25 kA for Grit Pump 32 A TP MCCB 25kA (for Pump 1 cap.) 16 A TP MCCB 25kA (for Grit Pump cap.) 63 A TP MCCB 35kA (for PLC Panel) 32 A TPN MCB 10kA (for LDB & PLC)
Capacity of D.G. Set - 140 kVA
Capacity of D.G. Set - 20 kVA
Capacity of D.G. Set - 40 kVA
Capacity of D.G. Set - 83 kVA
Supplying and clamping of variuos sizes of PVC insulated PVC sheathed armoured aluminium LT UG cable by MS clamps on wall.
- DO - 4 core 6sq.mm.
- DO - 4 core 10sq.mm.
- DO - 3 ½ core 25 sq.mm.
- DO - 3 ½ core 50 sq.mm.
- DO - 3 ½ core 120 sq.mm.
- DO - 3 core 6 sq.mm
- DO - 3 core 10 sq.mm
- DO - 3 core 16 sq.mm
- DO - 3 ½ core 70 sq.mm.
- DO - 3 ½ core 150 sq.mm
LT UG Cable (Underground)
- DO - 3 ½ core 150 sq.mm (underground)
- DO - 3 ½ core 70 sq.mm. (Underground)
- DO - 3 ½ core 25 sq.mm (Underground)
Supplying and laying following LTUG cables in a trench to be excavated at a depth of 2 ½ ' putting 6” layer of sand and covering the cable with brick and sand refilling the earth to make good as directed.
- DO - 2 core 4sq.mm.
- DO - 4 core 6 sq.mm.
- DO - 3 core 6 sq.mm.
- DO - 3 core 2.5 sq.mm copper cable
Supplying and fixing of cable gland and termination with Aluminium cable by PVC UG cable and with earth connection
- DO - 2 core 4sq.mm.
- DO - 4 core 6sq.mm.
- DO - 4 core 10sq.mm.
- DO - 3 ½ core 25 sq.mm.
- DO - 3 ½ core 50 sq.mm.
- DO - 3 ½ core 70 sq.mm.
- DO - 3 ½ core 120 sq.mm.
- DO - 3 ½ core 150 sq.mm.
- DO - 3 core 6 sq.mm
- DO - 3 core 10 sq.mm
- DO - 3 core 16 sq.mm
- DO - 3 core 2.5 sq.mm copper cable
Supply delivery and fixing of out door weather proof junction box fabricated in MS sheet steel (12 SWG for front 14 SWG for other sides) near the suction well for terminating the Pump power cable and control cable on an angle iron frame at convenient height for working and above the local MFL with provision for terminal block & earthing as per IS including incidental civil works etc.,complete.
Up to 20 HP
21 HP to 60 HP
Supply, delivery and fixing of out door wheater proof Local Push Button station in the compartment provided in the Junction Box with 1 No"ON" and 1 No "OFF" push buttons (the "OFF" push button shall be locable in "OFF" position).
Supply, delivery and erection of Single Phase 6 way 16 Amps, 10kA LDB with the following: 1 No. of 16A, DP RCCB 4 Nos of 6A, SP MCB in sheet steel enclosure fitted with busbars and neutral links and suitable angle iron frame works with provision for earthing etc. complete.
Supply, delivery and erection of Three Phase 6 way 32 Amps, 10kA LDB with the following: 1 No of 40 A FP isolator for incoming supply 3 Nos. of 16A, DP RCCB 3 Nos. of 16A, SP MCB 1 No of 16A, DP MCB 3 Nos of 6A, DP MCB in sheet steel enclosure fitted with busbars and neutral links and suitable angle iron frame works with provision for earthing etc. complete.
Run of 2 of 2.5 sq mm PVC unsheathed copper single core cable in PVC pipe for mains with continuous earth connection by 14 SWG wire From the MCB DB to the Switch boards in office, store,and 16A power socket.
Wiring with 2.5 sq mm PVC insulated single core copper cables of 650 V Grade on suitable rigid PVC pipe on wall and ceiling with PVC accessories, with MS switch box covered with 3 mm thick hylam sheet with continous earth wire connection of 14 SWG TC wire.
Light points
Fan Points
Wiring with 2.5 sq.mm PVC unsheathed single core copper cable on suitable rigid PVC pipe for 5A 3 pin CS plug non interlocking including supply and fixing of plug pin top in MS box with continuous earth connection by 14 SWG TC wire
Lighting Fixtures
Supplying and fixing of box type 4’ 20W single LED fitting complete with TW round block and tube on ceiling or wall with connection.
Supplying and fixing of 18 Watt LED lamp with round type LED Troffer recessed mounted fitting complete.
Supplying and fixing of 12" sweep AC exhaust fan complete including providing necessary opening in the wall.
Supply and fixing of 48" sweep AC ceiling fan complete with regulator with lm down rod (stem pipe) including supplying and fixing of fan clamp with side plates and cross arms
a) Supply and erection of 1 No 3" dia 2 m long tubular Wall Mounted post with complete 120W LED lamp with necessary fitting and other accessories etc.
Supplying and clamping of PVC , LTUG cable by M.S.clamps on wall for 2 core 4 sq.mm
Suppling and fixing of cable gland and termination with earth connection for 2 core 4 sq.mm
Supplying and fixing of 15 amps, single phase, DP SFU switch with F&N on suitable TW Board with earth connection only.
a) Supply and erection of 1 No 3" dia 5 m long tubular Pole Mounted post with complete 250W sodium vapour lampwith necessary fitting and other accessories etc.
Supplying and laying of PVC , LTUG cable under ground in a trench to be excavated at a depth of 2 ½ ' putting 6” layer of sand and covering the cable with brick and sand refilling the earth to make good as directed for 2 core 4 sq.mm
Supplying and clamping of PVC , LTUG cable by M.S.clamps on wall for 2 core 4 sq.mm
Suppling and fixing of cable gland and termination with earth connection for 2 core 4 sq.mm
Supplying and fixing of 15 amps, single phase, DP SFU switch with F&N on suitable TW Board with earth connection only
Supply and delivery of the following safety equipment
5 kg capacity ISI marked dry chemical powder type fire extinguisher.
First Aid box ( medium).
Fire bucket - 3 Nos with MS stand.
Rubber mat 6mmthick of 1.1 kv grade of size 2m x 1m
Fire safety rules chart
Shock treatment chart
Caution / Danger Board
Supply and delivery of the following tools:
Double ended open jaw spanner set of size in mm 6x7, 8x9, 10x11, 12x13, 14x15, 16x17, 18x19, 20x22, 20x23 24x27, 25x28 & 30x32
Ring spanner set of size in mm 6x7, 8x9, 10x11, 12x13, 14x15, 16x17, 18x19, 20x22 20x23 24x27, 25x28 & 30x32.
Screw driver of size 12 inches
Cutting plier of size 8 inches
Tong Tester ( clamp on type- multiutility) A C voltage 0 - 750 V AC current 0 - 1000 A D C voltage 0 - 1000 V Resistance 0 - 40 mega ohms
Electrical tester
Diesel Filling Pump (Hand operated )
Measuring Dip Rod (MS) (for measuring 200 ltr. standard Barrel )
Hack Saw frame with blade
Lever type Grease gun
Supply and delivery of Rechargeable emergency lamp with 600mm Fluorocuent lamp, dry type rechargable battery etc.,complete.
Earthing as per ISI specifications with necessary masonary work.
Supply and connection of earthing conductor including two coats of approved painting and laying between earth pit and equipment.
25 x 6 mm GI Flat
40 x 6 mm GI Flat
Supply, Delivery, erection, testing and commissioning of PLC Control Panel including the Remote Terminal Unit/ Programmable Logic Controller (RTU/PLC), Human Machine Interface (HMI), GPRS modem, 1 kVA UPS and accessories along with mounting assembly & cables including installing the PLC programming package and interconnecting with the existing SCADA System at Centralized Monitoring Location (the software will be provided by CMWSSB) as directed by Engineer and interconnecting with the ultrasonic level transmitters, electromagnetic flow meters and with existing MV panels, Capacitor panels at each sewage Pumping Station to switch ON/OFF the pumps based on level feedback, Switch ON/OFF the existing capacitor bank to maintain Powerfactor as per EB norms, and to monitor EB/ DG supply including incidental civil works etc., complete.
Supply, Delivery, erection, testing and commissioning of Ultrasonic Level Transmitter of range 0 - 15 meters in the collection well with necessary mounting arrangements including incidental civil works etc complete.
Operation and maintenance of the installation: Operation and maintenanceof the plant with all auxiliary equipment for a period of 120 days after satisfactory supply, erection , commissioning and operating the entire plant for 30 days, free of cost by the contractor before handing over the plant to the Board.
LS-01, LS-02, LS-03, LS-04& SPS-03
SPS-01, SPS-04 & SPS-05
Supply and delivery of odor control equipment with required Air flow suction capacity from sewage pumping station. Equipment should be capable to remove odor from sewer exhaust by using physical adsorption and chemical conversion. Adsorption uses activated carbon to act as the media.Equipments capable to remove 99.9%of all incoming contaminates.Odor control unit shall be very high efficient and capable to regenerate of carbon. Technical specification need to approved concern departmental engineer in charge.
Odor control unit inclues all basic and required components i.e; platform for instalation, Damper, Inlet, Drainage point, View Panel, Control panel with all electric accessoiries,media fillinf port, Pre filter, Regeration Port, Outlet, Adsorption Column. All components satisfied the required design parameter and Material of construction is MS with epoxy lining. Power supply three pahse. Noise level should be as per IS.
Equipments rate Inclusive of transortaion, loading, unloadin, freight, all taxes, packing, installation on site, with satisfactory competion testing and commisioning.
Air flow suctioncapacity :2000 CFM / 3400 CMH @ MPS01 and SPS04
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid