Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹14.2 LAccepted-AOC 1A BASEMENT 30 31 RAJA HOUSE NEHERU PLACE NEW DELHI | NEW DELHI | NEW DELHI | DELHI | L1 | Accepted-AOC Reasonable rate | |
| 2 | L2₹16.0 L+₹1.7 L (12.2%)Rejected-Finance 7TH MILE UPPER SHILLONG P O NONGLYER SHILLONG MEGHALAYA | EAST KHASI HILLS | MEGHALAYA | 793009 | L2 | Rejected-Finance Quoted amount higher than L1 | |
| 3 | L3₹16.1 L+₹1.9 L (13.1%)Rejected-Finance | L3 | Rejected-Finance Quoted amount higher than L1 | |
| 4 | L4₹17.0 L+₹2.7 L (19.0%)Rejected-Finance H M APARTMENT 4C S J ROAD ATHGAON GUWAHATI 781001 | GUWAHATI | KAMRUP METRO | ASSAM | 781001 | L4 | Rejected-Finance Quoted amount higher than L1 | |
| 5 | L5₹17.5 L+₹3.2 L (22.7%)Rejected-Finance 7TH MILE UPPER SHILLONG P O NONGLYER SHILLONG MEGHALAYA | EAST KHASI HILLS | MEGHALAYA | 793009 | L5 | Rejected-Finance Quoted amount higher than L1 |
Tender Value
₹14.9 L
EMD Value
₹29,720
Closing Date
6 Nov 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CDR
HQ 137 Wks Engrs PIN 914137 Co 99 APO
SPECIAL REPAIR FOR REPLACEMENT OF BER DG SET AT 160 MH POWER HOUSE AT MASIMPUR MIL STN
2021_MES_438043_4
8570/E8
Open Tender
Miscellaneous Works
Item Rate
180 days
Masimpur
Class E
Category b i
2 documents required · 2 mandatory
₹500
GE Silchar
₹29,720
4 Jan 2022
16 Oct 2021
8 Nov 2021
16 Oct 2021
6 Nov 2021
23 Oct 2021
60 days
Amount
Supply, Installing, testing and commissioning (a) Sound proof accoustic enclosure diesel engine driven generating set, fully wired 415 volts, +/- 1.5%, 3 phase 4 wire 50 HZ, +/- 0.5% 0.80 PF of capacity 125 KVA, 100 KW continous rating at 1500 RPM , brushless self excited and minimum of capacity engine turbo charged water cooled complete under NTP condition with provision for 10% overload for 1hr on continious 12hr (Total 13 hour) running and common base plate frame engine standard instrumental panel, self exciting and self regulating control panel with accessories , self starter 12 volts with battery 180 AH , 12 volts -01 Nos system with battery charging unit SCR type and battery cable leads , exhaust pipe with cladding by asbestos rope, sound proof canopy as per CPCB norms etc. Diesel engine set as per IS 10001 and alternator as per IS -13364 with inbuilt electronic speed governer with relay with inhouse canopy mounted fuel tank not less than 12 hours running capacity including necessary anti vibration pads including standard control panel as recommended by the manufacturer . (i) Fly wheel to suit coupling (ii) Flexible coupling with guard, bolts and nuts,etc.for exhaust system (iii) Dry type air cleaner filters (iv) Radiator with guard and radiator fan (v) Fuel pump complete with fuel injection systems
(vi) Electronic speed governor (vii) Fuel filter (viii) Lub oil filter (ix) Self starter 12 Volts DC (x) Exhaust silencer industrial type with pipe 3 m long (xi) Instrumental panel with the following:- (aa) Self starting key / switch on relay control panel (ab) Lubricating oil pressure guage (ac) Battery charging ammeter (ad) Hour meter and RPM indicator (ae) Lub oil temp guage (af) Water temp guage (xii) Turbo charger (xiii) Lub oil pump (xiv) Lub oil cooler assembly (xv) Dynamo 12 V for charging of battery (xvi) Control including charging system panel with MCCB 125 Amps 4 Pole 35 KA -01 No. (xvii) Provison of light inside the canopy. (xviii) Emergency stop push button outside the container. (xix) Low oil pressure protection cutoff. (xx) High temperature protection cutoff. (xxi) Overload protection cutoff.
(xxii) Digital display of Disel Engine and Alternators. (xxiii) Auto / Manual mode button. (xxiv) Starting batteries 12 V, 180 AH maintenance free with suitable size of cable including fitting and terminals on angle iron frame(self starter sytem with 12 voltDC) - 02 Nos Make Exide Express / TATA / AMARON. (xvii) Sheet steel components pre-treated with zinc phosphate prior to polyster powder coating (xxv) Zinc plated or stainless steel fasteners (xxvi) EPDM quality gasket (xxvii) Radiator filling access facility from out side (xxviii) Engine and alternator shall be mounted through AVM Pads on common channel iron base frame. (xxix) Noise level of less than 75 db (A) at 1 mtr distance controlled by providing specially designed alternator to controlled the sound at air entry and exit of the enclosure. (Note: (i) Cost of PCC foundation as per manufacturer's instruction shall be deemed to be included in the quoted rate. The foundation drawing of OEM shall be get aproved before execution. (ii) Fuel requirred for (12+1)Hour testing deemend to be included in quoted rate. (iii) Artificeal load, tools and plants etc requirred during performance testing need to be arranged by the contractor without any extra cost to the Government. )
(b) Alternator:- It shall be self exited self generated balanced 415 volts, 3 phase, 50 Cycles per second, 125 KVA at 0.8 PF or nearest in higher capacity, 1500 RPM, star connected, 4 wire, drip proof enclosure, air cool with radial fan mounted on rotor, screen peotected, self ventilated enclosure as per IS 4722/IS 2613 with drip proof enclosure with damper winding on pole faces, static automatic voltage regulator to provide voltage regulation 1% and harmonic factor bettr than 2% from no load to full load from 0.8 to unity power factor and insulation of H class and above as per standard practice
Material and labour for shifting of existing BER DG set of capacity 110 KVA installed at 160 MH power house to MES MT Yard with the help of hydraulic crane of suitable capacity including dismantling of cables from electric panel complete all as directed.
Demolition of cement concrete (unreinforced) in ground floors and paving n.exc.15cm thick (below or above ground level) and removal of rubbish from the site complete all as specified and as directed.
Taking down wooden chowkats or frames with shutters exc. 1.50 Sqm but n.exc. 4 Sqm each (without taking of shutters from the frames) complete all as specified and as directed.
Dismantling floor, hearth or wall tiling including cement mortar bedding (but not backing) removing serviceable tiles to store and rubbish off the premises complete all as specified and as directed.
Demolition of brick work or stone/boulder masonry, built in cement mortar including all quions, arches, pillers etc complete all as specified and as directed.
Material and labour for brick work with sub class `B` bricks, old size, straight or curved on plan exc 6m mean radius built in cement mortar (1:6) complete all as specified and as directed.
Material and labour for 20-25 mm thick machine cut kota stone slab shall be laid on floor, laid and jointed with grey cement slurry mixed with pigment to match the colour / shade of the slab over and including 20mm thick screed bed / bedding layer in cement mortar (1:6) with roughening of surface, including rubbing and polishing complete all as specified and as directed.
Material and labour for 20-25 mm thick machine cut kota stone slab shall be laid on wall / column / vertical surfaces, laid and jointed with grey cement slurry mixed with pigment to match the colour / shade of the slab over and including 10mm thick plastering / backing coat in cement mortar (1:4) with roughening of surface, including rubbing and polishing complete all as specified and as directed.
Material and labour for non skid ceramic coloured tiles 7 to 8mm thick (Square/rectangular) area of each tile exc 0.11 sqm but n.exc 0.18 sqm shall be laid on wall / column / vertical surfaces as in dado / skirting set and jointed in neat cement slurry and pointed in white cement with pigment to match the colour / shade / matrix of tiles over and including 10mm thick cement plastering / backing coat in CM (1:4) complete all as specified and as directed.
Material and labour for 200 mm thick PCC 1:2:4 type B2 (Using 40 mm graded stone aggregate) as in PCC base for DG set, finishing the surface fair and even complete all as specified and as directed.
Supply and fixing in repair steel rolling shutters of lath thickness 1.25 mm, gear operated type with bevel gear box and crank handle, including top cover, anchoring rod, hasp & staple including cutting and removing the existing corroded laths of rolling shutters and inserting new laths of 1.25 mm thick including necessary bending, revetting etc with one shop coat of red oxide zinc chrome primer and applying two coats of synthetic enamel paint after fixing complete all as specified and directed.
Material and labour for precast cement concrete chequered tiles of size 200 x 200 x 25 mm thick shall be laid on floor etc set, jointed and pointed in neat cement slurry laid over and including 15mm thick screed bed / bedding layer in CM (1:6) complete all as specified and as directed.
Supply and fixing on load change over switch AC 21 (Side handle), 400 Amps, 415 VAC and 50 Hz complete all as specified and directed. (Make: ABB/ L&T / SIEMENS / SCHNEIDER)
mahinder electricals
M/s Ravi Enterprise
M/S. SUBHAS CONSTRUCTION CO.
kapoor and co
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .