Tender Value
Refer Docs
EMD Value
₹20,000
Closing Date
18 Sept 2026, 4:00 pm
Executive Engineer, BMD, PHED
Office of the Executive Engineer. Bankura Mechanical Division. P.H.E. Dte. Ailakundi, PO Kenduadihi, Bankura 722102.
Repairing of H.T. Panel and Transformer, AVR units at Belatikri Water Supply Scheme, Block-Sarenga under Bankura Mechanical Division, P.H.E. Dte.
2026_PHED_5019418_23
WBPHED//BMD/NIeT- 05 OF 2026-2027
Open Tender
MECHANICAL
Item Rate
45 days
Bankura
Please refer Tender documents.
5 documents required · 5 mandatory
₹20,000
Yes
3 Sept 2026
3 Sept 2026
21 Sept 2026
3 Sept 2026
18 Sept 2026
3 Sept 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | For through out inspection for rectification of the existing Transformers, 4 &1 panel 630A, 11KV VCBs, 250KVA AVR with connecting HT, LT cables with hiring of all Testing kit / machine like Insulating Resistance Checking machine (1 KV, 2.5 KV, 5 KV) 3 Phase Variac, Current Injection machine / kit, Voltage injection machine / kit, Blower, Multimeter, Clamp meter, Different type of tools tackles, Various Testing Wires, MCBS, Wires & Cables, with engaiging expert Electrician and report submit as per direction of E.I.C. | 1 | each | - | - |
| 2 | 250 KVA HT AVR | - | - | - | - |
| 3 | Supply delivery of all kinds of Gaskets & Oil Seal supply for HT & LT Bushings, Top Cover, Inspection Cover, Valve, Radiator upper & down air release portion etc. of (A+C) Unit of 250 KVA AVR | 1 | LS | 2 | ₹2 |
| 4 | Charges for gasket changes for (A+C) Unit of 250 KVA AVR by disconnecting of all HT and LT terminals, draining transformer oil, opening of top cover, arresting of any oil leakage by changing of gasket and oil seal respectively various gasket portion like top cover, inspection cover, tap switch, conservator tank, radiators, buchholz, drain valve (as where required) and HT-LT bushing portion | 1 | LS | 3 | ₹3 |
| 5 | Supply delivery of Elysian Blue Color Silica Gel dry and desiccant crystals type in the Breather of above transformer as per direction | 1 | /Kg | 4 | ₹4 |
| 6 | Dehydration & Filtration of Transformer Oil by heat run process for improvement of IR Value (BDV minimum 60KV/mnt) by the hiring of Filtering Machine and Testing Machine & Kit etc as per I.E Rules.
B Unit (300 Ltrs.) + [A+C] Unit (600 Ltrs.) = 900 Ltrs | 900 | /Ltr | 5 | ₹4,500 |
| 7 | Charges for Di-Electric Strength Test (BDV Test) by the hiring of Testing Machine & Kit etc as per I.E Rules. | 1 | LS | 6 | ₹6 |
| 8 | Supply delivery and filling of Transformer Oil (minaral cooling Oil) as per IS-335-1993. | 70 | /Ltr | 7 | ₹490 |
| 9 | De-rusting and painting of the above AVR (A+C) unit by the ready mixed primer of approved make and brand incl. preparation of surface by sand paper, cleaning etc. for receiving two coat of superior quality synthetic anamal paint after applying one coat of red lead chromate primer as per direction of EIC Painting wil be done by the spray paiting machine | 1 | LS | 8 | ₹8 |
| 10 | 1100 VA UPS supply, Input: 230 V AC Make: APC | 1 | Each | 9 | ₹9 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.11 MB
Tendernotice_2.pdf
PDF • 12.63 MB
BOQ_5100351.xls
BOQ • 0.37 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].