REPAIRS / REPLACEMENT OF LT PANELS, FEEDER PILLAR AND CONNECTED WORKS IN DSTV UNDER GE HISAR AT HISAR MIL STN
2025_MES_716214_1
GE(H)-15/2025-26
Open Tender
Electrical and Maintenance Works
Item Rate
240 days
Hisar
A Per NIT
6 documents required · 6 mandatory
₹500
GE Hisar
₹90,000
Yes
27 Apr 2026
23 Jun 2025
31 Jul 2025
23 Jun 2025
23 Jul 2025
8 Jul 2025
Amount
Taking out the old unserviceable LT underground cable 16 Sqmm ,4 core 1100 volts grade, XLPE insulated and PVC sheathed, armoured heavy duty with multistrand aluminium conductors from trenches/wall/floor/road/ culverts or pole etc complete all as specified and directed. Note : Excavation and earth work, duct work, GI pipe for laying of cable and sand cushing/cable protection covers etc are beyond the scope of this item and shall be measured & paid for separately
Taking out the old unserviceable LT underground cable 25 Sqmm ,4 core 1100 volts grade, XLPE insulated and PVC sheathed, armoured heavy duty with multistrand aluminium conductors from trenches/wall/floor/road/ culverts or pole etc complete all as specified and directed. Note : Excavation and earth work, duct work, GI pipe for laying of cable and sand cushing/cable protection covers etc are beyond the scope of this item and shall be measured & paid for separately
Taking out the old unserviceable LT underground cable 35 Sqmm ,3.5 core 1100 volts grade, XLPE insulated and PVC sheathed, armoured heavy duty with multistrand aluminium conductors from trenches/wall/floor/road/ culverts or pole etc complete all as specified and directed. Note : Excavation and earth work, duct work, GI pipe for laying of cable and sand cushing/cable protection covers etc are beyond the scope of this item and shall be measured & paid for separately
Taking out the old unserviceable LT underground cable 95 Sqmm ,3.5 core 1100 volts grade, XLPE insulated and PVC sheathed, armoured heavy duty with multistrand aluminium conductors from trenches/wall/floor/road/ culverts or pole etc complete all as specified and directed. Note : Excavation and earth work, duct work, GI pipe for laying of cable and sand cushing/cable protection covers etc are beyond the scope of this item and shall be measured & paid for separately
Taking out the old unserviceable LT underground cable 120 Sqmm ,3.5 core 1100 volts grade, XLPE insulated and PVC sheathed, armoured heavy duty with multistrand aluminium conductors from trenches/wall/floor/road/ culverts or pole etc complete all as specified and directed. Note : Excavation and earth work, duct work, GI pipe for laying of cable and sand cushing/cable protection covers etc are beyond the scope of this item and shall be measured & paid for separately
Taking out the old unserviceable LT underground cable 185 Sqmm ,3.5 core 1100 volts grade, XLPE insulated and PVC sheathed, armoured heavy duty with multistrand aluminium conductors from trenches/wall/floor/road/ culverts or pole etc complete all as specified and directed. Note : Excavation and earth work, duct work, GI pipe for laying of cable and sand cushing/cable protection covers etc are beyond the scope of this item and shall be measured & paid for separately
Taking out the old unserviceable LT underground cable 240 Sqmm ,3.5 core 1100 volts grade, XLPE insulated and PVC sheathed, armoured heavy duty with multistrand aluminium conductors from trenches/wall/floor/road/ culverts or pole etc complete all as specified and directed. Note : Excavation and earth work, duct work, GI pipe for laying of cable and sand cushing/cable protection covers etc are beyond the scope of this item and shall be measured & paid for separately
Taking out the old unserviceable LT underground cable 400 Sqmm ,3.5 core 1100 volts grade, XLPE insulated and PVC sheathed, armoured heavy duty with multistrand aluminium conductors from trenches/wall/floor/road/ culverts or pole etc complete all as specified and directed. Note : Excavation and earth work, duct work, GI pipe for laying of cable and sand cushing/cable protection covers etc are beyond the scope of this item and shall be measured & paid for separately
Supply , laying , jointing, testing and commissioning of size 16 sqmm 4 core LT underground cable , 1100 volts grade, XLPE insulated and PVC sheathed, armoured heavy duty with multistrand aluminium conductors IS-7098, laid in trenches /fixed on wall /floor /road /culverts /pole or encased in GI pipe complete all as specified. Note : (i) Excavation and earth work, duct work, GI pipe for laying of cable and sand cushing/cable protection covers etc are beyond the scope of this item and shall be measured & paid for separately (ii) Sand cushioning, cable protection, GI protection pipe, clamps, jointing kits and excavation & earth work shall be measured & paid for separately.
Supply , laying , jointing, testing and commissioning of size 25 Sqmm 4 core LT underground cable , 1100 volts grade, XLPE insulated and PVC sheathed, armoured heavy duty with multistrand aluminium conductors IS-7098, laid in trenches /fixed on wall /floor /road /culverts /pole or encased in GI pipe complete all as specified. Note : (i) Excavation and earth work, duct work, GI pipe for laying of cable and sand cushing/cable protection covers etc are beyond the scope of this item and shall be measured & paid for separately (ii) Sand cushioning, cable protection, GI protection pipe, clamps, jointing kits and excavation & earth work shall be measured & paid for separately.
Supply , laying , jointing, testing and commissioning of size 35 Sqmm 3.5 core LT underground cable , 1100 volts grade, XLPE insulated and PVC sheathed, armoured heavy duty with multistrand aluminium conductors IS-7098, laid in trenches /fixed on wall /floor /road /culverts /pole or encased in GI pipe complete all as specified. Note : (i) Excavation and earth work, duct work, GI pipe for laying of cable and sand cushing/cable protection covers etc are beyond the scope of this item and shall be measured & paid for separately (ii) Sand cushioning, cable protection, GI protection pipe, clamps, jointing kits and excavation & earth work shall be measured & paid for separately.
Supply , laying , jointing, testing and commissioning of size 95 Sqmm 3.5 core LT underground cable , 1100 volts grade, XLPE insulated and PVC sheathed, armoured heavy duty with multistrand aluminium conductors IS-7098, laid in trenches /fixed on wall /floor /road /culverts /pole or encased in GI pipe complete all as specified. Note : (i) Excavation and earth work, duct work, GI pipe for laying of cable and sand cushing/cable protection covers etc are beyond the scope of this item and shall be measured & paid for separately (ii) Sand cushioning, cable protection, GI protection pipe, clamps, jointing kits and excavation & earth work shall be measured & paid for separately.
Supply , laying , jointing, testing and commissioning of size 120 Sqmm 3.5 core LT underground cable , 1100 volts grade, XLPE insulated and PVC sheathed, armoured heavy duty with multistrand aluminium conductors IS-7098, laid in trenches /fixed on wall /floor /road /culverts /pole or encased in GI pipe complete all as specified. Note : (i) Excavation and earth work, duct work, GI pipe for laying of cable and sand cushing/cable protection covers etc are beyond the scope of this item and shall be measured & paid for separately (ii) Sand cushioning, cable protection, GI protection pipe, clamps, jointing kits and excavation & earth work shall be measured & paid for separately.
Supply , laying , jointing, testing and commissioning of size 185 Sqmm 3.5 core LT underground cable , 1100 volts grade, XLPE insulated and PVC sheathed, armoured heavy duty with multistrand aluminium conductors IS-7098, laid in trenches /fixed on wall /floor /road /culverts /pole or encased in GI pipe complete all as specified. Note : (i) Excavation and earth work, duct work, GI pipe for laying of cable and sand cushing/cable protection covers etc are beyond the scope of this item and shall be measured & paid for separately (ii) Sand cushioning, cable protection, GI protection pipe, clamps, jointing kits and excavation & earth work shall be measured & paid for separately.
Supply , laying , jointing, testing and commissioning of size 240 Sqmm 3.5 core LT underground cable , 1100 volts grade, XLPE insulated and PVC sheathed, armoured heavy duty with multistrand aluminium conductors IS-7098, laid in trenches /fixed on wall /floor /road /culverts /pole or encased in GI pipe complete all as specified. Note : (i) Excavation and earth work, duct work, GI pipe for laying of cable and sand cushing/cable protection covers etc are beyond the scope of this item and shall be measured & paid for separately (ii) Sand cushioning, cable protection, GI protection pipe, clamps, jointing kits and excavation & earth work shall be measured & paid for separately.
Supply , laying , jointing, testing and commissioning of size 400 Sqmm 3.5 core LT underground cable , 1100 volts grade, XLPE insulated and PVC sheathed, armoured heavy duty with multistrand aluminium conductors IS-7098, laid in trenches /fixed on wall /floor /road /culverts /pole or encased in GI pipe complete all as specified. Note : (i) Excavation and earth work, duct work, GI pipe for laying of cable and sand cushing/cable protection covers etc are beyond the scope of this item and shall be measured & paid for separately (ii) Sand cushioning, cable protection, GI protection pipe, clamps, jointing kits and excavation & earth work shall be measured & paid for separately.
Excavation in trenches not exceeding 1.5 m wide and not exc. 1.5 m depth for laying cables, foundation for pole etc and getting out in soft/loose soil etc complete all as specified and as directed. Note : 1. The rate inclusive of taking down and refixing of any type of cheqered tiles, interlocking tiles complete as per existing for good make. 2. The PCC work shall be measured & paid for separately uner respective item of Sch 'A' / BOQ
M&L for Sand cushioning 230mm thickness with dry sand (one layer of 80mm thickness before laying of cable and other layer of 150mm thickness after laying of cable) and punned down to 180mm after laying of cable in trenches for protection of cable complete all as directed. Note :- For the purpose of payment only punned thickness shall be measured.
Taking up bricks laid as cable covers and stacking serviceable brick for reuse at site etc complete all as specified and directed.
Laying only old bricks retrieved from item Srl Item No. 24.00 as cable covers in trenches etc complete all as specified and directed.
M&L for brick covering to underground electric cable using sub class ‘B’ bricks, laid dry, flat, perpendicular to the direction of cable etc complete all as specified and directed. .
Returning filling in incl spreading leveling watering and well ramming in layers n. exc 25cm thick etc complete all as specified and as directed.
Removing excavated material to distance n. exc 50m and depositing where directed at a level n. exc 1.5m above the starting point etc complete all as specified and as directed. .
Boring of hole under road/pavement/hard standing or any other situation by mannual means and suitable for passing of GI pipe 100 mm bore and making good both ends all specified and directed
Supply and fixing in replacement 40 mm bore steel tube of light grade galvanised with all fittings fixed to walls / floors / poles or under road etc of following sizes complete all as specified and directed.
Supply and fixing in replacement 80 mm bore steel tube of light grade galvanised with all fittings fixed to walls / floors / poles or under road etc of following sizes complete all as specified and directed.
Disconnecting and taking out underground cable, including carry out megger testing of dismantle LT cable of length not more than 5 mtr and locating the fault and cutting the faulty damaged portion of cable, connecting with providing new heat shrinkable straight through jointing kit of cable size 25 to 50 Sqmm, 3.5/4 Core, including excavation, returning filling and all connected materials complete all as specified and directed. Note:-Necessary excavation , sand cushioning ,cable cover as bricks etc beyond 5 mtr should be measured and paid separately.
Disconnecting and taking out underground cable, including carry out megger testing of dismantle LT cable of length not more than 5 mtr and locating the fault and cutting the faulty damaged portion of cable, connecting with providing new heat shrinkable straight through jointing kit of cable size 70 to 150 Sqmm, 3.5 Core, including excavation, returning filling and all connected materials complete all as specified and directed. Note:-Necessary excavation , sand cushioning ,cable cover as bricks etc beyond 5 mtr should be measured and paid separately.
Disconnecting and taking out underground cable, including carry out megger testing of dismantle LT cable of length not more than 5 mtr and locating the fault and cutting the faulty damaged portion of cable, connecting with providing new heat shrinkable straight through jointing kit of cable size 185 to 240 Sqmm, 3.5 Core, including excavation, returning filling and all connected materials complete all as specified and directed. Note:-Necessary excavation , sand cushioning ,cable cover as bricks etc beyond 5 mtr should be measured and paid separately.
Disconnecting and taking out underground cable, including carry out megger testing of dismantle LT cable of length not more than 5 mtr and locating the fault and cutting the faulty damaged portion of cable, connecting with providing new heat shrinkable straight through jointing kit of cable size 300 to 400 Sqmm, 3.5 Core, including excavation, returning filling and all connected materials complete all as specified and directed. Note:-Necessary excavation , sand cushioning ,cable cover as bricks etc beyond 5 mtr should be measured and paid separately.
Testing and fault locating of LT undergroung cable if any size with the help of cable fault locating machine at site including removal of moisture content from cable all as directed.(Note:- The machine for locating of fault will be arranged by the contractor .The quoted rate is included for the fault locating machine. Necessary excavation , earthwork ,the joint shall be measured and paid separately).
Supply, installation, commissioning and testing in replacement of ABC 4 pole, (fixed on existing panel) 415 volt, 4 pole, 50 KA rupturing breaking capacity, 50Hz AC grade of capacity 1250 Amps capacity with Manual Draw out type, suitable for over current, earth fault and short circuit protection complete with spreader terminals (legs) and lugs with proper fitting in existing panel complete all as specified and as directed.
Supply, installation, commissioning and testing in replacement of MCCB 400 Amp, 36 KA (fixed on existing panel) 415 volt, 4 pole, 50 KA breaking capacity with adjustable current range for overload protection and thermal release complete with spreader terminals (legs) and with proper lugs complete all as specified and as directed.
Supply, installation, commissioning and testing in replacement of MCCB 250 Amp, 36 KA (fixed on existing panel) 415 volt, 4 pole, 50 KA breaking capacity with adjustable current range for overload protection and thermal release complete with spreader terminals (legs) and with proper lugs complete all as specified and as directed.
Supply, installation, commissioning and testing in replacement of MCCB 200 Amp, 36 KA (fixed on existing panel) 415 volt, 4 pole, 50 KA breaking capacity with adjustable current range for overload protection and thermal release complete with spreader terminals (legs) and with proper lugs complete all as specified and as directed.
Supply, installation, commissioning and testing in replacement of MCCB 63 Amp, 27 KA (fixed on existing panel) 415 volt, 4 pole, 50 KA breaking capacity with adjustable current range for overload protection and thermal release complete with spreader terminals (legs) and with proper lugs complete all as specified and as directed.
S&F in replacement MCB TPN of capacity 63A,10 KA, 415 volts complete all as specified and directed.
M&L for earthing complete with galvanized steel earth plate electrode 60cmx60cmx6mm thick burried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of plate not less than 1.5 m deep below normal ground level and connected to and including galvanized iron earth wire 4 mm dia by means of GI nuts, bolts, check nuts, washers thimbles, etc as shown in electrical plate No 3 of SSR Part-I and connection to main switch board/Test point/panel/equipment and testing on completion including excavation and earth work in any type of soil, returning filling in, and removal of surplus spoil to a distance not exc 50 metre, charcoal and salt in alternate layer 15 cm thick all around the earth plate electrode, MS funnel with wire mesh, GI pipe medium grade 20 mm bore for watering and 15 mm bore upto 7.50 metre long GI pipe light grade for earth wire protection fixed with poles/wall with two clamps, made from MS flat 25 mmx3mm, bolts, nuts and washers, PCC chamber (1:3:6) type C1, 40mm thick precast RCC cover 1:2:4 type B1 shall be provided on CI frame etc complete including taking down existing u/s earthing all as specified & as directed. Note :- PCC chamber shall be constructed at least 1.5m away from the earth electrode and pipe for watering shall be provided in slanting manners.
All as per srl item No 38 (here-in-before) but using galvanized iron strip 25 x 4 mm as earthing lead and GI protection pipe light grade 40 mm bore. NOTE for Srl item no 38.00 & 39.00 :- The unit rate quoted shall includes for protection pipe and GI earth strip 25x4mm from top of earth plate up to 7.5 meter above ground level.
Supply and fixing in replacement Indicator Lamp LED type (R-Y-B) 240 V, AC, single phase, on existing LT panel , all as directed Engr In Charge.
M & L for taking out the existing unsv Voltmeter and Supply & fixing in replacement Digital type Volt Meter 96 mm x 96 mm, of range 0-500 volts, class -1, incl internal wiring with 1.0 sqmm single core PVC wire all as directed.
M & L for taking out the existing unsv Ammeter and Supply & fixing in replacement Digital type Ammeter 96 mm x 96 mm, single phase , range up to 0-600 Amp, class -1, incl internal wiring with 1.0 sqmm single core PVC wire all as directed.
Material and labour for painting of LT panel boards with the help of jet spray paints, panel out door/in door of size up to 3.00 Sqm floor mounted installed at different locations including preparation of exposed surface by removing old paint from the body, cleaning the surface with thinner and applying two coats of synthetic enamelled smoke grey paint complete all as specified and directed.
Material and labour for painting of LT panel boards with the help of jet spray paints, panels out door/in door of size above 3.00 Sqmm and up to 10 Sqmm floor mounted installed at different locations including preparation of exposed surface by removing old paint from the body, cleaning the surface with thinner and applying two coats of synthetic enamelled smoke grey paint complete all as specified and directed.
Material and labour for repairing of existing LT panel by welding, replacing of 03 Nos of broken hinges as per existing size all as directed .
M & L for LT Danger notice plate of size 20 X 15 cm of 1.6 mm thick mild steel sheet, vitreous enameled white, with letters, figures, and conventional skull and bones, in signal red colour and fixed with MS CLAMPS, bolts, and nuts of approved size.
Surface excavation n exc 30 cm depth and averaging 15 cm depth and getting out in soft /loose soil including clearing away all grass and vegetation saplings , shrubs , bushes , undergrowth roots and removing rubbish upto a distance n exc 50 mtrs outside the periphery of the any installation/ feeder pillar area etc.(Note:-The contractor will ensure that no vegetation grows during the contract period on the area so excavated)
Supply and laying double wall corrugated pipe (DWC) in replacement conforming to IS 19430 Part - I of size 50mm outer dia and 38 mm inner dia complete all as specified and as directed
M&L for plain cement concrete (1:4:8) type D-2 using 40 mm graded crushed stone aggregate as in foundation complete all as specified and directed.
Natwadia Electrical Company (BID ID -3359397)
fauji electric works (BID ID -3360572)
M/s Devendera construction (BID ID -3368878)
M/S SURJIT CONSTRUCTION COMPANY (BID ID -3360322)
SAINI ELECTRIC STORE (BID ID -3360767)
malik constructions (BID ID -3360446)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
cancelled_1.pdf
pdf • 0.63 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.40 MB
TenderdocumentsGe15.pdf
Tender Documents • 1.22 MB
BOQ_801868.xls
BOQ • 0.33 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .