Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹15.0 LAccepted-AOC | L1 | Accepted-AOC Lowest | |
| 2 | L2₹18.5 L+₹3.5 L (23.2%)Rejected-AOC | L2 | Rejected-AOC Other than lowest | |
| 3 | L3₹19.9 L+₹4.9 L (32.7%)Rejected-AOC 901 GH 83 SECTOR 20 PANCHKULA 134116 | PANCHKULA | HARYANA | 134116 | L3 | Rejected-AOC Other than lowest | |
| 4 | L4₹26.9 L+₹11.9 L (79.4%)Rejected-AOC HOUSE NO 599 D SURYA NAGAR PHASE II SECTOR 91 FARIDABAD 121013 HARYANA | FARIDABAD | FARIDABAD | HARYANA | 121013 | L4 | Rejected-AOC Other than lowest |
Tender Value
Refer Docs
EMD Value
₹29,320
Closing Date
13 Feb 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE (U) Chandimandir
GE (U) Chandimandir Chandimandir Cantt Panchkula (HR)
GE(U)/CHM-39/20202-1- PROVN OF METERING SYSTEM FOR FEEDER NO HB-23 UNER GE (U) CHANDIMANDIR
2021_MES_412891_1
GE(U)/CHM-39/2020-21
Open Tender
Machineries/ Mechanical Engg Items
Item Rate
180 days
Chandimandir Cantt
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE (U) Chandimandir
₹29,320
Yes
6 Jan 2022
15 Jan 2021
15 Feb 2021
15 Jan 2021
13 Feb 2021
30 Jan 2021
60 days
Amount
Supply, installation , testing and commissioning of 66 KV outdoor type hermatically sealed CT oil cooled, single phase, wound primary type, 5 core, live tank type, with pocelain insulators having creepage distance of 1815 mm (min) Ratio 100/0.577-1-1-1-1 Amp, insulation level - 140/325 KV, 50 Hz, with and including hot dip galvanizing of all ferrous parts, complete all as directed by Engineer-in-Charge and as specified in Appx 'B'.
Supply, installation , testing and commissioning of 66 KV, hermatically sealed, outdoor type PT oil cooled, single phase, single pole insulated, Ratio 66000/rt3/110/rt3-110/rt3V, winding -1 10 VA, winding - 2 10VA, accuracy class - 0.2, V.F. - 1.2 cont & 1.5 for 30 sec, insulation level - 72.5/ 140/ 325 KV, 50 Hz with and including hot dip galvanizing of all ferrous parts, complete all as directed by Engineer-in-Charge and as specified in Appx 'B'.
Supply, installation, testing and commissioning of ABT meter (Set of two meters i.e. main & check meter) complete all as per specifications and as per approval of HVPNL/UHBVN all as directed by Engineer-in-Charge. Note - All connections, materials/cables/wires etc required for connections, meter cabin and any other minor work required for completion of item shall deemed to be included in the quoted rate of the item.
M & L cross arms, supports, clamps etc fabricated from GI channels/angles/flats/plates etc including nuts, bolts, washers, welding, bending ( cold or hot ) drilling holes for bolts bent to any shape or size as indicated or directed complete all as specified.
M & L PCC (1:1.5:3), type A-1, with using 20 mm graded stone aggregate for grouting of structure errected for mounting of CTs/PTs including form work as required at site, complete all as specified and as directed by Engineer-in-Charge.
M & L PCC (1:5:10), type E-2, with using 40 mm graded stone aggregate for lean concrete including earh work & form work all as required at site complete all as specified and as directed.
Excavation for foundation not exe 3.0 mtr in width and not exe 1.5 mtr in depth, getting out in hard/dense soil, returning/refilling and removal of surplus soil complete all as directed.
M & L TMT bars of size 10 mm dia and 8 mm dia for stirrups incl cutting/bending etc and winding wires complete .
M & L foundation bolts & nuts incl washers, 20 mm dia and 675 mm long with standard J or L hook at bottom complete with washers, nuts etc, complete all as specified and directed by Engineer-in-Charge.
Disconnecting the power supply, disconnecting all the connections from incoming/ outgoing side and control cables from the existing CTs & PTs including dismantling and taking down the existing CTs & PTs – 03 Nos each from the system at HVPN yard and depositing in the store yard, complete all as directed by Engineer-in-Charge.
M & L all misclaneous items such as ACSR, terminal connectors, junction boxes, PG clamps, base clamps, GI nuts bolts washers, jumpers & down conductors from main 66 KV bus up to CTs/PTs, control cables from CTs/PTs up to ABT meter or other system installed at 66 KV grid station, complete all as specified and directed by Engineer-in-Charge. Note :- Distance between CTs/PTs installed at 66 KV yard and ABT meter/other system installed inside sub station building shall be approx 100 mtrs.Control cables for CTs shall be 4 core 4 sqmm and PTs shall be 2 core 4 sqmm ( all copper conductor cables) and shall be as per specifications & approval of HVPN/UHBVN authorities only.
M & L testing of the complete system installed as above, all as per the norms of HVPNL/UHBVN through a NABL certified testing lab and submission of test reports dully signed and certified by HVPNL/UHBVN/MES authorities complete all as directed. Note - Testing shall be carried at HVPNL Grid Sector 1 Panchkula. Required equpements / mobile lab etc required for testing the system shall be brought at site only.
BANSAL ENGINEERING
HARISH SALES CORPORATION
unique power & control system
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .