Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.8 LAccepted-AOC | L1 | Accepted-AOC L1 Bidder Technically and Commercially Qualified | |
| 2 | L2₹9.2 L+₹44,900 (5.12%)Rejected-AOC NEW MARKET SINGRAULI DISTT SINGRAULI MP 486889 | SINGRAULI | SINGRAULI | MP | 486889 | L2 | Rejected-AOC L2 Bidder | |
| 3 | L3₹9.8 L+₹1.0 L (11.8%)Rejected-AOC JAYANT DISTT SINGRAULI MP PIN 486890 | JAYANT | SINGRAULI | MADHYA PRADESH | 486890 | L3 | Rejected-AOC L3 Bidder | |
| 4 | L4₹11.4 L+₹2.6 L (30.0%)Rejected-AOC ALAKHRAJ BHAWAN NEAR MAMTA MOTORS BHUSA MORE WARD NO 7 SINGRAULI M P 486889 | SINGRAULI | MADHYA PRADESH | 486889 | L4 | Rejected-AOC L4 Bidder |
Tender Value
₹14.6 L
EMD Value
₹18,190
Closing Date
3 Oct 2023, 5:00 pmClosed
GM(EnM) Dudhichua Area
PO-Khadia,Distt._Sonbhadra,UP-231222
Work of power supply arrangement work at newly constructed C and D type quarters with HT and LT overhead line at sector B and C township of Dudhichua Area
2023_NCL_288482_1
DCH/EnM/Tender/TS/23-24/034
Open Tender
Miscellaneous Works
Item Rate
60 days
Dudhichua Area
Please refer tender documents
4 documents required · 4 mandatory
₹18,190
25 Jul 2024
22 Sept 2023
4 Oct 2023
22 Sept 2023
3 Oct 2023
23 Sept 2023
22 Sept 2023 - 26 Sept 2023
Amount
Part A (Electrical work)
supply and erection of stay set complete (galvanised) with 19/20 mm dia X 1.8 meters long stay rod, anchor plate of size 45cmx45cmx7.5mm, thimble, stay clamps, bow tightener, 7/3.15mm dia G. stay wire and strain insulator etc in cement concrete 1:3:6 (1 cement: 3 coarse sand: 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required
Errection of steel tublar or rail pole strut in cement concrete 1:3:6 (1 cement: 3 coarse sand: 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling and secured with holding clamps, bolts, nuts, barbed wire etc. as required.
Laying of one number PVC Insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of upto 35 sq mm size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
Laying of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of above 95 sq mm and upto 185 sqmm size direct in ground including excavation, sand cushioning. protective covering and refilling the trench etc as required.
Laying and fixing of one number PVC Insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of upto 35 sq mm (clamped with 1mm thick saddle) on wall surface as required.
Laying and fixing of one number PVC Insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of above 95 sq mm and upto 185 sqmm (clamped with 25/40x3mm M5 flat clamp) on wall surface.as.required,
Supplying and embedding 40 mm dia G. pipe (medium class) in pole collar/foundation (during casting) for cable entry including bending the pipe to the required shape complete as required.
Providing and lying in position cement concrete 1:3:6 (1 cement: 2 coarse sand:6 graded stone aggregate 20 mm nominal size) of cable trench at different places after lying of cable on road/ pathway of residential Qtrs. Blocks, including plaster etc. as required C27
supply and installation of feeder piler distrubution box pannel as per price list of 'D' mak Energiaprivate private limited attached.
Supply and fixing of light class Gl pipe of 80 mm dia (nominal) 3 meter lenth along the pole for protection of under ground cable. as required
Errection of cradle guard as required.
Errection of all aluminium conductor of 7/3 40mm to 7/4.00 mm diameter and above including binding etc. as required.
Earthing with Gl pipe 4.5 meter long 40 mm dia including accessories, and provinding mansory enclosure with cover plate having locking arrangement and watering pipe etc. with charcol/coke and salt as required.
supplying and errection of 75mm X 90mm LT shackle insulator with GI bolt, nut and straps etc. as required
supplying and errection of 100mm x 65mm LT pin insulator compelete with Gi spindle and nuts etc. as required
Errection of disc/ pin insulator 11KV/6.6 KV over head lines as required.
steel work making and Errection of angle iron/channel iron cross iron arm on wood/RCC/PCC/steel tublar/rail pole etc. as required
supplying and fixing of 32 mm dia X 2 meters long Gl pipe (medium class) bracket for mounting of fluorescent/HPMV/HPSV street light fitting on pole including bending the pipe to the required shape, 2 nos 40 mm x 3 mm flat iron clamps with nuts, bolts and washer, painting the flat iron with primer and finish paint etc.as required
providing of 11 KV grade, 630 Amps triple pole centre post rotating manually gang operated horizontal mounting type off load isolator suitable for outdoor operation complete with hard drawn copper contact silver plated base channel assembly including post insulator, coupling pipe and pad locking arrangement.confirmine IS: 9921
Installation/errection and testing of gang operated air break switch/isolator 11 KV grade
supplying and errection three piece nonlinear resistor type lightning arrestor suitable for 3 wire, 11 kv overload lines with rated voltage 9 kv (RMS) with nominal discharge current rating of 5KA and complete with galvanised clamping arreangements G.I. bolts, nuts, washers etc as required
supplying and fixing SA to 32 apms rating, 240/415 volt, 10 kA, C curve, miniature circuit breaker suitable for inductive load of single pale in the existing MCB DB complete with connections,testing and commissioning etc. as required
Supplying and fixing cable End box (loose wire box) suitable for 6 way double door single pole and neutral, sheet steel, MCB distribution board,240 volts, on surface/recess, complete with testing and commissioning. As required.
Providing and fixing M.V. danger notice plate of 200 mm x 150 Imm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required
Supply of paint and painting of pole with brackets etc one coat of red oxide and 2 coat of Aluminium paint
Part B (Platform for Transformer)
Earth work in excavation by mechanical means (Hydraulic excavation)/ manual means in foundation trenches or drains (not) exceeding 1.5m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5m including getting out the excavated soil and disposal of surplus excavation soil as directed, wiyhin a load of 50m
Providing and lying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work upto plinth level: (1 cement: 2 coarse sand (zone-III):6 graded stone aggregate 20 mm nominal size
Brick work with non modular fly as (FLAG) confirming to ISI 12894 of class designate 7.5 avaerage compressive strength etc. complete in all respect in foundation and plinth in cement mortar 1:6 (1 cement: 6 coarse sand)
12 mm cement plaster of mix 1:6 (1 cement:6 fine sand)
Filling available excavated earth (excluding rock) in trenches,plinth, sides of foundation etc.in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead upto to 50 m and lift upto 15 m
Neat cement punning
Total impact of GST for the purpose of CTC
KUNWAR & SINHA ENGINEERING WORKS
M/S. AMAN ASSOCIATES
M/S. ATUL ENTERPRISES
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_298740.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .