| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹11.3 LAccepted-AOC 164 197 NEWAJPUR DASAULI KURSI ROAD LUCKNOW UTTAR PRADESH 226026 | LUCKNOW | UTTAR PRADESH | 226026 | L1 | Accepted-AOC Found lowest and reasonable and accepted | |
| 2 | L2₹13.9 L+₹1.6 L (13.3%)Rejected-Finance | L2 | Rejected-Finance In order but L3 | |
| 3 | L3₹14.5 L+₹2.2 L (18.0%)Rejected-Finance | L3 | Rejected-Finance In order but L3 | |
| 4 | L4₹14.5 L+₹2.3 L (18.4%)Rejected-Finance SHOP NO 106 1ST FLOOR ASHOKA SHOPPING CENTRE LT ROAD MUMBAI 400001 | MUMBAI | MUMBAI | MAHARASHTRA | 400001 | L4 | Rejected-Finance In order but L4 |
| Sl No | Description | Qty | Unit | KUKREJA BROTHERS L2 | PK ENTERPRISES L4 | NITHYA INFRATECH L3 | SIYA ASSOCIATES L1 |
|---|---|---|---|---|---|---|---|
| 1.00 | Supply, installing, testing and commissioning, factory made and tested , LT Panel (KIOSK) (FPB ), outdoor type, minium size 700 x 600x 500mm and platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated aluminum bus bars 400 Amps rating installed on porcelain insulators. The panel shall be dust and vermin proof, IP 65 class protection and SMC/made of 3.15mm CRCA MS sheet and 40x40x4mm thick angle iron frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, front opening type, with aprons for cable entry, with double door shutter and locking arrangement , internal wiring with PVC insulated, stranded copper conductor, FRLS cables, IS-7098 marked of adequate size but not less than 2.5 Sqmm. The platform shall be such that it is of a height 45 cm above the nearest road level. complete all as specified and directed including connections of all out going/in coming new / existing cables of any size by drawing /digging out cable from loops in trenches out side the Bldg including of necessary excavation and earth work as required and relaying the cables with retrieved bricks and providing new sand cushioning and crimping suitable size lugs for terminal connections of cables, necessary brick foundation with plastering to the Panel board, All out going feeders shall be connected and fixing danger notice plate made of 1.6mm thick mild steel sheet, vitreous enameled white, of size 20 x 15cm with letter, figures and conventional skull bones in signal red colour and fixed front & back door etc with voltage and danger indiated in Hindi and English complete all as specified all as specified and as directed by Engr-in-Charge , The scope of work includes the following: (NOTE:-LT Panel board should be as per IS/ICE 61439-part I&II Type Test certificates and Panel Builder should submit all Certificates before executing the job.) | 3 | Each | 43,000 ₹1,29,000 | 39,000 ₹1,17,000 | 38,500 ₹1,15,500 Lowest | 39,111 ₹1,17,333 |
| 1.01 | (I) INCOMING:-
(i) MCCB 4 Pole, Thermal Magnetic Based 160 A, Breaking capacity 25 KA, 415 V, 50 Hz with OL, SC, EF protection, -01 No along with Spreader terminals.
(ii) Digital Multi functional Amps/volt /PF/Hz meter 0-500 volts with selector switch - 01 No
(iii) Indicator lamp LED type (R, Y, B) complete with fuse -01 Set | - | - | - | - | - | - |
| 2.00 | Supply, installing, testing and commissioning, factory made and tested , LT Panel (KIOSK), outdoor type, minium size 900 x 600x 800mm and platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated aluminum bus bars 470 Amps rating installed on porcelain insulators. The panel shall be dust and vermin proof, IP 65 class protection and SMC/made of 3.15mm CRCA MS sheet and 50x50x5mm thick angle iron frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, front opening type, with aprons for cable entry, with double door shutter and locking arrangement , internal wiring with PVC insulated, stranded copper conductor, FRLS cables, IS-7098 marked of adequate size but not less than 2.5 Sqmm. The platform shall be such that it is of a height 45 cm above the nearest road level. complete all as specified and directed including connections of all out going/in coming new /existing cables of any size by drawing /digging out cable from loops in trenches out side the Bldg including of necessary excavation and earth work as required and relaying the cables with retrieved bricks and providing new sand cushioning and crimping suitable size lugs for terminal connections of cables, necessary brick foundation with plastering to the Panel board, All out going feeders shall be connected and fixing danger notice plate made of 1.6mm thick mild steel sheet, of size 20 x 15cm with letter, figures and conventional skull bones in signal red colour and fixed front & back door etc with voltage and danger indiated in Hindi and English complete incl taking out Unsv any type and size panel all as specified and as directed by Engr-in-Charge including taking out old U/S panel. The scope of work includes the following: (NOTE:-LT Panel board should be as per IS/ICE 61439-part I&II Type Test certificates and Panel Builder should submit all Certificates before executing the job.) | 1 | Each | 98,500 ₹98,500 | 1,50,000 ₹1,50,000 | 1,15,000 ₹1,15,000 | 97,111 ₹97,111 Lowest |
| 2.01 | (I) INCOMING:-
(i) MCCB 4 Pole, Thermal Magnetic Based 315 A, Breaking capacity 36 KA, 415 V, 50 Hz with OL, SC protection, -01 No
(ii) Digital Multi functional Amps/volt /PF/Hz meter 0-500 volts with selector switch - 01 No
(iii) Indicator lamp LED type (R, Y, B) complete with fuse -01 Set | - | - | - | - | - | - |
| 2.02 | (II) OUTGOING:-
(i) MCCB 4 Pole, Thermal Magnetic Based 160 A, Breaking capacity 25 KA, 415 V, 50 Hz with OL, SC protection, -02 No along with Spreader terminals.
(ii) MCCB 4 Pole, Thermal Magnetic Based 100 A, Breaking capacity 25 KA, 415 V, 50 Hz with OL, SC protection, -01 No along with Spreader terminals.
(iii) MCB TPN 4 Pole, Thermal Magnetic Based 40 A, Breaking capacity 10 KA, 415 V, 50 Hz with C -Curve, -01No along with Spreader terminals | - | - | - | - | - | - |
| 3.00 | M&L for plate earthing for LT panel complete with galvanised mild steel plate electrode 60×60cm.× 6 mm thick buried directly in ground vertically (in earth pit not less than 3.5 m below normal ground level) with the top edge of the earth plate at a depth not less than 2.75 m below normal ground level, the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides and incl GI earth strip 32 x 6 mm bolted (with GI nuts, bolts & check nuts) and riveted to earth plate at one end and connected to metallic bodies of LT equipments etc at the other, earth strip encased in and including 40mm bore GI light grade pipe with all fittings from top of electrode to body of equipment fixed with and including 25 x 3mm flat iron clamps, bolts, nuts and washer and also including providing watering pipe 20mm bore GI pipe medium grade from bottom of earth pit to top of electrode complete with earth pit in PCC 1:2:4 type B-1 using 20 mm graded crushed stone aggregate excavation & earth work and RCC cover complete all specified and shown in electrical plate No 3 of SSR Pt-I. | 8 | Each | 3,500 ₹28,000 | 3,600 ₹28,800 | 3,600 ₹28,800 | 3,111 ₹24,888 Lowest |
| 4.00 | Taking out unsv pole PCC/ Steel tubular and Supplying, transporting to site, erecting, and fixing in position, steel tubular swaged and welded poles of Overall height 9 metres, type 410 SP-31, IS-2713 marked, with mild steel base plate (fillet welded to poles), pole cap / finial taper plug, bolts, nuts, washers etc, and painting 05 nos band /strips with fluorescent , Black/ Red/ White/ Green and Black synthetic enamel paint ( 30 cm wide each) at a distance of 30 cm from plinth block and numbering of poles, complete all as specified and directed by Engr-in-Charge.(Note:- Poles shall be swaged and welded at manufacturer’s factory and not at site. The inner surface shall be factory painted) , | 22 | EACH | 13,500 ₹2,97,000 | 11,780 ₹2,59,160 | 13,500 ₹2,97,000 | 11,111 ₹2,44,442 Lowest |
| 5.00 | M&L for PCC (1:4:8)type D2 with 40 mm graded stone aggregate infoundation(below pole ) | 1.19 | Cum | 3,000 ₹3,564 | 3,600 ₹4,276.8 | 2,400 ₹2,851.2 Lowest | 3,111 ₹3,695.87 |
| 6.00 | M&L for cement concrete (1:3:6) type C-2 using 40mm graded stone aggregate for foundation of pole etc. (around the poles in pit) | 11.22 | CuM | 2,500 ₹28,050 | 2,200 ₹24,684 Lowest | 2,200 ₹24,684 Lowest | 2,211 ₹24,807.42 |
| 7.00 | M&L for PCC (1:2:4) type B-1 using 20 mm graded stone aggregate for coping of poles including necessary form work, fair finishing to exposed surfaces using extra cement | 1.05 | CuM | 3,000 ₹3,141 | 3,800 ₹3,978.6 | 2,800 ₹2,931.6 Lowest | 3,111 ₹3,257.22 |
Tender Value
₹19.5 L
EMD Value
₹39,100
Closing Date
30 Sept 2025, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE (U) Meerut Cantt
Roorkee road Meerut Cantt
SPL REPAIR OF OVERHEAD LINE CONVERT INTO UNDERGOING CABLE, SECURITY LIGHTS AND ALLIED SERVICES AT PARAMETER OF SDP MEERUT CANTT UNDER GE (U) MEERUT CANTT.
2025_MES_728920_1
8733/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Meerut Cantt
Please refer Tender documents.
12 documents required · 12 mandatory
₹500
GE (U) Meeerut Cantt
₹39,100
Yes
3 Dec 2025
2 Sept 2025
7 Oct 2025
2 Sept 2025
30 Sept 2025
16 Sept 2025
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .