Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.7 LAccepted-Finance | L1 | Accepted-Finance Being L1 | |
| 2 | L2₹2.9 L+₹14,000 (5.13%)Rejected-Finance | L2 | Rejected-Finance Being L2 |
| Sl No | Description | Qty | Unit | AMRITH ENGINEERS L2 | R.K. Builders L1 |
|---|---|---|---|---|---|
| 1.00 | Supply, install, testing and commissioning of enclosed Automatic Transfer Switch (ATS) for alternate operation of Transformers of capacity 250 KVA having capacity of 400 Amps , 415V, 50 HZ, 3 - phase supply, double-break contact system offering High short-time withstand, having required IS / IEC standard, suitable for Aluminium Tremination, adjustable time delay (0.1 Sec to 3 Hrs) having protection for phase sequence, single phasing and frequnecy complete all as specified and as directed.
Make :- L& T/ ABB / Siemens / Havells | 1 | Each | 1,63,500 ₹1,63,500 | 1,55,000 ₹1,55,000 Lowest |
| 2.00 | Supply , laying, connecting and commissioning of LT UG cable 120 sqmm 3.5 core 1100 volts grade XLPE insulated armoured heavy duty electric cables with aluminium conductor and connecting with suitable size of cable glands lugs etc. laid in trenches, passing through pipes/ ducts or fixed on walls complete all as specified and as directed . | 40 | Rm | 1,000 ₹40,000 Lowest | 1,450 ₹58,000 |
| 3.00 | Supply, install, test and commisssioning LT panel board of size 1000X1000X800mm out door cubical type factory made double door dust proof CPRI approved and vermin proof fabricated out of CRCA sheet not less than 3.00 mm thick fixed on angle iron frame made out of 50x50x6 mm grounded in PCC 1:3:6 pedestals,angle iron 450mm above ground level complete all as specified and as directed . | 1 | Each | 63,500 ₹63,500 | 45,000 ₹45,000 Lowest |
| 4.00 | Earthing complete with galvanized iron earth plate electrode 60cmx60cmx6mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of plate not less than 1.5 mtr below ground level connecting to the Galvanised iron earth lead 32x6 mm size, by means nut, bolt, check nuts and washer of galvanized iron and 32x6 mm as earth lead protected by provision of GI light grade pipe 40mm bore incl provn of concrete pit in PCC (1:2:4) type B-1 using 20mm graded stone aggregate with 40mm thick cover of RCC (1:2:4) reinforced (weight not less than 4Kg/Sqm) and frame of angle iron 25x25x6mm with lugs 2 Nos and with 6mm dia MS bar handle made to shape, GI light grade 20mm bore pipe for watering perforated at bottom 1.75 mtr long placed on top edge of earth plate, common salt and charcoal filling, test point with fixing arrangement CI funnel wire mesh and earth work in hard/dense soil, returning filling in and removal of surplus soil to a distance not exc 50 mtr all as per electrical plate No.3 of SSR Part I and connecting to earth test point including testing complete all as specified and as directed . | 2 | Each | 10,000 ₹20,000 | 7,500 ₹15,000 Lowest |
Tender Value
₹3.0 L
EMD Value
₹6,060
Closing Date
28 May 2025, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE NAVY LAKSHADWEEP
GE NAVY LAKSHADWEEP KAVARATTI
PROVISION OF AUTO TRANSFER SWITCH AT MAIN RECEIVING STATION AT ICGS KAVARATTI UNDER GE NAVY LAKSHADWEEP
2025_MES_705388_1
8418
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
KAVARATTI
Please refer Tender documents.
6 documents required · 6 mandatory
₹300
GE NAVY LAKSHADWEEP
₹6,060
Yes
17 Oct 2026
25 Apr 2025
31 May 2025
25 Apr 2025
28 May 2025
9 May 2025
Amount
Supply, install, testing and commissioning of enclosed Automatic Transfer Switch (ATS) for alternate operation of Transformers of capacity 250 KVA having capacity of 400 Amps , 415V, 50 HZ, 3 - phase supply, double-break contact system offering High short-time withstand, having required IS / IEC standard, suitable for Aluminium Tremination, adjustable time delay (0.1 Sec to 3 Hrs) having protection for phase sequence, single phasing and frequnecy complete all as specified and as directed. Make :- L& T/ ABB / Siemens / Havells
Supply , laying, connecting and commissioning of LT UG cable 120 sqmm 3.5 core 1100 volts grade XLPE insulated armoured heavy duty electric cables with aluminium conductor and connecting with suitable size of cable glands lugs etc. laid in trenches, passing through pipes/ ducts or fixed on walls complete all as specified and as directed .
Supply, install, test and commisssioning LT panel board of size 1000X1000X800mm out door cubical type factory made double door dust proof CPRI approved and vermin proof fabricated out of CRCA sheet not less than 3.00 mm thick fixed on angle iron frame made out of 50x50x6 mm grounded in PCC 1:3:6 pedestals,angle iron 450mm above ground level complete all as specified and as directed .
Earthing complete with galvanized iron earth plate electrode 60cmx60cmx6mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of plate not less than 1.5 mtr below ground level connecting to the Galvanised iron earth lead 32x6 mm size, by means nut, bolt, check nuts and washer of galvanized iron and 32x6 mm as earth lead protected by provision of GI light grade pipe 40mm bore incl provn of concrete pit in PCC (1:2:4) type B-1 using 20mm graded stone aggregate with 40mm thick cover of RCC (1:2:4) reinforced (weight not less than 4Kg/Sqm) and frame of angle iron 25x25x6mm with lugs 2 Nos and with 6mm dia MS bar handle made to shape, GI light grade 20mm bore pipe for watering perforated at bottom 1.75 mtr long placed on top edge of earth plate, common salt and charcoal filling, test point with fixing arrangement CI funnel wire mesh and earth work in hard/dense soil, returning filling in and removal of surplus soil to a distance not exc 50 mtr all as per electrical plate No.3 of SSR Part I and connecting to earth test point including testing complete all as specified and as directed .
AMRITH ENGINEERS (BID ID -3295021)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .