Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹47.3 LAccepted-AOC 441 G F LIG FLATS PH 2 SEC 14 PKT 3 DWARKA NEW DELHI SECTOR 14 DWARKA DWARKA SOUTH WEST DELHI DELHI 110078 | SOUTH WEST DELHI | DELHI | 110078 | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹52.8 L+₹4.5 L (9.42%)Rejected-Finance NEAR AVON PUBLIC SCHOOL DABHANW POST DANDI NAINI PRAYAGRAJ 211008 | PRAYAGRAJ | PRAYAGRAJ | UTTAR PRADESH | 211008 | L2 | Rejected-Finance Being L2 |
| Sl No | Description | Qty | Unit | NEXT POWER ENTERPRISES L2 | OMVIN ENTERPRISES LLP L1 |
|---|---|---|---|---|---|
| 1.00 | Supplying and laying or fixing in replacement, jointing and testing LT under ground electric power cable crossed linked polyethylene ( XLPE) insulated, galvanised steel strip or wire armoured, ISI marked, with aluminium conductor multi stranded , heavy duty 1100 Volts grade of size 10 sqmm cross sectional area, 2 core, complete laid in trenches / laid under floor or fixed naked with walls / on poles/ in ducts /in GI pipes etc. with and including MS Clamps, nuts, bolts, washers complete.
Note :- Excavation, earth work, protection pipe shall be measured and paid separately under appropriate items of the BOQ. | 250 | RM | 150 ₹37,500 | 115 ₹28,750 Lowest |
| 2.00 | All as per item No 01 above but LT UG Cable of size 10 Sqmm 4 core | 400 | RM | 200 ₹80,000 | 130 ₹52,000 Lowest |
| 3.00 | All as per item No 01 above but LT UG Cable of size 16 Sqmm 4 core | 150 | RM | 230 ₹34,500 | 155 ₹23,250 Lowest |
| 4.00 | All as per item No 01 above but LT UG Cable of size 25 Sqmm 3.5 core | 250 | RM | 270 ₹67,500 | 210 ₹52,500 Lowest |
| 5.00 | All as per item No 01 above but LT UG Cable of size 50 Sqmm 3.5 core | 100 | RM | 410 ₹41,000 | 280 ₹28,000 Lowest |
| 6.00 | All as per item No 01 above but LT UG Cable of size 95 Sqmm 3.5 core | 100 | RM | 480 ₹48,000 | 450 ₹45,000 Lowest |
| 7.00 | All as per item No 01 above but LT UG Cable of size 185 Sqmm 3.5 core | 250 | RM | 1,250 ₹3,12,500 | 900 ₹2,25,000 Lowest |
| 8.00 | All as per item No 01 above but LT UG Cable of size 240 Sqmm 3.5 core | 300 | RM | 1,450 ₹4,35,000 | 1,050 ₹3,15,000 Lowest |
| 9.00 | Excavation in trenches, not exceeding 1.5 m wide and not exceeding 1.5 m in depth for laying of cables, pipes etc. and getting out including trimming the sides and forming bottom surfaces to required levels in soft / loose soil complete. | 410 | Cum | 90 ₹36,900 Lowest | 90 ₹36,900 Lowest |
| 10.00 | Returning filling in,. Including spreading, levelling,. Watering and well ramming in layers not exceeding 25 cm thick, using excavated soil all as specified and directed. | 360 | Cum | 30 ₹10,800 | 20 ₹7,200 Lowest |
Tender Value
₹48.8 L
EMD Value
₹97,580
Closing Date
10 Jan 2026, 6:00 pmClosed
GE E/M Lucknow
Garrison Engineer E/M, 36 LBS Marg, Lucknow Cantt, Lucknow (U.P.) PIN 226002
REPAIR / MAINT OF EXTERNAL LT SUPPLY, LT PANEL BOARD, MCCB, LT SWITCHGEAR, STARTER, OVERHEAD LINE, POWER FACTOR CORRECTION SYSTEM AND ALLIED WORKS AT CH (CC) IN THE AREA OF AGE E/M (HOSP) UNDER GE E/M LUCKNOW
2025_MES_745474_1
GE/EM/LKO/HOSP/T-54 OF 2025-2026
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Lucknow
As per NIT
8 documents required · 8 mandatory
₹500
GE E/M Lucknow
₹97,580
Yes
7 Mar 2026
20 Dec 2025
12 Jan 2026
20 Dec 2025
10 Jan 2026
3 Jan 2026
Supplying and laying or fixing in replacement, jointing and testing LT under ground electric power cable crossed linked polyethylene ( XLPE) insulated, galvanised steel strip or wire armoured, ISI marked, with aluminium conductor multi stranded , heavy duty 1100 Volts grade of size 10 sqmm cross sectional area, 2 core, complete laid in trenches / laid under floor or fixed naked with walls / on poles/ in ducts /in GI pipes etc. with and including MS Clamps, nuts, bolts, washers complete. Note :- Excavation, earth work, sand cushioning, protection bricks/ tiles/ block and pipe shall be measured and paid separately under appropriate items.
All as per item No 02 above but LT UG Cable of size 10 Sqmm 4 core
All as per item No 02 above but LT UG Cable of size 16 Sqmm 4 core
All as per item No 02 above but LT UG Cable of size 25 Sqmm 3.5 core
All as per item No 02 above but LT UG Cable of size 50 Sqmm 3.5 core
All as per item No 02 above but LT UG Cable of size 95 Sqmm 3.5 core
All as per item No 02 above but LT UG Cable of size 185 Sqmm 3.5 core
All as per item No 02 above but LT UG Cable of size 240 Sqmm 3.5 core
Excavation in trenches, not exceeding 1.5 m wide and not exceeding 1.5 m in depth for laying of cables, pipes etc. and getting out including trimming the sides and forming bottom surfaces to required levels in soft / loose soil complete.
Returning filling in,. Including spreading, levelling,. Watering and well ramming in layers not exceeding 25 cm thick, using excavated soil all as specified and directed.
Supply and laying in trenches/Floor/road crossing or fixed to Pole/Wall GI pipe light grade ISI marked with fitting of size 50 mm bore for protection of cable including taking down existing pipe complete all as specified and directed by the Engineer-in-Charge.
Supply, fix, connecting and testing in repair MCCB 160 Amp 3 pole 16 KA 415 volts 50 Hz adjustable thermal & adjustable magnetic release with spreader, MCCB shall have double make, double break with Arc Chute per pole fixed in existing panel including all connection complete all as directed.
Supply only spring charge indication microswitch
Supply and laying or fixing HDPE Double wall corrugated pipe 40 mm outer dia & 32 mm inner dia along with all accessories like socket, couplers etc, ISI marked as per IS-16205 (Part-24), including cutting / jointing and laid in trenches, fixed to walls, floor etc. for cable protection complete all as specified & directed.
Supply and laying or fixing HDPE Double wall corrugated pipe 50 mm outer dia & 38 mm inner dia along with all accessories like socket, couplers etc, ISI marked as per IS-16205 (Part-24), including cutting / jointing and laid in trenches, fixed to walls, floor etc. for cable protection complete all as specified & directed.
Supply and laying or fixing HDPE Double wall corrugated pipe 77 mm outer dia & 63 mm inner dia along with all accessories like socket, couplers etc, ISI marked as per IS-16205 (Part-24), including cutting / jointing and laid in trenches, fixed to walls, floor etc. for cable protection complete all as specified & directed.
Supply and laying or fixing HDPE Double wall corrugated pipe 110 mm outer dia & 95 mm inner dia along with all accessories like socket, couplers etc, ISI marked as per IS-16205 (Part-24), including cutting / jointing and laid in trenches, fixed to walls, floor etc. for cable protection complete all as specified & directed.
Supply and laying or fixing HDPE Double wall corrugated pipe 120 mm outer dia & 103 mm inner dia along with all accessories like socket, couplers etc, ISI marked as per IS-16205 (Part-24), including cutting / jointing and laid in trenches, fixed to walls, floor etc. for cable protection complete all as specified & directed.
M& L for fabrication and fixing canopy headed junction box of size 30 x 25 x 15 cm with cover, suitable for fixing on LT Pole, made out 3.00 mm MS sheet, including 04 Nos aluminium bus bar of size 25 x 3 mm for phase and neutral, 01 Nos 06 Amps MCB SP with mounting channel, for control street light, cable gland, aluminium lug, MS Fixing clamp -02 Nos with nut bolt washer, painting with two coat of synthetic enamel paint over a coat of red oxide primer on external and internal surface complete
(b) Out going (a) MCCB FP 250 Amps, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 01 No (b) MCCB FP 160 Amp, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 01 No (c) MCCB FP 100 Amp, 25 KA (Icu=Ics) thermally adjustable between 70% to 100% - 02 Nos Note for MCCB : All incoming & outgoing MCCB shall have double make, double break with Arc Chute per pole.
(c) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The hight of platform shall be 45 cm above the nearest road level.
Note - (i) Following type test certificate for panel with switchgear as per IEC 61439 Part I & II shall be obtained from panel manufacturer by the contractor and shall be submitted along with panel Drawing for the approval the GE before supply of panel at site. A - Construction Requirement: (a) Strength of material and parts (b) Degree of protection of enclosures (c) Clearances (d) Creepage distances (e) Protection against electric shock and integrity of protective circuits (f) Incorporation of switching devices and components (g) Internal electrical circuits and connections (h) Terminals for external conductors B - Performance Requirement: (a) Di-electric properties (b) Verification of temperature rise (c) Short circuit withstand strength (d) Electromagnetic compatibility (e) Mechanical operations
Note (ii) All out going feeder shall be connected by cable through suitable size gland plate / glands. (iii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iv) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947-II/IS 13947-II (Latest Version). The
MCCB should have Ics=100%Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacturer (v) The enclosures shall be designed to take care of normal stress as well as abnormal electromechanical stress due to short circuit conditions. All covers and doors provided shall offer adequate safety to operating persons and provide ingress protection up to IP 54 unless otherwise stated. Ventilating openings and vent outlets, shall be arranged such that same ingress protection of IP 54 is retained. Suitable pressure relief devices shall be provided to minimize danger to operator during internal fault conditions. (vi) MCCBs up to 160A should have operating voltage 415Vac , insulation voltage 1000V ac , positive isolation , class II insulation , Line Load Reversibility , ICS=100%ICU , ROHS Compliant.
(c) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The hight of platform shall be 45 cm above the nearest road level.
Note - (i) Following type test certificate for panel with switchgear as per IEC 61439 Part I & II shall be obtained from panel manufacturer by the contractor and shall be submitted along with panel Drawing for the approval the GE before supply of panel at site. A - Construction Requirement: (a) Strength of material and parts (b) Degree of protection of enclosures (c) Clearances (d) Creepage distances (e) Protection against electric shock and integrity of protective circuits (f) Incorporation of switching devices and components (g) Internal electrical circuits and connections (h) Terminals for external conductors B - Performance Requirement: (a) Di-electric properties (b) Verification of temperature rise (c) Short circuit withstand strength (d) Electromagnetic compatibility (e) Mechanical operations
Note (ii) All out going feeder shall be connected by cable through suitable size gland plate / glands. (iii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iv) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947-II/IS 13947-II (Latest Version). The
(b) Out going (a) MCCB FP 250 Amps, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 03 Nos (b) MCCB FP 160 Amp, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 01 No (c) MCCB FP 100 Amp, 25 KA (Icu=Ics) thermally adjustable between 70% to 100% - 01 No Note for MCCB : All incoming & outgoing MCCB shall have double make, double break with Arc Chute per pole.
(c) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The hight of platform shall be 45 cm above the nearest road level.
Note - (i) Following type test certificate for panel with switchgear as per IEC 61439 Part I & II shall be obtained from panel manufacturer by the contractor and shall be submitted along with panel Drawing for the approval the GE before supply of panel at site. A - Construction Requirement: (a) Strength of material and parts (b) Degree of protection of enclosures (c) Clearances (d) Creepage distances (e) Protection against electric shock and integrity of protective circuits (f) Incorporation of switching devices and components (g) Internal electrical circuits and connections (h) Terminals for external conductors B - Performance Requirement: (a) Di-electric properties (b) Verification of temperature rise (c) Short circuit withstand strength (d) Electromagnetic compatibility (e) Mechanical operations
Note (ii) All out going feeder shall be connected by cable through suitable size gland plate / glands. (iii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iv) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947-II/IS 13947-II (Latest Version). The
(b) Out going (a) MCCB FP 400 Amps, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 01 Nos (b) MCCB FP 160 Amp, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 02 No Note for MCCB : All incoming & outgoing MCCB shall have double make, double break with Arc Chute per pole.
(c) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The hight of platform shall be 45 cm above the nearest road level.
Note - (i) Following type test certificate for panel with switchgear as per IEC 61439 Part I & II shall be obtained from panel manufacturer by the contractor and shall be submitted along with panel Drawing for the approval the GE before supply of panel at site. A - Construction Requirement: (a) Strength of material and parts (b) Degree of protection of enclosures (c) Clearances (d) Creepage distances (e) Protection against electric shock and integrity of protective circuits (f) Incorporation of switching devices and components (g) Internal electrical circuits and connections (h) Terminals for external conductors B - Performance Requirement: (a) Di-electric properties (b) Verification of temperature rise (c) Short circuit withstand strength (d) Electromagnetic compatibility (e) Mechanical operations
Note (ii) All out going feeder shall be connected by cable through suitable size gland plate / glands. (iii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iv) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947-II/IS 13947-II (Latest Version). The
(b) Out going (a) MCCB FP 160 Amps, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 02 Nos (b) MCCB FP 100 Amp, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 01 No Note for MCCB : All incoming & outgoing MCCB shall have double make, double break with Arc Chute per pole.
(c) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The hight of platform shall be 45 cm above the nearest road level.
Note - (i) Following type test certificate for panel with switchgear as per IEC 61439 Part I & II shall be obtained from panel manufacturer by the contractor and shall be submitted along with panel Drawing for the approval the GE before supply of panel at site. A - Construction Requirement: (a) Strength of material and parts (b) Degree of protection of enclosures (c) Clearances (d) Creepage distances (e) Protection against electric shock and integrity of protective circuits (f) Incorporation of switching devices and components (g) Internal electrical circuits and connections (h) Terminals for external conductors B - Performance Requirement: (a) Di-electric properties (b) Verification of temperature rise (c) Short circuit withstand strength (d) Electromagnetic compatibility (e) Mechanical operations
Note (ii) All out going feeder shall be connected by cable through suitable size gland plate / glands. (iii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iv) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947-II/IS 13947-II (Latest Version). The
(b) Out going (a) MCCB FP 160 Amps, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 02 Nos (b) MCCB FP 100 Amp, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 02 Nos Note for MCCB : All incoming & outgoing MCCB shall have double make, double break with Arc Chute per pole.
(c) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The hight of platform shall be 45 cm above the nearest road level.
Note - (i) Following type test certificate for panel with switchgear as per IEC 61439 Part I & II shall be obtained from panel manufacturer by the contractor and shall be submitted along with panel Drawing for the approval the GE before supply of panel at site. A - Construction Requirement: (a) Strength of material and parts (b) Degree of protection of enclosures (c) Clearances (d) Creepage distances (e) Protection against electric shock and integrity of protective circuits (f) Incorporation of switching devices and components (g) Internal electrical circuits and connections (h) Terminals for external conductors B - Performance Requirement: (a) Di-electric properties (b) Verification of temperature rise (c) Short circuit withstand strength (d) Electromagnetic compatibility (e) Mechanical operations
Note (ii) All out going feeder shall be connected by cable through suitable size gland plate / glands. (iii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iv) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947-II/IS 13947-II (Latest Version). The
(b) Out going (a) MCCB FP 250 Amps, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 01 Nos (b) MCCB FP 160 Amp, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 02 Nos (c) MCCB FP 100 Amp, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 01 Nos Note for MCCB : All incoming & outgoing MCCB shall have double make, double break with Arc Chute per pole.
(c) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The hight of platform shall be 45 cm above the nearest road level.
Note - (i) Following type test certificate for panel with switchgear as per IEC 61439 Part I & II shall be obtained from panel manufacturer by the contractor and shall be submitted along with panel Drawing for the approval the GE before supply of panel at site. A - Construction Requirement: (a) Strength of material and parts (b) Degree of protection of enclosures (c) Clearances (d) Creepage distances (e) Protection against electric shock and integrity of protective circuits (f) Incorporation of switching devices and components (g) Internal electrical circuits and connections (h) Terminals for external conductors B - Performance Requirement: (a) Di-electric properties (b) Verification of temperature rise (c) Short circuit withstand strength (d) Electromagnetic compatibility (e) Mechanical operations
Note (ii) All out going feeder shall be connected by cable through suitable size gland plate / glands. (iii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iv) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947-II/IS 13947-II (Latest Version). The
(b) Out going (a) MCCB FP 200 Amps, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 01 Nos (b) MCCB FP 160 Amp, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 01 Nos (c) MCCB FP 100 Amp, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 03 Nos Note for MCCB : All incoming & outgoing MCCB shall have double make, double break with Arc Chute per pole.
(c) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The hight of platform shall be 45 cm above the nearest road level.
Note - (i) Following type test certificate for panel with switchgear as per IEC 61439 Part I & II shall be obtained from panel manufacturer by the contractor and shall be submitted along with panel Drawing for the approval the GE before supply of panel at site. A - Construction Requirement: (a) Strength of material and parts (b) Degree of protection of enclosures (c) Clearances (d) Creepage distances (e) Protection against electric shock and integrity of protective circuits (f) Incorporation of switching devices and components (g) Internal electrical circuits and connections (h) Terminals for external conductors B - Performance Requirement: (a) Di-electric properties (b) Verification of temperature rise (c) Short circuit withstand strength (d) Electromagnetic compatibility (e) Mechanical operations
Note (ii) All out going feeder shall be connected by cable through suitable size gland plate / glands. (iii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iv) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947-II/IS 13947-II (Latest Version). The
(b) Out going (a) MCCB FP 200 Amps, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 01 Nos (b) MCCB FP 160 Amp, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 02 Nos (c) MCCB FP 100 Amp, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 02 Nos (d) MCCB FP 63 Amp, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 01 Nos Note for MCCB : All incoming & outgoing MCCB shall have double make, double break with Arc Chute per pole.
(c) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The hight of platform shall be 45 cm above the nearest road level.
Note - (i) Following type test certificate for panel with switchgear as per IEC 61439 Part I & II shall be obtained from panel manufacturer by the contractor and shall be submitted along with panel Drawing for the approval the GE before supply of panel at site. A - Construction Requirement: (a) Strength of material and parts (b) Degree of protection of enclosures (c) Clearances (d) Creepage distances (e) Protection against electric shock and integrity of protective circuits (f) Incorporation of switching devices and components (g) Internal electrical circuits and connections (h) Terminals for external conductors B - Performance Requirement: (a) Di-electric properties (b) Verification of temperature rise (c) Short circuit withstand strength (d) Electromagnetic compatibility (e) Mechanical operations
Note (ii) All out going feeder shall be connected by cable through suitable size gland plate / glands. (iii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iv) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947-II/IS 13947-II (Latest Version). The
(b) Out going (a) MCCB FP 160 Amps, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 02 Nos (b) MCCB FP 125 Amp, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 02 Nos (c) MCCB FP 63 Amp, 25 KA (Icu=Ics) thermally adjustable between 70% to 100%. - 02 Nos Note for MCCB : All incoming & outgoing MCCB shall have double make, double break with Arc Chute per pole.
M&L for Preparation of old painted surfaces of LT steel tubular pole 9 mitres long and applying one coat aluminium paint from bottom to top and painting up to 1.5 met
M&L for Preparation of old painted surfaces of LT panel by scrapping, making good disturbed surfaces by applying putties on uneven surface to make it even and spray painting to LT panel of any size with two coat of synthetic enamel paint with desired colour complete all as specified and directed.
S&F Off load change over switch (side operated handle) 400 Amps, 415 volts 4 pole in sheet metal enclosure with interlock door and pad lock facility including dismantling of existing change over switch, complete
Supply & fixing in replacement automatic street light timer panel 6 KW TP switch using Infrared Sensor based for automatic switching of street lights based on LUX level of natural light. Required illuminance for switching ON is < 30 Lux and for switching OFF > 10 Lux level. The sensor (nature switch) along with suitable power contactors, Input (supply) MCB and output (load) MCB(s), support terminals should be enclosed in pole/ wall mountable enclosure made of rust proof, electric shock proof, termite proof and FR graded SMC junction box conforming to IP-54 degree of ingress three phase 6 KW lightening load capacity including mounting bracket, cable glands, openable doors with lock complete all as specified & directed by Engr-in-Charge.
Deployment of manpower / tools / machinery etc for restringing of existing loose over head line having 4 run ACSR conductor and 01 Nos GI wire any size / type etc of existing LT pole including repair of aluminium binding wire or suitable size carefully without damaging of insulator etc. complete all as specified and as directed by Engineer-in-Charge. Note :- (i) 4 Run of ACSR conductor with 01 Run of GI wire shall be measured as 01 RM for payment, Linear length centre to centre of the poles shall only be measured (ii) Cleaning / pruning of tree branches falling around the conductor shall also deemed to be included in the quoted rates
Supplying and fixing in repair flat twin core ,1.5 sqmm nominal cross sectional area multistranded aluminium conductor cable, over all PVC sheathed, 1100 Volts grade heavy duty cable PVC insulated and PVC sheathed complete
Deployment of manpower / tools / machinery for Periodical servicing of air circuit breaker and disconnecting the electrical connection from unserviceable parts and taking out the unserviceable part from the ACB and supply and fix the new part as per existing make / model / capacity incl cleaning and greasing fixed and movement parts etc complete. Note :- (i) All unserviceable spare part will be measured & paid separately under relevant item of this BOQ (ii) Unit rates quoted by tenderers shall deem to include for, bolts, washers, lugs, thimble, wires and petty items required for efficient and smooth functioning of the equipment without any extra cost.
Supply only racking interlock
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.33 MB
BOQ_834738.xls
BOQ • 0.48 MB
Tender54.pdf
Tender Documents • 1.11 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .