Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹26.6 LAccepted-AOC 10 1 GROUND FLOOR WEST GHOSH PARA JAGATDAL JAGATDAL JAGATDAL NORTH 24 PARGANAS WEST BENGAL 743125 | 24 PARAGANAS NORTH | WEST BENGAL | 743125 | L1 | Accepted-AOC Lowest bidder | |
| 2 | L2₹31.0 L+₹2.6 L (9.11%)Rejected-AOC 44B CIRCULAR GARDEN REACH ROAD KOLKATA 700 023 | KOLKATA | WEST BENGAL | 700023 | L2 | Rejected-AOC Other than lowest bidder | |
| 3 | L3₹32.1 L+₹3.7 L (13.2%)Rejected-AOC | L3 | Rejected-AOC Other than lowest bidder | |
| 4 | L4₹32.1 L+₹3.8 L (13.2%)Rejected-AOC P 21 MANAS BAG KOLKATA 700 056 | KOLKATA | 24 PARAGANAS NORTH | WEST BENGAL | 700056 | L4 | Rejected-AOC Other than lowest bidder | |
| 5 | L5₹32.1 L+₹3.8 L (13.3%)Rejected-AOC 117 LENIN SARANI KOLKATA 700 013 WEST BENGAL | KOLKATA | KOLKATA | WEST BENGAL | 700013 | L5 | Rejected-AOC Other than lowest bidder |
Tender Value
₹35.5 L
EMD Value
₹71,000
Closing Date
1 Jul 2023, 6:00 pmClosed
CWE (S) Barrackpore
Commander Works Engineers (Sub) Military Engineer Services PO Barrackpore, Dist 24 Pgns (N) Kolkata 700120 (W.B)
REPAIR/MAINT OVERHAULING AND SERVICING OF HT AND LT EXTERNAL ELECTRIFICATION, LT/HT GADGETS INCLUDING VCBs, TRANSFORMER, ACBs, APFC PANEL, FEEDER PILLARS BOXES AND ALL OTHER LT ELECTRICAL RELATED SYSTEM ETC IN KOLKATA AREA UNDER GE (N) KOLKATA
2023_MES_600842_1
CWE/(N) KOL/07 of 2023-24
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE (North) Kolkata
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
GE (North) Kolkata
₹71,000
Yes
22 Jul 2023
3 Jun 2023
3 Jul 2023
3 Jun 2023
1 Jul 2023
17 Jun 2023
Amount
Supply and Fix Panel heater for VCB HT panel including necessary fixing arrangement including taking out unserviceable one all as spedified and as directed.
Material and Labour for reparing / replacement of locking arrangement of HT Panel including necessary fixing arrangement including taking out unserviceable one all as spedified and as directed.
Material and Labour for reparing/replacement of locking arrangement of LT Panel including necessary fixing arrangement including taking out unserviceable one all as spedified and as directed.
Repair / maintenance and servicing,refixing,commencing and testing of step down transformer 6.6 KV/433 Volt of capacity 500 KVA, comprising following work services :- (a) Disconnection carefully of cable end termination of HT & LT side. (b) Opening of top cover by removing nuts, bolts and all mounting accessories and conservator tanks. (c) Draining out transformer oil and keeping aside in barrel for re-use and then again pouring back after necessary filteration and dehydration including top up with new transformer oil to make up the reduced quantity. (d) Replacement of top and buttom Gaskets. (e) Servicing of tap changing gears by cleaning and polishing tapping contact points. (f) Labour only for Cleaning of bush and stud both HT/LT side and refixing the same with new cock sheet as required. (g) Replacing unserviceable stud and bush as required as directed by Engr-in-Charge. (h) Reconnection of all cable terminals HV & LV sides and refixing the top cover after replacement of gaskets, conservator tank in position. (j) Cleaning of breather and replacing with new silica gel. (k) Connecting HT & LT side with existing incoming and outgoing cables including reconnection of earth strip/lead. Note: (i) Filteration and dehydration of transformer oil, topping up of New transformer oil shall be measured and paid separately., (ii) Spares like bushes and studs,New silica gel,New buchholz relay and M seal monoplast, etc required for replacement shall be measured and paid for as supply only separately. The labour element involved in replacing the spares shall be deemed to include in the unit rate quoted. (iii) The unit rate quoted shall include the cost of all other minor spares as required not mentioned hereinafter.
Supply and fixing in repair, of HT CT of ratio 50/5 Amps all as spedified and as directed.
Repair/servicing of HT PT epoxy type including replacing of primary and secondary winding, replacement of PT bush-03 Nos and housing bush-03 Nos all as spedified and as directed.
Supply and fixinng, in repair, of triping coil 110/30 V DC all as spedified and as directed.
Supply and fixing in repair, of LT Epoxy Bush of 04 Nos.( three phase and one neutral) Spout (as per smaple) with all necessary connection complete for transformer of capacity 500KVA including replacing of primary and secondary winding complete all as spedified and as directed by Engr-in-Charge.
Supply only bushing and stud complete with porcelain insulators for LT side (as per existing size/Model) for following capacity of transformer 500 KVA
Supply only bushing and stud complete with porcelain insulator for HT side (as per existng size/Model) for following capacity of transforme , 500 KVA (Make:Alstom/AEG):-
Supply and fixing in repair, transformer oil temperature gauge dial type range 0 to 100 deg C as per existing type and model all as directed. (Make : PRECIMEASURE/GURU)
Supply only Silica gel in existing breather assembly all as directed.
Supply and fixing, in repair, of Amp meter 0-30 A for HT side all as directed.
Supply and fix ACB 4 pole,of capacity 800 Amp MDO, and breaking capacity 50 KA in replacement of old one complete all as specified and directed.
Supply and fix ACB 4 pole,of capacity 630 Amp MDO, and breaking capacity 50 KA in replacement of old one complete all as specified and directed.
Filteration and dehydration of old transformer oil and removing of sludge by continuous circulation through transformer oil filtration plant with heater strips to achieve dielectric strength of not less than 50 KV at 2.5 mm gap of electrode as per IS-1866(1985) and improvement of acidity by minimizing percentage of acidity using chemical reagents all as spedified and as directed by the Engn-in-Charge.
Supply and top up transformer oil having di-electric strength not less than 60 KV at 2.5 mm gap after initial dehydration/filteration conforming to IS 335 and ISI marked to be brought at site in sealed container all as directed by the Engr-in-Charge. (Make:- Castrol / Veedol / IOC / HPL).
Maintenance and servicing, testing and commisssioning, of 6.6 KV VCB of 400 Amp by opening out HT cable termination joints, checking and cleaning all the spares of VCB to avoid any chances of flashing / burning due to loose connection, replacement of all bolts, nuts & washers (if found damaged due to flashing) with new one (anodised) of existing size, testing and calibration of earth fault and over load relays complete after re-connection of all dismantled cables and again testing after re-charging the VCB complete all as specified and as directed. Note: - Servicing to be carried out by authorised Servicing Agencies.
Servicing, commissioning and testing of HT panel including replacement of burnt out lugs, scraping the bus bar chamber with emery paper, cleaning the bus bar panel, remove the burnt out electrical wiring and replacement of bolt, nuts, washer and new wiring for metering eqpt, phase sequence RYB with bus bar insulation tapes, heating with blower, reconnecting, testing and commissioning. Note:- Cost of Nuts, bolts, washers, insulation tapes, wiring & other connecting items shall be included in unit rate.
Servicing, commissioning and testing of LT panel including replacement of burnt out lugs, scraping the bus bar chamber with emery paper, cleaning the bus bar panel, remove the burnt out electrical wiring and replacement of bolt, nuts, washer and new wiring for metering eqpt, phase sequence RYB with bus bar insulation tapes, heating with blower, reconnecting, testing and commissioning. Note:- Cost of Nuts, bolts, washers, insulation tapes, wiring & other connecting items shall be included in unit rate.
Materials & labour for painting to Pannel any size (inside/out side) with angle iron support from the ground level with two coat blue synthetic enamel paint (including preparation of old surface) in complete all as specified and as directed
Relaying of UG cable after fault rectification of size 25 to 70 sqmm complete all as specified and as directed. Note : (i) Cost of excavation, returning/ filling etc included in unit item rate. (ii) Cost of items like joint kit etc to repair fault to be paid as separate item.
Relaying of UG cable after fault rectification of size 95 to 120 sqmm complete all as specified and as directed. Note : (i) Cost of excavation, returning/ filling etc included in unit item rate. (ii) Cost of items like joint kit etc to repair fault to be paid as separate item.
Grass cutting for cleaning the surrounding area of E/M installation including cutting of shrubs and bushes and removing from the campus complete all as specified and directed.
Excavation in trenches not exceeding 1.5 m width or n exc 10 sqm on plan and n.exe 1.5 m in depth for taking out/laying of cable,foundation etc and getting out in soft/loose soil complete all as specified and as directed.
Returning and filling in including spreading, leveling, watering and well ramming in layers not exceeding 25 cm thick in soft / loose soil complete all as specified and as directed.
Removing surplus soil to a distance not exceeding 50 mtrs and depositing where directed including spreading, leveling at a level not exceeding 1.5 mtr from the starting point complete all as specified and as directed
Material and labour for sand cushioning with clean dry sand in trenches for cable protection complete all as specified and as directed. Note:- Punned depth only shall be measured and paid.
Laying only, connecting, testing and commissioning of XLPE insulated and PVC sheathed, armoured heavy duty UG cable after taking down old unserviceable cable with stranded alluminium conductors 150.0 sqmm x 3.5 core,1100 Volt grade, laid in trenches/wall/roof/pole/through pipe ,compleate all as specified and as directed. Note :- (i) Pipe and bricks for cable protection and sand cushioning and earth work shall be measured and paid separately. (ii) LT UG cable will be issued free for fixing only.
Laying only, connecting, testing and commissioning of XLPE insulated and PVC sheathed, armoured heavy duty UG cable after taking down old unserviceable cable with stranded alluminium conductors 120.0 sqmm x 3.5 core,1100 Volt grade, laid in trenches/wall/roof/pole/through pipe ,compleate all as specified and as directed. Note :- (i) Pipe and bricks for cable protection and sand cushioning and earth work shall be measured and paid separately. (ii) LT UG cable will be issued free for fixing only.
Laying only, connecting, testing and commissioning of XLPE insulated and PVC sheathed, armoured heavy duty UG cable after taking down old unserviceable cable with stranded alluminium conductors 95.0 sqmm x 3.5 core,1100 Volt grade, laid in trenches/wall/roof/pole/through pipe ,compleate all as specified and as directed. Note :- (i) Pipe and bricks for cable protection and sand cushioning and earth work shall be measured and paid separately. (ii) LT UG cable will be issued free for fixing only.
Laying only, connecting, testing and commissioning of XLPE insulated and PVC sheathed, armoured heavy duty UG cable after taking down old unserviceable cable with stranded alluminium conductors 70.0 sqmm x 3.5 core,1100 Volt grade, laid in trenches/wall/roof/pole/through pipe ,compleate all as specified and as directed. Note :- (i) Pipe and bricks for cable protection and sand cushioning and earth work shall be measured and paid separately. (ii) LT UG cable will be issued free for fixing only.
Laying only, connecting, testing and commissioning of XLPE insulated and PVC sheathed, armoured heavy duty UG cable after taking down old unserviceable cable with stranded alluminium conductors 50.0 sqmm x 3.5 core,1100 Volt grade, laid in trenches/wall/roof/pole/through pipe ,compleate all as specified and as directed. Note :- (i) Pipe and bricks for cable protection and sand cushioning and earth work shall be measured and paid separately. (ii) LT UG cable will be issued free for fixing only.
Laying only, connecting, testing and commissioning of XLPE insulated and PVC sheathed, armoured heavy duty UG cable after taking down old unserviceable cable with stranded alluminium conductors 35.0 sqmm x 3.5 core,1100 Volt grade, laid in trenches/wall/roof/pole/through pipe ,compleate all as specified and as directed. Note :- (i) Pipe and bricks for cable protection and sand cushioning and earth work shall be measured and paid separately. (ii) LT UG cable will be issued free for fixing only.
Laying only, connecting, testing and commissioning of XLPE insulated and PVC sheathed, armoured heavy duty UG cable after taking down old unserviceable cable with stranded alluminium conductors 25.0 sqmm x 3.5 core,1100 Volt grade, laid in trenches/wall/roof/pole/through pipe ,compleate all as specified and as directed. Note :- (i) Pipe and bricks for cable protection and sand cushioning and earth work shall be measured and paid separately. (ii) LT UG cable will be issued free for fixing only.
Laying only, connecting, testing and commissioning of XLPE insulated and PVC sheathed, armoured heavy duty UG cable after taking down old unserviceable cable with stranded alluminium conductors 16.0 sqmm x 4 core,1100 Volt grade, laid in trenches/wall/roof/pole/through pipe ,compleate all as specified and as directed. Note :- (i) Pipe and bricks for cable protection and sand cushioning and earth work shall be measured and paid separately. (ii) LT UG cable will be issued free for fixing only.
Laying only, connecting, testing and commissioning of XLPE insulated and PVC sheathed, armoured heavy duty UG cable after taking down old unserviceable cable with stranded alluminium conductors 10.0 sqmm x 2 core,1100 Volt grade, laid in trenches/wall/roof/pole/through pipe ,compleate all as specified and as directed. Note :- (i) Pipe and bricks for cable protection and sand cushioning and earth work shall be measured and paid separately. (ii) LT UG cable will be issued free for fixing only.
Supply and lay sub class 'B' bricks laid dry in trenches for cable protection laid with its longitudinal axis perpendicular to the cable axis complete all as specified and as directed
All as per item no 38 above but laying of old serviceable bricks only.
Supply and fix in repairs galvanised iron pipe in 80 mm bore, light grade for protection of UG cable, laid in trenches/wall/roof/pole/through pipe etc complete all as directed.
Supply and fix in repairs galvanised iron pipe in 50 mm bore, light grade for protection of UG cable, laid in trenches/wall/roof/pole/through pipe etc complete all as directed.
Cutting hard standing / road for laying of cable / protection pipe not exceeding 30cm wide and not exceeding 30cm deep and making good after laying pipe/cable etc with PCC(1:3:6), Type C2, (using 40mm graded stone agregate) matching with existing road complete all as specified and as directed
Materials & labour for earthing complete with galvanized earth plate electrode 600 x 600 x 6.0 mm thick, buried directly in ground (earth pit not less than 2.25 m deep below normal ground level ) with top edge of the plate not less than 1.5 m below normal ground level, connected to GI strip of size 32x6 mm by means of bolts, nuts, check nuts and washers of galvanized iron or steel, earth strip protected by and including 40mm dia GI pipe(light grade), alternate layers of charcoal and salt, including 20 mm bore GI tubing for watering to earth electrode, earth strip connected to test point/ distribution panel /feeder pillar etc as directed including necessary earth work, concrete pit with PCC (1:3:6), type C1, pre-cast RCC(1:1.5:3), type A1 cover slab duly reinforced with 8 mm dia TMT bar 150mm c/c both way and two numbers lifting handle made of TMT bar and set in cement mortar (1:4), funnel, wire mesh, all as shown in electrical plate No 5 of SSR part-1 and testing on completion including taking out old earthing complete.
Materials & labour for earthing complete with galvanized earth plate electrode 600 x 600 x 6.0 mm thick, buried directly in ground (earth pit not less than 2.25 m deep below normal ground level ) with top edge of the plate not less than 1.5 m below normal ground level, connected to galvanized earth lead wire 4.0 mm dia of by means of bolts, nuts, check nuts and washers of galvanized iron or steel, earth lead wire protected by and including 15mm dia GI pipe(light grade), alternate layers of charcoal and salt, including 20 mm bore GI tubing for watering to earth electrode, earth lead connected to test point/ distribution panel /feeder pillar etc as directed including necessary earth work, concrete pit with PCC (1:3:6), type C1, pre-cast RCC(1:1.5:3), type A1 cover slab duly reinforced with 8 mm dia TMT bar 150mm c/c both way and two numbers lifting handle made of TMT bar and set in cement mortar (1:4), funnel, wire mesh, all as shown in electrical plate No 5 of SSR part-1 and testing on completion including taking out old earthing complete all as specified and as directed.
All as per item no 43 here in above but using copper plate 60x60cmx3.15mm thick electrode and 20x3mm copper strip as earthing lead.
supply and fix straight through heat shrink cable joint kit for LT UG cable of size 95/120/150 sqmm 3.5 core including excavatin of earth at undergruond cable fault position and making good surface at the fault position complete all as specified and as directed (Make- Raychem/ Mseal/ Denson.)
supply and fix straight through heat shrink cable joint kit for LT UG cable of size 50/70 sqmm 3.5 core including excavatin of earth at undergruond cable fault position and making good surface at the fault position complete all as specified and as directed. (Make- Raychem/ Mseal/ Denson.)
supply and fix straight through heat shrink cable joint kit for LT UG cable of size 35/25 sqmm 3.5 core including excavatin of earth at undergruond cable fault position and making good surface at the fault position complete all as specified and as directed. (Make- Raychem/ Mseal/ Denson.)
Supplying, fix in replacement, chequer plate of 6mm thick for covering the duct of cable including cutting in required dimension duct complete all as specified and directed..
Servicing / Repairing of control panel of automatic power factor unit 30 to 110 KVAR capacities by replacement of unserviceable / defective / burnt out wiring with appropriate and existing size copper flexible cable including all fixing arrangement and connections complete all as specified and as directed. Note : (i) Cost of dressing of cables etc. including provision of necessary cable lugs as required are deemed to be inclusive in the rates. (ii) spares shall be measure and paid seperately as supply only The labour element involved for replaceing spares is deemed to include in the unit rate quoted.
Supply and fixing 3 pole power contactor 32 Amps type ML-2 including taking down old unserviceable power contractor all as specififed and directed. (Make-L&T/ Havells / C&S/ or as per existing as approved by the GE.).
Supply and fixing 3 pole power contactor 70 Amps type ML-4 including taking down old unserviceable power contractor all as specififed and directed. (Make-L&T/ Havells / C&S/ or as per existing as approved by the GE.).
Supply and fixing, in repair, Digital volt meter 0-500 V all as specififed and directed. (Make-L&T/ HPL/ C&S/AE or as per existing as approved by the GE.).
Supply and fixing Heavy duty long life power Capacitor (KVAR) of various capcity as per required at site, 440 volts AC all as specififed and directed. (Make : Havells/ L& T/ Schinneder/ Legrand)
Supply and fixing , in repair, auto power controller suitable for existing stage complete all as specified and as directed. (Make :NEPTUNE/L&T/SIEMENS / Schinneder).
Supply and fixing, in repair, Ameter (100x100mm) square type, flush mounting complete with suitable CTs three numbers complete all as specififed and directed. (Make-L&T/ HPL/ C&S/AE or as per existing as approved by the GE.).
Supplying, fixing, connection and testing MCCB, 4 pole, 63 Amp capacity, 16 KA rupturing capacity, AC 415 volts with fixed thermal and magnetic settings including taking down old unserviceable MCCB complete all as specified and directed.. (Make: Havells / L&T / Legrand/ C&S/ Hager)
All as per item No. 57 above but 100 Amp capacity.(Make: Havells / L&T / Legrand/ C&S/ Hager)
Supplying, fixing, connection and testing MCCB, 4 pole, 160 Amp capacity, 36 KA rupturing capacity, AC 415 volts with with Microprocessor release including taking down old unserviceable MCCB complete all as specified and directed. (Make: Havells / L&T / Legrand/ C&S/ Hager)
All as per item No.59 above but 250 Amp capacity. (Make: Havells / L&T / legrand/C&S/Hager)
All as per item No.59 above but 400 Amp capacity. (Make: Havells / L&T / Legrand/C&S/Hager)
Supply and fix in replacement of old unserviceable changeover switches of capacity 200 A and 4 pole complete all as directed and specified. Make:Cat No:IHCNFE0200 of Havell's or Indoasian cat No. ITAS0200 or Legrand/C&S / HPL / Standard / L&T).
Supply and fix in replacement of old unserviceable changeover switches of capacity 100 A and 4 pole complete all as directed and specified. Make:Cat No:IHCNFE0100 of Havell's or Indoasian cat No. ITAS0100 or Legrand / C&S / HPL / L&T / Standard).
Supply and fix in replacement of old unserviceable changeover switches of capacity 63 A and 4 pole complete all as directed and specified. Make:Cat No:IHCNFE063 of Havell's or Indoasian cat No. ITAS0063 or Legrand/C&S / HPL / L&T / Standard)).
M/L for MS clamps, made out of FI, of adequate size and thickness, bend to shape as requited, drilling, bolting, etc complete, for fixing as in gi pipe, cables and the like, including preparing new steel and iron surfaces and applying two coats of synthetic enamel paint over a coat of primer, etc complete.
INDIA ELECTRICAL EQUIPMENTS
ChakrabortyTraders
THE PLANTERS ENGINEERING CORPORATION
BHARUKA ENTERPRISES
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .