GE AF OJHAR
GE AF OJHAR
REPAIR / REPLACEMENT OAND MAINTENANCE OF LT OVER HEAD LINE, LT CABLES, LT FEEDER PILLAR BOXES AND OTHER CONNECTED ITEMS OF VARIOUS LOCATIONS AT 25ED AFS DEOLALI
2023_MES_625116_1
8126/E8
Open Tender
Electrical and Maintenance Works
Item Rate
240 days
25 ED DEVLALI
As per tender documents
8 documents required · 8 mandatory
₹500
GE AF OJHAR
₹60,000
Yes
GE AF OJHAR
23 Jan 2024
26 Oct 2023
23 Nov 2023
27 Oct 2023
21 Nov 2023
7 Nov 2023
27 Oct 2023
Amount
S&F in repair PVC insulated and weather proof three core copper multi stranded conductor cable 2.5 Sqmm size as required length for replacing unserviceable cable for street light where ever found unserviceable and required from over head conductor or junction box to street light connector of Street Light fittings all as specified & as directed by Engr-in-Charge.
All as per Sl item No 1 here in above but single core of 1.5 Sqmm size all as specified & as directed by Engr-in-Charge.
M&L in replacement of 10 Sqmm, twin core 1100 volts grade heavy duty PVC insulated multistranded aluminium conductor and overall PVC sheathed in service connection complete all as specified and directed by Engr-In-Charge. Make:Paragon/PLAZA/Havells/KEI/HPL
All as per ser item No 3 above but 6 Sqmm of aluminium conductor.
M & L for Cutting of branches of trees having girth exceeding 5 cm but not exceeding 20 cm in over head conductor span approximate length 30-40 mtr including disposal of unserviceable material to a distance 100 mtr for removing/ cleaning over head ACSR conductor around the 3 mtrs all as directed by the Engineer in charge. Note : T &P for above mentioned work shall be arranged by contactor and included in quoted rate.
M&L for in repair of jointing & testing heat shrinkable cable joint kit , straight through , out door type for 1100 volts LT XLPE/PVC insulated cable of aluminium conductor up to 50 sqmm 3-1/2 core cable including necessary jointing work all as specified & directed
M&L inrepair for jointing & testing heat shrinkable cable joint kit , straight through , out door type for 1100 volts LT XLPE/PVC insulated cable of aluminium conductor 50sqmm to 120 sqmm 3.5 core cable including necessary jointing work all as specified & directed
Re-stringing of existing LT overhead line of copper/ACSR conductor after opening of binding wire from insulator and bringing the sag within limit rebinding the same with insulator with 16 SWG aluminium wire/suitable copper wire all including renewal of jumpers by providing heavy duty alkathine pipe of approved quality, reconnecting the service connections after cleaning the carbon and foreign material complete all as directed. Note : T &P for above mentioned work included in quoted rate.
S& F in repairs pin type porcelain, vitreous, white, brown or green insulator including one mild steel spindle, two galvanised iron washers and one galvanised iron nut 100mm height, 65 mm dia for 1100 volts grade on existing cross arms on LT poles
S&F in repairs shackle type porcelain, vitreous white brown or green, insulator for working pressure 6600 volts of 150 mmx 125mm including galvanised mild steel straps of 38x5 mm size 20mm dia bolts, washers & nuts or 50x6 mm size Flat iron D clamp etc on existing cross arms on LT pole all as specified and directed by Engr in charge.
Excavation in trenches n. exc 1.5 Mtr wide and n. exc 1.5 mtr in depth and getting out in soft soil.
Excavation in trenches n. exc 1.5 Mtr wide and n. exc 1.5 mtr in depth and getting out in hard soil.
Returning Filling in including spreading, leveling, watering & well ramming in layers n. exc 25 Cm.
Removing excavated/Surplus soil n exc 50 Mtr & depositing where directed at a level n. exc 1.5 Mtr above the starting point.
M&L in repair for double wall corrugated (DWC) duct (dure guard) as per IS 14930 part II LT UG cable protection including coupler, elbows, T joiints, Bends etc. and test report Make: Dura line/ Gemini/ Rex of size 38mm inner dia and 50mm outer dia all as per direted by Engr in charge.
M&L in repair for double wall corrugated (DWC) duct (dure guard) as per IS 14930 part II LT UG cable protection including coupler, elbows, T joiints, Bends etc. and test report Make: Dura line/ Gemini/ Rex of size 63mm inner dia and 77mm outer dia al as per direted by Engr in charge.
Supply and laying in repairs LT XLPE insulated heavy duty armoured cable 1100 volts grade, multi-stranded aluminium conductor electric cable, cross sectional area 120 Sqmm 3.5 Core including necessary connection with lugs, cable gland & fixing arrangements all as specified and directed.
Supply and laying in repairs LT XLPE insulated/PVC heavy duty armoured cablle 1100 volts grade UG stranded aluminium conductor electric cable cross sectional area 25 Sqmm 3.5 Core including necessary connection with provision of lugs & cable gland fixing arrangements all as specified and directed.
Supply and laying in repairs LT XLPE insulated heavy duty armoured cable 1100 volts grade, multi-stranded aluminium conductor electric cable, cross sectional area 70 Sqmm 3.5 Core including necessary connection with lugs, cable gland & fixing arrangements all as specified and directed.
Supply and laying in repairs LT XLPE insulated heavy duty armoured cable 1100 volts grade, multi-stranded aluminium conductor electric cable, cross sectional area 50 Sqmm 3.5 Core including necessary connection with lugs, cable gland & fixing arrangements all as specified and directed.
Supply and laying in repairs LT XLPE insulated heavy duty armoured cable 1100 volts grade, multi-stranded aluminium conductor electric cable, cross sectional area 35 Sqmm 3.5 Core including necessary connection with lugs, cable gland & fixing arrangements all as specified and directed.
Supply and laying in repairs LT XLPE insulated heavy duty armoured cable 1100 volts grade, multi-stranded aluminium conductor electric cable, cross sectional area 16 Sqmm 4 Core including necessary connection with lugs, cable gland & fixing arrangements all as specified and directed.
S & F in repairs single piece moulded PVC box of size 230X185X110mm outer dimensions (Sintex or equivalent of National ) consisting of one porcelain kit kat 16 Amps & one 4 way connector including all necessary fixing arrangements to fix to pole i.e. clamps, nuts, bolts & washers of suitable size after dismantling the existing pole coping and replacement of cable lugs and cable gland all as directed.
M&L in repair for Cable route indicator fabricated from 40x40x6mm angle iron 450 mm long, rivited or welded with 100mm dia CI or MS roung disc duly engraved " LT cable" in letters including grouted in ground with PCC 1:4:8 type D-2 complete all as specified and directed by Engr- in -Charge.
M & L in repair for cement concrete (1:3:6 ) type C-1 using 20 mm graded stone aggregate, including weathering, slightly rounded Chamfered angles and throating including necessary form work all as directed .
M & L in repair for cement concrete (1:4:8 ) type D-2 using 40 mm graded stone aggregate, in foundation all as directed .
M&L in repair for locating under ground cable fault within 06 hours including Sunday or any holiday using cable fault locator taking all necessary precaution as directed by Engr in charge. Note ; If fault not located by the contractor within specified time a recovery of an amount of Rs 5000/- will be recovered per day.
Preparation of old painted surfaces of steel tubular poles,cross arms and painting with two coat of aluminium paint after scrapping old paint all as directed for pole of LT pole up to 7 mtr long including marking of pole number.
Preparation of old painted surfaces of steel tubular poles,cross arms and painting with two coats of aluminium paint after scrapping old paint all as directed for pole of height more than 9.0 mtr including marking of pole number
M&L in repair for painting with two coat of cement based paint after scrapping old painted surfaces of concrete poles of height above GL upto 7 meters and including marking of poles numbers in white on black background complete all as directed.
M&L for painting with two coat of cement based paint after scrapping old painted surfaces of concrete poles of height above GL 7 to 9 meters and including marking of poles numbers in white on black background complete all as directed.
M&L in repair for cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers,welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated, with & inclusive of one coat red oxide primer & one under coat and one finishing coat of synthetic enamel paint after preperation of surfaces all as Specified and directed.
Supply and errection in position of steel tubular pole swaged complete with cast iron base plate finial taper plug, bolts, nuts, pole caps and screws, top cover all as specified type 410 SP 31 ( 9 mtr long ).The poles shall be painted with two coat of black bituminous paint through internally and externally up to planting depth and balance portion of pole shall be painted with two coats of aluminium paint over a coat of red oxide primer, all as specified, as directed by Engr in charge. Note:-Excavation and earth work shall be paid separatly
S&F in repairs galvanised iron continuous earth wire 4mm dia on cross arms of LT poles for guarding including necessary binding with 16 SWG G.I wire complete all as specified and directed.
S&F in repairs MCCB four pole, 415 Volts, of rating capacity 500 Amps, 50 KA, 50 Hz, with thermal setting adjustable including dismantaling and reconnecting all necessary connections & testing complete.
S&F in repairs MCCB four pole, 415 Volts, of rating capacity 200 Amps, 36 KA, 50 Hz, with thermal setting adjustable including dismantaling and reconnecting all necessary connections & testing complete.
S&F in repairs MCCB three pole, 415 Volts, of rating capacity 160Amps, 36 KA, 50 Hz with thermal setting adjustable including dismantaling and reconnecting all necessary connections & testing complete.
S&F in repairs on load change over switch of capacity 200 Amps in sheet steel enclosure, 415 Volts, 50 Hz, AC, 4 pole including necessary connections & modification in existing panel if required complete all as directed by Engr-in-charge.
All as per item No 38 but 63 Amps capacity
All as per item No-38 but 100 Amps capacity
Maintenance of two pole structure including cleaning the parts and replacement of jumper, worn out insulators, greasing with silicon grease, alligning of GOD knife and tightening of GOD parts containg any nos. of GOD's all as specified and directed by the Engr In charge
Maintenance of four pole structure including cleaning the parts and replacement of jumper, worn out insulators, greasing with silicon grease, alligning of GOD knife and tightening of GOD parts containg any nos. of GOD's all as specified and directed by the Engr In charge
M&L for earthing complete with galvanised steel earth plate electrode 600x600x6 mm thick, burried directly in ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, connected to GI wire 4 mm dia through GI pipe 15 mm dia light grade by means of bolts,nuts, check nuts and washers of galvanised iron or steel,with adequate quantity of charcoal and salt, proper watering arrangements including 20 mm dia medium grade GI tubing.PCC chamber,Chamber Cover all as shown in electrical plate No 3 of SSR part I 2009 connected to earthing test point all as specified or indicated and testing on completion. The end point connection of eatrhing will be carried out with the help of bolt grouted and washer and nut.
M&L for earthing complete with galvanised steel earth plate electrode 600x600x6 mm thick, burried directly in ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, connected to GI strip 25x4 mm through GI pipe 40 mm dia light grade by means of bolts,nuts, check nuts and washers of galvanised iron or steel,with adequate quantity of charcoal and salt, proper watering arrangements including 20 mm dia medium grade GI tubing.PCC chamber,Chamber Cover all as shown in electrical plate no 3of SSR part I 2009 connected to earthing test point all as specified or indicated and testing on completion. The end point connection of eatrhing will be carried out with the help of bolt grouted and washer and nut.
M&L for removal of green vegetation from substations, pumphouse area using chemcals if necessary etc including depositing the vegetation away from the places complete all as directed
Preparation of old painted surfaces of outdoor LT panel including scraping out old paint and painting with two coat of synthetic enameled paint all as directed including marking of building number on front face of panel in colour as directed by Engr in charge.
M & L for decorbonising /Cleaning of LT Panel/ feeder pillar box including taking elect shut down and cleaning the all bus bar system , incomming and out going calbles, MCBs/ MCCBs with blower and charge the eletrical panel as original condition after completion of decarbonising all as specified and directed by Engr- in - Charge.
Material and labour for earthing (in repair) complete with copper earth plate electrode of size 60cm x 60 cm x 3.0 mm thick buried directly in ground ( earth pit not less than 2.25 mtr deep below ground level) with top edge of earth plate not less than 1.5 mtr below ground level connected to copper strip 20 x 3 mm by means of galvanized iron nuts & bolts or as directed at site by Engineer -in-Charge protected by GI Pipe 40 mm dia light grade and connected to test point and further connected to equipment, machinery, electrical panel or any other as directed by Engineer-in-Charge, which to be earthed, all as shown in electrical plate No 3 of SSR Part I including provision of concrete earth pit constructed in PCC 1:3:6 type C-1 as earth pit and PCC 1:2:4 type B-1 for cover slab with necessary reinforcement with handle for lifting also including provision of funnel with wire mesh with 20 mm GI pipe medium grade for watering, charcoal and salt in alternative layers of 15 cm thick all around the electrode , including necessary excavation and earth work , testing and commissioning complete all as directed.
Supply, install, testing and commissioning of cubical type outdoor LT feeder pillar box fabricated out of 3.15mm thick CRCA sheet with separate locking arrangement, painted with epoxy powder coated over a coat of red oxide primer, factory made, cubicle type, double door hinged type, both side openable, provided with 3mm thick bakelite / fiber sheet for mounting electrical accessories, holes for cable entries, detachable gland plates at bottom, earth connection terminals etc. and mounted on 40x40x5 mm angle iron frame, adequate clearance from ground level for the entry and exit of cables, provision of ventilation on sides, manufacturer details, necessary PCC work for grouting and provn of cable lugs for connection etc. complete and consisting of following:- (a) MCCB 125A 4 pole, 25 KA -01 Nos ( as main incomer), (b) LED indication lamps 3 Phase, (c) TPN Aluminum bus bar 200 A current capacity. (d) MCCB TP 100 A, 25 KA- 01 Nos (outgoing) (e) MCCB 63 A, TP, 25 KA-02 Nos(outgoing) (f) Digital Multifunctional meter with suitable capacity CTs and PTs (g) Including internal wiring with copper cable of suitable capcity
M&L for stay assembly for LT pole complete with accessories as shown in electrical plate no 1 including stay rod 200 mm dia, loop type insulator, stay wire, stay clamp, excavation, concrete etc all as specified and directrdd by Engr in charge.
Labour only for following services are to be provided for to carry out the preventive maintenance for existing electrical LT equipment of 1100 Volt and LT over head lines and all accessories by employing min 01 elect & 01 Helper (Electricians and helpers shall be experienced in their trades).will report to JE E/M in charge of receiving sub station for to receiving instructions to carrying out repair at sharp 0900 hrs on every working day i.e. for 8 hrs with necessary tools complete all as directed. (a). Carrying out periodaical checking and maintenance of LT panel (b). Checking and tightning of all jumpers, earth connection, Lightning Arresters, fuses including putting of fuses and necessary repair and maintenance as required and as directed by Engineer-in-Charge / Rep of dept in all four pole structure under complete area of 25 ED AF. (c).Checking and tightning of all jumpers, earth connection, tightning of ACSR conductor and necessary repair and maintenance as required and as directed by Engineer-in-Charge / Rep of dept in all LT O/H Feeders and LT Two pole structure under complete 25 ED AF area. (d).Checking of Earthing, test points, earth leads, periodical testing of earth resistance, cheching and rectification of earth neutral voltage fault all as directed by Engineer-in-Charge. (e).Carrying out minor repair of LT Panel and MCCB DBs tightning of terminal studs, etc. (f). Carrying out maintenance and repair to Indoor / Outdoor LT distribution Feeder Pillar Box checking of all terminals, internal wiring, replacement of fuses all as required and directed by Engineer-in-Charge. Note 1:-. Complete material and necessary T&P ( earth megger, multi meter, all electrical tools, ladder, trasportation etc.) as required for rectification of defects/attending to fault shall be arranged by contractor and cost of the same will be deemed to be included in the unit rate quoted. Note 2:-. Any casualty or injury sustained by the contractor’s workers during the working hours shall be sole liability of the contractor. No claim on this account shall be entertained by the department
Labour only for attending the electrical / mechanical fault or breakdown by checking of existing electrical equipment, LT overhead line and LT cable complete including all accessories for continous electrical supply or detection of nature of defect including carrying out minor repairs etc as required to made the functional by employing requisite numbers of man power (Electricians and helpers shall be experienced in their trades).They will make themselves available to JE in charge/engineer-in-charge for attending the electric fault at all time including sunday and holiday at main receiving sub station. (a) Attending of every maximum 05 nos of electric fault in a single day, in Premises of 25 ED area will be considered as one job. (b) The contractor is required to and rectify the defects to within stipulated period, compensation of Rs. 500.00 (Rupees Five hundred only) per fault for each day (i.e. 24 hours) shall be recovered from the contractor and maximum recovery for this account shall be 10 days if contractor fail to rectify the defect/defects within anticipated completion time, the department can rectify the defect at his own arrangements and repair cost will be recovered as per market rate in addition to penalty imposed on contractor for not attending the fault and no payment will be made to contractor to this effect. c) Necessary T&P(all type of tools, Ladders, transportation etc) and minor stores like fuse wire, any size/type of aluminium lugs,jumpers, binding wire, alkathine pipe as required for rectification of defects/attending to fault shall be arranged by contractor and cost of the same will be deemed to be included in the unit rate quoted.
Supply and laying stone aggregate 40 mm grade including lime powder after taking out old aggregate all as specified and directed by Engr - in Charge.
MAHIMA CONSTRUCTION
M/s.NIKI ENTERPRISES
Shree Sai Samarth Enterprises
SV ASSOCIATE
sapana enterprises
Rama Electricals
SOURABH ENGINEERS
SHRI SULAI ELECTRICALS
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .