Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹87.6 LAccepted-AOC | L1 | Accepted-AOC Being Lowest | |
| 2 | L2₹93.9 L+₹2.1 L (2.31%)Rejected-Finance | L2 | Rejected-Finance Other than being lowest | |
| 3 | L3₹1.1 Cr+₹17.3 L (18.9%)Rejected-Finance 1 14 SUJAL MANSION B BLOCK BHANGWADI KALBADEVI ROAD MUMBAI 400 002 | MUMBAI | MAHARASHTRA | 400002 | L3 | Rejected-Finance Other than being lowest | |
| 4 | L4₹1.1 Cr+₹21.7 L (23.6%)Rejected-Finance BLOCK C 14 GROUND FLOOR PLOT 618 624 BHIVANDIWALA TERRACE JAGANNATH SHANKARSHETH MARG DHOBI TALAO NEAR KALBADEVI POST OFFICE MUMBAI 400002 | MUMBAI | MAHARASHTRA | 400002 | L4 | Rejected-Finance Other than being lowest | |
| 5 | L5₹1.3 Cr+₹39.1 L (42.6%)Rejected-Finance SHOP NO 10 BMC SHOPPING CENTRE MITHA NAGAR GOREGAON WEST MUMBAI 400 104 | MUMBAI | MUMBAI SUBURBAN | MAHARASHTRA | 400104 | L5 | Rejected-Finance Other than being lowest |
Tender Value
Refer Docs
EMD Value
₹2.0 L
Closing Date
3 Jun 2022, 6:00 pmClosed
CWE (NW) Mumbai
Commander Works Engineer NW Dr Homi Bhabha Road Navy Nagar Colaba Mumbai 05
REPAIR REPLACEMENT OF DETERIORATED METER PANEL BOARDS METERS LT PANEL FP BOX DEFECTIVE CABLES AND CONNECTED ITEMS AT NOFRA AND REPAIR REPLACEMENT OF FAULTY LT HT CABLES MCCBs DBs SUB MAIN WIRINGS AND REPAIR MAINTENANCE OF VARIOUS TYPE OF RECESS MOUN
2021_MES_498609_3
8709/CWE(NW)MUMBAI/E8
Open Tender
Civil Works
Item Rate
270 days
GE (NW) NOFRA
Class B
7 documents required · 7 mandatory
₹1,000
Yes
GE (NW) NOFRA
₹2.0 L
Yes
8 Jul 2022
11 May 2022
6 Jun 2022
11 May 2022
3 Jun 2022
20 May 2022
11 May 2022 - 18 May 2022
Amount
Taking up/out old U/S XLPE insulated screened. PVC bedded, galvanized steel strip or wire armored, electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor including taking up Old concrete cable cover from trenches/walls/ceiling/poles etc any size all as specified and directed by Engr-in-Charge
Excavation in trenches not exc 1.5 mtr wide and not exc 1.5 mtr in depth for foundation, laying of UG Electric cable / staying of steel tubular pole etc. and getting out in any type of soil complete all as specified and as directed by Engr-in-Charge.
Material and labour for Cutting existing road surface or hard standing 0.30 mtr depth using latest technology for laying of pipes/ cables and making good distrubed surface to match with existing complete with PCC all as specifed and directed by Engineer - in - Charge
Removing the excavated material/ soil not exc 50m out of MD land complete all as specified and directed .
Returning & filling in, including spreading, levelling, watering & well ramming in layers not exc 25 cm as in soil complete all as specified & directed .
Material and labour for dry clean river sand for cushioning of cable in trenches for cable protection including spreading, leveling and hand punning complete all as specified in SSR Part-I and as directed. Note :- Only compacted thickness of sand will be measured and paid.
Supplying and laying un-reinforced precast concrete cable cover, class LV Type I, flat, size 250 mm x 150 mm x 40 mm. laid in trenches complete all as specified and directed.
Fixing Only in repair PVC insulated XLPE, armoured LT cable, 1100 Volts grade with aluminium conductor of size 3.5 core 35 Sqmm laid in trenches / through pipe /ducts or fixed on wall etc complete all connections to LT panel with proper size glands & lugs all as specified & directed.
Fixing Only in repair PVC insulated XLPE, armoured LT cable, 1100 Volts grade with aluminium conductor of size 3.5 core 50 Sqmm laid in trenches/through pipe /ducts or fixed on wall etc complete all connections to LT panel with proper size glands & lugs all as specified & directed.
Fixing Only in repair PVC insulated XLPE, armoured LT cable, 1100 Volts grade with aluminium conductor of size 3.5 core 70 Sqmm laid in trenches/through pipe /ducts or fixed on wall etc complete all connections to LT panel with proper size glands & lugs all as specified & directed.
Fixing Only in repair PVC insulated XLPE, armoured LT cable, 1100 Volts grade with aluminium conductor of size 3.5 core 95 Sqmm laid in trenches/through pipe /ducts or fixed on wall etc complete all connections to LT panel with proper size glands & lugs all as specified & directed.
Fixing Only in repair PVC insulated XLPE, armoured LT cable, 1100 Volts grade with aluminium conductor of size 3.5 core 120 Sqmm laid in trenches/through pipe /ducts or fixed on wall etc complete all as specified & directed.
Fixing Only in repair PVC insulated XLPE, armoured LT cable, 1100 Volts grade with aluminium conductor of size 3.5 core 150 Sqmm laid in trenches/through pipe /ducts or fixed on wall etc complete all as specified & directed.
Fixing Only in repair PVC insulated XLPE, armoured LT cable, 1100 Volts grade with aluminium conductor of size 3.5 core 185 Sqmm laid in trenches/through pipe /ducts or fixed on wall etc complete all connections to LT panel with proper size glands & lugs all as specified & directed.
Fixing Only in repair PVC insulated XLPE, armoured LT cable, 1100 Volts grade with aluminium conductor of size 3.5 core 240 Sqmm laid in trenches/through pipe /ducts or fixed on wall etc complete all connections to LT panel with proper size glands & lugs all as specified & directed. Note :- for item Sr No 8 to 15 : The cables for laying will be issued under Sch 'B' items
Material and labour for servicing of LT panel including dismantling the old cable lugs by cutting the cable, meggering the cables with help of megger and detecting any faul/short circuit if any including fixing of new lugs by pealing the cable, cutting and joing the cables with the help of Cable Joint Kit of suitable size if required, servicing of MCCBs/MCBs/Bush Bar/ Checking/Replacing of Nut Bolts etc. all as specified and directed by Engineer in Charge. Note: i) The items i.e. MCCBs/MCBs, Cable Joint Kit of suitable size, Painting Job of Panel shall be measured and paid seperately under various item. ii) The material and labour required for servicing of LT panel i.e consumables/nut bolts etc shall be deemed to be included in the item rate.
Material and labour for Locating the cable fault in UG LT cable of size ranges upto 70 Sqmm and joining the cable with the help of cable joint kits of suitable size including excavation at the location of cable fault and return filling of the excavated material after joing the cable all inclusive all as specified and directed by Engineer - in - Charge. Note: i) The rate quoted shall be deemed to included the cost of fault locator if required. ii) The rate quoted shall be deemed to be included the cost of excavation and refilling etc
Material and labour for Locating the cable fault in UG LT cable of size ranges 95 to 185 Sqmm and joining the cable with the help of cable joint kits of suitable size including excavation at the location of cable fault and return filling of the excavated material after joing the cable all inclusive all as specified and directed by Engineer - in - Charge. Note: i) The rate quoted shall be deemed to included the cost of fault locator if required. ii) The rate quoted shall be deemed to be included the cost of excavation and refilling etc
Material and labour for Locating the cable fault in UG LT cable of size ranges 240 to 300 Sqmm and joining the cable with the help of cable joint kits of suitable size including excavation at the location of cable fault and return filling of the excavated material after joing the cable all inclusive all as specified and directed by Engineer - in - Charge. Note: i) The rate quoted shall be deemed to included the cost of fault locator if required. ii) The rate quoted shall be deemed to be included the cost of excavation and refilling etc
Supply, install, testing and commissioning of LT Feeder Pillar CPRI Approved mounted on angle iron frame 40x40x5 mm grouted on floor,cubical outdoor type, with both side opening Minimum size 1100x900x600 mm or suitable fixing of all breakers and controls, for 415V, 3 phase, made of 3 mm thick CRCA sheet weather, vermin proof factroy fabricated, CPRI approved, front open hinged door with locking arrangement powder coated, individual compartment for MCCBs and 800 Amps rated bus bar, top and bottom cable entry including disconnecting cable connections Panel and fixing/connecting in new insalled panel with provisions of thimble/lugs and necessary farmework and PCC foundation including shifting of existing of LT Panel if any making arrengement for fixing of panel and making good to disturbed surface as directed comprising of the following :- Onload change over switch FP, 400 Amps, - 01 Nos Note :-Panel layout should be submitted and got approved before installation
(a) MCCB 400 Amps, 36 KA, FP - 02 Nos Make: Legrand Cat Part No. 4220 35 of model DPX3 630/ L & T/ABB/Havells
(b) MCCB 250 Amps, 36 KA FP - 01 Nos Make: Legrand Cat Part No. 4202 49 of model DPX3 250/ L & T/ABB/Havells
(c) MCCB 200 Amps, 36 KA FP - 04 Nos Make: Legrand Cat Part No. 4202 48 of model DPX3 250/ L & T/ABB/Havells
(d) MCCB 160 Amps, 36 KA, FP - 03 Nos Make: Legrand Cat Part No. 4200 97 of model DPX3 160/ L & T/ABB/Havells
(e) MCCB 100 Amps, 36 KA, FP - 03 Nos Make: Legrand Cat Part No. 4200 96 of model DPX3 160/ L & T/ABB/Havells
(g) Aluminium bus bar 800 Amps for phase & 800 Amps for neutral complete with bus bar insulator,nuts & bolts complete.
(h) Power panel wiring between bus bar to MCCB of different capacity with PVC insulated multistranded copper cable , single core ,1100 volts grade of appropriate size complete with copper lugs
Supply, install, testing and commissioning of LT Feeder Pillar CPRI Approved mounted on angle iron frame 40x40x5 mm grouted on floor,cubical outdoor type, with both side opening Minimum size 1100x900x600 mm or suitable fixing of all breakers and controls for 415V, 3 phase, made of 3 mm thick CRCA sheet weather, vermin proof factory fabricated, CPRI approved, front open hinged door with locking arrangement powder coated, individual compartment for MCCBs and 800 Amps rated bus bar, top and bottom cable entry including disconnecting cable connections Panel and fixing/connecting in new insalled panel with provisions of thimble/lugs and necessary farmework and PCC foundation including shifting of existing of LT Panel if any making arrengement for fixing of panel and making good to disturbed surface as directed comprising of the following :- Note :- Panel layout should be submitted and got apporved before installation.
(a) ON Load LT Changeover , 4 POLE, 400 Amps
(b) MCCB 400 Amps, 36 KA, FP - 02 Nos Make: Legrand Cat Part No. 4220 35 of model DPX3 630/ L & T/ABB/Havells
(c) MCCB 320 Amps, 36 KA, FP - 02 Nos Make: Legrand Cat Part No. 4220 34 of model DPX3 630/ L & T/ABB/Havells
(d) MCCB 250 Amps, 36 KA FP - 02 Nos Make: Legrand Cat Part No. 4202 49 of model DPX3 250/ L & T/ABB/Havells
(e) MCCB 200 Amps, 36 KA FP - 02 Nos Make: Legrand Cat Part No. 4202 48 of model DPX3 250/ L & T/ABB/Havells
(f) MCCB 160 Amps, 36 KA, FP - 02 Nos Make: Legrand Cat Part No. 4200 97 of model DPX3 160/ L & T/ABB/Havells
(h) Aluminium bus bar 800 Amps for phase & 600 Amps for neutral complete with bus bar insulator,nuts & bolts complete.
(j) Power panel wiring between bus bar to MCCB of different capacity with PVC insulated multistranded copper cable , single core ,1100 volts grade of appropriate size complete with copper lugs
Material and labour for Changeover switch 630A rating with suitable panel CPRI Approved, made out of 3 mm thick CRCA Sheet, size 900x800x600 mm minimum suitable for fixing of MCCBs/Bus Bar etc, weather, vermin proof factory fabricated, with angle iron stand, outdoor type for independent mounting on floor/wall including provision for incoming and outgoing cables of any size comprising of following items including necessary PCC work for foundation, Frame work for stand and lugs, thimble etc required for fixing of panel complete all as specified and directed by Engineer in Charge. (i) Aluminum Bus Bar 1200 Amp for Phase and 800 A for Neutral - 1 Set (ii) Changeover Switch 630 Amp Rating - 01 No. (iii) Draw Out type ACB 630 Amp - 02 Nos (for I/C and O/G) Make: Legrand CAT Part No. 6695 42 of Model No. DMX SP - 2500 or Equivalent in L & T/ ABB/Havells Note :- Panel layout should be submitted and got approved before installation
S & Fixing Cable Straight Joint Kit heat shrinkable type of following size complete all as specified and directed by Engineer - in - Charge.
(ii) 240 to 300 Sqmm
(iii) 150 to 185 Sqmm
(iv) 70 to 120 Sqmm
(v) Upto 50 Sqmm
Fixing Only in repair MCCB 400A 4P, with Thermal Magnetic Protection Unit, Thermal adjustable/magnetic adjustable, breaking capacity 36 KA all as specified and directed by Engineer - in - Charge. Note for Item Srl No. 25 to 31: The materials for fixing will be issued under Sch B Items
Fixing Only in repair MCCB 320A 4P, with Thermal Magnetic Protection Unit, Thermal adjustable/magnetic adjustable, breaking capacity 36 KA all as specified and directed by Engineer - in - Charge.
Fixing Only in repair MCCB 250A 4P, with Thermal Magnetic Protection Unit, Thermal adjustable/magnetic adjustable, breaking capacity 36 KA all as specified and directed by Engineer - in - Charge.
Fixing Only in repair MCCB 200A 4P, with Thermal Magnetic Protection Unit, Thermal adjustable/magnetic adjustable, breaking capacity 36 KA all as specified and directed by Engineer - in - Charge.
Fixing Only in repair MCCB 160A 4P, with Thermal Magnetic Protection Unit, Thermal adjustable/magnetic adjustable, breaking capacity 36 KA all as specified and directed by Engineer - in - Charge.
Fixing Only in repair MCCB 100A 4P, with Thermal Magnetic Protection Unit, Thermal adjustable/magnetic adjustable, breaking capacity 36 KA all as specified and directed by Engineer - in - Charge.
Fixing Only in repair MCCB 63A 4P, with Thermal Magnetic Protection Unit, Thermal adjustable/magnetic adjustable, breaking capacity 36 KA all as specified and directed by Engineer - in - Charge.
Supply, install, testing and commissioning of LT Panel meter cabin panel mounted on angle iron frame 40x40x5 mm grouted on floor,cubical indoor type for 415V, 3 phase, made of 2 mm thick CRCA sheet weather, vermin proof factroy fabricated, CPRI approved, front open hinged door with locking arrangement powder coated, individual compartment for MCCBs and 400 Amps rated bus bar, top and bottom cable entry including disconnecting cable connections and electronic meters from old meter cabin panel and fixing/connecting in new insalled panel with provisions of thimble/lugs and necessary farmwork and PCC foundation including shifting of existing panel if any making arrangement for fixing of panel and making good to disturbed surface as directed comprising of the following :- Note :- Panel layout should be submitted and got approved before installation
(a) MCCB, FP, 250 Amps 25 kA- 02 Nos.
(b) MCB 63 Amps, 10KA, C series - 16 No .
(c) Sheet metal enclosure 2 way without bus bar - 16 No,
(d ) Copper Bus bar, 400 Amps Rated - R,Y,B & N
(e)Digital Ammeter-01 No, Make-HPL ,SP CL-1.0/AE
(f)Digital Voltmeter-01 No Make-HPL ,SP CL-1.0/AE
(g) Phase indicator lamp R,Y & B
(h) Making provision for fixing of digital electronic meters removed from old panel including fixing and providing vision glasses - 16 Nos.
(j) Material and labour for 2 core 10 Sqmm multistranded copper conductor cable 1100V from bus bar to electronic energy meters using suitable size copper thimbles/glads.
(k) Fixing of submain cable 2 core 10 Sqmm copper conductor with outgoing of energy meter all as directed.
Supply, install, testing and commissioning of meter cabin panel mounted on angle iron frame 40x40x5 mm grouted on floor,cubical indoor type for 415V, 3 phase, made of 2 mm thick CRCA sheet weather, vermin proof factory fabricated, CPRI approved, front open hinged door with locking arrangement powder coated, individual compartment for MCCBs and 300 Amps rated bus bar, top and bottom cable entry including disconnecting cable connections and electronic meters from old meter cabin panel and fixing/connecting in new insalled panel with provisions of thimble/lugs and necessary framework and PCC foundation including shifting of existing panel if any making arrangement for fixing of panel and making good to disturbed surface as directed comprising of the following :- Note :- Panel layout should be submitted and got approved before installation
(a) MCCB, FP, 200 Amps 25 kA- 02 Nos.
(b) MCB 63 Amps, 10KA, C series - 12 No.
(c) Sheet metal enclosure 2 way without bus bar - 12 No.
(d ) Copper Bus bar, 400 Amps Rated - R,Y,B & N
(e)Digital Ammeter-01 No, Make-HPL ,SP CL-1.0/AE
(f)Digital Voltmeter-01 No Make-HPL ,SP CL-1.0/AE
(g) Phase indicator lamp R,Y & B
(h) Making provision for fixing of digital electronic meters removed from old panel including fixing and providing vision glasses - 10 Nos.
(j) Material and labour for 2 core 10 Sqmm multistranded copper conductor cable 1100V from bus bar to electronic energy meters using suitable size copper thimbles/glads.
(k) Fixing of submain cable 2 core 10 Sqmm copper conductor with outgoing of energy meter all as directed.
Routine Checking for NLP Testing of Nimbus ESE lightning Arrestors Complete as Follows (i) Check the physical appearance of ESE-LR Noted any arcing make on NPL outer surface (ii) Check the mast stability foundation fitness (iii) Check down conductor physically about damage & continuity. (iv) Check the NIMBUS Lightning arrestor by LR Tester Passed. (v) Check the Counter reading and note the readings. (vi) Check the adaptor link connection with down conductor. (vii) Check LR down conductor termination on EP. (viii) Check the LR earthing pit grid resistance by fall of potential method. (ix) Check the EP clamp nut bolts tightness and corrosion. (x) 10> Any higher grid resistance value observed.
Supply of LEPD Make Surge Protection system Model No DMD 3/65 MAG. Supply of surge protection device model DMD350 MAG with 12.5 KA (ln) & 50ka (NPE) IMAX 65 KA, 3 PHASE - with Enclosure (class I _ II) with necessary accessories for lightening arrester systemhave specification as per latest NBC 2016 and latest revisions in IS/IEC 62305 electrical surge/lightning arrestors Manufacturer's mode/type numb DMD3-65 MAG
Supply & fix in repair of JEF Nimbus Early Streamer emission Air terminal (ESEAT). (i) ESEAT shall have a corrosion resistant stainless steel body (AISI 316 grade) capable of working in hazardous atmosphere. The Air terminal shall be non-radioactive and require no special licensing. The unit shall be fully autonomous (no battery, no external power supply required), collect energy from ambient electric field. (ii) ESEAT model must be tested in a high voltage laboratory in accordance with NFC 17 102 for a series of 100 shock waves equal to 325µs in order to measure the average gain in triggering. The average gain in triggering time (ΔT) obtained during the lab test for the offered model must be mentioned in the test report. (iii) ESEAT must work on negative as well as positively polarized discharges. (iv) ESEAT must have been tested for such discharges by a reputed (v)Indian Laboratory like Central Power Research Institute (CPRI) and to submit the test result. (vi) A dedicated tester should be avilable to test the healthiness of the ESEAT on request (Courtesy : Page No. 37, Point No. 3 of Clause 8.6 of the Revised NFC 17-102 version 2011). (vii) ESEAT Model : NLP 2200 - Radius of protection = 30 Mtrs Level of protection considered for the project = Level I.
Supply & fix in repair of Standard / Side mounting / Special Mounting Structure of GI + Aluminium of height 4.5 Mtrs with base plate suitable for roof mounting on concrete base and with FRP adapter without GUY kit complete all as specified and as directed by Engr-in-Charge.
Supply & fix in repair of Down conductor made of Copper only for lower impedance. It should have a minimum cross sectional area of 50mm² single core and comply with IEC 62 305 standard. The down conductor shall be routed as directly as possible to the ground avoiding electrical shafts and sharp bends (minimum bending radius of 0,5m). Any metallic object located less than 1 meter shall be connected to it complete all as specified and as directed.
Supply and fix in repair test link box in order to disconnect the earth termination system for enabling measurements complete all as specified and as directed.
Supply & fix in repair of 4 Digit electromechanical Lightning Event Counter in WEATHER PROOF ENCLOSURE. The counter should give the number of strikes intercepted by the lightning arrester complete all as specified and as directed.
Supply , fixing, testing in repairs of JEF ECO SAFE Maintenance Free Grounding Solution set comprising of High tensile low carbon steel rod of 3 Mts length & 25 mm dia with 250 micron ( averaSchneider ) molecularly bonded copper on the outer surface to confirm with requirements of UL467 along with Back-fill compound strictly be a Carbon based conductive concrete type which has a resistivity of less than 0.12 Ohm Mtr as per Clause 14.5D of IEEE : 80 standard. Back-fill compound should be electronically conductive ( Like in metals ) and should not depend on moisture for conduction. JEF Powerfill Loresco compound shall be supplied in 50 Pound Bag. ( 1 Bag of 50 Pounds required per earthing set). Back-fill compound should be environment friendly, should solidify when mixed with water and set like concrete and should not leach / diffuse into the ground. A suitable earth terminaton clamp should also be supplied along with the set alongwith earth pit weatherproof incl all as specified and measured the resistance and submit the report to Engr-in-Charge . Note - Back-fill compund shall not be mixed with any soil while pouring in the bore hole.
Material and labour for repair / replacement of Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required GI Strip 32 x 6 mm complete all as specified and directed by Engineer in charge.
Material and labour for Earthing with galvanised steel earth plate electrode 60 x 60 cm x 6 mm thick, burried directely in ground (earth pit not less than 2.5 mtr deep below ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, connected to galvanised iron strip 32 x 6 mm with the help of bolts, nuts, check nuts and washers of galvanised iron or steel, including necessary excavation, PCC 1:3:6 type D2 and PCC cover 1:2:4 type B1 weathering arrangement with GI pipe funnel, jali, complete all as specified and shown in electrical plate No.3 including connection to the earthing test point and testing on completion.
Taking down old unserviceable submain cable of any size and capacity and finishing wall surfaces.
Supply and fix submain wiring in repair with two single core FRLS unsheathed 1100 volts grade cable with stranded copper conductor of size 4 Sqmm in and including PVC conduit not less than 25mm width, ISI marked including 1 single core cable with stranded copper conductor of size 4 sqmm (green colour) for earthing. Note :- (i) Two runs of 4Sqmm cable, 1 run of PVC conduit and 1 run of 4 Sqmm cable shall be measured as 1 RM. (ii) Each submain wiring shall run in seperate PVC conduit
Supply and fix in repair submain wiring two single core 6 Sqmm for sub main wiring with copper conductor multistranded PVC insulated and unsheathed 1100Volts grade in and including PVC conduit not less than 25mm dia with fixing accessories including one run of 6.0 Sqmm copper conductor. Note :- (i) Two runs of 06 Sqmm cable, one run of 6.0 Sqmm earth cable and one run of PVC conduit shall be measured as one running meter. (ii) Each submain wiring shall run in seperate PVC conduit
Supply and fix submain wiring in repair 2 single core FRLS unsheathed 1100 volts grade cable with stranded copper conductor of size 10 Sqmm in and including PVC conduit not less than 25mm dia including 1 single core cable with stranded copper conductor of size 10 sqmm (green colour) for earthing. Note :- (i) Two runs of 10 Sqmm cable, 1 run of PVC casing caping/ conduit and 1 run of 10 Sqmm cable shall be measured as 1 RM. (ii) Each submain wiring shall run in seperate PVC conduit
Supply and fix in repair sheet metal enclosure 12 way Double door type having protection IP-54, with 200 Amps rated bus bar connecting with existing wiring circuits by providing copper pin terminals of suitable size complete all as directed of comprising of the following :-
(a) MCB SPN 63 Amps, 240 Volts - 01 No.
(b) MCB SP 6-32 Amps, 240 Volts.
Supply and fix in repair MCB, DB, SPN 8 way double door with protection type IP-54 with 200 Amps rated bus bar connecting with existing wiring circuits by providing copper pin terminals of suitable size complete all as directed, as approved comprising following :-
(a) MCB SPN 40 Amps 240 Volts-01 No (B Series).
(b) MCB SP 6- 32 Amps 240 Volts (B Series).
Supply and fix in repair single phase sheet metal powder coated double door distribution board 4 way comprising with following :- (a) MCB SPN 40Amps 240Volts, 10KA - 1 No ('B' Series) (b) MCB SP 6 - 32Amps 240Volts - 2No ('B' Series)
Supply and fix in repairs sheet metal enclosure 2 way without bus bar with MCB comprising following
(a) Isolator DP 63 Amps Breaking capacity 10 KA. (B series).
Supply & fix in repair MCB DB, TPN 8 way vertical type, 415 V with 200 Amps rated bus bar and double door connecting with existing wiring circuits by providing copper pin terminals of suitable size complete all as directed, comprising of the following : - (a) MCCB 3 Pole, 415 V fixed type, 160 Amps with breaking capacity 25 KA-01 Nos (incoming) (b) MCB TP 63 Amps, 10KA - 06 Nos (B Series) (Outgoing) (c) MCB SP 40 Amps, 10KA - 06 Nos (B Series) (Outgoing)
Taking down carefully aluminium point wiring (light, fan, socket or power) complete, (fittings such as switches, ceiling roses, pendants, regulators sockets etc to be measured separately) and making good disturbed surfaces of walls, floors, etc. complete all as specified and as directed.
Material and Labour for point wiring complete with 1.5 sqmm single core multistranded FRLS PVC insulated unsheathed copper conductors 1100 volts grade drawn through and including PVC non-metallic casing and caping of size not less than 25mm width, ISI marked with accessories fixed on wall/ceiling/truss etc with PVC non metallic ISI marked terminal boxes/ modular Cover plate concealed in wall including one FRLS PVC insulated & sheathed multistranded green colour copper conductor 1.5 sqmm as earth continuity conductor connected to common earth as earth dolly for :-
One light point controlled by one switch SP one way.
Material and Labour for point wiring complete with 4 sqmm single core multistranded FRLS PVC insulated unsheathed copper conductors 1100 volts grade drawn through and including PVC non-metallic casing and caping of size not less than 25mm width, ISI marked with accessories fixed on wall/ceiling/truss etc with PVC non metallic ISI marked terminal boxes / modular Cover plate concealed in wall including one FRLS PVC insulated & unsheathed multistranded green colour copper conductor 4 sqmm as earth continuity conductor connected to common earth as earth dolly.
Supply and fix in repair Modular Switch, 6Amp, One way, 1 module. Make- Legrand (Aretor)/ Schneider (Zencelo)/ Goldmedal (Nixon)
Supply and fix in repair Modular blank plate, One way, 1 module. Make- Legrand (Aretor)/ Schneider (Zencelo)/ Goldmedal (Nixon)
Supply and fix in repair Modular Switch, 16Amp, One way, 1 module. Make- Legrand (Aretor)/ Schneider (Zencelo)/ Goldmedal (Nixon)
Supply and fix in repair ceiling rose surface bakelite with ISI mark, flush type with ISI mark three terminals complete all as specified. Make - Legrand /Gold Medal / Anchor
Supply and fix in repair Modular Socket oulet, 6/16 Amps, 2/3 pin combined, 2 module. Make- Legrand (Aretor)/ Schneider (Zencelo)/ Goldmedal (Nixon)
Supply and fix in repair Modular white cover plate with Frame 1 Module. Make- Legrand (Aretor)/ Schneider (Zencelo)/ Goldmedal (WEGA)
Supply and fix in repair Modular white cover plate with Frame 2 Module. Make- Legrand (Aretor)/ Schneider (Zencelo)/ Goldmedal (WEGA)
Supply and fix in repair Modular white cover plate with Frame 3 Module. Make- Legrand (Aretor)/ Schneider (Zencelo)/ Goldmedal (WEGA)
Supply and fix in repair Modular metal flush box 1 module. Make- Legrand (Aretor)/ Schneider (Zencelo)/ Goldmedal (WEGA)
Supply and fix in repair Modular metal flush box 2 module. Make- Legrand (Aretor)/ Schneider (Zencelo)/ Goldmedal (WEGA)
Supply and fix in repair Modular metal flush box 3 module. Make- Legrand (Aretor)/ Schneider (Zencelo)/ Goldmedal (WEGA)
Fixing Only in repair Linear Aluminium Baten LED T/L 20W Aluminium Extruded Chanel Powder Coated with opaque diffuser for glare free light complete with accessories internally prewired and including connecting up with twin core twisted flexible copper conductor cable with suitable size complete all as specified. Note for Item Srl No. 73,74 & 78 to 92: The materials for fixing will be issued under Sch B Items
Fixing Only in repair Linear Aluminium Baten LED T/L 10W Aluminium Extruded Chanel Powder Coated with opaque diffuser for glare free light complete with accessories internally prewired and including connecting up with twin core twisted flexible copper conductor cable with suitable size complete all as specified.
Supply and fix in repair LED lamp suitable for 14 watts, 240 volts, single phase, 50 Hzs, Lumen 1450 AC supply.
Material and Labour in repair for Lamp holder, PVC /Polycarbonate type with cord grip cap suitable for pendant fittings complete all as directed by Engineer-in-Charge.
Supply and fix in repair Plug and Socket enclosure, in sheet metal enclosure with MCB, SP 20 Amps 240 Volts complete with metal clad socket for window type air conditioners.
Fixing in repairs Recess Mounting LED panel, 2'x2', 28 Watt capacity, environmentlal friendly, new generation, ashthetically designed ultra modern, fully diffused, white powder coated, with polymer diffuser complete with acessories suitable for Armstrong/Grid Ceiling all as specified and directed .
Fixing in repairs Recess Mounting LED panel, 2'x2', 34 Watt capacity, environmentlal friendly, new generation, ashthetically designed ultra modern, fully diffused, white powder coated, with polymer diffuser complete with acessories suitable for Armstrong/Grid Ceiling all as specified and directed .
Fixing in repairs Surface Mounting LED panel, 2'x2', 34 Watt capacity, environmentlal friendly, new generation, ashthetically designed ultra modern, fully diffused, white powder coated, with polymer diffuser complete with acessories suitable for surface all as specified and directed .
Fixing in repairs Surface Mounting LED panel, 4'x1', 42 Watt capacity, environmentlal friendly, new generation, ashthetically designed ultra modern, fully diffused, white powder coated, with polymer diffuser complete with acessories suitable for surface all as specified and directed .
Fixing in repairs Recess Mounting LED panel, 2'x1', 20 Watt capacity, environmentlal friendly, new generation, ashthetically designed ultra modern, fully diffused, white powder coated, with polymer diffuser complete with acessories suitable for Armstrong/Grid Ceiling all as specified and directed .
Fixing in repairs Recess Mounting LED panel, 1'x1', 15 Watt capacity, environmentlal friendly, new generation, ashthetically designed ultra modern, fully diffused, white powder coated, with polymer diffuser complete with acessories suitable for Armstrong/Grid Ceiling all as specified and directed .
Fixing in repairs Recess Mounting LED panel, 4'x1', 30 Watt capacity, environmentlal friendly, new generation, ashthetically designed ultra modern, fully diffused, white powder coated, with polymer diffuser complete with acessories suitable for Armstrong/Grid Ceiling all as specified and directed .
Fixing in repairs Recess Mounting LED panel, 4'x1', 36 Watt capacity, environmentlal friendly, new generation, ashthetically designed ultra modern, fully diffused, white powder coated, with polymer diffuser complete with acessories suitable for Armstrong/Grid Ceiling all as specified and directed .
Fixing in repairs Recess Mounting LED panel, 210mm x 210mm 18Watt capacity, environmentlal friendly, new generation, ashthetically designed ultra modern, fully diffused, white powder coated, with polymer diffuser complete with acessories suitable for Armstrong/Grid Ceiling all as specified and directed .
Fixing in repairs Recess Mounting LED down lighter with pressure die cast aluminium heat sink and PC diffuser 10 Watt capacity, environmentlal friendly, new generation, ashthetically designed ultra modern, fully diffused, white powder coated complete with integrated driver incl all acessories suitable for Armstrong/Grid Ceiling all as specified and directed .
Fixing in repairs Recess Mounting LED down lighter with pressure die cast aluminium heat sink and PC diffuser 15 Watt capacity, environmentlal friendly, new generation, ashthetically designed ultra modern, fully diffused, white powder coated complete with integrated driver incl all acessories suitable for Armstrong/Grid Ceiling all as specified and directed .
Fixing in repairs Recess Mounting LED down lighter with pressure die cast aluminium heat sink and PC diffuser 24 Watt capacity, environmentlal friendly, new generation, ashthetically designed ultra modern, fully diffused, white powder coated complete with integrated driver incl all acessories suitable for Armstrong/Grid Ceiling all as specified and directed .
Fixing in repairs Recess Mounting LED drop down lighter with pressure die cast optimised heat sink and PC diffuser 15 Watt capacity, environmentlal friendly, new generation, ashthetically designed ultra modern, fully diffused, white powder coated complete with integrated driver incl all acessories suitable for Armstrong/Grid Ceiling all as specified and directed .
Fixing in repairs Recess Mounting LED drop down lighter with pressure die cast optimised heat sink 18 Watt capacity, round profile, environmentlal friendly, new generation, ashthetically designed ultra modern, fully diffused, white powder coated complete with sepeartd driver incl all acessories suitable for Armstrong/Grid Ceiling all as specified and directed .
Fixing in repairs Recess Mounting LED drop down lighter 100lm/watt, with pressure die cast optimised heat sink 25 Watt capacity, round profile, environmentlal friendly, new generation, ashthetically designed ultra modern, fully diffused, white powder coated complete with sepeartd driver incl all acessories suitable for Armstrong/Grid Ceiling complete all as specified and as directed by Engr-in-Charge. .
Relaying only HT cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 11000 Volts grade with stranded aluminium conductor and Earthed grade passing through trench/ wall/ duct/ roads etc of size of 3 c x 185 sqmm/ 240 sqmm complete all as specified and as directed by Engr-in-Charge.
Material and labour for HT Cable jointing kit for 11 KV (Earthed) grade cable for indoor end termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 185 sqmm/240 sqmm complete all as specified and as directed by Engr-in-Charge.
Material and labour for HT Cable jointing kit for 11 KV (Earthed) grade cable for indoor stright through joint heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 185 sqmm / 240 sqmm complete all as specified and as directed by Engr-in-Charge.
Supply and fixing equal MS angle iron / flat iron any size / brackets / Clamps / supports etc cut to pices as per site incl welding , cutting , bend to as required shape and fixing on wall etc as required at site complete all as specified and as directed by Engr-in-Charge.
Material and labour for GI pipe light grade of 100 mm dia of size for protection of Cables of any size / any type for passing through roads / trench / walls/ duct etc , Incl all necessary fittings and fixtures etc complete all as specified and as directed by Engr-in-Charge.
Dismanting / disconnecting of Old HT Cable connections from VCB panels and refixing of the same or refixing with new HT cable to VCB panels with all necessary arrrangments complete all as specified and as directed by Engr-in-Charge.
Material and labour for Cutting by manual / by tools of existing HTcables for repairs as directed of size 3 x 180 sqmm / 3 x 240 sqmm , 11 KV for making of HT joints incl necessary excavation in any type of soil and removal incl with all arragments complete all as specified and as directed by Engr-in-Charge.
Supply and fixing HT Cables covers for protection of HT Cables, Un-reinforced precast concrete cable cover, class HV, type1, flat size, size 300mm x 180mm x 40mm complete all as specified and as directed by Engr-in-Charge.
Material and labour for PCC 1:3:6, type C1, for grading 20 mm graded coarse aggregate for repairing of walls/ filling/ ducts etc as requied at site complete all as specified and as directed by Engr-in-Charge.
ORIENT ELECTRIC CO
Chakshu Enterprise
AGRAWAL ASSOCIATES
Shree Ayyappa Engineering
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .