Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹20.7 LAccepted-AOC 101 BLOCK QP MAURYA ENCLAVE PITAM PURA NORTH WEST DELHI DELHI 110088 | NORTH DELHI | DELHI | 110088 | ₹20.7 L | L-1 | Accepted-AOC Being the lowest bidder |
| 2 | L-2₹23.7 L+₹3.0 L (14.6%)Rejected-Finance KARNATAKA | RAICHUR | KARNATAKA | 584123 | ₹23.7 L+₹3.0 L (14.6%) | L-2 | Rejected-Finance Not the lowest bidder |
| 3 | L-3₹24.6 L+₹3.9 L (18.9%)Rejected-Finance | ₹24.6 L+₹3.9 L (18.9%) | L-3 | Rejected-Finance Not the lowest bidder |
| 4 | L-4₹24.8 L+₹4.0 L (19.5%)Rejected-Finance 94 D POCKET J AND K DILSHAD GARDEN DELHI DELHI 110095 UDYAM DL 02 0018675 07AHCPD1811D1Z7 B R | SHAHDARA | DELHI | 110095 | ₹24.8 L+₹4.0 L (19.5%) | L-4 | Rejected-Finance Not the lowest bidder |
| 5 | Rejected-Technical C 36 DUGGAL COLONY KHANPUR DEVLI ROAD DELHI 110062 | SOUTH | DELHI | 110062 | - | - | Rejected-Technical Not meeting NIT criteria |
| Sl No | Description | Qty | Unit | NATIONAL SAFETY ENGINEERS L4 | ECS ENGINEERING PVT LTD L2 | DY Infra & Projects Private Limited L3 | SYNERGY LIGHTING SOLUTIONS L1 |
|---|---|---|---|---|---|---|---|
| 1.00SITC of Electrical Spares / Light Fixtures | |||||||
| 1.01 | LED Panel light 2x2 ft. (System lumen efficacy ≥105 <120 lm/Watt)
Supplying, Installation, Testing & Commissioning of 36 Watt Panel light 2x2 ft. of following body material and construction as per IS:10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, freq 50/ 60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection, THD<10%, PF.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating)<19, Flicker free, (flicker should be below 5%), life time (LED, Driver & Electrical Circuitry) of minimum 50000 Burning Hours with, 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6000°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and fixture shall be of relevant BIS standard & trade mark certificate (TC). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c connections with suitable size FRLS, PVC insulated copper conductor single core cable & earthing etc. as required with minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output, LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size & CCT shall be as approved by Engineer-in-Charge as per requirement.(Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). CRCA Sheet body (Thickness>0.50 mm) | 92 | NOS. | 1,630 ₹1,49,960 | 1,500 ₹1,38,000 Lowest | 3,550 ₹3,26,600 | 2,000 ₹1,84,000 |
| 1.02 | LED Down lighter (SMD Type) (System lumen efficacy ≥ 105 < 120 lm/Watt)
Supplying, Installation, Testing & Commissioning of 18 Watt LED Recessed/Surface Down lighter (Round/ square/ Rectangular) SMD type of following body material with PMMA & prismatic diffuser and construction as per IS: 10322 with driver as per the requirement with Driver efficiency >85%, Operating Voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp. range -15 deg to 40 deg. centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection, THD <10%, P.F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5%), life time (LED, Driver & Electrical Circuitary), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K / 6000°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating & fixture shall be confirming to relevant BIS standard & trade mark certificate (TC). Manufactures Word Mark / Name Engraved/ Embossing/ Screen printing on housing complete in all respect i/c connections with suitable size FRLS, PVC insulated copper conductor single core cable & earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 & <120 lm/Watt output. LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size & CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body i/c trim with Aluminium Reflector | 34 | NOS. | 1,000 ₹34,000 | 816 ₹27,744 Lowest | 1,670 ₹56,780 | 1,000 ₹34,000 |
| 1.03 | LED Flood Light, powder coated pressure die cast aluminium (System lumen efficacy ≥120 & <135 lm/Watt)
Supplying, Installation, Testing & Commissioning of 70 Watt Flood Light, powder coated pressure die cast aluminum body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15°C to 50°C, internal surge protection of 5 KV L, N, E as per IEC 61000-4-5, Driver efficiency >85%, THD <10% as per IEC 61000-3-2, P.F. ≥0.95, IP-66, IK-10, CRI >80, under voltage & over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle 30 deg -120 deg as per the application & project requirement deg. suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K / 6000°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and fixture shall be of relevant BIS standard complete in all respect i/c connections with suitable size FRLS, PVC insulated copper conductor single core cable & earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 & <135 lm/Watt output. LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size & CCT shall be as approved by E-I-C as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). | 9 | NOS. | 2,180 ₹19,620 | 1,776 ₹15,984 Lowest | 5,500 ₹49,500 | 3,000 ₹27,000 |
| 1.04 | LED Flood Light, powder coated pressure die cast aluminium (System lumen efficacy ≥120 & <135 lm/Watt)
Supplying, Installation, Testing & Commissioning of 100 Watt Flood Light, powder coated pressure die cast aluminum body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD <10% as per IEC 61000-3-2, P.F.≥0.95, IP-66, IK-10, CRI >80, under voltage & over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle 30 deg -120 deg as per the application & the project requirement deg, suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K / 6000°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <5, Maximum Power Consumption should not more than the specified rating & fixture shall be of relevant BIS standard complete in all respect i/c connections with suitable size FRLS, PVC insulated copper conductor single core cable & earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 & <135 lm/ Watt output. LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size & CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). | 18 | NOS. | 2,760 ₹49,680 | 2,280 ₹41,040 Lowest | 8,250 ₹1,48,500 | 4,000 ₹72,000 |
| 1.05 | Supply, Installation, Testing & Commissioning of heavy duty wall mount Industrial AC Air circulators operating on single phase 240V having sweep of 750 mm having 03 blades, 03 speed control etc. and as directed by E-I-C. | 9 | JOB | 14,000 ₹1,26,000 | 12,950 ₹1,16,550 | 6,500 ₹58,500 Lowest | 10,000 ₹90,000 |
| 1.06 | Supply, Installation, Testing & Commissioning of heavy duty wall mount Industrial exhaust fans operating on single phase 240V, minimum 600mm sweep, 900 rpm as directed by E-I-C. | 4 | JOB | 12,500 ₹50,000 | 10,200 ₹40,800 | 4,800 ₹19,200 Lowest | 9,000 ₹36,000 |
| 1.07 | Supply, Installation, Testing & Commissioning of geyser with 25 Ltr. storage, 5 star BEE rating suitable for operating on single phase AC supply having glass coated heating element, metal body having water pressure of approx 8 bar with all safety features complete as required as directed by E-I-C. | 1 | JOB | 9,000 ₹9,000 | 7,500 ₹7,500 Lowest | 9,800 ₹9,800 | 8,000 ₹8,000 |
| 2.00SITC of Split Air-Conditioning Units | |||||||
| 2.01 | Supply of 2.0 TR BEE-5 star rating wall mounted Inverter Split type Air Conditioning Units operating on eco-refrigerant (R32 preferrably), copper condenser & copper evaporator coils suitable for operation on 220-240V, single phase, 50 Hz supply having all safety features, air filters, cordless remote for operation etc. incl. all accessories such as std. length copper pipe (not less than 3 mtrs), drain pipe, laying of power cable, control cable etc. having compressor warranty of minimum 10 years complete as required. | 11 | NOS. | 60,000 ₹6,60,000 | 57,800 ₹6,35,800 | 68,000 ₹7,48,000 | 50,000 ₹5,50,000 Lowest |
Tender Value
₹27.5 L
EMD Value
₹82,495
Closing Date
6 Jun 2026, 6:00 pmClosed
Parmeet Dahiya
Sr. Manager Engg(E) NATS Complex, New Delhi-110037
Renovation Modification Works at MT Workshop at RHQ, NR. SH-Electrical Works
2026_AAI_276901_1
AAI/RHQ-MT/MEW/2026-27/
Open Tender
Electrical Works
Item Rate
90 days
AAI, RHQ, NR
Please refer Tender documents.
5 documents required · 5 mandatory
₹1,180
₹82,495
15 Jul 2026
15 May 2026
8 Jun 2026
15 May 2026
6 Jun 2026
15 May 2026
15 May 2026 - 18 May 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1SITC of Electrical Spares / Light Fixtures | |||||
| 1.01 | LED Panel light 2x2 ft. (System lumen efficacy ≥105 <120 lm/Watt)
Supplying, Installation, Testing & Commissioning of 36 Watt Panel light 2x2 ft. of following body material and construction as per IS:10322 with driver as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, freq 50/ 60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection, THD<10%, PF.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating)<19, Flicker free, (flicker should be below 5%), life time (LED, Driver & Electrical Circuitry) of minimum 50000 Burning Hours with, 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6000°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and fixture shall be of relevant BIS standard & trade mark certificate (TC). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c connections with suitable size FRLS, PVC insulated copper conductor single core cable & earthing etc. as required with minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output, LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size & CCT shall be as approved by Engineer-in-Charge as per requirement.(Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). CRCA Sheet body (Thickness>0.50 mm) | - | NOS. | - | - |
| 1.02 | LED Down lighter (SMD Type) (System lumen efficacy ≥ 105 < 120 lm/Watt)
Supplying, Installation, Testing & Commissioning of 18 Watt LED Recessed/Surface Down lighter (Round/ square/ Rectangular) SMD type of following body material with PMMA & prismatic diffuser and construction as per IS: 10322 with driver as per the requirement with Driver efficiency >85%, Operating Voltage AC 140-270 Volt, frequency 50/60 hz, Operating temp. range -15 deg to 40 deg. centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection, THD <10%, P.F.≥0.95, IP20, CRI >80, UGR (Unified Glare Rating) < 19, Flicker free (flicker should be below 5%), life time (LED, Driver & Electrical Circuitary), of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K / 6000°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating & fixture shall be confirming to relevant BIS standard & trade mark certificate (TC). Manufactures Word Mark / Name Engraved/ Embossing/ Screen printing on housing complete in all respect i/c connections with suitable size FRLS, PVC insulated copper conductor single core cable & earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 & <120 lm/Watt output. LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size & CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). Powder coated die cast /Extruded aluminium Body i/c trim with Aluminium Reflector | - | NOS. | - | - |
| 1.03 | LED Flood Light, powder coated pressure die cast aluminium (System lumen efficacy ≥120 & <135 lm/Watt)
Supplying, Installation, Testing & Commissioning of 70 Watt Flood Light, powder coated pressure die cast aluminum body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15°C to 50°C, internal surge protection of 5 KV L, N, E as per IEC 61000-4-5, Driver efficiency >85%, THD <10% as per IEC 61000-3-2, P.F. ≥0.95, IP-66, IK-10, CRI >80, under voltage & over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle 30 deg -120 deg as per the application & project requirement deg. suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K / 6000°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and fixture shall be of relevant BIS standard complete in all respect i/c connections with suitable size FRLS, PVC insulated copper conductor single core cable & earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 & <135 lm/Watt output. LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size & CCT shall be as approved by E-I-C as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). | - | NOS. | - | - |
| 1.04 | LED Flood Light, powder coated pressure die cast aluminium (System lumen efficacy ≥120 & <135 lm/Watt)
Supplying, Installation, Testing & Commissioning of 100 Watt Flood Light, powder coated pressure die cast aluminum body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage: Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD <10% as per IEC 61000-3-2, P.F.≥0.95, IP-66, IK-10, CRI >80, under voltage & over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle 30 deg -120 deg as per the application & the project requirement deg, suitable tilt able fitting, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K / 6000°K / 6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <5, Maximum Power Consumption should not more than the specified rating & fixture shall be of relevant BIS standard complete in all respect i/c connections with suitable size FRLS, PVC insulated copper conductor single core cable & earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥120 & <135 lm/ Watt output. LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size & CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). | - | NOS. | - | - |
| 1.05 | Supply, Installation, Testing & Commissioning of heavy duty wall mount Industrial AC Air circulators operating on single phase 240V having sweep of 750 mm having 03 blades, 03 speed control etc. and as directed by E-I-C. | - | JOB | - | - |
| 1.06 | Supply, Installation, Testing & Commissioning of heavy duty wall mount Industrial exhaust fans operating on single phase 240V, minimum 600mm sweep, 900 rpm as directed by E-I-C. | - | JOB | - | - |
| 1.07 | Supply, Installation, Testing & Commissioning of geyser with 25 Ltr. storage, 5 star BEE rating suitable for operating on single phase AC supply having glass coated heating element, metal body having water pressure of approx 8 bar with all safety features complete as required as directed by E-I-C. | - | JOB | - | - |
| 2SITC of Split Air-Conditioning Units | |||||
| 2.01 | Supply of 2.0 TR BEE-5 star rating wall mounted Inverter Split type Air Conditioning Units operating on eco-refrigerant (R32 preferrably), copper condenser & copper evaporator coils suitable for operation on 220-240V, single phase, 50 Hz supply having all safety features, air filters, cordless remote for operation etc. incl. all accessories such as std. length copper pipe (not less than 3 mtrs), drain pipe, laying of power cable, control cable etc. having compressor warranty of minimum 10 years complete as required. | - | NOS. | - | - |
stage.html
html • 0.05 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 3.30 MB
TenDoc.pdf
Tender Documents • 14.08 MB
BOQ_324155.xls
BOQ • 0.34 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .