Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹26.1 LAccepted-AOC 6 9 GRAND SQUARE DANAPUR CANTT PATNA BIHAR 801503 | PATNA | PATNA | BIHAR | 801503 | L1 | Accepted-AOC Lowest | |
| 2 | L2₹27.1 L+₹65,164 (2.46%)Rejected-Finance ATAL JI KI GALI SHINDE KI CHHAWANI LASHKAR GWALIOR MADHYA PRADESH 474009 | GWALIOR | MADHYA PRADESH | 474009 | L2 | Rejected-Finance OTHER THAN LOWEST | |
| 3 | L3₹28.4 L+₹1.9 L (7.21%)Rejected-Finance | L3 | Rejected-Finance OTHER THAN LOWEST | |
| 4 | L4₹29.0 L+₹2.5 L (9.42%)Rejected-Finance | L4 | Rejected-Finance OTHER THAN LOWEST | |
| 5 | L5₹29.5 L+₹3.0 L (11.4%)Rejected-Finance SULTANPUR NEAR POLICE CHAUKI DANAPUR CANTT PATNA 801503 | PATNA | PATNA | BIHAR | 801503 | L5 | Rejected-Finance OTHER THAN LOWEST |
Tender Value
Refer Docs
EMD Value
₹54,000
Closing Date
6 Mar 2021, 6:00 pmClosed
GARRISON ENGINEER
GARRISON ENGINEER (MES) DANAPUR CANTT
PROVN OF LED LIGHT WITH POLE FROM TWEET GATE TO AKHURA CINEMA HALL AND SPL REPAIR REPLACEMENT CONVERSION OF LT OH LINE AERIAL CABLE AT FURNITURE YARD AND BUTCHERY AREA AND PROVN CERTAIN MINOR WORK IN AGE EM UNDER GE DANAPUR CANTT
2021_MES_415219_2
GE/DNR/T-61 OF 2020-21 / 8441/E8
Open Tender
Miscellaneous Works
Item Rate
180 days
DANAPUR CANTT
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
Yes
GARRISON ENGINEER
₹54,000
Yes
12 Mar 2021
18 Feb 2021
8 Mar 2021
18 Feb 2021
6 Mar 2021
22 Feb 2021
18 Feb 2021 - 20 Feb 2021
Amount
Excavating in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth for laying of cables & foundation of poles , stay assembly and getting out in any type of soil complete all as specified and directed.
Excavation in trenches not exc. 1.50 m wide and exc. 1.50 m in depth but not exc 3.0 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. not exc. 10 Sqm on plan and getting out in soft / loose soil complete all as specified and directed.
Returning, filling in excavated approved soil, including spreading, leveling, watering and well ramming in layers not exceeding 25 cm each layer ,complete all as specified and directed.
Removing excavated soil not exceeding 50 m and depositing where directed at a level not exceeding 1.5m above the starting point ,complete all as specified and directed.
M & L for dry sand cushioning to underground cables with 8cm thick before laying of cables and 15cm thick after laying and stretching of cable and gentally hand ramming and consolidation etc. complete all as specified and directed. Note :- Thickness of sand shall be measured 18 cm thick after punning.
M & L for old size sub class ‘B’ bricks, laid in trenches as cable covers / protection complete all as specified and directed.
M & L for plain cement concrete, 1:4:8 type D-2 (using 40 mm graded stone aggregate) as in foundation, filling and mass concrete complete all as specified and directed.
M & L for plain cement concrete, 1:3:6 type C-2 (using 40 mm graded stone aggregate) as in foundation, filling and mass concrete complete all as specified and directed.
M & L for cement concrete 1:2:4 type B-1 using 20mm graded stone aggregate in copings to poles & the like, etc including weathering, slightly rounded or chamfered angles and throating as directed including necessary form work complete all as specified and directed.
Supply and erecting steel tubular swaged poles complete with cast iron base plate, finial taper plug bolts, nuts and screw as specified, type 410 SP-31, 9.0 Metre long Swan Neck Type complete including painting all external exposed steel surfaces with two coats of aluminium paint over a coat of red oxide zine chrome primer and all internal surfaces & external surfaces in contract with concrete with two coats of black bituminous paint and painting of bottom portion of the pole upto 0.75m from top of the copping with two coat of synthetic enamel paint over a coat of red oxide primer complete all as specified and as directed. Note :- Excavation & Earth work and PCC foundation/base shall be measured and paid separately under relevant items of this Sxhedule 'A')
Supply and fixing LED light fitting for street/security lighting energy saving & environmental friendly long life versatile pressure die-cast housing with toughened glass and individual high power LED with secondary optics of capacity 60 Watt 240 volts AC 50 Hz , IP 66 protection suitable for 40 mm dia GI pipe bracket including three years on site warranty from manufacturer complete all as specified and directed. Make: Bajaj, Cat No: BRTFG 60W LED V3 / Crompton Greaves, Cat No: LSTP-60-CDL-M/ HPL , Cat No: HPLLEDSL6060WS.
Supply and fixing in reapir PVC Sheathed multi stranded unarmed copper conductor cable LT 1100 volt grade Conforming to IS 7098 FRLS (inner sheet) of size 1.5 Sqmm 3 Core (Nominal Area) from pole junction box to light fitting with suitable size copper cable lugs and connector all complete as specified and directed. Make : Plaza/Havells/Polycab.
Supply, laying & testing XLPE insulated, armoured, heavy duty electric cable with stranded aluminium conductor, 1100 volts grade, laid in trenches, sleeving through pipes or fixed on poles & walls or laid under floors including jointing with suitable size aluminium lugs complete of size 16 Sqmm nominal cross section x 4 core complete all as specifed and as directed. Makes of cable : Finolex/Polycab/ Havells/Grandlay.
Supply and fixing pole mounted junction box/bus bar chamber for loop connection of street light cable of size 295x195x100 mm with four nos alluminium bus bar of 63 amps capacity on hydrograpic insulator fixed on steel/ PCC pole with suitable two flat iron clamp 25x4mm with nuts and bolts (duly painted with two coats of aluminium paint over a coat of red oxide primer) and dismantling of old unserviceable one complete all as specified and as directed. Make: Sintex, Cat No: GSJB-3020 or equivalent make of Hansel/Rittel.
S&F MCB, Single pole, 6 amps, 240 volts, ‘C’ curve, 10 KA all complete as specified and as directed. Make : Legrand/ Hager/ABB/Siemens
Supply ,fabrication, installation and testing of LT out door type factory made CPRI Approved ,feeder piller box of size 700mmX500mmX400mm (over all dimension) made out of 3.00 mm thick CRCA sheet dully supported with mild steel angle iron of size 40X40X5mm vertical legs frame with front and back side openable ,single hinged door / shutter with locking arrengement and powder coated finish both internal and external steel surfaces after necessary preparation of steel surfaces including providing PCC (1:3:6) type C2 foundation of suitable size and connections of all outgoing / incomming existing cable of any size drawing / digging out cable from loops in trenches inclusive of necessary excavation and earthwork as required and relaying the cables including the following fitment accessories all complete as specified and as directed.
OUTGOING :- (a) MCB Single Pole 32 Amps,240 volts, 10 KA breaking capacity C curve - 04 Nos Make :- Legrand/L&T/Schneider. (b) Digital type time Switch 240 volts AC Single Phase, Make :- L&T, Cat No AUTS02DIG00 or equivalent model of Legrand//Schneider. (c) Power contractor 32 amps 3 Pole 415 Volts AC - 01 No Make: L&T, Model: MNX40 Cat No:- CS94190 or equivalent model of Schneider/Siemens. (d) Enamelled iron danger notice plate of 1.60 mm thick mild steel sheet of size 200 mm X 150mm , white with letters , figures and conventional skull and bones in signal red and fixed with nuts and bolts on door / shutter of JB for LT -01 No.
Supply and fixing of GI tubing, light grade, 40 mm bore with all fitting lais in trenches / pole / wall for protection of cables complete all as specified and as directed.
M & L for Earthing to OH/Sub stn with galvanised steel earth plate electrode 60cm x 60cm x 6mm thick, buried directly in ground (earth pit not less than 2.25m below normal ground level) with top edge of earth plate not less than 1.5m below normal ground level connected to main earth lead 32 x 6 mm galvanised iron strip dia by means of bolts, nut, check nuts and washers of galvanized iron or steel all as shown in electrical plate No.5 of MES Schedule pt-I 1991, GI earth strip 32 x 6 mm protected by GI pipe 40 mm dia light grade and connected to earth test point including excavation in any type of soil,returning filling, disposal of soil, providing charcoal dust and common salt upto top edge of earth plate, construction of PCC pit with RCC cover, funnel, watering pipe of 20mm dia GI light grade and provision of earth test point including testing on completion complete all as specified and directed.
Dismentling and taking out broken serviceable ACSR conductor from existing poles / dismantled poles / pole structures of any size from LT over head line as directed and keep in safe custody for re-use if found serviseable complete all as specified and directed.
Dismantling and taking out servicable insulators of any size and any type from existing poles / dismantled poles / pole structures complete all as specified and directed.
Dismentling of old unserviceable earth wire or distributor span, cardle ground etc. complete all as specified and directed.
Dismantling and taking out servicable cross arms, bracings, supports, clamps and back plates from existing poles / dismantled poles / pole structures complete all as specified and directed.
Supply, fixing and testing of LT Aerial bunch cable on existing steel/PCC poles with XLPE insulated LT Aerial Bunch cable heavy duty 1100 volts grade with aluminium conductor of cross section area 150 sqmm X 3 core + 16 sqmm X 1 core with insulated messenger cum neutral conductor of size 95 sqmm X 1 core including all fixing accessories such as suspension clamp, piercing connector, dead end etc complete all as specifed and as directed. Makes of cable : Finolex/Polycab/ Havells/Grandlay.
Supply, fixing and testing of LT Aerial bunch cable on existing steel/PCC poles with XLPE insulated LT Aerial Bunch cable heavy duty 1100 volts grade with aluminium conductor of cross section area 95 sqmm X 3 core + 16 sqmm X 1 core with insulated messenger cum neutral conductor of size 70 sqmm X 1 core including all fixing accessories such as suspension clamp, piercing connector, dead end etc complete all as specifed and as directed. Makes of cable : Finolex/Polycab/ Havells/Grandlay.
Supply and erecting steel tubular pole, swaged, complete with cast iron base plate, finial taper plug, bolts, nuts, washer and screws including painting with two coats of aluminium paint over one coat of red oxide primer on all exposed surfaces and tarring with black bituminous paints to portion embedded in PCC including numbering of poles with two coats of synthetic enamel paints, type 410-SP-31 (9 meter long) complete, Including disconnecting and taking out old damage PCC pole all as directed. Note Excavation & Earth work and PCC foundation/base shall be measured and paid separately under relevant items of this BoQ.
M & L for Cross arms, bracing, supports, clamps and back plate, fabricated from structural steel section including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as directed including two coats of aluminium paint over a coat of red oxide primer for fixing flood light complete all as directed.
Supply and fixing pole mounted junction box/bus bar chamber for connection of single phase service connection of size 400x300x190 mm with 63 amps alluminium 4 nos busbar wrapped with PVC sleeves and maintained the colour code and provision of making holes with GI nuts, bolts & washers for connections and mounted on hydrograpic insulators with nuts & bolts at both ends of busbar complete all as specified and as directed. Make: Sintex , Cat No: GSJB4030 or equivalent model of Hensel/Rittel.
Supply and fixing pole mounted junction box/bus bar chamber for loop connection of street light cable of size 240x130x95 mm with 2 nos 32 amps aluminium busbar wrapped with PVC sleeves and maintained the colour code and provision of making holes with GI nuts, bolts & washers for connections and mounted on hydrograpic insulators with nuts & bolts at both ends of busbar and suitable arrangement for fixing one no MCB complete all as specified and as directed. Make: Sintex , Cat No: GSJB2817 or equivalent model of Hensel/Rittel.
Supply, installation, commissioning and testing high wall split units indoor and outdoor complete unit with cordless remote control unit and with inbuilt air ioniser and plasma filter for better indoor air quality with PM 2.5 filter, BEE 5 Star rating and EER 3.2 of capacity 1.5 TR (Ton of refrigeration) including metal wall hunger of suitable size for fixing outdoor unit at wall complete all as specified and directed. Make:- Carrier or equivalent model of Voltas/Blue Star/LG.
Supply and installation of Voltage stablizer for automatic operation, single phase naturally air cooled indoor type and dsigned for input variation between 170 Volts to 250 Volts with output Voltage Stablizer at 230 with of +- 2.5% and capacity of 4 KVA complete all as specified and as directed. Make: V-Gaurd /Blue Star/ Voltas.
M&L for sub main wiring with two runs of single core multistranded copper conductor cable of size 6 sqmm drawn through in and incl rigid PVC conduit and conduit accessories dia not less than 20 mm dia with 4 sqmm PVC insulated unsheathed single core copper conductor 1100 volts grade as earth continuity conductor complete all as specified & as directed. Note:- Out of two runs of cable, one runs of earth wire & one runs of PVC conductor shall be measured as one unit.
S&F single pole and neutral sheet metal enclosure with 2/3 pin and each plug and socket complete with one MCB SP 32 Amps 240 Volt 'C' Seriescomplete all as specified & as directed .
RAJ AND SONS
HARINANDAN RAI SONS
MS CHAKRAVARTY PRITHIVI RAJ
jaglalchoudharyandsons
Vijay Bakshi and Son
M/S SHOBHA CONSTRUCTIONS
M/S SAROJ KUMAR SINGH
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .