EXECUTIVE ENGINEER
XEN PWD ELECT DIV ALWAR
Installation of the additional 500 KVA Compact Substation at Bikaner House New Delhi
2026_CEPWD_554709_1
102 NIT 02/2026-27 EE PWD ELECT ALWAR
Open Tender
Electrical Works
180 days
bikaner house new delhi
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,000
MD RISL / XEN PWD ELECT DIV ALWAR
₹1.6 L
Yes
XEN PWD ELECT DIV ALWAR
22 May 2026
29 Apr 2026
8 May 2026
29 Apr 2026
7 May 2026
29 Apr 2026
5 May 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | CE Approved vide CE(Elect.)/Non-BSR/2025-26/D-1157 dated 23.03.2026 | - | - | - | - |
| 2 | SITC of 11 kV Factory Assembled Outdoor Package Sub-Station (PSS), Design and manufactured by the OEM. The PSS shall comprise of RMU, LT Switchgear (ACB), Transformer, etc ,The PSS should consist of following sections and their specifications as per A, B, C, D & E | - | - | - | - |
| 3 | A) HT Compartment: Ring Main Unit 11kV 630 Amps 21KA and above /1 Sec IAC AFLR 21 KA/1Sec. SF6 insulated, non-extensible, compact switchgear (Type VVV+M)consisting of Three Nos fixed Manual Vaccum Circuit Breaker (VCB )(manually operated and Operating Sequence of VCB Should be O-0.3S-CO-3Min-CO.or as per type test design) with Copper busbar in SF6 insulated stainless steel Outdoor enclosure of thickness of 1.6mm/ 2 mm and tank of stainless steel Outdoor enclosure of thickness 3mm with manometer. Interconnection between HT switchgear and transformer by Suitable Sized Aluminium un-armoured HT XLPE Cable. The HV switchgear and control gear should be confirming to IEC-62271-100,IEC62271-202, IEC-62271-200-2003 & IEC-60694-1996. The Gas tank of the RMU should be internal arc tested for 21KA and above /1 Sec. VI should be of make for which type test was done.
- 1 no. microprocessor based Self powered numerical relay with over Current/ earth fault & short circuit protection with each VCB feeder.
- 3 Nos. Protection CT shall be of Burden 2.5VA, ratio 50/1A, Class of Accuracy class 5P10 for O/C and E/F protection for each VCB feeder
-1 No. Manometer - Metering Provision as per NDMC requirement for which Metering CT 40/1 A, 2.5 VA Class, 0.5 Accuracy and Metering BUS PT- 11000/√3 110V/√3 50VA Class 0.5 Accuracy. Digital mulitfunction meter CL -0.5 with RS485 Port. | - | - | - | - |
| 4 | B) Transformer: As recommended by OEM 11kV/433V, 3phase,50 HZ,DYN-11 Copper wound hermetically sealed oil type step down transformer having delta connection on primary side and star connection on secondary side complete with all modern fitting as given in the specification , off load tap changer (-10% +5% in the step of 2.5%) etc. as required with losses as per ECBC 2017 or updated , Class H with 115 Deg temperature rise allowed .
- One No. Winding Temperature Indicator with Alarm and trip Contacts | - | - | - | - |
| 5 | C) LV Compartment: Incoming cum Outgoing with One number manual spring charged drawout type 4 pole 415V ACB with breaking capacity 50KA with Ics = Icu = Icw (1 sec) = 50KA with microprocessor release for over current, earth fault & short circuit protections. Interconnection between Transformer & LT switchgear using Aluminum Bus bars of ACB Current rating with heat shrinkable colored sleeves. | - | - | - | - |
| 6 | D) The Outdoor enclosure shall be made of 2.0 mm for Load bearing and 1.5 mm thickness for Non load bearing part, Galvanized Sheet Steel tropicalised to meet Indian weather conditions including all the partition Sheets & doors. The enclosure base shall be of 4.0 mm thickness Hot Dip Galvanized Sheet Steel. The entire Package Substation shall be Factory Assemble & Factory Fitted. The enclosure shall have IP54 degree of protection for HT & LT switchgear compartment IP-23 degree of protection for Transformer compartment. The Enclosure should be type tested for Internal Arc fault test to the tune of at least 21 KA for 1 second adhering to as per latest IEC 62271- 202. The offered enclosure should be type tested for K10 class temparature raise. Type test reports to be submitted. The enclosure exterior shall be powder coated. The compartment illumination lamp and space heater with door operated switch shall be provided for MV & LV compartment. Internal earthing connections by using 50x6mm GI Strips. | - | - | - | - |
| 7 | E) OEM of PSS shall provide Type test certificates for the RMU, Transformer & LT Switchgear. | - | - | - | - |
| 8 | Factory Tests: All test shall be conducted as per the QAP of OEM at the Manufacturing facility and same shall be witnessed by departmental Engineers. | - | - | - | - |
| 10 | Transformer Capacity 500 KVA, ACB Rating 1000 Amps. ( Complete rate- 5414826) | 1 | Each | 45,88,835.59 | ₹45,88,835.59 |
| 11 | CE Approved vide CE(Elect.)/Non-BSR/2025-26/D-1157 dated 23.03.2026 | - | - | - | - |
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.86 MB
Tendernotice_2.pdf
PDF • 6.19 MB
Tendernotice_3.pdf
PDF • 1.78 MB
noc.pdf
Tender Documents • 0.65 MB
GENCOND.pdf
Other Document • 0.61 MB
BOQ_987983.xls
BOQ • 0.32 MB
Download all tender documents and submit your bid