Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹39.9 LAccepted-AOC NO 7 VANIDASAN STREET KOSAPALAYAM PUDUCHERRY 605013 | PONDICHERRY | PUDUCHERRY | 605013 | ₹39.9 L | L1 | Accepted-AOC Lowest |
| 2 | L2₹40.5 L+₹53,617 (1.34%)Rejected-Finance NO 1055 MAIN ROAD ODIAMPET VILLIANUR PUDUCHERRY 605110 | CUDDALORE | TAMIL NADU | 605110 | ₹40.5 L+₹53,617 (1.34%) | L2 | Rejected-Finance Not lowest |
Tender Value
₹43.9 L
EMD Value
₹87,746
Closing Date
20 Jun 2023, 3:30 pmClosed
Executive Engineer, SBD-II, PWD, Puducherry
No.1, Rue Eveche, Puducherry - 605001
Sub Work a Providing internal and external electrification for the 64 dwelling units in 4 blocks B4, B5, B6 and B7 and Community Hall at Lambert Saravanan Nagar, Reddiyarpalayam, Puducherry
2023_PWDC2_12910_1
13/PW/SBDII/2023-24
Open Tender
Electrical Works
Item Rate
300 days
Lambert Saravanan Nagar, Reddiarpalayam
Please refer tender documents
3 documents required · 3 mandatory
₹525
₹87,746
8 Sept 2023
13 Jun 2023
20 Jun 2023
13 Jun 2023
20 Jun 2023
13 Jun 2023
Amount
Wiring or light point / fan point / exhaust fan point / call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class pvc conduit , with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc.as required - GROUP B
Supplying and fixing two module stepped type electronic fan per regulator on the existing modular plate switch box including connections but excluding modular plate etc as required
Supplying and fixing suitable size G.I box with modular plate and cover in front of surface or in recess, including providing and fixing 3 Pin 5/6 A modular socket outlet and 5/6 A modular switch, connection etc., as required.
Supplying and fixing suitable size G.I box with modular plate and cover in front of surface or in recess, including providing and fixing 6/16 A modular socket outlet and 6/16 A modular switch, connection etc., as required.
Wiring for circuit / submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor , single core cable in surface / recessed medium class PVC conduit as required - 2 X 2.5 sq.mm + 1 x 2.5 sq.mm earth
Wiring for circuit / submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor , single core cable in surface / recessed medium class PVC conduit as required - 2 X 4 sq.mm + 1 x 4 sq.mm earth wire
Supply of 4 x 50 Sq.mm armoured aluminium XLPE U.G cable - 1.1 KV grade.
Laying of one number PVC insulated and PVC sheathed /XLPE power cable of 1.1 kV grade of following size direct in ground including excavation , sand cushioning, protective covering and refilling the trench etc.as required - above 35 sq.mm and upto 95 sq.mm
Providing , laying and fixing following dia G.I.pipe (medium class) in ground complete with G.I.fittings including trenching (75 cm deep) and re-filling etc as required- 80mm dia
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required - 4 X25 sq.mm (28 mm)
Earthing with G.I. earth pipe 4.5 meter long, 40 mm dia including accessories , and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal / coke and salt as required
Supplying and fixing following way , single pole and neutral , sheet steel , MCB disribution board , 240 V, on surface / recess , complete with tinned copper bus bar , neutral bus bar , earth bar , din bar , interconnections , powder painted including earthing etc. as required (But without MCB / RCCB / Isolator) - 8 way ,double door
Supplying and fixing 5 A to 32 A rating , 240/415 V, 10 kA, per "C" curve , miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections , testing and commissioning etc .as required. - Single Pole
Supplying and fixing 5 A to 32 A rating , 240/415 V, 10 kA, "C" curve , miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections , testing and commissioning etc .as required. - Double Pole
Supplying and fixing of surface mounting, batten type 20W LED tube light (Foour feet) luminare with efficient driver (efficiency shall be more than 90%) & required minimum of 1600 lumens output, comprising of hig quality diffuser technology complete with efficient & constant currrent output driver suitable for operation on 230V, single phase, 50Hz AC supply, efficient heat sink, effective thermal management and with colour temprature shall be >5000k. the LED with suitable control gears and power factor >0.9. and necessaty fixing accessories as required. Make: Philips - Smart light BN121C LED20S PSC CW GR52 of similar Wipro of equivalent.
Installation , testing and commissioning of ceiling fan , including wiring the down rods of standard length (upto 30 cm) with 1.5 sq.mm FRLS PVC insulated , copper conductor , single core cable , including providing and fixing phenolic laminated sheet cover on the fan box etc as required
Installation , testing and commissioning of wall bracket / ceiling fittings of all sizes and shapes containing upto two GLS / CFL /LED lamps per fitting . Complete with all accessories including connections etc as required
Supplying and fixing of 32--100A HRC fuse link for fuse base in the Areial board, cost should be inclusive of minor modification suitable for site condition as approved by the Engineer-in-charge. (Make: HPL/ Havells/ C & S).
Supplying and fixing of 125/200/250/315A DIN HRC fuse base for Ariel board in the E.D pole for control the metering panel supplu. Make; HPL/ Havells/ C&S. cost should be inclusive of minor modification suitable for site condition etc. complete as approved by the Engineer-in-charge.
8 SWG copper wire (4.0 mm dia) kg
Supply, of metering panel board for the power supply of size 1500mm x 1650mm x 300mm made out of 16SWG thick cold rolled M.S. Sheet. The panel has to be mounted on MS angle frame fixed suitable on the wall. The panel board should have compartments for providing 9 nos of meter with viewing glass and for providing 9 nos of 32A DP SFU cubical switch, (Make: Standard & L&T) 1 no. of 125A TPN SFU cubical switch, (Make Standard & L&T) with out SS enclosure, excluding fuse link with copper busbar and 3 nos of signal lamps. The switch units are to be fixed within the alloted size in the panel board, the bottom sheet of the shell should be of thick rolled sheet for cable entry. The metering compartments should have 10mm thick hylem sheet of suitable size for fixing the energy meters and fuse units. (excluding fuse) all the doors sealing facility. The panel Zinc chromate and two coats of anti corrosive epoxy shade 631 siemens grey paint after completion of de-rusting process. The panel provided with removable type gland plated to the bottom and with sufficient holes of required diameter. The cost should be inclusive of minor modifications suitable for site condition as approved by the Engineer-in-charge.
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface / recess including cutting the wall and making good the same in case of recessed conduit as required - 20mm
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface / recess including cutting the wall and making good the same in case of recessed conduit as required - 25mm
Concealed type ceiling fan metal hook. (L.M.R)
3mm thick mica plate for fan hook box (L.M.R)
Supplying and fixing of following size of PVC junction box in required position along the line of PVC conduit as required. Make:Avonplast/Vijaya:- 25mm Junction Box four way
Supplying and fixing following size / modules , GI box alongwith modular base & cover plate for modular switches in recess etc. as required - 12 module (125 mm x 125 mm)
Supplying and fixing following size / modules , GI box alongwith modular base & cover plate for modular switches in recess etc. as required - 8 module (125 mm x 125 mm)
Wiring for circuit / submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor , single core cable in surface / recessed medium class PVC conduit as required - 2 X 1.5 sq.mm + 1 x 1.5 sq.mm earth
Wiring for circuit / submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor , single core cable in surface / recessed medium class PVC conduit as required - 2 X 6 sq.mm + 1 x 6 sq.mm earth wire
Supplying and fixing 3 pin , 5 A ceiling rose on the existing junction box / wooden block including connection etc as required
Supplying and fixing brass batten / angle holder including connection etc.as required
Supplying and fixing following modular switch / socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required - 5/6 A switch
Supplying and fixing following modular switch / socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required - 3 pin 5/6 A socket outlet
Supplying and fixing following modular switch / socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required - 15/16 A switch
Supplying and fixing following modular switch / socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required - 6 pin 15/16 A socket outlet
Supplying and fixing following modular switch / socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required - 2 way 5/6 A switch
Supplying and fixing following way , horizontal type three pole and neutral , sheet steel , MCB distribution board , 415 V, on surface / recess , complete with tinned copper bus bar , neutral bus bar , earth bar , din bar, Interconnections , powder painted including earthing etc. as required (but without MCB / RCCB / Isolator ) 4way (4+12) , double door
Supplying and fixing 5 A to 32 A rating , 240/415 V, 10 kA, "C" curve , miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections , testing and commissioning etc .as required. - Single Pole and neutral
Supplying and fixing 5 A to 32 A rating , 240/415 V, 10 kA, "C" curve , miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections , testing and commissioning etc .as required. - Triple pole and neutral
1 x 40w decorative fitting with end cover. Make: Philips/Bajaj
2 x 36/40w surface mounting Mirror optics fittings with Special aqua - Xtend Aqua .Make: Philips/Bajaj
40W tube light. Make: Philips
25W CFL lamp for pendent holder Make: Philips
1200mm sweep double ball bearing ceiling fan Make:Almonard/Usha
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size direct in ground including excavation , sand cushioning, protective covering and refilling the trench etc.as required - Upto 35 sq.mm
Supplying and fixing of following size Teak woodenn board on recess including cutting the wall and finishing the surface good the same as required - 375mm X 200mm X 50mm deep
Providing and fixing of following size of phenolic coated sheet on the existing wooden board:- 200mm X 150mm X 3mm thick
Providing and fixing of following size of phenolic coated sheet on the existing wooden board:- 300mm X 200mm X 3mm thick
Providing and fixing of following size of phenolic coated sheet on the existing wooden board:- 375mm X 200mm X 3mm thick
Supplying and fixing of 32/63/100/200A DIN HRC fuse base. Make: Standard/Havells/C&S/L&T
Supplying and fixing of 32-100A HRC fuse link (DIN type). Make: Standard/Havells/C&S/L&T
Fabrication, supply, erection, testing and commissioning of one no of three pole metering panel board for the power supply of over all size 1100x650x250mm made out of 16 SWG thick cold rolled M.S sheet. The panel has to be mounted on MS angle frame fixed suitably on the wall. the panel baord has to be fitted 1 no. of 125 A cubical switch without SS enclosure excluding fuse link bolted type (Make: Srandard/ C& S), 3 nos. of 100 A rewirable porcelain fuse unit - 415V (Make - Kundan/ Havells), 3 Nos. of signal lamp and toggle switch are to be fixed wit in the allotted size in the 10mm hylem sheet. Interior connection between the switch fuse are to be done with 10.00 Sqmm ISI marked, FR PVC insulted, single core copper conductor cable (Make - Finolex/ Polycab). The switche units are to be fixed with in the allotted size in the 10mm hylem sheet. The bottom sheet of the shell should be of 16 SWG thick cold rolled M.S sheet with brass gland for cable entry. The panel has to be mounted on the floor with height of 375mm interior connection between the switch fuse units are to be done with 10.00sqmm ISI marked. FR PVC insulated, single core copper conductor cable (Make Finolex/ Polycab). The door should be of flush tyoe inter locking in one position and 2 nos. of 200mm x 150mm M.V danger notice plate are fixed in the front side door of the panel Board. The panel provided with removable type gland plated to the bottom and with sufficient holes of required diametre. the panel should be painted with two coats of rust proof Zinc Chromate and two coats of anti corrosive epoxy shade 631 siemens grey paint after completion of de-rusting process. the cost should inclusive of minor modification suitable for site condition as approved by the Engineer-in-charge.
Rajavel Electro Mechanical Works
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .