Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹39.4 LAccepted-AOC 10 0 RAMBAG COLONY RATLAM RATLAM MADHYA PRADESH 457001 | RATLAM | MADHYA PRADESH | 457001 | L1 | Accepted-AOC Being a lowest | |
| 2 | L2₹42.9 L+₹2.7 L (6.72%)Rejected-Finance | L2 | Rejected-Finance Not a lowest tender |
Tender Value
₹45 L
EMD Value
₹90,000
Closing Date
21 Jun 2023, 6:00 pmClosed
GE AF TA Gwalior
GE AF TA Gwalior 474020
REPAIR/MAINT OF CERTAIN B/R WORKS AND E/M WORKS AT WSA IN TECH AREA AT AF STN GWALIOR
2023_MES_591719_2
8900/1484/GWL/E8
Open Tender
Civil Works
Item Rate
330 days
AF STN Gwalior
As per tender documents
8 documents required · 8 mandatory
₹500
GE AF TA Gwalior
₹90,000
Yes
14 Jul 2023
6 Jun 2023
23 Jun 2023
6 Jun 2023
21 Jun 2023
8 Jun 2023
Amount
Demolition of cement concrete ( unreinforced) ground floors and pavings n. exc 15 cm thick below or above ground level and removing the demolished material to a distance exc 500 m but not exceeding 1.5 km and depositing where directed, complete all as specified and directed.
Demolition of cement concrete (unreinforced) of any description and in any position not otherwise specifically provided for complete all as specified and directed.
Demollition of cement concrete ( reinforced) of any description and in any position not otherwise specifically provided for complete all as specifeid and directed.
M&L for 75 mm thick plain cement concrete (1:3:6) type C1, using 20 mm graded stone aggregate as in Plinth protection and finishing the surface even & smooth without using extra cement complete all as specified and directed.
M & L for 100mm thick cement concrete type B-1. 1:2:4 (20mm graded aggregate) as in FLOOR/HARDSTANDING all as specified and directed.
M& L for forming 20mm thick Expansion joints filled with pre-formed bituminous filler and top 30mm primed and sealed with sealing compound, Grade ‘A’
M&L for 100 mm thick plain cement concrete (1:4:8) type D2, using 40 mm graded stone aggregate as in sub base and finishing the surface even & smooth without using extra cement complete all as specified and directed.
M&L for Sand/stone dust filling under floors to receive interlocking paver blocks incl consolidation complete all as specified and as directed.
M&L for 80 mm thickness Machine pressed precast conctete interlocking paver block any shape and size of M-40 Grade confirming to IS 15658-2006 with grey cement and no pigment incl dismentling of Stone slabs and tiles of any description or thickness in floors, aprons etc laid dry and pointed and complete all as specified and as directed.
Taking down existing steel doors of any description and in any position n exc 10 Sqm in size with complete fittings and fixture and refixing in the same opening after repairing/servicing/greasing & adjustment of hinge/wheel/weilding etc complete all as specified and directed. Note : including materials roller palte etc
Demolition of brick work or stone boulders masonry built in cement mortor or cement lime mortor including all quoins arches pillars etc., but excluding ashlar facing dressed stone work and precast concrete articles, complete all as specified and directed.
M&L for brick work with sub class 'B' bricks , straight or curved on plan exc. 6 m mean radius built in CM 1:6 complete all as specified and directed.
Description same all as per item No 12 above but, except brick using old retrieved bricks obtained from demolition in serviceable conditions complete all as specified and directed.
M&L for stone walling of random rubble masonry uncourse, well bonded, bedded and solidly hearted built in CM (1:6) complete all as specified and directed.
All as per item above here-in-before but, except stone complete all as specified and directed. (Note :- Old retrieved stones obtained from demolition in serviceable condition shall be used in the work).
M&L for flush pointing to random rubble masonry/stone walling in cement mortar (1:4) complete all as specified and directed.
M&L for plain cement concrete (1:3:6) type C2, using 40 mm graded stone aggregate as in foundations, filling and mass concrete etc complete all as specified and directed.
M&L for PCC (1:2:4) type B-1, (using 20 mm graded stone aggregate) as in surface channel etc complete all as specified made to shape and size as directed.
M & L for PCC (1:2:4) type B0, using 12.5mm graded stone aggregate as in coping including necessary form work complete all as specified and directed .
Extra for forming fair finish drain or channel 30cm inner girth in cement concrete, using extra cement including forms, moulds, mitered/stooped ends etc complete all as specified and directed.
Add or deduct for each 25 mm girth or part thereof over or under 30cm ditto
M&L for precast RCC (1:2:4) type B1 (using 20mm graded aggregate) as in shelves, cover slabs for manholes/drains etc set in cement mortar (1:6) including necessary form work etc complete all as specified and directed. (Note : Reinforcement shall be measured and paid separately) under appropriate item of Sch ‘A’
S&F mild steel TMT bars of 10 mm dia and over cut to length, bent to shape as required including cranking, bending, spirally for hooping for column hooking ends and binding with and including mild steel wire (annealed) not less than 0.9 mm dia for securing with clips complete all as specified and directed.
Taking down cement plaster on brick surface or stone including raking out joints hacking for key, scrubbing down with water etc complete all as specified and directed by Engr-in-Charge.
M&L for 15mm thick rendering other than fare face of brick/stone masonry walls in CM 1:6 finished even and smooth without using extra cement all as specified and directed.
M&L for 15mm thick rendering fare face of brick/stone masonry walls in CM 1:4 finished even and smooth without using extra cement all as specified and directed.
M&L for Preparation of newly plastered surface and applying two coat of weather coat exterior emultion (Make : APEX of Asian Paints or equivalent in Berger Paints etc) white or tinted by the use of rollers over a coat of putty as approved complete all as specified and directed.
M&L for Preparation of newly plastered surface and applying two coat of distemper oil emulsion white or tinted by the use of rollers over a coat of Putty as approved complete all as specified and directed.
M&L for 600mm bore reinforced concrete pipes class NP-2 ,laid and jointed complete with collars complete all as specified and directed including dimantling of old RCC pipe& necessary excavation.
M&L for concrete bed to drain pipe incl packing under and completely surrounding pipes with cement concrete 1:3:6 mix,type C-2(using 40mm geaded stone aggregate)complete all as specified and directed.
Dismantling floor, hearth or wall tiling including cement mortar bedding and removing rubbish off the premises complete all as specified and directed.
M&L for joint free coloured Glazed ceramic tiles in vertical surface 450X 300X 7mm thick set and jointed in neat cement slurry and pointed in white or colour cement to match the tiles including 10 mm thick rendering/ backing coat in CM 1:4 all as specifide and as directed.
M&L for 25mm Plain Cement concrete type B-1, 1:2:4 (20mm graded aggregate) as in subbase of floor/path complete all as specified and directed
M&L for non skid ceramic joint less coloured tiles 7 to 8mm thick (square/ rectangular) area of each tile exceeding 0.06 sqm but not exceeding 0.11 sqm, in floors etc. , laid over and including 15mm thick screed bed in cement mortar 1:6 , set, jointed in neet cement slurry and pointed in coloured cement to match with shade of tiles complete all as specified and directed.
S&F in repair Kitchen sinks with drainage board made of stainless steel lmm thick kitchen or laboratory with plugs, washers and wastes; including bedding in cement mortar to dwarf wall or including fixing cantilever brackets and connecting union to pipe overall size 915mm x 460mm bowl size 410mm x 330mm x 160mm complete all as specified and directed.
S&F in repair vitreous china wash hand basin, white oval type, size 550mmx400mm fixed over marble slab, including 32mm dia brass waste coupling and including fixing of tap, waste fitting and union complete all as specified and as directed . Note: pillar tap shall be measured as supply only under respective items
S&F in repair brass CP wall mixer 15mm dia bore mixing hot & cold water for wash hand basin and kitchen sink screwed down for iron pipe and fixed.
S&F in repair PVC connection 15mm dia with Brass nuts of length 450mm etc complete.
S&F in repair 15 mm bore angle stop cock long thread fancy type chromium plated cast copper alloy, screwed down high pressure with crutch or butter fly handle screwed both and for iron pipe or for union and fixed etc complete.
S & F in repair rotational moulded polye-thylene triple layer puff based water storage tanks of capacity 1000ltr (cylindrical vertical with closed top) hoisted and fixed in position including float valve 20mm dia including dismantling of old u/s water tanks all as specifeid and directed.
S&F in repair coloured vitreous china squatting pan orissa pattern size 580 x 440mm white with P or S trap ,front & back inlet ,intergral floot rest including flush pipe fixed in position and made serviceable complete all as specified and directed.
S&F in repair coloured vitreous china Urinal half stall type complete including providing and fixing plugs bedding urinal against wall in cement mortar (1:2), securing urinal to plugs with and including 60 mm long brass screws, pointing around urinal back in cement , PVC waste coupling and pipe complete all as specified and directed.
S&F brass chromium plated Tubular towel rail, 20mm dia, D type, 60 Cm long between flanges including taking down of old PVC towel rail complete all as specified and directed.
S&F in repair coloured PVC low level flushing cistern 10 litres capacity with inlet 15 mm bore ball valve float and handle including 32 mm bore PVC flush pipe of required length complete all as specified and directed
M&L for 0.63mm Plain, galvanised, mild steel sheeting, in ridges, hips, valley gutters, drip and straight flashings (length and girth as fixed) with grade of zinc coating 275 incl all necessary fitting including Dismentling of existing Plain or corrugated steel/PGI Sheet complete all as specified and directed.
S&F in repair 75 mm internal bore of PVC (SWR) pipes single socketed, in any length with rubber ring joints, laid in trenches or in floors/walls etc complete.
S&F in repair 75 mm internal bore of PVC (SWR) bends with access door any radius etc complete.
S & F in repair 20mm dia Gun metal gate valve with iron wheel head, screwed both ends for iron pipe complete all as specified and as directed.
Supply only 20 mm bore Ball valves high pressure of PTMT with epoxy coated Aluminium rod & high-density plastic ball screwed for iron pipe and fixed. .(Minimum weight 15mm-142gms/ 20mm-210 gms./25mm-455gms/ 40mm etc complete.
S&F in repair 15 mm bore bib taps long body chromium plated fancy type, cast copper alloy with crutch or butter fly handle screwed down screwed for iron pipe or for unions and fixed 15 mm bore etc complete.
M&L for Rough excavation not exceeding 1.5M deep and getting out soft/loose soil complete all as specified and as directed.
Removing excavated material exc 1.5 KM but n;exc 5KM and depositing where directed.
Forming embankments and traverses including raising(or lowering) earth,spreding in layers n:exc 30 cm thick , watering,ramming/rolling and finishing to required size,shape,etc n, exc 6.00 M high from base complete all as specified and directed.
S&F in repairs HDPE perforated GEOCELL mesh for slope protection of earth any shape with size (330-100mm) 1.50mm thick fixed to earth with necessary arrangements 'J' hooks and jointing clips including leveliing and ramming earth to required gradient by using the existing traverse earth complete all as specified and directed. (Make:- Terrain Infratech, Geological structial infra Pvt Ltd., Omega Construction etc.)
Cutting of all bushes ,grass and sarcandas, shrubs, vegetation etc including trees n'exc 30 cm girth and removing the material exc 500m and n exc 1 KM complete all as specified and directed.
Removal of existing roof treatment (screed plaster, & tarfelt of any description) and removing to a distance exc. 500 m and n.exc. 5 Km from site complete all as specified and directed.
M & L 25mm thick PCC (1:2:4) type B-0 using 12.5mm graded stone aggregate as in benching,kerbs and levelling course etc over roof surface complete all as specified and as directed
Supply only liquid water proofing compound complete all as specified and directed.
M & L for 10 mm thick screed bed in cement mortar 1:4 mixed with using liquid water proofing compound as per manufacturers instructions (Note:Water proofing compound shall be measured and paid seprerately under respective item of "BoQ") over roof top surface finished even and smooth using extra cement and application of water proofing treatment using APP modified roof membrane over existing inaccessible RCC roof slab / chajjah / canopy / parapet wall to be executed through approved applicator of the membrane manufacturer with following specification etc complete all as specified and directed :- (a) Cleaning existing surface properly. (b) Applying oil bound bitumen primer @ 0.30 litre / Sqm manufactured by the same agency as that of APP membrane with a density 0.87-0.89 Kg per liter at 25 degree centigrade on prepared surface. (c) Applying hot blown grade bituminen 85/25 @ 1.2 Kg/Sq M over primer. (d) Laying not less than 3mm thick APP modified water proofing membrane weighing not less than 3.60 Kg/Sqm reinforced with non woven polyster fiber weight not less than 160gsm/Sqm using butane torch by torch application with 10cm side laps and 15cm end lap. Physical property of membrane shall be as under :- (i) Membrane weight not less than 3.60 Kg/Sqm.
M&L for PCC (1:3:6) type C1, using 20mm graded stone aggregate as in foundation illing mass concrete complete all as specified and directed.
Dismantling mild steel work of any description not otherwise provided for complete all as specified and directed.
M & L for MS work as in swan neck / brackets etc for fencing post & strut in fencing etc including cutting tops to shape as directed, drilling holes, riveting for wires etc including all necessary drilled bolting or riveting etc and similar work conforming to Fe290 Gde E-165 complete all as specified and directed.
S & F in repair galvanized 2 stranded steel barbed wire 2.24 mm dia barbed with 2 mm dia barbs at 75 mm spacing and fixing to any type of standard hooks, including securing and tying at crossing with and provision of galvanized mild steel wire staples or steel pins etc complete all as specified and directed.
Tightening /restraining and resecuring of old existing barbed wire including making good staples etc in same position complete all as specified and directed .
Preparing new steel & iron surfaces of any description over 10cm in width or girth and M&L for applying two coat of synthetic enamel paint over a coat of red oxide complete all as specified and directed.
Preparing old painted steel & iron surfaces of any description over 10cm in width or girth and M&L for applying one coat of synthetic enamel paint complete all as specified and directed.
Preparing old painted steel & iron surfaces of any description n.exc over 10cm in width or girth and M&L for applying one coat of synthetic enamel paint complete all as specified and directed.
Preparing New painted steel & iron surfaces of any description n.exc over 10cm in width or girth and M&L for applying one coat of synthetic enamel paint over a coat of red oxide complete all as specified and directed.
M&L in repairs of Running welding exc 6mm thick welded metal etc complete ® all as specified and as directed .
Dismantling posts or struts (Wood, steel, or RCC) any section, including taking out embeded portion and making good distrubed ground, including any type fencing all as specified and directed.
Fixing only Chain link fencing including line wires, any mesh, size and type to any type of standards, rails, straining bolts, etc including provission of binding wire complete all as specified and directed.
Supply only Chain link MS galvanised 4mm dia (wt. not less than 4kg) fencing any size or type all as specified and directed .
S&F in repair of concertina coil size n exc 600 mm in one rows between the double layer fencing including all fixing arrangement complete all as specified and directed .
S&F in repair Framed work as in Sliding doors/ gates/danger boards of angle or other section with gusset plates, rails, braces, etc., complete, drilled for fixing of steel sheeting or other covering. Doors, etc. to be prepared for hanging or sliding with and including either hooks and hinges or steel hanging door fittings including Cast iron wheel of any size, steel sheeting or other covering, running rails and guides and hanging; also fastening and fixing etc. conforming to Fe 410-W (Gde- E- 250) quality-A complete all as specified and directed.
M&L for applying one coat of external emulsion paint/weather coat, in camouflaging pattern on CCD scheme (Pattern as approved by GE) on surfaces of any type of building, wall, any surfaces, any height, incl preparation of old decorated surfaces complete all as specified and directed. Note- Rate quoted by contractor incl scaffolding and T&P upto 15m height of the building. No extra payment admissible on this account. (Make : APEX of Asian Paints or equivalent in Berger Paints etc)
M&L for Complete removal of existing treatment on walls (any number of layers) by scrapping with steel scrappers or any other means, and filling the cracks and depressions with putty/ chalk whitening to make the surface even and smooth matching to the adjacent wall surfaces applying two coat of external emulsion paint/weather coat, in camouflaging pattern on CCD scheme (Pattern as approved by GE) by the use of rollers/Brush on surfaces of any type of building, wall, any surfaces, any height, over a coat of primer complete all as specified and directed. Note- Rate quoted by contractor incl scaffolding and T&P upto 15m height of the building. No extra payment admissible on this account. (Make : Apex of Asian Paints or equivalent in Berger Paints etc)
M&L for Preparation of old decorated surfaces of ceilings including cornices, plastered or unplastered surfaces by brooming down or steel wire brushing to remove dust, dirt and loose scales of lime wash and other foreign material, scrapping down, smoke soot, moulds, moss and efflorescent salts, trading oil and greasy spots etc and applying one coat of white wash using rollers complete all as specified and directed.
M&L for Complete removal of existing treatment on walls (any number of layers) by scrapping with steel scrappers and and applying a coat with putty to make the surface even and smooth matching to the adjacent wall surfaces and applying two coats distemper oil emulsion by the use of rollers, over a coat of primer all as specified and directed.
Taking down chowkhat or frames with shutters (without taking off shutters from the frame) n.exc 1.5 Sqm each complete all as specified and directed.
Taking down shutters of any description exc 1 sqm but n exc 2 sqm each each complete all as specified and directed.
Taking down chowkhat or frames with shutters (without taking off shutters from the frame) exc 1.5 Sqm but n'exc 4 Sqm each complete all as specified and directed.
Taking down shutters of any description exc 2 sqm each each complete all as specified and directed.
S & F solid PVC door frame of size 50 mm x 47 mm made out of 5 mm thick plain colour PVC sheet reinforced with MS Square tube complete all as specified and directed.
S&F Factory Made Solid PVC Moulded Door Shutter with wood free EPS, 28 to 30mm thick(stiles), with 2, 4, or 6 raised panel design with 2mm thick Moulded PVC Sheet on the front face & 2mm plain colour PVC sheet on back face, supplying & fixing in frame at site as per specification & drawing complete all as specified and directed.
S&F including fabricating of powder coated aluminium frame for door/Shutter, window, ventilator , partition with one or more rebates including jointing cleats for fixing etc, minimum thickness of powder coating 50 Micron complete all as specified and directed.
S&F 5mm thick tinted glass fixed with necessary rubber gasket and aluminium snap beadings tint match with existing complete all as specified and directed.
S&F 100 mm long butt hinges, extruded aluminium alloy with galvanised mild steel hinge pin, anodised and fixed, type C21 complete all as directed and specified
S&F for 150 mm long aluminium, anodised, barrel tower bolts of extruded section complete all as directed and specified
S&F for 150 mm long aluminium handles, cast type, anodised complete all as directed and specified
S&F for 200 mm long aluminium alloy, anodised, sliding door bolt with hasp, staples(bolt type) and fixing clips of sheet, cast or extruded sections and fixing bolts and sliding bolts of extruded sections or csat aluminium alloy complete all as directed and specified
M&L double action floor spring hydraulically regulated made up of minimum 1.25mm thick aluminium alloy sheet foundation box, main body with stainless steel cover, governing pivot made of brass other parts made of mild steel heavy duty and fixed complete all as specified and directed.
S&F Aluminium (extruded section ) body door closer hydraulically regulated designation No 3, universal type suitable for any type of door shutters complete all as specified and directed.
S&F 100mm brass motrice lock 2 livers, vertical type complete all as specified and directed.
S&f in repair bird proofing net for hanger/shed/sheler/DBs entrance etc upto 15m height complete as per manufacturer instructions: (a) Type of bird proofing net : Polyolefin all weather proof co-primer (b) Method of knotting : Machine knotting using CNC machine with DSLS technology for anti slip knotting (c) Heat Setting : Steam set for greater dimensional stability and knot firmness (d) Diametre of the twine : 1mm dia wire with square mesh size 25mmx25mm (+/- 2mm) (e) TBS (twine breaking strength) : 16kgf min (f) MBS (Mesh breaking strength) : 12kgf min (g) KBS (knott breaking strength) : 22kgf min Note : All necessary items i.e clip, nuts, washers and other acessories required for proper fixing as per manufacturer instructions shall deemed to be included in the quoted rate.
Taking down carefully existing unserviceable flame proof point wiring of any description & in any height ( 4m to 16m ) position with and including existing conduit fixed on surface with and including existing junction boxes in between the point wiring complete, including making good the disturbed surface of walls, floors, ceiling etc to match with the existing surfaces complete all as specified and directed. NOTE: (i) Old existing junction boxes obtained in serviceable condition from taking down of point wiring shall be re-used in the work. (ii) Taking down / replacement of existing fittings like switches/sockets / switch fuses / tube light fittings etc. if any, shall be measured and paid for separately under appropriate item of Schedule `A'
Taking down carefully existing unserviceable flame proof point wiring of any description & in any position , any height ( 4m to 16m ) from existing conduits fixed on surface or concealed including accessaries & fixtures etc and making good the distrubed surface of walls, floors, ceiling etc to match with the existing surface complete all as specified and directed NOTE: (i) Taking down / replacement of existing fittings like switches/sockets / switch fuses / tube light fitting etc. if any, shall be measured and paid for separately under appropriate item of Schedule `A'
Material and labour for flame proof point wiring for one light point or one socket point controlled by one switch with using 1.5 Sqmm (nominal area) stranded copper conductor, single core, FRLSH PVC insulated & unsheathed cable, 1100 volts grade in and including stove enameled black, rigid steel conduits of size not less than 20 mm dia (Medium grade) fixed on surface of walls/ceilings any height ( 4m to 16m )as directed with all accessories and using 1.5 Sqmm (nominal area) stranded copper conductor single core FRLSH, PVC insulated & unsheathed cable as in earth wire connected to common earth dolly / fittings etc. complete all as specified and directed NOTE : (i) Old junction boxes retrieved in serviceable conditions shall be re-used in the work. However, additional junction boxes, if any required, for making new point wiring other than the quantity of junction boxes retrieved from taking down of point wiring, shall be measured and paid for separately as ‘’supply only’’ under appropriate item of Schedule `A' but fixing element of any type of junction boxes new or old is deemed to be included in the rates quoted by the contractor for the above item. (ii) Wiring shall be terminated and connected to the relevant switch / controlling switch gear and relevant fittings / sockets all as directed and controlling switch / fittings shall be measured and paid for separately under appropriate item of Schedule `A'.
All as per item No 98 here-in-before but point wiring with using 2.5 Sqmm (nominal area) stranded copper conductor, single core, FRLSH PVC insulated & unsheathed cable for 16 A Flame proof Switch and socket
Material and labour for flame proof point wiring for one light point or one socket point controlled by one switch with using 1.5 Sqmm (nominal area) stranded copper conductor, single core, FRLSH PVC insulated & unsheathed cable, 1100 volts grade in existing conduit fixed on surface of walls/ceilings as directed and using 1.5 Sqmm (nominal area) stranded copper conductor single core FRLSH, PVC insulated & unsheathed cable any height ( 4m to 16m ) as in earth wire connected to common earth dolly / fittings etc. complete all as specified and directed NOTE : (i) Point wiring shall be executed with using existing conduits and junction boxes but contractor’s quoted rates for the above item is deemed to include the cost of fixing the existing conduits and junction boxes in position properly as per site requirement and as directed by the Engineer-in-Charge. (ii) Wiring shall be terminated and connected to the relevant switch / controlling switch gear and relevant fittings / sockets all as directed and controlling switch / fittings shall be measured and paid for separately under appropriate item of Schedule `A'.
All as per item above here-in-before but point wiring with using 2.5 Sqmm (nominal area) stranded copper conductor, single core, FRLSH PVC insulated & unsheathed cable for 16 A Flame proof Switch and socket complete all as specified and directed.
M&L for sub main wiring in repair concealed using Four single core PVC insulated, FRLSH, stranded copper conductor cable any height ( 4m to 16m ) of size 4 Sqmm for sub main wiring, along with one run of 4Sqmm PVC insulated, FRLSH, Stranded copper conductor cable for earth continuity conductor in steeel conduit complete all as specified and directed. Note: Four run of single core PVC cable with one run of earth wire and one run of steel conduit together shall be measured as one unit.
All as per item No. 102 here-in-before but using Two single core, 2.5 Sqmm copper conductor cable and with earth continuity conductor. Note: Two run of single core PVC cable with one run of earth wire and one run of steel conduit together shall be measured as one unit.
All as per item No. 102 here-in-before but using Two single core, 1.5 Sqmm copper conductor cable and with earth continuity conductor. Note: Two run of single core PVC cable with one run of earth wire and one run of steel conduit together shall be measured as one unit.
Disconnecting and taking down carefully flame proof, weather proof, toggle type switches and making good the disturbed surfaces complete all as specified and directed.
Disconnecting and taking down carefully flame proof DB’s of any size/way and making good the disturbed surfaces complete all as specified and directed.
Disconnecting and taking down carefully flame proof, Switch socket of any capacity and making good the disturbed surface complete all as specified and directed.
Supply & fixing flame proof push button 10 Amps in LM 6 metal enclosures, conforming to cat part No PBS / OA /1010-1A of make Sudhir or equivalent model of other make as specified complete all as specified & directed.
Supplying & fixing flame proof, switch socket & plug combined made of aluminum alloy LM-6 having 2 pole + earth suitable for 250 volts supply and current rating of 16 Amps complete all as specified & directed. (Make/model – Sudhir cat part No. SS/OA/1010 -1 or equivalent model of other make as specified).
Supplying & fixing flame proof, switch socket & plug combined made of aluminum alloy LM-6 having 4 pole + earth suitable for 500 volts supply and current rating of 32 Amps complete all as specified & directed. (Make/model – Sudhir cat part No. SS/187 or equivalent model of other make as specified).
Disconnecting & taking out existing unserviceable socket’s plug of any description and in any position and supplying & fixing new spare plug suitable for existing flame proof, weather proof, switch, socket & plug combined in LM-6 for 2 poles + earth & current rating of 16 Amps complete all as specified and directed. (Make – Sudhir or other make as specified ).
All as per item No 111 here-in-before but plug suitable for 4 pole + earth & current rating of 32 Amps (Make – Sudhir or other make as specified).
Supply & replace flameproof distribution board 8 way single pole & neutral in LM-6 metal enclosures with and including 01 No MCBs single pole and neutral 40 Amps & 06 Nos MCB single pole 16 Amps `C’ series complete all as specified and directed. (Make : Cat part no MCDB-186 of Sudhir or equivalent model of other make as specified.
Supply & replace flameproof distribution board 4 way Triple pole & neutral in LM-6 metal enclosures with and including 01 No MCBs tripple pole and neutral 63 Amps & 06 Nos MCB single pole 16 Amps `C’ series complete all as specified and directed. (Make : Cat part no MCDB-186 of Sudhir or equivalent model of other make as specified).
Supply & fixing in replacement flameproof distribution board 4 way Triple pole & neutral in LM-6 metal enclosures with and including 01 No MCCB tripple pole and neutral 100 Amps as Incoming & Out going MCB 63 Amps TPN 415 volts -01 No,MCB DP 32 Amps 240 Volts-01 No and MCB SP 16 Amps 240 Volts -03 Nos complete all as specified and directed. (Make : Cat part no MCDB-186 of Sudhir or equivalent model of other make as specified).
Supply & fixing in replacement FLP Flexible metelic Hose conduit M20/3/4ET 300 mm long complete all as specified and directed. (Make : Cat part no FH/199of Sudhir or equivalent model of other make as specified).
Supply and fixing LED driver 240 V 50 Hz suitable for the existing LED flame proof lights fittings installed at any height ranging from 3m to 16m (Make Sudir) for the following watt :- (a) 75-90 Watt
(a) 120-180 Watt
Supply & fixing in replacement flame proof FLP Flood light 60 W LED fittings as per IS : 2148 / 1981 & 2206 (Part-I )1984, Temperature class T-4, & made of cast aluminum alloy LM-6 having inside & outside light grey powder coating shade No 631 as per IS: 5 & one No internal earthing terminal and 02 Nos external earthings of screw of M6- size with 02 Nos plain washers heat resistant glass including taking down the unserviceable fitting from any height ( 3m to 16m) complete all as specified and directed. Make : Sudhir /Baliga/CG..
Supply & fixing in replacement flame proof FLP Flood light 70 W LED fittings as per IS : 2148 / 1981 & 2206 (Part-I )1984, Temperature class T-4, & made of cast aluminum alloy LM-6 having inside & outside light grey powder coating shade No 631 as per IS: 5 & one No internal earthing terminal and 02 Nos external earthings of screw of M6- size with 02 Nos plain washers heat resistant glass ncluding taking down the unserviceable fitting from any height ( 3m to 16m) complete all as specified and directed. Make : Sudhir/Baliga/CG..
Supply & fixing flame proof FLP Flood light 90 W LED fittings as per IS : 2148 / 1981 & 2206 (Part-I )1984, Temperature class T-4, & made of cast aluminum alloy LM-6 having inside & outside light grey powder coating shade No 631 as per IS: 5 & one No internal earthing terminal and 02 Nos external earthings of screw of M6- size with 02 Nos plain washers heat resistant glass ncluding taking down the unserviceable fitting from any height ( 3m to 16m) complete all as specified and directed. Make : Sudhir Cat Part No 0151 /Baliga/CG..
Supply & fixing flame proof FLP Flood light 120 W LED fittings as per IS : 2148 / 1981 & 2206 (Part-I )1984, Temperature class T-4, & made of cast aluminum alloy LM-6 having inside & outside light grey powder coating shade No 631 as per IS: 5 & one No internal earthing terminal and 02 Nos external earthings of screw of M6- size with 02 Nos plain washers heat resistant glass ncluding taking down the unserviceable fitting from any height ( 3m to 16m) complete all as specified and directed. Make : Sudhir Cat Part No 1251 /Baliga/CG..
Supply and replace LED Tube rod 28 W T-5 suitable for existing flame proof tube light fitting installed at any height 3m to 16m complete all as specified and directed.
Supply and fixing in distribution board, single pole (SP) MCB 6 to 20 Amps, 240 volts, 50 Hz, AC made from molded self extinguishing thermostat plastic and suitable for ‘ C ‘ curve, 10 KA breaking capacity conforming to IS : 8828 of 1996 including taking down unserviceable MCB complete all as specified and directed.
Supplying and fixing flame proof junction box 3 way ¾ “ entry in LM – 6 complete all as specified and directed.
Supply and replace LED flame proof well glass fitting 70 Watt including taking down the unserviceable fitting from any height ( 3m to 16m) fith necessary driver, fittings and fixtures complete all as specified and as directed.
S&F in repair Ultra bright glass 20W LED tube light and high efficiency from any height 3 m to 16 m suited for installation in exsiting flame proof Tube light fitting (T-8) alongwith G3 lamp holders complete all as specified and directed. Make :-Havells Cat part No -CRYSTAL1213T8DSTL20WLED865SGLASS or equivalent model of make Philips/Oshram
M & L for checking & repairing flame proof tube lights/flood lights/ & other flame proof connected work installed at any height from 3m to 16m as directed in tech area and repairing of flameprrof lights found unserviceable during checking or as per directed by JE/Engr-in-Charge/men on complaint cell including rectification of fault of wirng etc by deploying skilled Electrician, helper with all tools & plants, ladder, gaskets safety arrangements and including providing minor materials like insulation tap and connected material by contractor to make light serviceable complete all as specified and directed. NOTES :- (i) Rate quoted shall deemed to be included for required minor material like insulation tap,rubber gasket and packing materilas required for of junction box with lugs etc. (ii) Items like Driver for LED and other items other than mentioned above paid separately.
Supply and replce LED driver 240 V 50 Hz suitable for the existing LED flame proof lights installed (at any height from 3m to 16m ) fittings (Make Sudir) for the following watt :- (a) 75 - 90Watt
(a) 120 - 180Watt
Taking down carefully the flame proof distribution board cover of any capacity any make, replacing the buntout wiring of any type and any size, tightning the connectors and MCB's, refixing the cover after cleaning complete all as specified and as directed.
Supply and replace MCB C Series SPN 32 Amp complete suitable for fixing inside flame proof distribution Board
Supply and replace MCB C Series TPN 40 Amp complete suitable for fixing inside flame proof distribution Board
Supply and replace MCB C Series SP 6 to 32 Amp complete suitable for fixing inside flame proof distribution Board
Taking down carefully earth strip alumium of any size and any type from any height (3m to 16 m) of building or hangar ( roof conductor and down conductor) of Lightning protection and refixing the same with necessary insulators complete all as specified and as directed.
All as per above item but Air Termination rod of any size
Taking down carefully any light fitting from ceiling/wall and refixing the same along with necessary wires and fittings complete all as specified and as directed
All as per above item but Celing fan of any make and capacity
JNK BOND
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .