Fire Fighting System for Comprehensive Store at Burdwan Medical College and Hospital, Purba Bardhaman ------ Fire Detection System
2019_WBPWD_240093_1
WBPWD/EEBED/NIQ-16/2019-20_3rd
Open Tender
ELECTRICAL WORKS ORG
Item Rate
30 days
Purba Bardhaman
Please refer Tender documents.
5 documents required · 5 mandatory
₹10,000
16 Sept 2020
26 Aug 2019
5 Sept 2019
26 Aug 2019
3 Sept 2019
26 Aug 2019
Amount
Supply, Installation,Testing & Commisioning of Microprocessor based Intelligent, aressable 2 Loops fire alarm control panel having expandable features ( VDS / UL approved ) fully networkable with each loop capable of taking minimum 120 devices, 1/4 VGA display character alpha-numeric liquid crystal display.The panel shall be soft addressable type.The panel shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches when ever any alarm is triggered.The Panel should be able to store sufficient numbers of log events in its Memory as per recommended standards. The panel shall have in built rectifier, provision for external & internal printer ( if required ), Loop cards, L C D unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, in built Surge protection facility, integral SMF lead acid batteries with sealed cells of 24 V capable of running for 24 hours normal working and then be capable of operating the system for 30 minutes during Emargency condition, with integral battery charger complete as required. The panel shall have extra loop card to serve as stand by in case of burntout or malfunctioning of any operating loop cards. The FACP shall be capable of being networked ( future expansion ) with other similar FACP located at different part of the premises through single RS 485 bus.The FACP shall have provision for interfacing with the public address system and BMS( RS 485 )The system must be preloaded with licenced software.(Approved Make: Simens/Secutron/ Notifer / Edward / Bosch/ Honeywell).
Supply, Installation,Testing & Commisioning of Analog Addressable Intelligent multisensor detector ( VDS / UL / approved ) with inbuilt optical smoke sensors as well as additional heat detector sensor with decentralise intelligence, soft addressable Photothermal type with inbuilt fault isolator as per NFPA style 7 wiring complete with base having IP as per recommended standard.(Note : Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices ( Numbers of addressable devices in a group will be as per latest recommended standards ) without any additional cost).(Approved Make: Simens/Secutron/ Notifer / Edward / Bosch/ Honeywell)
Supply, Installation,Testing & Commisioning of Addressable Manual Call Point ( VDS / UL / FM / ULC approved )soft addressable type with in built fault isolator as per NFPA style 7 wiring complete as required. (Approved Make: Simens/Secutron/ Notifer / Edward / Bosch/ Honeywell)
Supply, Installation, Testing & Commissioning of Addressable Loop Powered Hooter ( sound output of minimum 90 db ) cum strobe (strength of light 10 cd)complete with inbuilt isolator & IP65 base and ( VDS / UL / FM / ULC approved) approved. (Approved Make: Simens/Secutron/ Notifer / Edward / Bosch/ Honeywell).
Supply, Installation, Testing & Commissioning of Power supply 230 V AC to 12 V DC with all other accessories. (Make: Reputed)
Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable (For Loop) (Make. Polycab/Gloster/Finolex) with 20 mm NB PVC rigid conduit pipe(Make: Precisson-Medium) on the surface of the wall.
NOTE : 1. The Fire Alarm system shall comply with latest requirements of -- 1. National Fire Protection Association (NFPA) Standards. 2. IS 2189 3. NFPA 70 National Electric Code 4. NFPA 72 National Fire Alarm Code 5. local Statutory Regulations 6. Manufacturer Recommendation. TESTS:1.The system shall be tested and commissioned by a qualified competent,trained engineer or technician authorized by the manufacturer of the fire alarm equipment to technically supervise and participate during all of the adjustments and tests for the system. 2. Before energizing the cables and wires, check for correct connections and test for short circuits, ground faults, continuity, and insulation and other tests as per above standards must be done.
Rates to be quoted will be inclusive of all the taxes incl. GST. No other additional charges will be applicable in addition to the quoted rates.
GLYPTIC
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .