Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹59.5 CrAdmitted-Finance | ₹59.5 Cr | L1 | Admitted-Finance |
| 2 | L2₹62.1 CrAdmitted-Finance 5TH FLOOR NEHERU NAGAR WAGLE INDUSTRIAL ESTATE THANE WEST THANE MAHARASHTRA 400604 | THANE | MAHARASHTRA | 400604 | ₹62.1 Cr | L2 | Admitted-Finance |
| 3 | L3₹66.1 CrAdmitted-Finance | ₹66.1 Cr | L3 | Admitted-Finance |
| 4 | L4₹70.2 CrAdmitted-Finance | ₹70.2 Cr | L4 | Admitted-Finance |
| 5 | L5₹100.0 CrAdmitted-Finance | ₹100.0 Cr | L5 | Admitted-Finance |
| Sl No | Description | Qty | Unit | Pace Process Controls Pvt Ltd L4 | Tuaman Engineering Limited L5 | Miraj Instrumentation Services I Pvt. Ltd. L2 | ELMATICS ENGINEERS PVT LTD L3 | Konstelec Engineers Limited L1 |
|---|---|---|---|---|---|---|---|---|
| 1.00PRESSURE INSTRUMENTS | ||||||||
| 2.00INSTALLATION OF PRESSURE GAUGES ( WITHOUT DIAPHRAGM SEAL TYPE) | ||||||||
| 3.00 | Scope of work includes taking delivery from warehouse or from the places of storage, on site transportation, handling, storage, unpacking etc. The activity includes following operations:
a) Installation of Line mounted / vessel mounted or Remote mounted or Local Panel or Gauge Board mounted Pressure gauges ( flush panel mounted or mounted on stanchion) with or without Pulsation Dampener / Siphon / Over range protector/ Flow check valve , isolation valve / two valve manifold etc as per Hook-up standard
b) Connection of the pressure gauge to the process line.
c) Proper Installation of Pressure gauges in mounting brackets
d) Cleaning, Flushing and Hydraulic test of the impulse line for the pressure gauge. Payment for the same is covered in Fabrication and installation of Impulse Pipes.
e) Installation with impulse piping arrangement with manifold (as applicable) as per approved hookup drawings
g) Supply, stenciling and Installation of Tag plate for instrument as per Installation standard
h) If required during installation of gauges, making temporary supports / scaffolding etc. is in contractor's(bidder) scope of work.
i) Any other work not specified above but required for installation of pressure gauge is also in contractor's(bidder) scope of work.
j) Free issue to contractor :- Supply of Pressure gauges, valve manifolds & its accessories , hook-up materials etc | 216 | NOS | 8,788 ₹19.0 L | 11,488 ₹24.8 L | 4,500 ₹9.7 L | 4,500 ₹9.7 L | 9,447 ₹20.4 L |
| 4.00INSTALLATION OF DIFF. PRESSURE GAUGES ( WITHOUT DIAPHRAGM SEAL TYPE) | ||||||||
| 5.00 | Scope of work includes taking delivery from warehouse or from the places of storage, on site transportation, handling, storage, unpacking etc. The activity includes following operations:
a) Installation of Line mounted / vessel mounted or Remote mounted or Local Panel or Gauge Board mounted Diff. Pressure Gauges ( flush panel mounted or mounted on stanchion) with or without Pulsation Dampener / Siphon / Over range protector/ Flow check valve , isolation valve / five valve manifold etc as per Hook-up standard.
b) Connection of the pressure gauge to the process line.
c) Proper Installation of Pressure gauges in mounting brackets.
d) Cleaning, Flushing and Hydraulic test of the impulse line for the pressure gauge. Payment for the same is covered in Fabrication and installation of Impulse Pipes.
e) Installation with impulse piping arrangement with manifold (as applicable) as per approved hookup drawings
g) Supply, stenciling and Installation of Tag plate for instrument as per Installation standard
h) If required during installation of gauges, making temporary supports / scaffolding etc. is in contractor's scope of work.
i) Any other work not specified above but required for installation of pressure gauge is also in contractor's scope of work.
j) Free issue to contractor :- Supply of diff. pressure gauge,valve manifolds & its accessories ,hook-up materials etc | 1 | NOS | 10,175 ₹10,175 | 44,185 ₹44,185 | 5,500 ₹5,500 | 6,000 ₹6,000 | 36,122 ₹36,122 |
| 6.00INSTALLATION OF PRESSURE GAUGES ( DIAPHRAGM SEAL TYPE WITH OR WITHOUT CAPILLARY) | ||||||||
| 7.00 | Scope of work includes taking delivery from warehouse or from the places of storage, on site transportation, handling, storage, unpacking etc. The activity includes following operations:
a) Pressure gauges are supplied with :- i) Flanged diaphragm seal of various sizes & pressure rating, ii) Drip ring of various sizes.
b) Installation of line mounted / vessel mounted, Local Panel or Gauge Board mounted Pressure gauges on pre-fabricated stand or stanchion.
c) Installation, bolting & tightening of flanged diaphragm seal along with drip ring on the flanged nozzle (of vessel or on process line). Isolation valves shall be installed on the flushing ports of the drip ring.
d) Laying, supporting, clamping of capillary tubes of diaphragm seal pressure gauge
e) Installation with impulse piping arrangement with manifold (as applicable) as per approved hookup drawings
f) Supply, stenciling and Installation of Tag plate for instrument as per Installation standard
g) If required during installation of gauges, making temporary supports / scaffolding etc. is in contractors(bidder) scope of work.
h) Any other work not specified above but however required for installation of pressure gauges are also in contractor's(bidder) scope of work.
i) Free issue to contractor :- Supply of Pressure gauges with diaphragm seal, Drip ring & its accessories like Nuts,bolts,gaskets ,hook up materials,tray for capillary routing etc, | 342 | NOS | 10,638 ₹36.4 L | 4,384 ₹15.0 L | 3,500 ₹12.0 L | 5,000 ₹17.1 L | 3,612 ₹12.4 L |
| 8.00INSTALLATION OF PRESSURE TRANSMITTER / DIFF. PRESSURE TRANSMITTERS WITHOUT DIAPHRAGM SEAL (SMART / CONVENTIONAL TYPE & EX PROOF / IS) | ||||||||
| 9.00 | Scope of work includes taking delivery from warehouse or from the places of storage, on site transportation, handling, storage, unpacking etc. The activity includes following operations:
a) Fixing of the transmitter on the mounting stand/stanchion.
b) Installation & connection of valve manifold (2-way, 3-way or 5-way as the case may be) to the transmitter and to the impulse line/process line.
c) Cleaning, Flushing and Hydraulic test of the impulse line for the transmitter.Payment for the same is covered in Fabrication and installation of Impulse Pipes.
d) Installation with impulse piping arrangement with manifold (as applicable) as per approved hookup drawings
e) Supply and Installation of Tag plate(Stenciling) for instrument as per Installation standard
f) Unused entries to be plugged
g) If required during installation of transmitter, making temporary supports / scaffolding etc. is in contractors(bidder) scope of work.
h) Any other work not specified above but required for installation of transmitter is also in contractor's(bidder) scope of work.
i) Free Issue to contractor :- Supply of Pressure & diff pressure transmitters, valve manifolds, cables, tray , glands , Hook-up materials etc. | 211 | NOS | 19,425 ₹41.0 L | 29,094 ₹61.4 L | 8,500 ₹17.9 L | 9,000 ₹19.0 L | 23,896 ₹50.4 L |
| 10.00INSTALLATION OF PRESSURE TRANSMITTER / DIFF. PRESSURE TRANSMITTERS WITH DIAPHRAGM SEAL (SMART / CONVENTIONAL TYPE & EX PROOF / IS) | ||||||||
Updated dates
Tender Value
Refer Docs
EMD Value
₹40 L
Closing Date
12 Feb 2026, 3:00 pmClosed
Mukesh Chugh
TECHNIP TOWER A4 SECTOR 1 NOIDA UP 201301
INSTRUMENTATION WORKS FOR EPCM2 SERVICES FOR RPTU UNIT FOR NUMALIGARH REFINERY EXPANSION PROJECT NREP NUMALIGARH ASSAM GROUP A
2025_NRL_891216_1
TPIL/CONS/NRL/200663C/009
Open Tender
Miscellaneous Works
540 days
Numaligarh Refinery Assam
Please refer Tender documents.
6 documents required · 6 mandatory
₹0
₹40 L
Yes
Online MS Teams
20 May 2026
24 Dec 2025
13 Feb 2026
24 Dec 2025
12 Feb 2026
8 Jan 2026
24 Dec 2025 - 30 Dec 2025
30 Dec 2025
PRESSURE INSTRUMENTS
INSTALLATION OF PRESSURE GAUGES ( WITHOUT DIAPHRAGM SEAL TYPE)
Scope of work includes taking delivery from warehouse or from the places of storage, on site transportation, handling, storage, unpacking etc. The activity includes following operations: a) Installation of Line mounted / vessel mounted or Remote mounted or Local Panel or Gauge Board mounted Pressure gauges ( flush panel mounted or mounted on stanchion) with or without Pulsation Dampener / Siphon / Over range protector/ Flow check valve , isolation valve / two valve manifold etc as per Hook-up standard b) Connection of the pressure gauge to the process line. c) Proper Installation of Pressure gauges in mounting brackets d) Cleaning, Flushing and Hydraulic test of the impulse line for the pressure gauge. Payment for the same is covered in Fabrication and installation of Impulse Pipes. e) Installation with impulse piping arrangement with manifold (as applicable) as per approved hookup drawings g) Supply, stenciling and Installation of Tag plate for instrument as per Installation standard h) If required during installation of gauges, making temporary supports / scaffolding etc. is in contractor's(bidder) scope of work. i) Any other work not specified above but required for installation of pressure gauge is also in contractor's(bidder) scope of work. j) Free issue to contractor :- Supply of Pressure gauges, valve manifolds & its accessories , hook-up materials etc
INSTALLATION OF DIFF. PRESSURE GAUGES ( WITHOUT DIAPHRAGM SEAL TYPE)
Scope of work includes taking delivery from warehouse or from the places of storage, on site transportation, handling, storage, unpacking etc. The activity includes following operations: a) Installation of Line mounted / vessel mounted or Remote mounted or Local Panel or Gauge Board mounted Diff. Pressure Gauges ( flush panel mounted or mounted on stanchion) with or without Pulsation Dampener / Siphon / Over range protector/ Flow check valve , isolation valve / five valve manifold etc as per Hook-up standard. b) Connection of the pressure gauge to the process line. c) Proper Installation of Pressure gauges in mounting brackets. d) Cleaning, Flushing and Hydraulic test of the impulse line for the pressure gauge. Payment for the same is covered in Fabrication and installation of Impulse Pipes. e) Installation with impulse piping arrangement with manifold (as applicable) as per approved hookup drawings g) Supply, stenciling and Installation of Tag plate for instrument as per Installation standard h) If required during installation of gauges, making temporary supports / scaffolding etc. is in contractor's scope of work. i) Any other work not specified above but required for installation of pressure gauge is also in contractor's scope of work. j) Free issue to contractor :- Supply of diff. pressure gauge,valve manifolds & its accessories ,hook-up materials etc
INSTALLATION OF PRESSURE GAUGES ( DIAPHRAGM SEAL TYPE WITH OR WITHOUT CAPILLARY)
Scope of work includes taking delivery from warehouse or from the places of storage, on site transportation, handling, storage, unpacking etc. The activity includes following operations: a) Pressure gauges are supplied with :- i) Flanged diaphragm seal of various sizes & pressure rating, ii) Drip ring of various sizes. b) Installation of line mounted / vessel mounted, Local Panel or Gauge Board mounted Pressure gauges on pre-fabricated stand or stanchion. c) Installation, bolting & tightening of flanged diaphragm seal along with drip ring on the flanged nozzle (of vessel or on process line). Isolation valves shall be installed on the flushing ports of the drip ring. d) Laying, supporting, clamping of capillary tubes of diaphragm seal pressure gauge e) Installation with impulse piping arrangement with manifold (as applicable) as per approved hookup drawings f) Supply, stenciling and Installation of Tag plate for instrument as per Installation standard g) If required during installation of gauges, making temporary supports / scaffolding etc. is in contractors(bidder) scope of work. h) Any other work not specified above but however required for installation of pressure gauges are also in contractor's(bidder) scope of work. i) Free issue to contractor :- Supply of Pressure gauges with diaphragm seal, Drip ring & its accessories like Nuts,bolts,gaskets ,hook up materials,tray for capillary routing etc,
INSTALLATION OF PRESSURE TRANSMITTER / DIFF. PRESSURE TRANSMITTERS WITHOUT DIAPHRAGM SEAL (SMART / CONVENTIONAL TYPE & EX PROOF / IS)
Scope of work includes taking delivery from warehouse or from the places of storage, on site transportation, handling, storage, unpacking etc. The activity includes following operations: a) Fixing of the transmitter on the mounting stand/stanchion. b) Installation & connection of valve manifold (2-way, 3-way or 5-way as the case may be) to the transmitter and to the impulse line/process line. c) Cleaning, Flushing and Hydraulic test of the impulse line for the transmitter.Payment for the same is covered in Fabrication and installation of Impulse Pipes. d) Installation with impulse piping arrangement with manifold (as applicable) as per approved hookup drawings e) Supply and Installation of Tag plate(Stenciling) for instrument as per Installation standard f) Unused entries to be plugged g) If required during installation of transmitter, making temporary supports / scaffolding etc. is in contractors(bidder) scope of work. h) Any other work not specified above but required for installation of transmitter is also in contractor's(bidder) scope of work. i) Free Issue to contractor :- Supply of Pressure & diff pressure transmitters, valve manifolds, cables, tray , glands , Hook-up materials etc.
INSTALLATION OF PRESSURE TRANSMITTER / DIFF. PRESSURE TRANSMITTERS WITH DIAPHRAGM SEAL (SMART / CONVENTIONAL TYPE & EX PROOF / IS)
Scope of work includes taking delivery from warehouse or from the places of storage, on site transportation, handling, storage, unpacking etc. The activity includes following operations: a) Pressure & Diff Pressure Transmitters are supplied with :- i) Flanged diaphragm seal of various sizes & pressure rating, ii) Drip ring of various sizes. b) Fixing of the transmitter on the mounting stand/ stanchion as per Hook up drawings c) Installation, bolting & tightening of flanged diaphragm seal along with drip ring on the flanged nozzle (of vessel or on process line). Isolation valves shall be installed on the flushing ports of the drip ring. d) Laying, supporting, clamping of capillary tubes of diaphragm seal transmitter. e) Installation with impulse piping arrangement with manifold (as applicable). f) Supply, stenciling and Installation of Tag plate for instrument as per Installation standard g) If required during installation of transmitter, making temporary supports / scaffolding etc. is in contractors scope of work. h) Any other work not specified above but required for installation of transmitter is also in contractor's scope of work. i) Free Issue to contractor :- Supply of Pressure & diff pressure transmitters with diaphragm seal , Drip ring & its accessories like Nuts,bolts,gaskets , isolation valves, cables , tray , glands , Hook-up materials, tray for capillary routing etc.,
Clamp Assembly for High Pressure Hub connection, 2500# a) scope of work same as 1.5.1 b) Free Issue to contractor :- Supply of Pressure & diff pressure transmitters with diaphragm seal , Drip ring & its accessories like clamp assembly, Hub, seal ring and bolts & nuts, isolation valves, cables , tray , glands , Hook-up materials, tray for capillary routing etc.,
INSTALLATION OF LEVEL INSTRUMENTS
INSTALLATION OF EXTERNAL CAGE TYPE / TOP MOUNTED TYPE GUIDED WAVE RADAR LEVEL TRANSMITTER , (SMART / CONVENTIONAL TYPE & EX-PROOF/ IS)
Scope of work includes taking delivery from warehouse or from the places of storage, on site transportation, handling, storage, unpacking etc. a) Installation, bolting & tightening of flanged level transmitter with external chamber ( various center to center distance & pressure rating) on the vessel or on the stand pipe as the case may be and the installation, bolting & tightening of flange in case of top mounted GWR on the vessels.. b) Installation of drain & vent valves on the level transmitter. c) Interconnection of level transmitter to the vessel or to the stand pipe along with isolation valves. d) Drain & vent valves shall be connected to drain & vent lines. e) Installation of GWR probe/ transmitter directly on vessel (Internal mounting) or on external chamber/ cage (External mounting) f) Installation of chamber/cage (for external mounted Instruments) h) Supply, stenciling and Installation of Tag plate for instrument i) Installation of full bore isolation valve for non-contact type radar transmitter j) If required during installation of level instrument making temporary supports / scaffolding etc. is in contractors scope of work. k) Any other work not specified above but required for installation of level transmitter is also in contractor's(bidder) scope of work. l) Installation with impulse piping arrangement with manifold (as applicable) as per approved hookup drawings/level sketche. m) Free Issue to the contractor:- Supply of Level transmitter, isolation valves, drain & vent valves, cables, glands, trays , gaskets, studs & bolts etc
INSTALLATION OF LEVEL GAUGES (REFLEX, BI -COLOUR AND TRANSPARENT TYPE)
Scope of work includes taking delivery from warehouse or from the places of storage, on site transportation, handling, storage, unpacking etc. a) Installation, bolting & tighting offlanged level gauge (various center to center distance & pressure rating) on the vessel or on the stand pipe as the case may be. b) Installation of drain & vent valves on the level gauge. c) Interconnection of level gauge to the vessel or to the stand pipe alongwith isolation valves. d) Drain & vent valves shall be connected to drain & vent lines. e) If transparent level gauge illuminator is supplied loose, it should be assembled before installation & shall be connected to power supply cable. f) Any other accessory supplied for level gauge, it should also be installed and interconnected. g) If required during installation of level instrument making temporary supports / scafolding etc. is in contractors scope of work. h) Any other work not specified above but required for installation of level gauge is also in contractor's(bidder) scope of work. i) Inst. installation with fittings (as applicable) and arrangement shown as per approved hookup drawings/level sketches. j) Free Issue to the contractor:- Supply of Level gauges , drain & vent valve , cable glands,studs , nuts & gaskets etc.
INSTALLATION OF MAGNETIC LEVEL GAUGES
Scope of work includes taking delivery from warehouse or from the places of storage, on site transportation, handling, storage, unpacking etc. a) Installation, bolting & tightening of flanged level gauge (various center to center distance & pressure rating) on the vessel or on the stand pipe as the case may be. b) Installation of drain & vent valves on the level gauge. c) Interconnection of level gauge to the vessel or to the stand pipe along with isolation valves. d) Drain & vent valves shall be connected to drain & vent lines. e) In case level gauge body & float are supplied seperately or stoppers are provided for float ,Stoppers should removed & it should be assembled. f) On arrival of equipment, flange rating & centre to centre distance (C-C) to be verified by Contractor. g) Supply, stenciling and Installation of Tag plate for instrument as per Installation standard. h) If required during installation of level instrument making temporary supports / scaffolding etc. is in contractors scope of work. i) Any other work not specified above but required for installation of level gauge is also in contractor's(bidder) scope of work. j) Inst. installation with fittings (as applicable) and arrangement shown as per approved hookup drawings/level sketches. j) Free Issue to the contractor:- Supply of level gauge, drain & vent valve, gaskets, studs, nuts && gaskets etc.
INSTALLATION OF DIFF. PRESSURE TRANSMITTERS FOR LEVEL MEASUREMENT WITHOUT DIAPHRAGM SEAL (SMART / CONVENTIONAL TYPE & EX PROOF / IS)
Scope of work includes taking delivery from warehouse or from the places of storage, on site transportation, handling, storage, unpacking etc. The activity includes following operations: a) Fixing of the transmitter on the mounting stand/ stanchion. b) Installation & connection of valve manifold (2-way, 3-way or 5-way as the case may be) to the transmitter and to the impulse line/process line. c) Cleaning, Flushing and Hydraulic test of the impulse line for the transmitter. Payment for the same is covered in Fabrication and installation of Impulse Pipes. d) Supply, stenciling and Installation of Tag plate for instrument as per Installation standard e) Unused entries to be plugged f) Zero elevation and Zero supression (wherever applicable) shall be done by Contractor g) If required during installation of transmitter, making temporary supports / scaffolding etc. is in contractor's(bidder) scope of work. h) Any other work not specified above but required for installation of transmitter is also in contractor's(bidder) scope of work. i) Installation with impulse piping arrangement with manifold (as applicable) as per approved hookup drawings/level sketches. j) Free Issue to the contractor:- Supply of diff pressure level transmitters, valve manifolds, cable , tray , gland , hook-up materials etc.
INSTALLATION OF DP TRANSMITTER FOR LEVEL MEASUREMENT WITH DIAPHRAGM SEAL (SMART / CONVENTIONAL TYPE & EX PROOF / IS)
Scope of work includes taking delivery from warehouse or from the places of storage, on site transportation, handling, storage, unpacking etc. The activity includes following operations: a) DP level Transmitters are supplied with :- i) Flanged diaphragm seal of various sizes & pressure rating, ii) Drip ring of various sizes. b) Fixing of the transmitter on the mounting stand/ stanchion. c) Installation, bolting & tightening of flanged diaphragm seal along with drip ring on the flanged nozzle (of vessel or on process line). Isolation valves shall be installed on the flushing ports of the drip ring. d) Laying, supporting, clamping of capillary tubes of diaphragm seal transmitter. f) Supply, stenciling and Installation of Tag plate for instrument as per Installation standard g) Unused entries to be plugged h) Zero elevation and Zero supression (wherever applicable) shall be done by bidder. i) If required during installation of transmitter, making temporary supports / scaffolding etc. is in bidders scope of work. j) Any other work not specified above but required for installation of transmitter is also in bidder's scope of work. k) Installation with impulse piping arrangement with manifold (as applicable) as per approved hookup drawings/level sketches. l) Free Issue to the contractor:- Supply of diff pressure level transmitters with diaphragm seal , drip ring & its accessories like Nuts,bolts,gaskets , isolation valves, cables , tray , glands , Hook-up materials,tray for capillary routing etc
INSTALLATION OF DISPLACER TYPE LEVEL TRANSMITTER
Scope of work includes taking delivery from warehouse or from the places of storage, on site transportation, handling, storage, unpacking , calibration along with supply of consumables etc. The activity includes following operations: a) Installation of External Displacer type Level instruments with or without Controllers including installation of Instruments on nozzles b) Orientation of the head shall be checked and mounted by Contractor(bidder) after discussion with the EIC/Consultant/EPCM. c) Installation of primary piping, drain valve/ vent valve assembly as per standard and hydraulic testing of instrument d) Supply, stenciling and Installation of Tag plate for instrument as per Installation standard e) If required during installation of transmitter, making temporary supports / scaffolding etc. is in contractors(bidder) scope of work. f) Any other work not specified above but required for installation of transmitter is also in contractor's(bidder) scope of work. g) Inst. installation with fittings (as applicable) and arrangement shown as per approved hookup drawings/level sketches. h) Free Issue to contractor :- Supply of displacer level transmitter, cables , tray , glands , Hook-up materials etc
INSTALLATION OF NUCLEAR LEVEL TRANSMITTER
Scope of work includes taking delivery from warehouse or from the places of storage, on site transportation, handling, storage, unpacking etc. The activity includes following operations: a) Installation of Nucleonic Level Transmitter and Receiver with its mounting bracket on the vessel under supervision of Instrument vendor. Mounting bracket to be welded to lug on the vessel as required. Scope also includes the connection of instrument air/ cooling water to the level transmitter. c) If required during installation of level instrument making temporary supports / scaffolding etc. is in contractors scope of work. d) Any other work not specified above but required for installation of level transmitter is also in contractor's(bidder) scope of work. e) Free Issue to the contractor:- Nucleonic Level Transmitter and Receiver, cable glands etc.
INSTALLATION OF TUNNING FORK LEVEL SWITCH
Scope of work includes taking delivery from warehouse or from the places of storage, on site transportation, handling, storage, unpacking etc. a) Installation, bolting & tightening of flanged level switch on the vessel. b) Interconnection of level switch to the vessel or to the stand pipe along with isolation valves. c) If required during installation of level instrument making temporary supports / scaffolding etc. is in contractor's(bidder) scope of work. d) Any other work not specified above but required for installation of level switch is also in contractor's(bidder) scope of work. e) Supply, stenciling and Installation of Tag plate for instrument as per Installation standard. f) Inst. installation with fittings (as applicable) and arrangement shown as per approved hookup drawings/level sketches. g) Free Issue to the contractor:- Supply of Level Switch, cable glands, gaskets, studs & bolts etc.
TEMPERATURE INSTRUMENTS
INSTALLATION OF TEMPERATURE ELEMENTS WITH THERMOWELL (THERMOCOUPLES OR RTDS) & TEST THERMOWELLS
Scope of work includes taking delivery from warehouse or from the places of storage, on site transportation, handling, storage, unpacking etc. The activity includes following operations: a) Contractor(bidder) shall check intergrity of the element & shall also check that temperature element confirm to the specification. b) Generally temperature element is mounted in flanged thermowell & supplied together. If temperature element & thermowell are supplied seperately, contractor(bidder) shall assemble both the pieces. (Temperature element & thermowell are of various immersion length & pressure ratings) c) Tempearture elements to be installed on the vessel, contractor(bidder) shall agree to installation procedure with EIC/Consultant/EPCM. d) Install temperature element on the process lines / vessel & tighten studs & nuts. Temperature elements to be installed on vessels, contractor shall check that temperature elements are correctly installed & does not interfere with the vessel internals. e) Unused entries to be plugged. f) Supply, stenciling and Installation of Tag plate for instrument as per Installation standard. g) If required during installation of temperature instrument making temporary supports / scaffolding etc. is in contractors scope of work. h) Any other work not specified above but required for installation of temperature element is also in contractor's(bidder) scope of work. i) Free Issue to contractor :- Supply of Temperature elements & thermowells, tray, glands, gaskets, studs & nuts.
INSTALLATION OF DUAL TEMPERATURE ELEMENTS WITH THERMOWELL
Scope of work includes taking delivery from warehouse or from the places of storage, on site transportation, handling, storage, unpacking etc. The activity includes following operations: a) Contractor(bidder) shall check intergrity of the element & shall also check that temperature element confirm to the specification. b) Generally temperature element is mounted in flanged thermowell & supplied together. If temperature element & thermowell are supplied seperatly, contractor shall assemble both the pieces. (Temperature element & thermowell are of various immersion length & pressure ratings) c) Tempearture elements to be installed on the vessel, contractor(bidder) shall agree to installation procedure with EIC/Consultant/EPCM. d) Install temperature element on the process lines / vessel & tighten studs & nuts. Temperature elements to be installed on vessels, contractor(bidder) shall check that temperature elements are correctly installed & does not interfere with the vessel internals. e) If required during installation of temperature instrument making temporary supports / scafolding etc. is in contractor's(bidder) scope of work. f) Any other work not specified above but required for installation of temperature element is also in contractor's(bidder) scope of work. g) Free Issue to contractor :- Supply of Dual Temperature elements & thermowells, cable gland, gaskets, studs& nuts.
INSTALLATION OF TEMPERATURE GAUGES WITH THERMOWELL (WITHOUT CAPILARY TUBE)
Scope of work includes taking delivery from warehouse or from the places of storage, on site transportation, handling, storage, unpacking etc. The activity includes following operations: a) Install temperature gauge thermowell along with temperature gauge on the process lines / vessel & tighten studs & nuts. b) Dial of temperature gauge shall be rotated to facilitate easy reading. c) Supply, stenciling and Installation of Tag plate for instrument as per Installation standard. d) If required during installation of temperature gauge, making temporary supports / scaffolding etc. is in contractor's(bidder) scope of work. e) Any other work not specified above but required for installation of temperature temperature gauge is also in contractor's(bidder) scope of work. f) Temperature gauges are of various immersion lengths & pressure rating. g) Free Issue to contractor :- Supply of Temperature gauges with Thermowell , gaskets, studs & nuts.
INSTALLATION OF TEMPERATURE GAUGES WITH THERMOWELL (Clamp Assembly for High Pressure Hub connection,2500#) a) Scope of work same as 3.3.1 b) Free Issue to contractor :- Supply of Temperature gauges with Thermowell , clamp assembly, Hub, seal ring and bolts & nuts.
INSTALLATION OF TEMPERATURE GAUGES (SKIN TYPE)
Scope of work includes taking delivery from warehouse or from the places of storage, on site transportation, handling, storage, unpacking etc. The activity includes following operations: a) Fixing of skin Temperature gauge to the equipment and in case of piping installation, welding of weld pad on pipe and installation of skin temperature gauge in the weld pad. b) If required during installation of skin temperature gauge, making temporary supports / scaffolding etc. is in contractor's(bidder) scope of work. c) Any other work not specified above but required for installation of skin temperature gauge is also in contractor's(bidder) scope of work. d) Free Issue to contractor :- Supply of skin temperature gauge, weld pad.
INSTALLATION OF TEMPERATURE TRANSMITTERS (SMART)
INSTALLATION OF SKIN TEMPERATURE ELEMENTS (THERMOCOUPLES OR RTDS)
Scope of work includes taking delivery from warehouse or from the places of storage, on site transportation, handling, storage, unpacking etc. The activity includes following operations: a) Fixing of skin thermocouple/RTD to the equipment and in case of piping installation, welding of weld pad on pipe and installation of skin thermocouple in the weld pad. b) If required during installation of skin thermo-couple/RTD, making temporary supports / scaffolding etc. is in contractor's(bidder) scope of work. c) Any other work not specified above but required for installation of skin thermocouple/RTD is also in contractor's(bidder) scope of work. d) Free Issue to contractor :- Supply of skin thermocouple/RTD, weld pad, cable glands etc.
FLOW INSTRUMENTS
INSTALLATION OF CORIOLIS FLOW METER
Coriolis Flow meter (jacketed/ non- jacketed) is to be installed on the process line and flow transmitter to be installed on pre- fabricated stanchion . The activity includes following works: a) Scope of work includes taking delivery from warehouse or from the places of storage, on site transportation, handling, storage, unpacking etc. b) Coriolis Flow meter to be supplied by Manufacturer along with Sensor, Transmitter, cables from Sensor to transmitter. c) Installation of flowmeter in the process line, bolting and other similar activities and installtion of transmitter on pre-fabricated stand/ stanchion. d) Co-ordinating with the mechanical subcontractor for providing the exact flange to flange dimensions in the pipeline for mounting the Flow meter.
e) Scope includes cabling from Flow sensor to Transmitter as per Manfacturer requirement / approved vendor drawing/ installation manual. Connection of the transmitter to the signal cable , Connection of power cable to the transmitter including instrument earthing. f) Contractor(bidder) shall provide technical assistance to the manufacturer specialist for calibration, start-up & commissioning. g) Supply, stenciling and Installation of Tag plate for instrument as per Installation standard. h) Unused entries to be plugged. i) If required during installation of Coriolis Flow meter, making temporary supports / scaffolding etc. is in contractors scope of work. j) Any other work not specified above but required for of installation of Coriolis flowmeter assembly in the process line is also in contractor's(bidder) scope. k) Free Issue to contractor :- Coriolis flow meter along with transmitter, cable glands , studs & nuts, gaskets, cables/special cables, trays etc.
Line Size/ Pressure Rating -8" / ANSI 150# : Material of construction of process line ASTM - A106 Gr.B
Line Size/ Pressure Rating -3" / ANSI 300# : Material of construction of process line ASTM - A106 Gr.B
Line Size/ Pressure Rating -6" / ANSI 300# : Material of construction of process line ASTM - A106 Gr.B
Line Size/ Pressure Rating -10" / ANSI 300# : Material of construction of process line ASTM - A106 Gr.B
INSTALLATION OF ULTRASONIC FLOW METER
Ultrasonic flowmeter is to be installed on the process line and flare line. The activity includes following works: a) Scope of work includes taking delivery from warehouse or from the places of storage, on site transportation, handling, storage, unpacking etc. b) Ultrasonic flowmeter is supplied along with set of sensor & receiver units, electronic control unit, flanged nozzles for installation of sensor & receiver units, retractable mechanism (complete with flanged ball valves) & set of interconnecting cables & other accessories. c) Installation of Ultrasonic flow meters including mounting of the instrument of different sizes in pipeline located at different elevations, co-ordinating with the mechanical contractor(bidder) for providing the exact flange to flange dimensions in the pipeline for mounting the Flow meter. d) Check the alignment of pipeline for mounting the flowmeter. e) Check whether proper supports are provided on the upstream & downstream pipeline and whether the provided supports are adequate for holding the meter in pipeline. f) Check the proper flow directions. g) Scope of work includes drilling of pipe, welding of flanged nozzles on the process line. Fixing , alignment, bolting of the retractrable mechanism along with sensor / receiver units on the flanged nozzle. h) Fixing of the electronic control unit on the pre- fabricated mounting stand/ stanchion. i) Supply, stenciling and Installation of Tag plate for instrument as per Installation standard. j) Unused entries to be plugged.
k) For clamp-on type Ultrasonic flow meter in Flare , Contractor(bidder) shall co-ordinate with manufacturer for installation until performance requirement is met. l) If required during installation of flow instrument making temporary supports / scaffolding etc. is in contractor's(bidder) scope of work. m) Any other work not specified above but required for installation of ultrasonic flowmeter on the process line is also in contractor's(bidder) scope. n) Laying, support & clamping of interconnecting cables between sensor-receiver units & to the electronic control unit. o) Connection of power & signal cables to the electronic control unit including instrument earthing. p) Contractor(bidder) shall provide technical assistance to the manufacturer specialist for calibration, start-up & commissioning. q) Free Issue to contractor :- Supply of ultrasonic flow meter, retractable assembly, flanged ball valves, flanged nozzles, sensor receiver units, electronic control unit, interconnecting cables, trays , cable glands studs & nuts, gaskets etc.
Line Size/ Pressure Rating - 36" / ANSI 150# : Material of Construction of Process Line - ASTM A 106 Gr.B
Line Size/ Pressure Rating - 12" / ANSI 300# : Material of Construction of Process Line - ASTM A 106 Gr.B
INSTALLATION OF ULTRASONIC FLOW METER (Clamp-on) Scope of work defined at Serial No. 4.4
Line Size- 2"
Line Size - 3"
Line Size - 4"
Line Size - 6"
Line Size - 8"
Line Size - 10"
Line Size - 12"
INSTALLATION OF ELECTROMAGNETIC FLOW METER
Electromagnetic flow meter is to be installed on the process line and flow transmitter to be installed on stanchion in case of remote type. The activity includes following works: a) Scope of work includes taking delivery of magnetic flow meter from warehouse or from the places of storage, on site transportation, handling, storage, unpacking etc. b) Installation of electromagnetic flow meters of different sizes including mounting of instrument in pipeline located at different elevations, coordinating with the mechanical subcontractor for providing the exact flange to flange dimensions in the pipeline for mounting the flowmeter. c) Checking the alignment of pipeline for mounting the flowmeter. d) Checking whether proper supports are provided on the upstream & downstream pipeline and whether the provided supports are adequate for holding the meter in pipeline. e) Installing the grounding rings. f) Checking the proper flow directions connecting the earth wires from grounding rings to the nearest earth pit including supply of required length of G.I earth wires. g) Connection of grounding cable from grounding rings to transmitter head.
h) Installation of flow meter is covered in Mechanical & Piping Contractor's scope however, Mechanical efforts and material handling equipment , if required shall be arranged by Instrumentation Contractor(bidder). i) Unused entries to be plugged. j) If required during installation of flow instrument making temporary supports / scaffolding etc. is in subcontractors scope of work. k) Supply, stenciling and Installation of Tag plate for instrument as per Installation standard. l) Any other work not specified above but required for of installation of magnetic flowmeter on the process line is also in subcontractor's scope. m) Connecting the earth wires from grounding rings to the nearest earth pit including supply of required length of earth wires. n) Connection of power & signal cables to the electronic unit including instrument earthing. o) Connection of grounding cable from grounding rings to transmitter head. p) Free Issue to contractor :- Supply of magnetic flow meter, cables, trays, cable glands etc.
Line Size/ Pressure Rating -3" / ANSI 150# : Material of construction of process line CPVC+CS
Line Size/ Pressure Rating -4" / ANSI 150# : Material of construction of process line CS
Line Size/ Pressure Rating -26" / ANSI 150# : Material of construction of process line CS
Line Size/ Pressure Rating -28" / ANSI 150# : Material of construction of process line CS
Line Size/ Pressure Rating -40" / ANSI 150# : Material of construction of process line CS
INSTALLATION OF DIFF. PRESSURE TRANSMITTERS FOR FLOW MEASUREMENT WITHOUT DIAPHRAGM SEAL (SMART / CONVENTIONAL TYPE & EX PROOF / IS)
Scope of work includes taking delivery from warehouse or from the places of storage, on site transportation, handling, storage, unpacking etc. The activity includes following operations: a) Fixing of the transmitter on the mounting stand/ stanchion. b) Installation & connection of valve manifold (2-way, 3-way or 5-way as the case may be) to the transmitter and to the impulse line/process line/impulse pipe (upto the oval flange). c) Cleaning, Flushing and Hydraulic test of the impulse line for the transmitter. Payment for the same is covered in Fabrication and installation of Impulse Pipes. e) Supply, stenciling and Installation of Tag plate for instrument as per Installation standard. f) Unused entries to be plugged. g) If required during installation of transmitter, making temporary supports / scaffolding etc. is in contractor's (bidder) scope of work. h) Any other work not specified above but required for installation of transmitter is also in contractor's (bidder) scope of work. i) Installation with impulse piping arrangement with manifold (as applicable) as per approved hookup drawings. j) Free Issue to the contractor:- Supply of diff pressure flow transmitters, valve manifolds, trays, hook-up material etc.
INSTALLATION OF DIFF. PRESSURE TRANSMITTERS FOR FLOW MEASUREMENT WITH DIAPHRAGM SEAL (SMART / CONVENTIONAL TYPE & EX PROOF / IS)
Scope of work includes taking delivery from warehouse or from the places of storage, on site transportation, handling, storage, unpacking etc. The activity includes following operations: a) DP Flow Transmitters are supplied with :- i) Flanged diaphragm seal of various sizes & pressure rating, ii) Drip ring of various sizes. b) Fixing of the transmitter on the mounting stand/ stanchion. c) Installation, bolting & tightening of flanged diaphragm seal along with drip ring on the flanged nozzle (of vessel or on process line). Isolation valves shall be installed on the flushing ports of the drip ring. d) Laying, supporting, clamping of capillary tubes of diaphragm seal transmitter. e) Cleaning, Flushing and Hydraulic test of the impulse line for the transmitter. Payment for the same is covered in Fabrication and installation of Impulse Pipes. f) Laying of impluse capillary line from diaphragm seal to transmitter. g) If required during installation of transmitter, making temporary supports / scaffolding etc. is in contractor's(bidder) scope of work. h) Supply, stenciling and Installation of Tag plate for instrument as per Installation standard i) Any other work not specified above but required for installation of transmitter is also in contractor's(bidder) scope of work. j) Installation with impulse piping arrangement with manifold (as applicable) as per approved hookup drawings. k) Free Issue to the contractor:- Supply of diff pressure flow transmitters with diaphragm seal , drip ring and its accessories like nuts , bolts & gaskets,isolation valves, cables , trays , glands , Hook-up materials,tray for capillary routing etc .,
INSTALLATION OF DIFF. PRESSURE TRANSMITTERS FOR FLOW MEASUREMENT WITH DIAPHRAGM SEAL (SMART / CONVENTIONAL TYPE & EX PROOF / IS) for Clamp Assembly for High Pressure Hub connection,2500# a) Scope of work same as 4.5.1 b) Free Issue to the contractor:- Supply of diff pressure flow transmitters with diaphragm seal , drip ring and its accessories like clamp assembly, Hub, seal ring and bolts & nuts,isolation valves, cables , trays , glands , Hook-up materials,tray for capillary routing etc.
INSTALLATION OF ROTAMETER (VARIOUS SIZES AND PRESSURE RATING)
Rotameter of upto 2" size and Pressure Ratings 150# are to be installed between the piping flanges. Installation activity includes following works.Size, rating and specification details shall be shared later a) Scope of work includes taking delivery of rotameter from warehouse or from the places of storage, on site transportation, handling, storage, unpacking etc. b) Installation of the Rotameters of upto 2" size in line including mounting of the instrument in line located at different elevations, coordinating with the mechanical contractor for providing the exact flange to flange dimensions in the pipeline for mounting the meter. c) Check the alignment of pipeline for mounting the meter. d) Installation & Fixing rotameter in the process line, bolting and other similar activities. e) Supply, stenciling and Installation of Tag plate for instrument as per Installation standard f) If required during installation of flow instrument making temporary supports / scaffolding etc. is in contractor's(bidder) scope of work. g) Any other work not specified above but required for of installation of rotameter in the process line is also in contractor's(bidder) scope. h) Free Issue to contractor :- Rotameter, gaskets, nuts & studs.
INSTALLATION OF VENTURI METER
Scope of work includes taking delivery of venturi meter from warehouse or from the places of storage, on site transportation, handling, storage, unpacking etc. a) Installation of the venturi meter (various size) along with the flange assembly (various sizes & pressure rating) in the process line, bolting of gaskets and other similar activities. b) Supply, stenciling and Installation of Tag plate for instrument as per Installation standard c) If required during installation of venturi , making temporary supports / scaffolding etc. is in contractor's (bidder) scope of work. d) Any other work not specified above but required for installation venturi in the line is also in contractor's (bidder) scope of work. e) Free Issue to contractor :- Supply of venturi, gaskets, nuts & studs.
Line Size/ Pressure Rating - 4" / ANSI 300#
Line Size/ Pressure Rating - 6" / ANSI 300#
Line Size/ Pressure Rating - 8" / ANSI 300#
Line Size/ Pressure Rating - 12" / ANSI 300#
Line Size/ Pressure Rating - 16" / ANSI 300#
Line Size/ Pressure Rating - 18" / ANSI 300#
Line Size/ Pressure Rating - 10" / ANSI 1500#
Line Size/ Pressure Rating - 4" / ANSI 2500# (Clamp Assembly for High Pressure Hub connection)
Line Size/ Pressure Rating - 8" / ANSI 2500# (Clamp Assembly for High Pressure Hub connection)
INSTALLATION OF FLOW NOZZLE Scope of work includes taking delivery of flow nozzle from warehouse or from the places of storage, on site transportation, handling, storage, unpacking etc. a) Installation of the venturi meter (various size) in the process line, bolting of gaskets and other similar activities. b) Supply, stenciling and Installation of Tag plate for instrument as per Installation standard c) If required during installation of venturi , making temporary supports / scaffolding etc. is in contractor's (bidder) scope of work. d) Any other work not specified above but required for installation venturi in the line is also in contractor's (bidder) scope of work. e) Free Issue to contractor :- Supply of Flow nozzle, gaskets, nuts & studs.
Line Size/ Pressure Rating - 3" / ANSI 600#
Line Size/ Pressure Rating - 4" / ANSI 600#
Line Size/ Pressure Rating - 6" / ANSI 600#
Line Size/ Pressure Rating - 8" / ANSI 600#
INSTALLATION OF LOCAL INDICATORS (SMART / CONVENTIONAL,TYPE & EX PROOF / IS )
Scope of work includes taking delivery from warehouse or from the places of storage, on site transportation, handling, storage, unpacking etc. The activity includes following operations: a) Installation and Fixing of the local indicator on the pre-fabricated mounting stand/ stanchion b) If required during installation of local indicator, making temporary supports / scaffolding etc. is in contractors scope of work. c) Supply, stenciling and Installation of Tag plate for instrument as per Installation standard. d) Any other work not specified above but required for installation of local indicator is also in contractor's (bidder) scope of work. e) Free Issue to the contractor:- Local indicator.
SUPPLY AND INSTALLATION OF CONDENSATE POT
Scope of work includes supply, transportation to site, erection, handling, storage, unpacking etc. The activity includes following operation: a) Contractor(bidder) shall study optimal routing from the process connection up to the instrument as per process hook up drawing provided by the Technip Energies. b) Contractor(bidder) shall supply the material as per approved vendor list. c) Contractor(bidder) shall submit the mill test certificates complying to EN 10204 type 3.1 for all pressure parts.
3" Pot with, 1/2"x1/2"x1/2", SW, 6000#, ASTM A105N (IBR)
Supply & Erection
3" Pot with, 3/4"x3/4"x3/4", SW, 6000#, ASTM A105N (IBR)
Supply & Erection
3" Pot with, 3/4"x3/4"x3/4", SW, 6000#, ASTM A182 Gr.F11 Cl.2 (IBR)
Supply & Erection
3" Pot with, 1"x1"x1", BW, 6000#, ASTM A105N(IBR)
Supply & Erection
ANALYSER SHELTER AND FIELD MOUNTED ANALYZERS
INSTALLATION OF PREFABRICATED ANALYSER SHELTER WITH ANALYSERS AND FIELD MOUNTED ANALYZERS
The listed below following activities are to be performed by erection contractor(bidder) under Supervision of analyser Vendor. Supervision of Erection/Installation by analyser Vendor. a) Taking delivery from warehouse or from the places of storage, handling, unpacking, on site transportation of shleter upto concrete base (provided by others on the site). Scope also includes the transpotation of all loose supplied items from warehouse or place of storage to the site location. b) Installation of the shelter in the correct postion as per project layout drawing/ vendor drawing & fixing the shelter in postion with the anchor bolts & grouting (as applicable) on the concrete base .Contractor(bidder) shall do necessary chipping of pockets (if required). c) Installation & connection of the those items supplied loose (e.g. retractable sample probes, IJB skid, canopies, AC/HVAC Units with panels, sample tubing/piping between sample take-off probe and the SHS located on shelter, liquid validation tanks, sample recovery system, validation bottles, carrier and calibration gas & zero gas bottles/ cylinders with pre-fabricated rack with canopy ,eye wash, shelter ladder, fresh air duct supports, special tubing like EHT, Pre-Insulated, electropolished and sulfinert coated tubing with their accessories and seal kits, EHT JBs (in field as applicable), anchor bolts, grouting plates, fresh air ducts with bird mesh and LEL Gas detector box, chemical filter assembly, fast loop pump skids ducting between shelter & HVAC units ,gaskets, nuts bolts, etc supplied by analyser vendor). d) Installation of PSHS near tapping points etc. Fabrication of frames for mounting the PSHS and EHT JBs.
e) Study the shortest & optimal route for the sample lines/fast loop and utility lines.Installation of cable tray & tube trays between the sample probe and analyser shelter with supports on route, lay sample lines (EHT/Electropolished/Sulfinert Coated/ Pre-Insulated (pipes /tubes) & fast loops including accessories in accordance with the project drawings. f) Installation of HVAC units or AC supplied supplied loose, which shall be installed together with the air intake duct of the blower and interconnect blower/AC to the air suction duct of the shelter. g) Connection of the utilty headers at the tie-in point of the shelter. h) Signal & power cable supporting, laying, clamping & termination. i) Hydraulic test of sample lines & utility lines as per project requirement. j) Shelter & analyser junction boxes, IJBs, PDBs frames, etc., shall be grounded by means of connection to grouding network with single core copper wire according to the project drawing. k) Contractor(bidder) shall provide technical assisatnce to the analysers/NIR manufactutrer specialist wherever required for calibration, start up & pre-commissioning & commissioning activities during SAT (site acceptance Test) and model build up of analyser package. l) If required during installation, making temporary supports / scafolding etc. is in contractor's(bidder) scope of work. m) Supply & erection of pipes/tubes with required fittings between probe & Primeary/Secondary sample handling system, for fast loop returns of sample from SHS to any process lines,Sample Return Tubing / vent and drain tubing / Fast Loop tubing to Plant Vent / Flare from Analyzer Vent / Drain Header, calibration bottles and secondary sample handling system.Total 360 meters tube/pipe length considered between tapping points (for three analysers located inside shelter. For fast loop return common return line considered so another 120 meters added. Approx 20 meters tubing between SHS & Validation tanks/SRS/Vendor & drain headers. Total tube/piping to be considered for analyser package =500 meters (to be supplied and installed by site contractor(bidder).
n) Loop checking for analog, digital and serial communication signals between Analyzers ,shelters and customer DCS / PLC / ESD. o) Laying and termination of Signal, Power & Communication cables for field analysers,analyser shelters, fast loop pump skids, liquid recovery system skid, IJB skid, Carrier gas rack, HVAC units, sample probe, EHT Jbs etc. p)Laying & termination of Serial communication cables between the Analyzes(located in field cabinets) to Anlyser Shelter. Also laying and termination of the serial communication cables between analyser shelter and DCS in control room. q) Laying & supply of GI cable trays for sample tubing between Analyzer Shelter / Field analyser cabinet and Sample Take-off point / Return point. r) Laying & supply of GI cable trays for Instrumentation signal cables, UPS power cables, serial communication cables between Analyzer Shelter / Field analyser cabinet and Sample Take-off point, Fast loop pump skids, Liquid recovery system skids, HVAC units and Control Room. s) Any other work not specified above but required for of installation of analyser and analyser shelter is also in contractor's scope of work. t) Exclusion in Contractor's (bidder)scope:- Supply of Analyser shelter with canopy, Analyser, retractable sample probes, analyser control unit / transmitter, Safeguarding PLC, HVAC Units with panels, SHS (primary & secondary), PDBs, JBs, F&G detectors, liquid validation tanks, validation bottles, sample recovery system, calibration, carrier gas & zero gas bottles with pre-fabricated rack with canopy ,eye wash, anchor bolts, grouting plates, fresh air ducts, fast loop pump skids ,gaskets, nuts bolts, & accessories etc.
Field Mounted Analyzers
Scope of work includes taking delivery from warehouse or from the places of storage, on site transportation, handling, storage, unpacking etc. The activity includes following operations: a) Installation of field mounted analysers with analyser racks/field mounted cabinets with utility connections,purging & cooling arrangements for the field mounted cabinet, cable for interfacing with CPCB & PCBA interface (as per approved specification/ design basis), and installation of cables from field mounted analyser cabinet to SRR and further to ADAS in Main control room (as per approved specification/ design basis), inspection, testing, Calibration and commisioning. b) Special tools etc shall be in the scope of contractor(bidder). c) Fabrication of Support steel, installation and painting of all supports required. d) Analyzer panel/rack installation. e) Fabrication, installation and painting of protection shelter, if required. f) Installations and connection to the process of sampling and conditioning systems. g) Installation and connection of pneumatic and/or electronic signals to/from analyzers. h) Installation of sample conditioning system and cylinders.Analyser cabinet installation shall be in Contractor's(bidder) scope. i) Execution connections. j) Supply, stenciling and Installation of Tag plate for instrument as per Installation standard. k) Any other work not specified above but required for of installation of Analyzers is also in contractor's (bidder) scope of work. l) Any activity not specified above but required for the installation shall be in the scope of contractor(bidder). m) Installation of Canopies for Analyser cabinet shall be in the scope of contractor(bidder). n) Free Issue to the contractor:- Analysers , Analyser cabinet etc.,
Analyzer Transmitter/detector (Density - Nuclear) Scope of work includes taking delivery from warehouse or from the places of storage, on site transportation, handling, storage, unpacking etc. The activity includes following operations: a) Installation of Nucleonic internal source with its source holder and well divider and detector with its mounting bracket on the vessel under supervision of Instrument vendor. Mounting bracket to be welded to lug on the vessel as required. Scope also includes the connection of instrument air to the transmitter. Scope also includes the connection of instrument air/ cooling water to the level transmitter. b) If required during installation of level instrument making temporary supports / scaffolding etc. is in contractor's(bidder) scope of work. c) Any other work not specified above but required for installation of level transmitter is also in contractor's (bidder) scope of work. d) Free Issue to the contractor:- Supply of Nucleonic Transmitter and Receiver, cable glands etc.
Analyzer Transmitter/detector (Density - Nuclear)
Analyzer Sensor/source (Density - Nuclear)
INSTALLATION OF GAS DETECTOR/ FLAME DETECTOR/ BEACONS/ HOOTERS
H2 Detectors In field Scope of work includes taking delivery from warehouse or from the places of storage, on site transportation, handling, storage, unpacking etc. The activity includes following operations: a) Installation & Fixing of the detector on the mounting stand as per installation manual provided by detector vendor. b) Installation of canopy which is supplied by Detector vendor. c) Installation of detector on the supports d) Installation of fire alarm modules , barriers (for IS devices) inside Junction box and connection of non-addressable devices to barriers & modules upto Fire alarm panel. e) Supply, stenciling and Installation of Tag plate for instrument as per Installation standard f) If required during installation of gas detector, making temporary supports / scaffolding etc. is in contractor's (bidder) scope of work. g) Any other work not specified above but required for installation of transmitter is also in contractor's (bidder) scope of work h) Free Issue to contractor: Supply of Detector , Canopies, etc.
H2S Detectors in field Installation of gas detector as per scope of work defined at serial no 7.1
H2S Detectors in Duct a) Installation and Fixing of the detector on the duct as per installation manual provided by detector vendor. b) Supply, stenciling and Installation of Tag plate for instrument as per Installation standard c) If required during installation of gas detector, making temporary supports / scaffolding etc. is in contractor's (bidder) scope of work. d) Any other work not specified above but required for installation of transmitter is also in contractor's (bidder) scope of work e) Free Issue to contractor: Supply of Detector , duct mount kit , Calibration kit
Hydrocarbon Detectors in Field Installation of gas detector as per scope of work defined at serial no 7.1
Hydrocarbon Detectors in Duct Installation of gas detector as per scope of work defined at serial no 7.3
UV/IR Flame Detector Installation of Flame detector as per scope of work defined at serial no 7.1
Flame (H2) detectors Installation of Flame detector as per scope of work defined at serial no 7.1
HC Detectors (LOS)-Transmitter / Receiver Installation of Flame (H2) detector as per scope of work defined at serial no 7.1
Hooters (in field) Installation of Hooter as per scope of work defined at serial no 7.1
Beacon (in field) Installation of Beacon as per scope of work defined at serial no 7.1
INSTALLATION OF CCTV, PA, FCS, TELEPHONE IN FIELD AND BUILDINGS
Scope of work includes taking delivery from warehouse or from the places of storage, on site transportation, handling, storage, unpacking etc. The activity includes following operations: a) Installation of Telephone/Acoustic booth/Visual light/Sounder/Loudspeaker/Field call station/Flashing Beacons/Speaker/Network switches etc. for safe area (including Junction box) on the supports & all associated accessories for telecom system. b) Installation of Telecom Equipment / cabinets, instrument & all associated accessories for telecom system. c) Equipment erection, alignment and fixing. d) Installation of canopy which is supplied by vendor. e) Cable trays/conduits installation from devices to junction box and Junction box to cabinet. f) Signal and Power Cables installation for connection of devices up to the junction box and Junction box to cabinet including Gland installation. g) Grounding of the devices and its supports as required. h) Supply, stenciling and Installation of Tag plate for devices as per Installation standard. i) Loop check and Cable testing like megger, continuity test, etc... j) FO cable splicing, termination & testing, under supervision of vendor. k) Structured cabling shall be terminated & tested by Certified technician, under supervision of vendor shall be of contractor's(bidder) scope. Test report shall be generated in pdf format. l) If required during installation of devices, making temporary supports / scaffolding etc. is in contractor's(bidder) scope of work. m) Any other work not specified above but required for installation of devices is also in contractor's (bidder) scope of work. n) Free Issue to contractor: Supply of Telephone, Acoustic booth, Visual light, Sounder, Loudspeaker, Field call station, Flashing Beacons, Speaker for safe area (including Junction box), cable, glands, tray, Canopies, etc.,
INSTALLATION OF CCTV CAMERA (EX. PROOF ) - PTZ CAMERA IN FIELD
This item refers to the installation of CCTV system, each CCTV system consists of CCTV cameras, CCTV system cabinet, Poles for mounting CCTV camera, Junction boxes, CCTV Monitors & interconnecting cables etc. Scope of work includes taking delivery of CCTV system hardware from warehouse or from the place of storage, on-site transportation, handling, storage, unpacking etc. Pole and Cabling Works for Installation of CCTV systems shall be paid separately as per respective items.
Ex Proof CCTV camera along with the accessories such as wiper assembly, Pan & tilt assembly etc., (To be Installed in the field at various locations) CCTV Cameras with Ex proof enclosure and wiper assembly:- The installation work includes following activity a) Collection of CCTV camera along with accessories from warehouse, on site transportation, verify quantity & status of CCTV cameras and its accessories. b) Prefabrication & installation of the supports. These supports shall be welded or bolted to the structures, for fixing supports on concrete structure HILTI I Anchor's shall be used. Supports shall be painted. c) Supply and installation of poles for mounting the CCTV camera is in Contractor's (bidder)scope. d) Installation & fixing of CCTV cameras along with the accessories (such as wiper assembly, pan & tilt assembly, water unit assembly etc.,).Installation will be as per vendor drawing. e) Connection of the cooling water line to the CCTV camera wiper assembly. f) Installation of washer unit tubing assembly shall be in Contractor's(bidder) scope. Supply and installation of the washer unit stanchion/stand shall be in Contractor's(bidder) scope. g) Connection of the power supply cable and control cable to the CCTV camera. h) Installation & testing of camera shall be done under supervision of CCTV vendor and contactor(bidder) to provide all the required assistance.. i) Installation of Ex proof junction box with canopy which is supplied by CCTV vendor in which receiver and encoder units are installed on the prefabricated mounting stand.
j) CCTV system cabinets and monitors are to be installed at various control room as indicated above. k) Laying, Supporting and clamping of all types of cables (power supply, signal, Video cables, VGA cables and communication cables) termination and testing shall be done under supervision of CCTV system vendor specialist. l) FO cable splicing and termination under supervision of vendor shall be in contractor's(bidder) scope. m) FO cable conduit shall be supplied and installed by Contractor(bidder). n) If required during installation of poles for CCTV camera, making temporary supports / scaffolding etc. is in Subcontractors scope of work.. o) Any other activity not indicated above and required for the completion of installation of CCTV system shall be under contractor's scope of work. p) Temporary protection to be provided. q) Free issue to Contractor - CCTV camera + wiper unit , cables , junction box, glands , trays , washer unit assembly, other mounting accessories etc.
INSTALLATION OF CCTV CABINET
Installation of CCTV Cabinet as per scope of work defined at serial no.8.1.1
INSTALLATION OF CCTV JUNCTION BOX
Installation of CCTV junction boxes for receiver / power supply distribution to Cameras at field as per scope of work defined at serial no.8.1.1
INSTALLATION OF IMPULSE PIPES, FITTINGS AND VALVES
j) If required during laying of impulse lines, making temporary supports / scafolding etc. is in contractors scope of work. k) Sealing of all threaded joints using suitable sealants and/ or by seal welding as specified in hook-up drawing. Any other work not specified above but required for laying of impulse pipe (manifold) is also in contractor's(bidder) scope of work. l) Hook-ups shall be fabricated and installed strictly as per project hook-up drawings maintaining required slope from tapping point. Also, Scope includes the erection of any hook- up , loose supplied by package vendor as per the hook- up drawing supplied by package vendor. For package loose supplied Hook Up Material, Unit rate of erection is applicable. m) Supply of Pipe/ Tube thread sealants suitable for process conditions shall be in the scope of Contractor(bidder).
IMPULSE PIPING & FITTING (1/2")-WELDED JOINTS
Carbon Steel (CS)
Carbon Steel (CS) (H2)
Carbon Steel (CS) (NACE)
Carbon Steel (CS) (NACE+H2)
Carbon Steel (CS) (IBR)
Alloy steel 1.25 Cr - 0.5 Mo (NACE)
Alloy steel 1.25 Cr - 0.5 Mo (NACE+H2)
Alloy steel 1.25 Cr - 0.5 Mo (IBR)
Alloy steel 9 Cr - 1 Mo (NACE)
Alloy steel 9 Cr - 1 Mo
Nickel Alloy UNS N10276 (NACE)
Nickel Alloy UNS N08825 (NACE+H2)
Nickel Alloy UNS N08825 (NACE)
SS 304 (NACE)
SS 304L (NACE)
SS 316L (NACE)
SS 316L (NACE+H2)
SS 321 (NACE)
IMPULSE PIPING & FITTINGS (3/4")-WELDED JOINTS
Alloy steel 1.25 Cr - 0.5 Mo (IBR)
Alloy steel 1.25 Cr - 0.5 Mo (NACE)
Alloy steel 9 Cr - 1 Mo
Alloy steel 9 Cr - 1 Mo (NACE)
CS (NACE)
CS (NACE+H2)
CS (IBR)
Incoloy 825
Incoloy 825 (NACE)
Nickel Alloy UNS N10276 (NACE)
SS 304 (NACE)
SS 304L (NACE)
SS 304L (NACE+H2)
SS321 (NACE)
SS321 (NACE+H2)
UNS N08825 (NACE)
IMPULSE PIPING & FITTINGS (1")-WELDED JOINTS
Alloy steel 9 Cr - 1 Mo
Alloy steel 9 Cr - 1 Mo (NACE)
Alloy steel 1.25 Cr - 0.5 Mo (NACE)
Alloy steel 1.25 Cr - 0.5 Mo (NACE+H2)
CS (IBR)
CS (NACE)
CS (NACE+H2)
Incoloy 825 (NACE)
Incoloy 825 (NACE+H2)
SS 304L (NACE+H2)
SS316L (NACE)
SS321 (NACE)
SS321 (NACE+H2)
UNS N08825 (NACE)
SS321 (NACE) hub connection weld
SS316L (NACE) hub connection weld
SS347 (NACE) hub connection weld
SS 304L (NACE)
SUPPLY AND INSTALLATION OF IMPULSE TUBES & FITTINGS
Scope of work includes supply, transportation to site, erection, handling, storage, unpacking etc. The activity includes following operation: a) Contractor(bidder) shall study optimal routing from the process connection up to the instrument as per process hook up drawing provided by the Technip Energies. b) Laying, supporting, clamping, cutting, theading bending & other similar works involved in fabrication of hookup of SS tubes, tube fitting and accessories including bolt tightening and torquing as per project specifications. c) Fixing of isolation valves & tube fittings etc as per process hook up drawing. d) Instrument Manifold installation, supporting and clamping. e) SS tube connection to the process / impulse pipe &, to the instruments. f) Cleaning / blowing & pressure test of the tubing and dechocking of Impulse lines if required. g) Impulse tube shall be calmped at every one meter interval. h) Sealing of all threaded joints using suitable sealants and/ or by seal welding as specified in hook-up drawing. i) PWHT, Radiography, DP test etc. shall be applicable as per project requirement. j) Proper clamping shall be done for overhead SS tubes. k) Pressure test / leakage test shall be done for fittings and ferrule joints. l) Hook-ups shall be fabricated and installed strictly as per project hook-up drawings maintaining required slope from tapping point m) Erection of pipe listed in BOM below includes erection of all the pipe fittings, seal pot, valves & other accessories as per Hook- up drawings.
n) Also, Scope includes the erection of any hook- up , loose supplied by package vendor as per the hook- up drawing supplied by package vendor. For package loose supplied Hook Up Material, Unit rate of erection is applicable. o) If required during Installation of impulse tube making temporary supports / scafolding etc. is in contractor's (bidder) scope of work. p) Any other work not specified above but required for installation SS tubes is also in contractor's (bidder) scope of work. q) Contractor(bidder) shall supply the material as per approved vendor list. r) Contractor(bidder) shall submit the mill test certificates complying to EN 10204 type 3.1 for all pressure parts. s) All valves shall be forged type only and of minimum 800 LBS rating.
Seamless Tubing 1/2" OD x 1.65mm WT, SS316L
Supply
Installation
Male connector 1/2" NPTM x 1/2" OD, 3000#, SS316L
Supply
Installation
Female connector 1/2" NPTF x 1/2" OD, 3000#, SS316L
Supply
Installation
Tube union 1/2" OD x 1/2" OD, 3000#, SS316L
Supply
Installation
Tube cap 1/2" OD, 3000#, SS316L
Supply
Installation
Gate valve 1/2" NPTF x 1/2" NPTF, 800#, ASTM A105N
Supply
Installation
Union Tee 1/2" OD, x 1/2" OD, x 1/2" OD, 3000#, SS316L
Supply
Installation
Seamless Tubing 1" OD x 1.65mm WT, SS316L
Supply
Installation
Seamless Tubing 1.5" OD x 1.65mm WT, SS316L
Supply
Installation
Male connector 1" NPTM x 1" OD, 3000#, SS316L
Supply
Installation
Male connector 1.5" NPTM x 1.5" OD, 3000#, SS316L
Supply
Installation
Female connector 1" NPTF x 1" OD, 3000#, SS316L
Supply
Installation
Female connector 1.5" NPTF x 1.5" OD, 3000#, SS316L
Supply
Installation
Tube union 1" OD x 1" OD, 3000#, SS316L
Supply
Installation
Tube union 1.5" OD x 1.5" OD, 3000#, SS316L
Supply
Installation
Gate valve 1" NPTF x 1" NPTF, 800#, ASTM A105N
Supply
Installation
Gate valve 1.5" NPTF x 1.5" NPTF, 800#, ASTM A105N
Supply
Installation
Tube union 3/4" OD x 3/4" OD, 3000#, SS316L
Supply
Installation
SUPPLY AND INSTALLATION OF INSTRUMENTS AIR DISTRIBUTION MANIFOLD
Scope of work also includes supply, transportation to site, erection, handling, storage, unpacking etc and installation of Instrument Air Manifold as per applicable Hook up drawings. The activity includes follwing operation: a) Installation of prefabricated supports on the columns & other permanent structure in the plant. These supports shall be welded or bolted to the structures, for fixing supports on concrete structure HILTI Anchor's shall be used. Supports shall be painted. b) Fixing of instrument air distribution manifold on the supports. c) Fixing of pipe fittings, tube fittings, isolation valves & drain valves etc on the air distribution manifold. d) Connection of instrument air supply line & to the instrument. (for both direct connection to air header as well as through manifold) e) Cleaning / blowing & pressure test of the instrument air distribution manifold alongwith SS tubing up to the instrument. f) Scope includes supply of welding elecctrodes, paints , clamps, supports sealing compound & other consumables etc g) If required during Installation of air distribution manifold, making temporary supports / scafolding etc. is in contractors scope of work. h) Any other work not specified above but required for installation of air distribution manifold is also in contractor's (bidder) scope of work. i) All connections on instrument Air Manifold shall be SS TIG Welded. Ball valve shall be of approved make only. Radiography applicable for all welded joints. j) Contractor(bidder) shall supply the material as per approved vendor list. k) Contractor(bidder) shall submit the mill test certificates complying to EN 10204 type 3.1 for all pressure parts. l) All valves shall be forged type only and of minimum 800 LBS rating.
2" Air Distributor, SS304 Sch 160, 6 Users (1/2"NPTF), 1" 300# RF Inlet connection and Drain valve connection ( 1/2"NPTF), all distribution and drain valves shall be packless gland type full-bore ball valves and body material shall be SS 304.
Supply & Erection
HEX PLUG, 1/2" NPTM, SS316
Supply & Erection
CAP, 1/2" NPTF, SS316
Supply & Erection
PIPE NIPPLE, 1/2" NPTM x 1/2" NPTM, SS316 Sch 160
Supply & Erection
2" Air Distributor, SS304 Sch 160, 10 Users (1/2"NPTF), 1" 300# RF Inlet connection and Drain valve connection ( 1/2"NPTF), all distribution and drain valves shall be packless gland type full-bore ball valves and body material shall be SS 304.
Supply & Erection
HEX PLUG, 1/2" NPTM, SS316
Supply & Erection
CAP, 1/2" NPTF, SS316
Supply & Erection
PIPE NIPPLE, 1/2" NPTM x 1/2" NPTM, SS316 Sch 160
Supply & Erection
SUPPLY AND INSTALLATION OF INSTRUMENT AIR SUPPLY TUBING
Scope of work includes supply, transportation to site, erection, handling, storage, unpacking etc. The activity includes follwing operation: a) Contractor shall study optimal routing from the instrument air disribution manifold up to the instrument as per pneumatic hook ups, instrument location layout, air distribution layout provided by the site incharge. Main instrument air header to Instrument air manifold routing by mechnaical / piping contractor. b) Installtaion of prefabricated supports. These supports shall be welded or bolted to the structures. Supports shall be painted. c) Fabrication of instrument air piping sub headers (1”) and branch pipes (1/4”,3/8”,1/2”,3/4”) on the basis of instrument air distribution layout, instrument location layout and field study. d) Laying, supporting, clamping, cutting, threading bending & other similar works involved in laying instrument air tubes, tube fitting and accessorires. e) Fixing of tubes & tube fittings. f) Connection to the instrument air distribution manifold and to the instruments. g) Cleaning / blowing & pressure test of the instrument air tubing starting from instrument air distribution manifold up to the instrument. h) Hook-up supporting shall be done through perforated tray as per installation standard. i) Installation of Air tubing from air distribution manifold to respective valves shall be performed by Inst. Subcontractor. j) Installation and connection of instrument air tubing from branch isolation ball valve(threaded) to the instruments as per pneumatic hook-up drawing and instrument location layout.
k) Sealing of all threaded joints using suitable sealants as specified in hook-up drawing. l) Scope includes supply of welding elecctrodes, paints , clamps, supports, consumables and other material required. m) Pressure test / leakage test shall be done for fittings and ferrule joints. n) Cleaning / blowing/ flushing & hydraulic test of the pneumatic lines. o) Instrument airline hook-up test shall be done by subcontractor. p) Scope includes supply of bender, cutter, clamps, thread sealants, consumables and other material required. q) Erection of pipe and tube listed in BOM below includes the erection of pipe/ tube fittings etc. r) If required during Installation of air supply tubing making temporary supports / scafolding etc. is in contractors scope of work. s) Any other work not specified above but required for laying of instru. air line from main header to Instrument air manifold is also in contractor's(bidder) scope of work. t) Contractor(bidder) shall supply the material as per approved vendor list. u) Contractor(bidder) shall submit the mill test certificates complying to EN 10204 type 3.1 for all pressure parts.
Seamless Tubing 1/4" OD x 1.65mm WT, Seamless, SS316L
Supply & Erection
Male Connector 1/4" NPTM X 1/4" OD, Stainless steel 316L
Supply & Erection
Male Connector 1/2" NPTM X 1/4" OD, Stainless steel 316L
Supply & Erection
Male Connector 1/4" NPTM X 1/2" OD, Stainless steel 316L
Supply & Erection
Tube Union 1/4"x1/4" OD, Stainless steel 316L
Supply & Erection
Seamless Tubing 1/2" OD x 1.65mm WT, Seamless, SS316L
Supply & Erection
Male Connector 1/2" NPTM X 1/2" OD, Stainless steel 316L
Supply & Erection
Tube Union 1/2"x1/2" OD, Stainless steel 316L
Supply & Erection
Seamless Tubing 3/4" OD x 1.8mm WT, Seamless, SS316L
Supply & Erection
Male Connector 3/4" NPTM X 3/4" OD, Stainless steel 316L
Supply & Erection
Adaptor 1/2" NPTM X 3/4" NPTF, Stainless steel 316L
Supply & Erection
Tube Union 3/4"x3/4" OD, Stainless steel 316L
Supply & Erection
Seamless Tubing 1" OD x 2mm WT, Seamless, SS316L
Supply & Erection
Male Connector 1" NPTM X 1" OD, Stainless steel 316L
Supply & Erection
Adaptor 1/2" NPTM X 1" NPTF, Stainless steel 316L
Supply & Erection
Tube Union 1"x1" OD, Stainless steel 316L
Supply & Erection
SUPPLY & INSTALLATION OF MOUNTING STANDS FOR INSTRUMENTS / GAS DETECTORS / HOOTER,BEACON/SPEAKER
Supply & Installation of mouting stands /Stanchions for mounting of Transmitters, Gas detectors & other field instruments, remote mounted and Beacon, Speaker, CCTV along with required accessories like base plate etc., as per Installation standard TP-1P30A-IC-IND-0001. The activity includes following works: a) Mounting stands shall be suitable installation on the plant permanent structure,/ RCC platform / grade etc. as the case may be. b) Mounting stands shall be either welded or bolted to the permanent structures, for fixing supports on concrete structure HILTI Anchor's bolts shall be used. Minor civil work involved in the installation of the mounting stand shall be also done the contactor including supply of cement, bricks,concrete, anchor bolts etc. c) Scope of work includes cutting, welding, threading, cleaning, painting and other similar works involved in the fabrication of mounting stands. d) All the welded joints & machined parts shall be protected by epoxy painting. e) Scope includes supply of welding electrodes, 2" NB Sch. 40 MS Pipe epoxy painted for (All instruments Mild Steel Plate (plate thickness 10mm), MS channel, nuts & bolts, anchor fastners, paints, cement, sand, bricks, concrete etc. and other similar material required for fabrication and installation of mounting stands. f) Fixing of the FRP canopies on the mounting stands, scope includes supply of nuts & bolts required for fixing canopy on the mounting stand.
g) Contractor(bidder) shall obtain approval of the mouting stand from site incharge, only after getting written approval from site incharge, fabrication of mouting stands shall be started by the contractor. h) Earthing for mounting stand (stanchion) shall be in Contractor's(bidder) scope i) If required during erection making of temporary supports / scafolding etc. is in contractors scope. j) Any other work not specified above but required for fabrication of mounting stand is also in contractor's (bidder) scope of work. k) Wall mounted stanchion for Hooter, Beacon, MCP, Speaker, Analog telephone. l) Supply of installation supoort, stand/stanchion shall be as per Typical Instrument instalation drawing (TP-1P30A-IC-IND-0001). m) Contractor(bidder) shall supply the material as per approved vendor list. n) Contractor(bidder) shall submit the mill test certificates complying to EN 10204 type 3.1 for all pressure parts.
Stanchion / Column Mounting stand with 2" NB Sch. 40 MS Pipe Epoxy Painted, 1.6 meter height
Mounting Stand for Presusre Gauge - Diaphragm Seal
Mounting Stand for Diff. Presusre Gauge
Mounting Stand for Loop powered indicator
Mounting Stand for Motor Stop Switch at Field (30m away)
Mounting Stand for Hand-Off-Auto Switch at Field
Mounting Stand for Hand Operated Switch - Close for MOV at Field (30m away)
Mounting Stand for Hand Operated Switch - Reset/Close for On-Off valve
Mounting Stand for Single Transmitter
Mounting Stand for Dual Transmitters
Mounting Stand for Triple Transmitters
Mounting Stand for Quadruple Transmitters
Mounting Stand for Multipoint Temperature Transmitters
Multiple Instrument mounting stand (for 8 nos of instruments)
Multiple Instrument mounting stand (for 10 nos of instruments)
Multiple Instrument mounting stand (for 14 nos of instruments)
Multiple Instrument mounting stand(for 16 nos of instruments)
Multiple Instrument mounting stand (for 28 nos of instruments on front and back of stand)
Mounting Stand for Gas detectors
Stanchion/ Column Mounting stand with 2" NB Sch. 40 MS Pipe Epoxy painted - Single Detector Mounting, 0.6 meter height
Stanchion/ Column Mounting stand with 4" NB Sch. 40 MS Pipe Epoxy Painted - Single Detector Mounting, 3 meter height
Supply and Installation of the poles in the correct position as per project layout drawing & fixing & alignment of the pole in postion with the anchor bolts on the concrete base . Scope includes supply of anchor bolts, concrete,cement etc.Contractor scope includes preparation of the foundation for the installation of Flashing Beacon/Outdoor Speaker pole as details clearly shown in Installation standard a) Fixing of Flashing Beacon/Outdoor Speaker along with the accessories on the pole as per Installation standard TP-1ZZZA-IC-STD-0001 b) Earth stud , supports on Flashing Beacon/Outdoor Speaker pole shall be supplied and installed by Contractor c) If required during installation of poles for Flashing Beacon/Outdoor Speaker, making temporary supports / scafolding etc. is in contractors scope of work.. c) Any other activity not indicated above but required for the installation of pole shall be under contractor scope of work.
Mounting Stand for Flashing Beacon (dimensions as indicated in Installation standard)
Mounting Stand for Outdoor Speaker (dimensions as indicated in Installation standard)
SUPPLY, FABRICATION AND INSTALLATION OF STRUCTURAL STEEL
Supply, Fabrication & installation of supports required for cable ducts, cable trays, impulse pipes & tubes, trays (for impuse pipe and capillary). Mounting panels for junction boxes, stanchions for Instruments & Gas detector, . The activity includes following works: a) Supports shall be suitable for installation on the plant permanent structure,/ RCC structure/ platform / grade as the case may be. b) Supports shall be either welded or bolted to the permanent structures, for fixing supports on concrete structure HILTI Anchor's bolts shall be used. Minor civil work involved in the installation of the supports shall be also done the contactor including supply of cement, bricks,concrete, anchor bolts etc. c) If required during erection making of temporary supports / scafolding etc. is in contractor's(bidder) scope. d) Scope of work includes cutting, welding, threading, cleaning and other similar works involved in the fabrication of mounting stands and installation of cable trays, impulse pipes & tubes, junction boxes and its frame, local panel along with its base frame as per Installation standard. e) Deisgn, Specification and Material shall be as per Installation standard TP-1P30A-IC-IND-0001. f) Supply of Structural Steel jointing fittings. g) Support shall be painted (corrosion resistant epoxy painted). h) Scope of work includes supply of structural steel (i.e plates, flats, channels, angles, Tubular Structures etc of and other consumables i.e. welding electrodes, gas, primer, final paint. Erection contractor(bidder) scope also includes welding, cutting, threading,cleaning, surface preparation for welding and painting and other similar works. i) When items requires tig welding qulaified person shall be employed to carryout described work providing required finish meeting all quality requirements j) Any other work not specified above but required for fabrication of structural steel is also in contractor's (bidder) scope of work. k) Contractor(bidder) shall supply the material as per approved vendor list.
INSTALLATION OF LOCAL PANELS
Scope of work includes taking delivery from warehouse or from the places of storage, on site transportation, handling, storage, unpacking etc. The activity includes following operations: a) Installation of the local panel in the correct postion as per project layout drawing & fixing the panel in postion with the anchor bolts on the concrete base/ Platform . Scope includes supply of anchor bolts, concrete,cement etc.Contractor shall also do necessary chipping of pockets (if required) provided in the concrete base for installation panel. b) Contractor(bidder) shall align all the sections of the panel. c) Cleaning, de-dusting, painting touch up (if necessary) & maintance of the local panel. d) Painting as per project specification e) Any other work not specified above but required for installation of installation local panel is also in contractor's(bidder) scope of work. f) Free issue - Local panels.
Installation of local panel (Panel size [1000 mm (D) X 1650 mm (W) X 2115 mm (H)])
Installation of local panel (Panel size [1400 mm (D) X 2400 mm (W) X 2000 mm (H)])
Installation of local panel (Panel size [2200 mm (D) X 800 mm (W) X 1600 mm (H)])
Installation of local panel (Panel size [800 mm (D) X 1600 mm (W) X 2115 mm (H)])
Installation of local panel (Panel size [1100 mm (D) X 1900 mm (W) X 2115 mm (H)])
Installation of local panel (Panel size [2358 mm (D) X 800 mm (W) X 2600 mm (H)])
SUPPLY AND INSTALLATION OF FRP CANOPIES (FOR ALL APPLICABLE ITEMS)
Canopies shall be of adequate size to protect the transmitters, JB,Temperature elements, LCP, Push Button Station, Analysers and F&G detectors etc from the sunlight and rain. a) Canopy shall be fabricated from 3 mm(min.) thick FRP sheet suitable for a design surface temp. of 65 C, Fire retardant to BS 476 parts 7. Anti- static to BS 5501 Part1. Contractor shall furnish drawing of the canopy along with offer. b) Fabrication of canopy shall be as per Installation standard TP-1P30A-IC-IND-0001. c) Mounting accessories suitable for 2" pipe shall be supplied along with the canopy. Necessary SS 304 nuts & Bolts shall be supplied with bracket. d) Bidder shall supply the material as per approved vendor list and shall obtain drawing approval from consultant. e) The canopy shall be of FRP of ISO 9001 certified manufacturer. Scope Includes but not limited to:- Supply, Fabrication & Installation of canopies of 3 mm(min.) thick FRP sheet on 2"/4" mounting stanchions for field instruments / push buttons / LCP housed outdoor/ JB.
Supply & installation of Canopy for Transmitters (Mounting stand or other options)
Supply
Installation
Supply & installation of Canopy for F&G detectors
Supply
Installation
Supply & installation of Canopy for Temperature elements
Supply
Installation
PURGE PANELS
INSTALLATION OF PURGE PANEL
Installation of purge panels Scope of work includes taking delivery from warehouse or from the places of storage, on site transportation, handling, storage, unpacking etc. The activity includes following operations: a) Installation of the purge panel in the correct postion as per project layout drawing & fixing the panel in postion with the anchor bolts on the concrete base/ Platform . Scope includes supply of anchor bolts, concrete,cement etc.Contractor shall also do necessary chipping of pockets (if required) provided in the concrete base for installation panel. b) Contractor(bidder) shall align all the sections of the panel. c) Contractor(bidder) shall remove the gland plate from the panel, shall drill the gland plate for fixing cable glands/bulk heads etc. and shall re-fix (by bolting) the gland plate in the panel (gas cutting not permitted for making holes in the gland plates). Once cable laying & termination is completed all the spare cable entries in the gland plate shall be plugged by contractor(bidder). d) Installation, termination & connection of the those instruments & accessories supplied along with the panel. e) Laying, supproting, clamping & termination of cables inside panel. f) Cleaning, de-dusting, painting touch up (if necessary) & maintance of the local panel. g) Earthing of the Local Panel & signals (i.e.sperate earthing required for IS/ NON-IS signals & safety earth ) shall done by the contractor. Single core PVC insulated copper wire shall be used for connecting to plant earth grid (lugs, ferrules & wires shall be supplied by the contractor). Earthing shall be as per Project drawing/as per manufacturer recommndation. h) Contractor(bidder) shall provide technical assisatnce to the system manufactutrer's specialist for calibration, start up & commissioning.
i) Painting as per project specification. j) Any other work not specified above but required for installation of installation local panel is also in contractor's(bidder) scope of work.
Purge Panels
Installaion/Erection
Installation of purging pipes, fittings & Tube bundle
k) Any other work not specified above but required for laying of purge pipe (manifold) is also in contractor's scope of work. l) Erection of pipe listed in BOM below includes erection of all the pipe fittings, seal pot, valves & other accesories as per Hook- up drawings. Also, Scope includes the erection of any hook- up , loose supplied by package vendor as per the hook- up drawing supplied by package vendor. For package loose supplied Hook Up Material, Unit rate of erection is applicable. m) Free issue to Contractor : Pipe & Pipe fittings and Tube bundles.
PURGE PIPING & FITTING (3/4")-WELDED JOINTS
Carbon Steel (CS) (NACE)
Carbon Steel (CS) (NACE+H2)
Carbon Steel (CS)
SS 304L (NACE)
SS 304L (NACE+H2)
SS 321 (NACE+H2)
SS 321 (NACE)
Alloy Steel 9Cr-1 Mo
Nickel Alloy UNS N10276 (NACE)
PURGE PIPING & FITTING (1")-WELDED JOINTS
Alloy Steel 9Cr-1 Mo - PWHT
SS 304L (NACE)
SS 321 (NACE)
SS 321 (NACE+H2)
SS 316L (Hub connection weld)
SS 347 (Hub connection weld)
Alloy Steel 9Cr-1 Mo (Hub connection weld)
SS 321 (NACE+H2) (Hub connection weld)
SUPPLY AND INSTALLATION/ERECTION OF TUBE BUNDLE (WITH STEAM TRACER)
Supply and installation of tube bundles scope of work includes taking delivery from warehouse or from the places of storage, local transportation, handling, storage, unpacking, etc., fabrication & installation of tube bundle with tray and supports and fittings (Installation of fittings are part of erection of tube bundle in running Metre) with suitable heavy duty mild steel supports (with 2 primer coatings & 1 epoxy coating). a) Contractor(bidder) shall study optimal routing for the tube bundle from purge panel to the consumers as per hook up drawing provided by the Technip. c) Laying, welding, supporting, clamping, cutting, bending & other similar works involved intube bundle installation/errection. g) Cleaning / blowing & hydraulic test of the tube bundles and dechocking of tube bundles if required. h) Scope includes supply of welding elecctrodes, paints , clamps, consumables, and other material required. j) If required during laying of impulse lines, making temporary supports / scafolding etc. is in contractor's (bidder) scope of work. k) Tube bundles shall be insulated with Ceramic ropes and Aluminium cladding by contractor(bidder).
Tube bundle with steam tracer →Tube shall be 3/4" OD SS 316L →Tracer tube shall be 10 mm OD copper tube
Supply
Installaion/Erection
Gate valve 3/4" NPTF x 3/4" NPTF, 800#, ASTM A105N, B1A/A1A/B35A/D35A (ITEM CODE 246)
Supply
Installaion/Erection
Lift Check valve 3/4" NPTF x 3/4" NPTF, 800#, ASTM A105N, B1A/A1A/B35A/D35A (ITEM CODE 247)
Supply
Installaion/Erection
Lift Check valve 3/4" NPTF x 3/4" NPTF, 800#, ASTM A182 Gr.F9,B1G (ITEM CODE 248)
Supply
Installaion/Erection
Gate valve 3/4" NPTF x 3/4" NPTF, 800#, ASTM A182 Gr.F9,B1G (ITEM CODE 249)
Supply
Installaion/Erection
Female Connector 3/4" NPTF X 3/4" OD, Stainless steel 316L, 3000#
Supply
Installaion/Erection
Male Connector 3/4" NPTM X 3/4" OD, Stainless steel 316L, 3000#
Supply
Installaion/Erection
Tube union Brass with chrome Plated (10mm OD x 10mm OD, 3000#)
Supply
Installaion/Erection
Male Connector Brass with chrome Plated (1/2" NPTM x 10mm OD, 3000#)
Supply
Installaion/Erection
Gate valve 3/4" NPTF x 3/4" NPTF, 800#, ASTM A105N, B36A,NACE+PWHT (ITEM CODE 204N)
Supply
Installaion/Erection
Lift Check valve 3/4" NPTF x 3/4" NPTF, 800#, ASTM A105N, B36A,NACE+PWHT (ITEM CODE 205N)
Supply
Installaion/Erection
Gate valve 3/4" NPTF x 3/4" NPTF, 800#, ASTM A182 Gr.F304L, B37A,NACE (ITEM CODE 206N)
Supply
Installaion/Erection
Lift Check valve 3/4" NPTF x 3/4" NPTF, 800#, ASTM A182 Gr.F304L, B37A,NACE (ITEM CODE 207N)
Supply
Installaion/Erection
Gate valve 3/4" NPTF x 3/4" NPTF, 800#, ASTM A182 Gr.F304L, D26K,NACE+H2 (ITEM CODE 196NH)
Supply
Installaion/Erection
Lift Check valve 3/4" NPTF x 3/4" NPTF, 800#, ASTM A182 Gr.F304L, D26K,NACE+H2 (ITEM CODE 197NH)
Supply
Installaion/Erection
Gate valve 3/4" NPTF x 3/4" NPTF, 800#, ASTM A105N, B37A,NACE+PWHT+H2 (ITEM CODE 194NH)
Supply
Installaion/Erection
Lift Check valve 3/4" NPTF x 3/4" NPTF, 800#, ASTM A105N, B37A,NACE+PWHT+H2 (ITEM CODE 195NH)
Supply
Installaion/Erection
Gate valve 3/4" NPTF x 3/4" NPTF, 800#,STM A182 Gr.F321, B18M/B3M,NACE (ITEM CODE 208N)
Supply
Installaion/Erection
Lift Check valve 3/4" NPTF x 3/4" NPTF, 800#,STM A182 Gr.F321, B18M/B3M,NACE (ITEM CODE 209N)
Supply
Installaion/Erection
Gate valve 1" NPTF x 1" NPTF, 800#, ASTM A182 Gr.F304L, B22K/B36K NACE (ITEM CODE 202N)
Supply
Installaion/Erection
Lift Check valve 1" NPTF x 1" NPTF, 800#, ASTM A182 Gr.F304L, B22K/B36K NACE (ITEM CODE 203N)
Supply
Installaion/Erection
Gate valve 1" NPTF x 1" NPTF, 800#, ASTM A182 Gr.F9L, B3G (ITEM CODE 244)
Supply
Installaion/Erection
Lift Check valve 1" NPTF x 1" NPTF, 800#, ASTM A182 Gr.F9L, B3G (ITEM CODE 245)
Supply
Installaion/Erection
Gate valve 1" NPTF x 1" NPTF, 800#, ASTM A182 Gr.F321, B3G NACE+H2 (ITEM CODE 190NH)
Supply
Installaion/Erection
Lift Check valve 1" NPTF x 1" NPTF, 800#, ASTM A182 Gr.F321, B3G NACE+H2 (ITEM CODE 191NH)
Supply
Installaion/Erection
SUPPLY AND INSTALLATION OF COPPER TUBES FOR STEAM TRACING ON INSTRUMENTS
Seamless Copper tube (10 mm OD x 0.6mm WT)
Supply
Installation/Erection
Male Connector Brass with chrome Plated (1/2" NPTM x 10mm OD, 3000#)
Supply
Installation/Erection
Female Connector Brass with chrome Plated (1/2" NPTF x 10mm OD, 3000#)
Supply
Installation/Erection
Tube union Brass with chrome Plated (10mm OD x 10mm OD, 3000#)
Supply
Installation/Erection
TEE Brass with chrome Plated (10mm OD x 10mm OD x 10mm OD, 3000#)
Supply
Installation/Erection
Pipe Nipple, ASTM A106 GR.B, 1/2" NPTM X 1/2" PE , SCH XS, L=4"
Supply
Installation/Erection
SUPPLY OF PIPE, PIPE FITTINGS (ELBOW, NIPPLE, FLANGES, ADAPTOR, PLUG, FLANGES, BLIND, GASKETS, STUD BOLTS) AND VALVES
SEAMLESS PIPE
1/2", Sch.160 PE, ASTM A106 Gr.B, A2A, IBR (ITEM CODE 01I)
Supply
1/2", Sch.160 PE, ASTM A106 Gr.B, B2A, IBR (ITEM CODE 25I)
Supply
3/4", Sch.160 PE, ASTM A106 Gr.B, B1A (ITEM CODE 37)
Supply
3/4", Sch.XXS PE, ASTM A106 Gr.B, B35A (ITEM CODE 63)
Supply
3/4", Sch.XXS PE, ASTM A106 Gr.B, D35A (ITEM CODE 119)
Supply
3/4",Sch.160 PE, ASTM A312 Gr.TP304, A3K (ITEM CODE 50)
Supply
3/4", Sch.160 PE, ERW, A3A (ITEM CODE 192)
Supply
3/4", Sch.160 PE, ASTM A106 Gr.B, B10A, H2 (ITEM CODE 01H)
Supply
3/4", Sch.160 PE, ASTM A106 Gr.B, D10A, H2+PWHT (ITEM CODE 23H)
Supply
3/4", Sch.160 PE, ASTM A106 Gr.B, D2A, IBR (ITEM CODE 39I)
Supply
3/4", Sch.160 PE, ASTM A106 Gr.B, A2A, IBR (ITEM CODE 52I)
Supply
3/4", Sch.160 PE, ASTM A106 Gr.B, B2A, IBR (ITEM CODE 91I)
Supply
3/4", Sch.XXS PE, ASTM A106 Gr.B, B37A/B14A, NACE+H2+PWHT (ITEM CODE 13NH)
Supply
3/4", Sch.XXS PE, ASTM A106 Gr.B, B36A, NACE+PWHT (ITEM CODE 01N)
Supply
3/4", Sch.160 PE, ASTM A106 Gr.B, A37A, NACE+PWHT (ITEM CODE 163N)
Supply
3/4", Sch.XXS BE, ASTM A106 Gr.B, B38A/B39A, NACE+PWHT (ITEM CODE 26N)
Supply
3/4", Sch.160 PE, ASTM A312 Gr.TP304L, B22K/B36K, NACE (ITEM CODE 43N)
Supply
3/4", Sch.160 PE, ASTM A312 Gr.TP304L, B35K/B13K/B34K, NACE+H2 (ITEM CODE 75NH)
Supply
3/4", Sch.160 PE, ASTM A312 Gr.TP304L, D26K, NACE+H2 (ITEM CODE 146NH)
Supply
3/4", Sch.160 PE, ASTM A312 Gr.TP321, B18M/B3M, NACE (ITEM CODE 88N)
Supply
3/4", Sch.160 PE, ASTM A335 Gr.P11, D14D, NACE+PWHT+H2 (ITEM CODE 160NH)
Supply
3/4", Sch.160 PE, ASTM A335 Gr.P11, D2D, IBR+PWHT (ITEM CODE 11I)
Supply
3/4", Sch.160 PE, ASTM A335 Gr.P9, B1G, PWHT (ITEM CODE 24)
Supply
3/4", Sch.XXS PE, ASTM A335 Gr.P9, B3G, PWHT (ITEM CODE 135)
Supply
3/4", Sch.160 PE, ASTM B622 UNS N10276, B18C, NACE (ITEM CODE 174N)
Supply
1", Sch.160 BE, ASTM A106 Gr.B, E2A, IBR (ITEM CODE 67I)
Supply
1", Sch. XXS BE, ASTM A106 Gr.B, G92A (ITEM CODE 89)
Supply
1", Sch.160 BE, ASTM A106 Gr.B, E55A, H2 (ITEM CODE 33H)
Supply
1", Sch. XXS BE, ASTM A106 Gr.B, F36A/F38A, NACE+PWHT (ITEM CODE 57N)
Supply
1", Sch. XXS BE, ASTM A106 Gr.B, E14A, NACE+H2+PWHT (ITEM CODE 25NH)
Supply
1", Sch. 160 BE, ASTM A106 Gr.B, F14A, NACE+H2+PWHT (ITEM CODE 37NH)
Supply
1", Sch. 160 BE, ASTM A312 Gr.TP321, G35M, NACE+H2 (ITEM CODE 49NH)
Supply
1", Sch. XXS BE, ASTM A335 Gr.P9, G1G, PWHT (ITEM CODE 156)
Supply
1", Sch.160 BE, ASTM B423 UNS N08825 annealed, F15Q, NACE+H2 (ITEM CODE 61NH)
Supply
1", Sch.160 PE, ASTM D1784 Cl.23447, J2AL (ITEM CODE 182)
Supply
1", NPTM Ends, Sch 160, ERW, Pipes, IS 1239 Part 1, IS 1239 Part 1 Galv, A3AL (ITEM CODE 12)
Supply
1", Sch.160 BE, ASTM A335 Gr.P11, F1D, NACE+H2+PWHT (ITEM CODE 01NH)
Supply
1", SCH.XXS BE, ASTM A312 Gr.TP321, G45M, NACE+H2 (ITEM CODE G56NH)
Supply
1", SCH.XXS BE, ASTM A312 Gr.TP347, G47M, - (ITEM CODE G66)
Supply
1", SCH.160 BE, ASTM A335 Gr.P9 , G42G, PWHT (ITEM CODE G76)
Supply
PIPE NIPPLE
1" x 1" BE, Sch. 160, L=4", ASTM A106 Gr.B, E2A, IBR (ITEM CODE 72I)
Supply
1" x 1" BE, Sch. XXS, L=4", ASTM A106 Gr.B, G92A/G35A (ITEM CODE 101)
Supply
1" x 1" BE, Sch. XXS, L=6", ASTM A106 Gr.B, G92A, NACE+PWHT (ITEM CODE 102)
Supply
1" x 1" BE, Sch. 160, L=4", ASTM A106 Gr.B, E55A, H2 (ITEM CODE 38H)
Supply
3/4" NPTM x 3/4" PE, Sch. 160, L=4", ASTM A106 Gr.B, B10A, H2 (ITEM CODE 22H)
Supply
3/4" x 3/4" PE, Sch. 160, L=4", ASTM A106 Gr.B, B10A, H2 (ITEM CODE 07H)
Supply
3/4" x 3/4" PE, Sch. 160, L=4", ASTM A106 Gr.B, D10A, H2+PWHT (ITEM CODE 28H)
Supply
3/4" NPTM x 3/4" PE, Sch. 160, L=4", ASTM A106 Gr.B, B1A (ITEM CODE 38)
Supply
3/4" NPTM x 3/4" PE, Sch. XXS, L=4", ASTM A106 Gr.B, D35A (ITEM CODE 126)
Supply
3/4" NPTM x 3/4" PE, Sch. XXS, L=4", ASTM A106 Gr.B, B35A (ITEM CODE 64)
Supply
3/4" x 3/4" PE, Sch. XXS, L=4", ASTM A106 Gr.B, D35A (ITEM CODE 132)
Supply
3/4" x 3/4" PE, Sch. 160, L=4", ASTM A106 Gr.B, B1A (ITEM CODE 84)
Supply
3/4" x 3/4" PE, Sch. 160, L=4", ASTM A106 Gr.B, B35A (ITEM CODE 88)
Supply
3/4" NPTM x 3/4" PE, Sch. 160, L=4", ASTM A106 Gr.B, A2A, IBR (ITEM CODE 53I)
Supply
3/4" NPTM x 3/4" PE, Sch. 160, L=4", ASTM A106 Gr.B, B2A, IBR (ITEM CODE 92I)
Supply
3/4" x 3/4" PE, Sch. 160, L=4", ASTM A106 Gr.B, D2A, IBR (ITEM CODE 40I)
Supply
3/4" NPTM x 3/4" BE, Sch. XXS, L=4", ASTM A106 Gr.B, B38A, NACE+PWHT (ITEM CODE 17N)
Supply
3/4" NPTM x 3/4" PE, Sch. XXS, L=4", ASTM A106 Gr.B, B36A, NACE+PWHT (ITEM CODE 02N)
Supply
3/4" x 3/4" BE, Sch. XXS, L=4", ASTM A106 Gr.B, B38A, NACE+PWHT (ITEM CODE 35N)
Supply
3/4" x 3/4" PE, Sch. XXS, L=4", ASTM A106 Gr.B, B36A, NACE+PWHT (ITEM CODE 25N)
Supply
3/4" NPTM x 3/4" PE, Sch. XXS, L=6", ASTM A106 Gr.B, B54A/B65A/B37A, NACE+H2+PWHT (ITEM CODE 124NH)
Supply
3/4" x 3/4" PE, Sch. XXS, L=4", ASTM A106 Gr.B, B37A/B14A, NACE+H2+PWHT (ITEM CODE 19NH)
Supply
3/4" NPTM x 3/4" PE, Sch. 160, L=4", ASTM A312 Gr.TP304, A3K, - (ITEM CODE 51)
Supply
3/4" NPTM x 3/4" PE, Sch. 160, L=4", ASTM A312 Gr.TP304L, D22K, NACE (ITEM CODE 120N)
Supply
3/4" x 3/4" PE, Sch. 160, L=4", ASTM A312 Gr.TP304L, D22K, NACE (ITEM CODE 122N)
Supply
3/4" NPTM x 3/4" PE, Sch. 160, L=4", ASTM A312 Gr.TP304L, B22K/B36K, NACE (ITEM CODE 44N)
Supply
3/4" x 3/4" PE, Sch. 160, L=4", ASTM A312 Gr.TP304L, B36K, NACE (ITEM CODE 83N)
Supply
3/4" x 3/4" PE, Sch. 160, L=4", ASTM A312 Gr.TP304L, B13K/B35K/B34K/D26K, NACE+H2 (ITEM CODE 87NH)
Supply
3/4" NPTM x 3/4" PE, Sch. 160, L=4", ASTM A312 Gr.TP304L, B13K/B35K, NACE+H2 (ITEM CODE 94NH)
Supply
3/4" NPTM x 3/4" PE, Sch. 160, L=4", ASTM A312 Gr.TP304L, D26K, NACE+H2 (ITEM CODE 81NH)
Supply
3/4" NPTM x 3/4" PE, Sch. 160, L=4", ASTM A312 Gr.TP321, B18M/B3M, NACE (ITEM CODE 53N)
Supply
3/4" x 3/4" PE, Sch. 160, L=4", ASTM A312 Gr.TP321, B18M/B3M, NACE (ITEM CODE 97N)
Supply
3/4" NPTM x 1" BE, Sch. 160, L=4", ASTM A312 Gr.TP321, G35M, NACE+H2 (ITEM CODE 138NH)
Supply
3/4" NPTM x 3/4" PE, Sch. 160, L=4", ASTM A312 Gr.TP321, D32M/D35M, NACE+H2 (ITEM CODE 104NH)
Supply
3/4" x 3/4" PE, Sch. 160, L=4", ASTM A312 Gr.TP321, D32M/D35M, NACE+H2 (ITEM CODE 109NH)
Supply
3/4" x 3/4" PE, Sch. 160, L=4", ASTM A335 Gr.P11, D14D, NACE+H2+PWHT (ITEM CODE 161NH)
Supply
3/4" x 3/4" PE, Sch. 160, L=4", ASTM A335 Gr.P11, D2D, IBR+PWHT (ITEM CODE 12I)
Supply
3/4" NPTM x 3/4" PE, Sch. 160, L=4", ASTM B423 UNS N08825, B12Q, NACE+H2 (ITEM CODE 144NH)
Supply
3/4" NPTM x 1" BE, Sch. XXS, L=4", ASTM A335 Gr.P9, G1G, PWHT (ITEM CODE 165)
Supply
3/4" NPTM x 3/4" PE, Sch. 160, L=4", ASTM A335 Gr.P9, B1G, PWHT (ITEM CODE 25)
Supply
3/4" NPTM x 3/4" PE, Sch. XXS, L=4", ASTM A335 Gr.P9, B3G, PWHT (ITEM CODE 230)
Supply
3/4" x 3/4" PE, Sch. 160, L=4", ASTM A335 Gr.P9, B1G, PWHT (ITEM CODE 80)
Supply
3/4" x 3/4" PE, Sch. XXS, L=4", ASTM A335 Gr.P9, B3G, PWHT (ITEM CODE 146)
Supply
3/4" NPTM x 3/4" PE, Sch. 160, L=4", ASTM B622 UNS N10276, B18C, NACE (ITEM CODE 111N)
Supply
3/4" x 3/4" PE, Sch. 160, L=6", ASTM A312 Gr.TP304L, D26K, NACE+H2 (ITEM CODE 154NH)
Supply
3/4" NPTM x 3/4" PE, Sch. 160, L=4", IS 1239 Part 2, IS 1239 Part 1 Black, A3A, - (ITEM CODE 201)
Supply
3/4" NPTM x 3/4" PE, Sch. 160, L=4", ASTM A312 Gr.TP316L, B14N, - (ITEM CODE 115)
Supply
1/2" NPTM x 1/2" PE, Sch. 160, L=4", ASTM A106 Gr.B, A2A, IBR (ITEM CODE 02I)
Supply
1/2" NPTM x 1/2" PE, Sch. 160, L=4", ASTM A106 Gr.B, B2A, IBR (ITEM CODE 26I)
Supply
1/2" NPTM x 1/2" PE, Sch. 160, L=6", ASTM A106 Gr.B, B2A, IBR (ITEM CODE 27I)
Supply
1/2" NPTM x 1/2" PE, Sch. 160, L=6", ASTM A106 Gr.B, A2A, IBR (ITEM CODE 66I)
Supply
1/2" x 1/2" PE, Sch. 160, L=4", ASTM A106 Gr.B, A2A, IBR (ITEM CODE 22I)
Supply
1" x 1" BE, Sch. XXS, L=4", ASTM A106 Gr.B, F36A, NACE+PWHT (ITEM CODE 69N)
Supply
1" x 1" BE, Sch. XXS, L=4", ASTM A106 Gr.B, F38A, NACE+PWHT (ITEM CODE 86N)
Supply
1" x 1" BE, Sch. XXS, L=6", ASTM A106 Gr.B, F36A, NACE+PWHT (ITEM CODE 70N)
Supply
1" x 1" BE, Sch. XXS, L=6", ASTM A106 Gr.B, F38A, NACE+PWHT (ITEM CODE 109N)
Supply
1" x 1" BE, Sch. 160, L=4", ASTM A106 Gr.B, F14A, NACE+H2+PWHT (ITEM CODE 43NH)
Supply
1" x 1" BE, Sch. 160, L=4", ASTM A106 Gr.B, E14A, NACE+H2+PWHT (ITEM CODE 31NH)
Supply
1" x 1" BE, Sch. XXS, L=4", ASTM A106 Gr.B, F9A/F37A, NACE+H2+PWHT (ITEM CODE 185NH)
Supply
1" X 1" NPTM, Sch 160, L= 4", ASTM A106 Gr.B Galv., A3AL, - (ITEM CODE 01)
Supply
1" x 1" BE, Sch. 160, L=4", ASTM A182 Gr.F304L, F14K, NACE+H2 (ITEM CODE 136NH)
Supply
1" x 1" BE, Sch. 160, L=4", ASTM A312 Gr.TP304L, F28K, NACE (ITEM CODE 133N)
Supply
1" x 1" BE, Sch. 160, L=4", ASTM A312 Gr.TP321, G35M, NACE+H2 (ITEM CODE 55NH)
Supply
1" x 1" BE, Sch. 160, L=6", ASTM A312 Gr.TP321, G35M, NACE+H2 (ITEM CODE 139NH)
Supply
1" x 1" BE, Sch. 160, L=4", ASTM A335 Gr.P11, F1D, NACE+H2+PWHT (ITEM CODE 07NH)
Supply
1" NPTM x 1" BE, Sch. 160, L=4", ASTM B423 UNS N08825 annealed, F15Q, NACE+H2 (ITEM CODE 67NH)
Supply
1" x 1" BE, Sch. 160, L=4", ASTM B423 UNS N08825 annealed, F15Q/F12Q, NACE+H2 (ITEM CODE 73NH)
Supply
1" x 1" BE, Sch. XXS, L=6", ASTM A335 Gr.P9, G1G, PWHT (ITEM CODE 166)
Supply
1" x 1" BE, Sch. XXS, L=4", ASTM A335 Gr.P9, G1G, PWHT (ITEM CODE 161)
Supply
1" NPTM x 1" SE, Sch. 160, L=4", ASTM D1784 Cl.23447, J2AL, - (ITEM CODE 191)
Supply
1", SCH 160 BE, L=4", ASTM A312 Gr.TP316L, G41N, PWHT (ITEM CODE G34)
Supply
1", SCH 160 BE, L=4", ASTM A312 Gr.TP321, G43M, NACE+H2 (ITEM CODE G10NH)
Supply
1", SCH 160 BE, L=4", ASTM A312 Gr.TP321, G44M, NACE+H2 (ITEM CODE G43NH)
Supply
1", SCH XXS BE, L=4", ASTM A312 Gr.TP321, G45M, NACE+H2 (ITEM CODE G26NH)
Supply
1", SCH XXS BE, L=6", ASTM A312 Gr.TP321, G45M, NACE+H2 (ITEM CODE G55NH)
Supply
1", SCH XXS BE, L=4", ASTM A312 Gr.TP347, G47M, - (ITEM CODE G18)
Supply
1", SCH XXS BE, L=6", ASTM A312 Gr.TP347, G47M, - (ITEM CODE G65)
Supply
1", SCH 160 BE, L=4", ASTM A335 Gr.P9, G42G, PWHT (ITEM CODE G02)
Supply
1", SCH 160 BE, L=6", ASTM A335 Gr.P9, G42G, PWHT (ITEM CODE G75)
Supply
3/4" NPTM x 1" BE, SCH 160, L=4" , ASTM A312 Gr.TP316L, G41N, PWHT (ITEM CODE G33)
Supply
3/4" NPTM x 1" BE, SCH 160, L=4" , ASTM A312 Gr.TP321, G43M, NACE+H2 (ITEM CODE G09NH)
Supply
3/4" NPTM x 1" BE, SCH 160, L=4" , ASTM A312 Gr.TP321, G44M, NACE+H2 (ITEM CODE G42NH)
Supply
3/4" NPTM x 1" BE, SCH XXS, L=4" , ASTM A312 Gr.TP321, G45M, NACE+H2 (ITEM CODE G25NH)
Supply
3/4" NPTM x 1" BE, SCH XXS, L=4" , ASTM A312 Gr.TP347, G47M, - (ITEM CODE G17)
Supply
3/4" NPTM x 1" BE, SCH 160, L=4" , ASTM A335 Gr.P9, G42G, PWHT (ITEM CODE G01)
Supply
1" NPTM x 1" BE, Sch. 160, L=4", ASTM A312 Gr.TP304L, B22K/B36K, NACE (ITEM CODE 201N)
Supply
1" NPTM x 1" BE, Sch. XXS, L=4", ASTM A335 Gr.P9, B3G (ITEM CODE 242)
Supply
SWAGE NIPPLE
1/2" NPTM x 3/4" PE, Sch. 160, L=4", ASTM A105N, B2A, IBR (ITEM CODE 99I)
Supply
1/2" NPTM x 1" BE, Sch. 160, L=4", ASTM A106 Gr.B, E2A, IBR (ITEM CODE 78I)
Supply
1/2" NPTM x 1" BE, Sch. 160, L=6", ASTM A106 Gr.B, E2A, IBR (ITEM CODE 79I)
Supply
1/2" NPTM x 3/4" PE, Sch. 160, L=4", ASTM A106 Gr.B, B1A, - (ITEM CODE 48)
Supply
1/2" NPTM x 3/4" PE, Sch. 160, L=4", ASTM A106 Gr.B, B10A, H2 (ITEM CODE 11H)
Supply
1/2" NPTM x 3/4" PE, Sch. 160, L=6", ASTM A106 Gr.B, B1A, - (ITEM CODE 49)
Supply
1/2" NPTM x 3/4" PE, Sch. XXS, L=4", ASTM A106 Gr.B, B35A, - (ITEM CODE 74)
Supply
1/2" NPTM x 1" BE, Sch.XXS, L=4", ASTM A106 Gr.B, E14A/E55A, NACE+H2+PWHT (ITEM CODE 35NH)
Supply
1/2" NPTM x 3/4" PE, Sch. 160, L=4", ASTM A106 Gr.B, D10A, H2+PWHT (ITEM CODE 32H)
Supply
1/2" NPTM x 3/4" PE, Sch. 160, L=6", ASTM A106 Gr.B, B10A, H2 (ITEM CODE 12H)
Supply
1/2" NPTM x 3/4" PE, Sch. 160, L=6", ASTM A106 Gr.B, D2A, IBR (ITEM CODE 51I)
Supply
1/2" NPTM x 3/4" PE, Sch. 160, L=6", ASTM A106 Gr.B, A2A, IBR (ITEM CODE 64I)
Supply
1/2" NPTM x 3/4" PE, Sch. 160, L=4", ASTM A106 Gr.B, D2A, IBR (ITEM CODE 48I)
Supply
1/2" NPTM x 3/4" PE, Sch. 160, L=4", ASTM A106 Gr.B, A2A, IBR (ITEM CODE 62I)
Supply
1/2" NPTM x 3/4" PE, Sch. XXS, L=4", ASTM A106 Gr.B, B37A/B14A, NACE+H2+PWHT (ITEM CODE 23NH)
Supply
1/2" NPTM x 3/4" BE, Sch. XXS, L=6", ASTM A106 Gr.B, B39A, NACE+PWHT (ITEM CODE 161N)
Supply
1/2" NPTM x 3/4" PE, Sch. 160, L=4", ASTM A106 Gr.B, A37A, NACE+PWHT (ITEM CODE 166N)
Supply
1/2" NPTM x 3/4" PE, Sch. XXS, L=4", ASTM A106 Gr.B, B36A, NACE+PWHT (ITEM CODE 03N)
Supply
1/2" NPTM x 3/4" PE, Sch. XXS, L=6", ASTM A106 Gr.B, B36A, NACE+PWHT (ITEM CODE 20N)
Supply
1/2" NPTM x 1" BE, Sch. 160, L=4", ASTM A106 Gr.B, F14A, NACE+H2+PWHT (ITEM CODE 47NH)
Supply
1/2" NPTM x 1" BE, Sch. 160, L=6", ASTM A106 Gr.B, F14A, NACE+H2+PWHT (ITEM CODE 48NH)
Supply
1/2" NPTM x 1" BE, Sch. XXS, L=6", ASTM A106 Gr.B, E14A, NACE+H2+PWHT (ITEM CODE 36NH)
Supply
1/2" NPTM x 3/4" PE, Sch. XXS, L=6", ASTM A106 Gr.B, B37A/B14A, NACE+H2+PWHT (ITEM CODE 24NH)
Supply
1/2" NPTM x 3/4" PE, Sch. 160, L=4", ASTM A182 Gr.F304, A3K, - (ITEM CODE 61)
Supply
1/2" NPTM x 3/4" PE, Sch. 160, L=6", ASTM A182 Gr.F304, A3K, - (ITEM CODE 62)
Supply
1/2" NPTM x 3/4" PE,, Sch. 160, L=4", ASTM A182 Gr.F304L, B22K, NACE (ITEM CODE 51N)
Supply
1/2" NPTM x 3/4" PE, Sch. 160, L=6", ASTM A182 Gr.F304L, B22K, NACE (ITEM CODE 52N)
Supply
1/2" NPTM x 3/4" PE, Sch. 160, L=4", ASTM A312 Gr.TP321, B18M, NACE (ITEM CODE 157N)
Supply
1/2" NPTM x 1" BE, Sch. 160, L=4", ASTM A312 Gr.TP321, G35M, NACE+H2 (ITEM CODE 59NH)
Supply
1/2" NPTM x 1" BE, Sch. 160, L=6", ASTM A312 Gr.TP321, G35M, NACE+H2 (ITEM CODE 60NH)
Supply
1/2" NPTM x 1" BE, Sch. 160, L=4", ASTM A335 Gr.P11, F1D, NACE+H2+PWHT (ITEM CODE 11NH)
Supply
1/2" NPTM x 1" BE, Sch. 160, L=6", ASTM A335 Gr.P11, F1D, NACE+H2+PWHT (ITEM CODE 12NH)
Supply
1/2" NPTM x 3/4" PE, Sch. 160, L=4", ASTM A335 Gr.P11, D14D, NACE+H2+PWHT (ITEM CODE 168NH)
Supply
1/2" NPTM x 3/4" PE, Sch. 160, L=4", ASTM A335 Gr.P11, D2D, IBR+PWHT (ITEM CODE 20I)
Supply
1/2" NPTM x 3/4" PE,, Sch. 160, L=6", ASTM A335 Gr.P11, D2D, IBR+PWHT (ITEM CODE 38I)
Supply
1/2" NPTM x 3/4" PE, Sch. 160, L=4", ASTM A335 Gr.P9, B1G, PWHT (ITEM CODE 35)
Supply
1/2" NPTM x 3/4" PE, Sch. 160, L=6", ASTM A335 Gr.P9, B1G, PWHT (ITEM CODE 36)
Supply
1/2" NPTM x 3/4" PE, Sch. 160, L=4", ASTM B622 UNS N10276, B18C, NACE (ITEM CODE 180N)
Supply
1/2" NPTM x 1" PE, Sch. 160, L=4", ASTM D1784 Cl.23447, J2AL, - (ITEM CODE 190)
Supply
1/2" NPTM x 3/4" PE, Sch. 160, L=4", IS 1239 Part 2, IS 1239 Part 1 Black, A3A, - (ITEM CODE 200)
Supply
3/4" NPTM x 1" BE, Sch. XXS, L=4", ASTM A106 Gr.B, G92A/G35A, - (ITEM CODE 95)
Supply
3/4" NPTM x 1" BE, Sch. XXS, L=4", ASTM A106 Gr.B, F36A, NACE+PWHT (ITEM CODE 63N)
Supply
3/4" NPTM x 1" BE, Sch. XXS, L=4", ASTM A106 Gr.B, F38A, NACE+PWHT (ITEM CODE 56N)
Supply
3/4" NPTM x 1" BE, Sch. 160, L=4", ASTM A106 Gr.B, F9A/F37A, NACE+H2+PWHT (ITEM CODE 137NH)
Supply
3/4" NPTM x 1" BE, Sch. 160, L=4", ASTM A106 Gr.B, G35M, NACE+H2 (ITEM CODE 155NH)
Supply
3/4" NPTM x 1" BE, Sch. 160, L=4", ASTM A312 Gr.TP304L, F28K, NACE (ITEM CODE 131N)
Supply
3/4" NPTM x 1" BE, Sch. 160, L=4", ASTM A312 Gr.TP304L, F41K, NACE+H2 (ITEM CODE 130NH)
Supply
3/4" NPTM x 1" BE, Sch. 160, L=4", ASTM A312 Gr.TP321, G35M, NACE+H2 (ITEM CODE 115NH)
Supply
3/4" NPTM x 1" BE, Sch. XXS, L=4", ASTM A335 Gr.P9, G1G, PWHT (ITEM CODE 174)
Supply
3/4" NPTM x 1" BE, Sch. 160, L=4", ASTM B423 UNS N08825 annealed, F15Q/F12Q, NACE+H2 (ITEM CODE 129NH)
Supply
1" X 1/2" NPTM, Sch 160, L= 4", ASTM A106 Gr.B Galv., A3AL, - (ITEM CODE 02)
Supply
1" X 1/2" NPTM, Sch 160, L= 6", ASTM A106 Gr.B Galv., A3AL, - (ITEM CODE 16)
Supply
BALL VALVES
3/4", metal seated,FB, SW, 800#, ASTM A105N, B1A, - (ITEM CODE 147)
Supply
3/4" , metal seated,FB, SW, 800#, ASTM A105N, B36A, NACE+PWHT (ITEM CODE 156N)
Supply
3/4", metal seated,FB, BW, 300#, ASTM A105N, B39A, NACE+PWHT (ITEM CODE 158N)
Supply
3/4", metal seated,FB, SW, 800#, ASTM A182 Gr.F304L, B22K, NACE (ITEM CODE 114N)
Supply
3/4", metal seated,FB, SW, 800#, ASTM A182 Gr.F9, B3G, PWHT (ITEM CODE 141)
Supply
1", metal seated, FB, BW 2500 #, ASTM A182 Gr.F321 , G43M, NACE+H2 (ITEM CODE G11NH)
Supply
1", metal seated, FB, BW 2500 #, ASTM A182 Gr.F321 , G45M, NACE+H2 (ITEM CODE G41NH)
Supply
1", metal seated, FB, BW 2500 #, ASTM A564 UNS N08825 , G47M, - (ITEM CODE G19)
Supply
1", metal seated, FB, BW 2500 #, ASTM A564 UNS N08825 , G44M, NACE+H2 (ITEM CODE G44NH)
Supply
GATE VALVES
1", NPTF, 800#, ASTM A105 Normalized Galvanized, A3AL, - (ITEM CODE 08)
Supply
1", BW, 1500#, ASTM A105N, E2A, IBR (ITEM CODE 75I)
Supply
1/2", NPTF, 800#, ASTM A105N, A1A/A3A/B1A, - (ITEM CODE 23)
Supply
3/4", SW, 800#, ASTM A105N, 35A/A1A/A3A/A93A, - (ITEM CODE 44)
Supply
3/4", SW, 800#, ASTM A105N, D35A, - (ITEM CODE 125)
Supply
1/2", SW, 800#, ASTM A105N, A2A/B2A, IBR (ITEM CODE 06I)
Supply
3/4", SW, 800#, ASTM A105N, A2A/B2A/D2A, IBR (ITEM CODE 46I)
Supply
3/4", SW, 800#, ASTM A105N, A37A/B36A, NACE+PWHT (ITEM CODE 07N)
Supply
3/4", BW, 300#, ASTM A105N, B39A, NACE+PWHT (ITEM CODE 159N)
Supply
3/4", SW, 800#, ASTM A105N, B37A, NACE+H2+PWHT (ITEM CODE 156NH)
Supply
3/4", SW, 800#, ASTM A182 Gr.F11 Cl.2, D2D, IBR+PWHT (ITEM CODE 18I)
Supply
3/4", SW, 800#, ASTM A182 Gr.F304, A3K, - (ITEM CODE 57)
Supply
3/4", SW, 800#, ASTM A182 Gr.F304L, B22K, NACE (ITEM CODE 181N)
Supply
3/4", SW, 800#, ASTM A182 Gr.F316L, B14N, - (ITEM CODE 133)
Supply
3/4", SW, 800#, ASTM A182 Gr.F321, B18M/B3M, NACE (ITEM CODE 54N)
Supply
3/4", SW, 800#, ASTM A182 Gr.F9, B1G/B3G, PWHT (ITEM CODE 31)
Supply
1", SE, 800#, ASTM D1784 Cl.23447, J2AL, - (ITEM CODE 187)
Supply
GLOBE VALVES
1", NPTF, 800#, ASTM A105 Normalized Galvanized, A3AL, - (ITEM CODE 15)
Supply
1", BW, 1500#, ASTM A105N, E2A, IBR (ITEM CODE 76I)
Supply
3/4", SW, 800#, ASTM A105N, B1A/B35A/D35A, - (ITEM CODE 43)
Supply
1/2", SW, 800#, ASTM A105N, B2A/A2A, IBR (ITEM CODE 32I)
Supply
3/4", SW, 800#, ASTM A105N, A2A/D2A, IBR (ITEM CODE 50I)
Supply
3/4", SW, 800#, ASTM A182 Gr.F11 Cl.2, D2D, IBR+PWHT (ITEM CODE 37I)
Supply
3/4", SW, 800#, ASTM A182 Gr.F304, A3K, - (ITEM CODE 56)
Supply
3/4", SW, 800#, ASTM A182 Gr.F321, B18M/B3M, NACE (ITEM CODE 98N)
Supply
3/4" , SW, 800#, ASTM A182 Gr.F9, B1G/B3G, PWHT (ITEM CODE 30)
Supply
GLOBE VALVES (Y TYPE)
1" , BW, 2500#, ASTM A105N, G35A, - (ITEM CODE 94)
Supply
3/4", SW, 800#, ASTM A105N, B35A, - (ITEM CODE 231)
Supply
1/2", NPTF, 800#, ASTM A105N, B36A, NACE+PWHT (ITEM CODE 202)
Supply
3/4", SW, 800#, ASTM A105N (H2), B10A, H2 (ITEM CODE 09H)
Supply
3/4", SW, 800#, ASTM A105N (H2), D10A, H2+PWHT (ITEM CODE 30H)
Supply
1", BW, 1500#, ASTM A105N (H2), E55A, H2 (ITEM CODE 40H)
Supply
1", BW, 1500#, ASTM A105N, F36A, NACE+PWHT (ITEM CODE 62N)
Supply
1" , BW, 1500#, ASTM A105N, F38A, NACE+PWHT (ITEM CODE 60N)
Supply
3/4", BW, 300#, ASTM A105N, B39A, NACE+PWHT (ITEM CODE 18N)
Supply
3/4", SW, 800#, ASTM A105N, A37A/B36A/A36A/B53A, NACE+PWHT (ITEM CODE 11N)
Supply
3/4", SW, 800#, ASTM A105N, B54A/B14A/B37A/B65A, NACE+H2+PWHT (ITEM CODE 21NH)
Supply
1" , BW, 1500#, ASTM A105N, E14A, NACE+H2+PWHT (ITEM CODE 33NH)
Supply
1", BW, 1500#, ASTM A105N, F14A/F9A/F37A, 1" Valve, (ITEM CODE 45NH)
Supply
1", BW, 1500#, ASTM A182 Gr.F11 Cl.2, F1D, NACE+H2+PWHT (ITEM CODE 09NH)
Supply
3/4", SW, 800#, ASTM A182 Gr.F11 Cl.2, D14D, NACE+H2+PWHT (ITEM CODE 167NH)
Supply
1", BW, 1500#, ASTM A182 Gr.F304L, F28K, NACE (ITEM CODE 130N)
Supply
3/4", SW, 800#, ASTM A182 Gr.F304L, D22K, NACE (ITEM CODE 119N)
Supply
3/4", SW, 800#, ASTM A182 Gr.F304L, B36K, NACE (ITEM CODE 47N)
Supply
1", BW, 1500#, ASTM A182 Gr.F304L, F14K, NACE+H2 (ITEM CODE 134NH)
Supply
3/4", SW, 800#, ASTM A182 Gr.F304L, B35K/B13K/B34K/D26K, NACE+H2 (ITEM CODE 80NH)
Supply
3/4", SW, 800#, ASTM A182 Gr.F321, B18M, NACE (ITEM CODE 115N)
Supply
1", BW, 2500#, ASTM A182 Gr.F321, G35M, NACE+H2 (ITEM CODE 57NH)
Supply
3/4", SW, 800#, ASTM A182 Gr.F321, D32M/D35M, NACE+H2 (ITEM CODE 105NH)
Supply
1", BW, 2500#, ASTM A182 Gr.F9, G1G, PWHT (ITEM CODE 173)
Supply
3/4", SW, 800#, ASTM A182 Gr.F9, B1G, PWHT (ITEM CODE 76)
Supply
3/4", SW, 800#, ASTM A182 Gr.F9, B3G, PWHT (ITEM CODE 155)
Supply
1", BW, 1500#, ASTM B564 UNS N08825, F15Q, NACE+H2 (ITEM CODE 66NH)
Supply
3/4", SW, 800#, ASTM B564 UNS N08825, B12Q, NACE+H2 (ITEM CODE 143NH)
Supply
3/4", SW, 800#, ASTM B564 UNS N10276, B18C, NACE (ITEM CODE 112N)
Supply
1", BW,2500 #, ASTM A182 Gr.F316L, G41N, PWHT (ITEM CODE G35)
Supply
1", BW,2500 #, ASTM A182 Gr.F9, G42G, PWHT (ITEM CODE G03)
Supply
1", BW,2500 #, ASTM B564 UNS N08825 , G45M, NACE+H2 (ITEM CODE G27NH)
Supply
45° ELBOWS
1" x 1", NPTF Ends, 3000#, ASTM A105 Normalized Galvanized, A3AL, - (ITEM CODE 13)
Supply
3/4" x 3/4", SW, 6000#, ASTM A105N, B1A, - (ITEM CODE 47)
Supply
3/4" x 3/4", SW, 9000#, ASTM A105N, B35A, - (ITEM CODE 73)
Supply
3/4" x 3/4", SW, 6000#, ASTM A105N, B10A, H2 (ITEM CODE 05H)
Supply
1/2" x 1/2", SW, 6000#, ASTM A105N, A2A/B2A, IBR (ITEM CODE 28I)
Supply
3/4" x 3/4", SW, 6000#, ASTM A105N, D2A/A2A, IBR (ITEM CODE 41I)
Supply
3/4" x 3/4, SW, 9000#, ASTM A105N, B36A, NACE+PWHT (ITEM CODE 21N)
Supply
3/4" x 3/4", SW, 9000#, ASTM A105N, B37A/B14A, NACE+H2+PWHT (ITEM CODE 17NH)
Supply
3/4" x 3/4", SW, 6000#, ASTM A182 Gr.F11 Cl.2, D2D, IBR+PWHT (ITEM CODE 13I)
Supply
3/4" x 3/4", SW, 6000#, ASTM A182 Gr.F304, A3K, - (ITEM CODE 60)
Supply
3/4" x 3/4", SW, 6000#, ASTM A182 Gr.F9, B1G, PWHT (ITEM CODE 34)
Supply
1" x 1", BW, 1500#, ASTM A234 Gr.WP11 Cl.1, F1D, NACE+H2+PWHT (ITEM CODE 05NH)
Supply
1" x 1", BW, 1500#, ASTM A234 Gr.WPB, E2A, IBR (ITEM CODE 71I)
Supply
1" x 1", BW, 1500#, ASTM A234 Gr.WPB, F14A, NACE+H2+PWHT (ITEM CODE 29NH)
Supply
1" x 1", BW, 2500#, ASTM A403 Gr.WP321, G35M, NACE+H2 (ITEM CODE 53NH)
Supply
90° ELBOWS
1" x 1", NPTF Ends, 3000#, ASTM A105 Normalized Galvanized, A3AL, - (ITEM CODE 14)
Supply
3/4" x 3/4", SW, 6000#, ASTM A105N, B1A/A3A, - (ITEM CODE 46)
Supply
3/4" x 3/4", SW, 9000#, ASTM A105N, D35A, - (ITEM CODE 72)
Supply
3/4" x 3/4", SW, 6000#, ASTM A105N, B10A, H2 (ITEM CODE 06H)
Supply
3/4" x 3/4", SW, 6000#, ASTM A105N, D10A, H2+PWHT (ITEM CODE 27H)
Supply
1/2" x 1/2", SW, 6000#, ASTM A105N, A2A/B2A, IBR (ITEM CODE 80I)
Supply
3/4" x 3/4", SW, 6000#, ASTM A105N, D2A/B2A, IBR (ITEM CODE 81I)
Supply
3/4" x 3/4", SW, 9000#, ASTM A105N, B36A/A37A, NACE+PWHT (ITEM CODE 04N)
Supply
3/4" x 3/4", SW, 9000#, ASTM A105N, B37A/B14A, NACE+H2+PWHT (ITEM CODE 18NH)
Supply
3/4" x 3/4", SW, 6000#, ASTM A335 Gr.P11, D14D, NACE+PWHT+H2 (ITEM CODE 162NH)
Supply
3/4" x 3/4", SW, 6000#, ASTM A335 Gr.P11, D2D, IBR+PWHT (ITEM CODE 88I)
Supply
3/4" x 3/4", SW, 6000#, ASTM A182 Gr.F304, A3K, - (ITEM CODE 59)
Supply
3/4" x 3/4", SW, 6000#, ASTM A182 Gr.F304L, B36K, NACE (ITEM CODE 79N)
Supply
3/4" x 3/4", SW, 3000#, ASTM A182 Gr.F304L, B22K, NACE (ITEM CODE 50N)
Supply
3/4" x 3/4", SW, 6000#, ASTM A182 Gr.F304L, D26K, NACE+H2 (ITEM CODE 83NH)
Supply
3/4" x 3/4", SW, 6000#, ASTM A182 Gr.F321, B18M/B3M, NACE (ITEM CODE 93N)
Supply
3/4" x 3/4", SW, 6000#, ASTM A182 Gr.F9, B1G, PWHT (ITEM CODE 33)
Supply
3/4" x 3/4", SW, 9000#, ASTM A182 Gr.F9, B3G, PWHT (ITEM CODE 142)
Supply
1" x 1", BW, 1500#, ASTM A234 Gr.WP11 Cl.1, F1D, NACE+H2+PWHT (ITEM CODE 06NH)
Supply
1" x 1", BW, 2500#, ASTM A234 Gr.WP9 Cl.1, G1G, PWHT (ITEM CODE 160)
Supply
1" x 1", BW, 2500#, ASTM A234 Gr.WPB, G92A, - (ITEM CODE 97)
Supply
1" x 1", BW, 1500#, ASTM A234 Gr.WPB, E2A, IBR (ITEM CODE 105I)
Supply
1" x 1", BW, 1500#, ASTM A234 Gr.WPB (H2), E55A, H2 (ITEM CODE 37H)
Supply
1" x 1", BW, 1500#, ASTM A234 Gr.WPB, F38A, NACE+PWHT (ITEM CODE 65N)
Supply
1" x 1", BW, 2500#, ASTM A403 Gr.WP321, G35M, NACE+H2 (ITEM CODE 54NH)
Supply
1" x 1", BW, 1500#, ASTM A234 Gr.WPB, E14A/F14A, NACE+H2+PWHT (ITEM CODE 42NH)
Supply
3/4" x 3/4", SW, 6000#, ASTM A312 Gr.TP304L, B13K, NACE+H2 (ITEM CODE 96NH)
Supply
1" x 1", BW, 1500#, ASTM B366 Gr.WPNICMC, F15Q, NACE+H2 (ITEM CODE 69NH)
Supply
3/4" x 3/4", SW, 6000#, ASTM B564 UNS N10276, B18C, NACE (ITEM CODE 178N)
Supply
1" x 1", SE, 6000#, ASTM D1784 Cl.23447, J2AL, - (ITEM CODE 189)
Supply
3/4" x 3/4", BW, 300#, ASTM A234 Gr.WPB, B38A/B39A, NACE+PWHT (ITEM CODE 31N)
Supply
1"x1", BW, 2500#, ASTM A403 Gr.WP321, G45M, NACE+H2 (ITEM CODE G57NH)
Supply
1"x1", BW, 2500#, ASTM A403 Gr.WP347, G47M, - (ITEM CODE G67)
Supply
1"x1", BW, 2500#, ASTM A234 Gr.WP9 Cl.1, G42G, PWHT (ITEM CODE G77)
Supply
EQUAL TEES
1/2" x 1/2" x 1/2", SW, 6000#, ASTM A105N , A2A, IBR (ITEM CODE 04I)
Supply
1/2" x 1/2" x 1/2", SW, 6000#, ASTM A105N , B2A, IBR (ITEM CODE 29I)
Supply
3/4" x 3/4" x 3/4", SW, 6000#, ASTM A105N , A2A, IBR (ITEM CODE 55I)
Supply
3/4" x 3/4" x 3/4", SW, 9000#, ASTM A105N , A37A, NACE+PWHT (ITEM CODE 164N)
Supply
3/4" x 3/4" x 3/4", SW, 3000#, ASTM A105N, A3A, - (ITEM CODE 196)
Supply
3/4" x 3/4" x 3/4", SW, 6000#, ASTM A105N , B10A, H2 (ITEM CODE 10H)
Supply
3/4" x 3/4" x 3/4", SW, 6000#, ASTM A105N, B1A, - (ITEM CODE 45)
Supply
3/4" x 3/4" x 3/4", SW, 6000#, ASTM A105N , B2A, NACE+PWHT (ITEM CODE 100I)
Supply
3/4" x 3/4" x 3/4", SW, 9000#, ASTM A105N, B35A, - (ITEM CODE 71)
Supply
3/4" x 3/4" x 3/4", SW, 9000#, ASTM A105N , B36A, NACE+PWHT (ITEM CODE 05N)
Supply
3/4" x 3/4" x 3/4", SW, 9000#, ASTM A105N , B37A/B14A, NACE+H2+PWHT (ITEM CODE 22NH)
Supply
3/4" x 3/4" x 3/4", BW, 300# , ASTM A105N , B39A, NACE+PWHT (ITEM CODE 192N)
Supply
3/4" x 3/4" x 3/4", SW, 6000#, ASTM A105N , D10A, H2+PWHT (ITEM CODE 31H)
Supply
3/4" x 3/4" x 3/4", SW, 6000#, ASTM A105N , D2A, IBR (ITEM CODE 42I)
Supply
3/4" x 3/4" x 3/4", SW, 6000#, ASTM A105N, D35A, - (ITEM CODE 123)
Supply
3/4" x 3/4" x 3/4", SW, 6000#, ASTM A182 Gr.F11 Cl.2, D2D, IBR+PWHT (ITEM CODE 14I)
Supply
3/4" x 3/4" x 3/4", SW, 6000#, ASTM A182 Gr.F11 Cl.2, D14D, NACE+PWHT+H2 (ITEM CODE 163NH)
Supply
3/4" x 3/4" x 3/4", SW, 6000#, ASTM A182 Gr.F304, A3K, - (ITEM CODE 58)
Supply
3/4" x 3/4" x 3/4", SW, 6000#, ASTM A182 Gr.F304L, B13K, NACE+H2 (ITEM CODE 92NH)
Supply
3/4" x 3/4" x 3/4", SW, 3000#, ASTM A182 Gr.F304L, B22K, NACE (ITEM CODE 49N)
Supply
3/4" x 3/4" x 3/4", SW, 6000#, ASTM A182 Gr.F304L, B34K, NACE+H2 (ITEM CODE 120NH)
Supply
3/4" x 3/4" x 3/4", SW, 6000#, ASTM A182 Gr.F304L, B35K, NACE+H2 (ITEM CODE 79NH)
Supply
3/4" x 3/4" x 3/4", SW, 6000#, ASTM A182 Gr.F304L, B36K, NACE (ITEM CODE 75N)
Supply
3/4" x 3/4" x 3/4", SW, 6000#, ASTM A182 Gr.F304L, D26K, NACE+H2 (ITEM CODE 147NH)
Supply
3/4" x 3/4" x 3/4", SW, 6000#, ASTM A182 Gr.F321, B18M/B3M, NACE (ITEM CODE 92N)
Supply
3/4" x 3/4" x 3/4", SW, 6000#, ASTM A182 Gr.F9, B1G, PWHT (ITEM CODE 32)
Supply
3/4" x 3/4" x 3/4", SW, 6000#, ASTM A182 Gr.F9, B3G, PWHT (ITEM CODE 139)
Supply
3/4" x 3/4" x 3/4", BW, 300# , ASTM A234 Gr.WPB, B38A, NACE+PWHT (ITEM CODE 30N)
Supply
3/4" x 3/4" x 3/4", SW, 3000#, ASTM B564 UNS N10276 , B18C, NACE (ITEM CODE 179N)
Supply
1" x 1" x 1", NPTF, 3000# , ASTM A105 Normalized Galvanized, A3AL, - (ITEM CODE 04)
Supply
1" x 1" x 1", BW, 1500#, ASTM A234 Gr.WP11 Cl.1, F1D, NACE+H2+PWHT (ITEM CODE 10NH)
Supply
1" x 1" x 1", BW, 2500#, ASTM A234 Gr.WP9 Cl.1, G1G, PWHT (ITEM CODE 164)
Supply
1" x 1" x 1", BW, 1500#, ASTM A234 Gr.WPB, E14A, NACE+H2+PWHT (ITEM CODE 34NH)
Supply
1" x 1" x 1", BW, 1500#, ASTM A234 Gr.WPB, E2A, IBR (ITEM CODE 77I)
Supply
1" x 1" x 1", BW, 1500#, ASTM A234 Gr.WPB, E55A, H2 (ITEM CODE 41H)
Supply
1" x 1" x 1", BW, 1500#, ASTM A234 Gr.WPB, F14A, NACE+H2+PWHT (ITEM CODE 46NH)
Supply
1" x 1" x 1", BW, 1500#, ASTM A234 Gr.WPB, F36A, NACE+PWHT (ITEM CODE 61N)
Supply
1" x 1" x 1", BW, 1500#, ASTM A234 Gr.WPB, F38A, NACE+PWHT (ITEM CODE 104N)
Supply
1" x 1" x 1", BW, 2500#, ASTM A234 Gr.WPB, G92A, - (ITEM CODE 93)
Supply
1" x 1" x 1", BW, 2500#, ASTM A403 Gr.WP321 , G35M, NACE+H2 (ITEM CODE 58NH)
Supply
1" x 1" x 1", BW, 1500#, ASTM B366 Gr.WPNICMC, F15Q, NACE+H2 (ITEM CODE 65NH)
Supply
1" x 1" x 1", SE, 6000#, ASTM D1784 Cl.23447, J2AL, - (ITEM CODE 186)
Supply
1" x 1" x 1", BW, 2500# , ASTM A403 Gr.WP321 , G45M, NACE+H2 (ITEM CODE G54NH)
Supply
1" x 1" x 1", BW, 2500# , ASTM A403 Gr.WP347, G47M, - (ITEM CODE G62)
Supply
1" x 1" x 1", BW, 2500# , ASTM A234 Gr.WP9 Cl.1, G42G, PWHT (ITEM CODE G72)
Supply
FLANGES
1/2", 150# RF/SW , ASTM A105N, A2A, IBR (ITEM CODE 05I)
Supply
1/2", 300# RF/SW , ASTM A105N, B2A, IBR (ITEM CODE 30I)
Supply
3/4", 150# RF/SW , ASTM A105N, A2A, IBR (ITEM CODE 56I)
Supply
3/4", 150# RF/SW , ASTM A105N, A37A, NACE+PWHT (ITEM CODE 167N)
Supply
3/4", 150# RF/SW , ASTM A105N, A3A, - (ITEM CODE 193)
Supply
3/4", 300# RF/SW , ASTM A105N, B10A, H2 (ITEM CODE 02H)
Supply
3/4", 300# RF/SW , ASTM A105N, B1A, - (ITEM CODE 40)
Supply
3/4", 300# RF/SW , ASTM A105N, B2A, IBR (ITEM CODE 93I)
Supply
3/4", 300# RF/SW , ASTM A105N, B35A, - (ITEM CODE 66)
Supply
3/4", 300# RF/SW , ASTM A105N, B36A, NACE+PWHT (ITEM CODE 10N)
Supply
3/4", 300# RF/SW , ASTM A105N, B37A/B14A, NACE+H2+PWHT (ITEM CODE 14NH)
Supply
3/4", 300# RF/BW , ASTM A105N, B38A/B39A, NACE+PWHT (ITEM CODE 27N)
Supply
3/4", 600# RF/SW , ASTM A105N, D10A, H2+PWHT (ITEM CODE 24H)
Supply
3/4", 600# RF/SW , ASTM A105N, D2A, IBR (ITEM CODE 43I)
Supply
3/4", 600# RF/SW , ASTM A105N, D35A, - (ITEM CODE 120)
Supply
3/4", 600# RTJ/SW, ASTM A182 Gr.F11 Cl.2, D14D, NACE+PWHT+H2 (ITEM CODE 164NH)
Supply
3/4", 600# RF/SW , ASTM A182 Gr.F11 Cl.2, D2D, IBR+PWHT (ITEM CODE 15I)
Supply
3/4", 300# RF/SW , ASTM A182 Gr.F304, A3K, - (ITEM CODE 53)
Supply
3/4", 300# RF/SW , ASTM A182 Gr.F304L, B13K/B34K/B35K, NACE+H2 (ITEM CODE 89NH)
Supply
3/4", 300# RF/SW , ASTM A182 Gr.F304L, B22K/B36K, NACE (ITEM CODE 42N)
Supply
3/4", 600# RF/SW , ASTM A182 Gr.F304L, D22K, NACE (ITEM CODE 116N)
Supply
3/4", 600# RF/SW , ASTM A182 Gr.F304L, D26K, NACE+H2 (ITEM CODE 101NH)
Supply
3/4", 300# RF/SW , ASTM A182 Gr.F321, B18M, NACE (ITEM CODE 89N)
Supply
3/4", 300# RTJ/SW, ASTM A182 Gr.F321, B3M, NACE (ITEM CODE 99N)
Supply
3/4", 600# RTJ/SW, ASTM A182 Gr.F321, D32M/D35M, NACE+H2 (ITEM CODE 106NH)
Supply
3/4", 300# RTJ/SW , ASTM A182 Gr.F9, B1G, PWHT (ITEM CODE 27)
Supply
3/4", 300# RTJ/SW , ASTM A182 Gr.F9, B3G, PWHT (ITEM CODE 136)
Supply
3/4", 300# RF/SW , ASTM B564 UNS N10276, B18C, NACE (ITEM CODE 175N)
Supply
1", 300# RF/NPTF, ASTM A105 Normalized Galvanized, A3AL, - (ITEM CODE 05)
Supply
1", 1500# RTJ/BW, ASTM A105N, E14A, NACE+H2+PWHT (ITEM CODE 26NH)
Supply
1", 1500# RTJ/BW, ASTM A105N, E2A, IBR (ITEM CODE 68I)
Supply
1", 1500# RTJ/BW, ASTM A105N, E55A, H2 (ITEM CODE 34H)
Supply
1", 1500# RTJ/BW, ASTM A105N, F14A/F37A/ F9A, NACE+H2+PWHT (ITEM CODE 38NH)
Supply
1", 1500# RTJ/BW, ASTM A105N, F36A/F38A, NACE+PWHT (ITEM CODE 84N)
Supply
1", 2500# RTJ/BW, ASTM A105N, G92A/G35A, - (ITEM CODE 90)
Supply
1", 1500# RTJ/BW, ASTM A182 Gr.F11 Cl.2, F1D, NACE+H2+PWHT (ITEM CODE 02NH)
Supply
1", 1500# RTJ/BW, ASTM A182 Gr.F304L, F14K, NACE+H2 (ITEM CODE 131NH)
Supply
1", 1500# RTJ/BW, ASTM A182 Gr.F304L, F28K, NACE (ITEM CODE 127N)
Supply
1", 2500# RTJ/BW, ASTM A182 Gr.F321, G35M, NACE+H2 (ITEM CODE 50NH)
Supply
1", 2500# RTJ/BW, ASTM A182 Gr.F9, G1G, PWHT (ITEM CODE 157)
Supply
1", 1500# RTJ/BW, ASTM B564 UNS N08825 , F15Q/F12Q, NACE+H2 (ITEM CODE 62NH)
Supply
1", 150# FF/SE , ASTM D1784 Cl.23447, J2AL, - (ITEM CODE 183)
Supply
1", 2500#, RTJ/BW , ASTM A182 Gr.F321, G43M, NACE+H2 (ITEM CODE G12NH)
Supply
1", 2500#, RTJ/BW , ASTM A182 Gr.F321, G44M, NACE+H2 (ITEM CODE G45NH)
Supply
1", 2500#, RTJ/BW , ASTM A182 Gr.F321, G45M, NACE+H2 (ITEM CODE G79NH)
Supply
1", 2500#, RTJ/BW , ASTM A182 Gr.F316L, G41N, PWHT (ITEM CODE G36)
Supply
1", 2500#, RTJ/BW , ASTM A182 Gr.F9, G42G, PWHT (ITEM CODE G78)
Supply
1", 2500#, RTJ/BW , ASTM A182 Gr.F347, G47M, - (ITEM CODE G80)
Supply
1", 300# RF/BW , ASTM A182 Gr.F304L, B22K/B36K, NACE (ITEM CODE 200N)
Supply
1", 300# RTJ/BW , ASTM A182 Gr.F9, B3G, PWHT (ITEM CODE 241)
Supply
REDUCING FLANGES
2"x 3/4", 300#, RF/SW, ASTM A105N, B36A, NACE+PWHT (ITEM CODE 36N)
Supply
3"x 3/4", 300#, RF/SW, ASTM A105N, B1A, - (ITEM CODE 81)
Supply
3"x 3/4", 300#, RF/SW, ASTM A105N, B35A, - (ITEM CODE 85)
Supply
3"x 3/4", 300#, RF/SW, ASTM A105N, B36A, NACE+PWHT (ITEM CODE 22N)
Supply
3"x 3/4", 300#, RF/BW, ASTM A105N, B38A, NACE+PWHT (ITEM CODE 32N)
Supply
3"x 3/4", 600#, RF/SW, ASTM A105N, D35A, - (ITEM CODE 129)
Supply
3"x 3/4", 300#, RF/SW, ASTM A182 Gr.F304L , B35K/B13K/B34K, NACE+H2 (ITEM CODE 84NH)
Supply
3"x 3/4", 300#, RF/SW, ASTM A182 Gr.F304L , B36K, NACE (ITEM CODE 80N)
Supply
3"x 3/4", 600#, RF/SW, ASTM A182 Gr.F304L , D26K, NACE+H2 (ITEM CODE 150NH)
Supply
3"x 3/4", 300#, RF/SW, ASTM A182 Gr.F321 , B18M, NACE (ITEM CODE 94N)
Supply
3"x 3/4", 300#, RTJ/SW , ASTM A182 Gr.F321 , B3M, NACE (ITEM CODE 101N)
Supply
3"x 3/4", 300#, RTJ /SW, ASTM A182 Gr.F9, B1G, PWHT (ITEM CODE 77)
Supply
3"x 3/4", 300#, RTJ /SW, ASTM A182 Gr.F9, B3G, PWHT (ITEM CODE 143)
Supply
3"x 1", 1500#, RTJ/BW, ASTM A105N, F36A/F38A, NACE+PWHT (ITEM CODE 66N)
Supply
3"x 1", 2500#, RTJ/BW, ASTM A105N, G92A, - (ITEM CODE 98)
Supply
3"x 1", 2500#, RTJ/BW, ASTM A182 Gr.F321 , G35M, NACE+H2 (ITEM CODE 140NH)
Supply
3"x 1", 2500#, RTJ/BW, ASTM A182 Gr.F9, G1G, PWHT (ITEM CODE 167)
Supply
3"x 1", 1500#, WN RTJ, ASTM B564 UNS N08825 , F15Q, NACE+H2 (ITEM CODE 70NH)
Supply
1"x 3/4", 300#, RF/SW, ASTM A105N, B35A (ITEM CODE 235 )
Supply
1"x 3/4", 300#, RF/SW, ASTM A105N, B35A (ITEM CODE 238 )
Supply
BLIND FLANGES
3/4", 600# RF , ASTM A105N, D35A, - (ITEM CODE 127)
Supply
3/4", 600# RF , ASTM A105N , D10A, H2+PWHT (ITEM CODE 29H)
Supply
3/4", 600# RF , ASTM A105N , D2A, IBR (ITEM CODE 49I)
Supply
3/4" , 300# RF, ASTM A105N , B36A, NACE+PWHT (ITEM CODE 15N)
Supply
3/4" , 600# RTJ, ASTM A182 Gr.F11 Cl.2, D14D, NACE+H2+PWHT (ITEM CODE 169NH)
Supply
3/4" , 600# RF , ASTM A182 Gr.F11 Cl.2, D2D, IBR+PWHT (ITEM CODE 21I)
Supply
3/4" , 600# RF , ASTM A182 Gr.F304L, D22K, NACE (ITEM CODE 121N)
Supply
3/4" , 600# RF , ASTM A182 Gr.F304L , D26K, NACE+H2 (ITEM CODE 103NH)
Supply
3/4" , 300# RF , ASTM A182 Gr.F304L , B13K/B35K, NACE+H2 (ITEM CODE 114NH)
Supply
3/4" , 600# RTJ, ASTM A182 Gr.F321 , D32M/D35M, NACE+H2 (ITEM CODE 110NH)
Supply
1", 1500# RTJ, ASTM A105N, E2A, IBR (ITEM CODE 73I)
Supply
1", 2500# RTJ, ASTM A105N, G92A/G35A, - (ITEM CODE 96)
Supply
1", 1500# RTJ, ASTM A105N , E55A, H2 (ITEM CODE 39H)
Supply
1", 1500# RTJ, ASTM A105N , F36A, NACE+PWHT (ITEM CODE 64N)
Supply
1", 1500# RTJ, ASTM A105N , F38A, NACE+PWHT (ITEM CODE 85N)
Supply
1", 1500# RTJ, ASTM A105N , E14A/F14A/ F9A/F37A, NACE+H2+PWHT (ITEM CODE 44NH)
Supply
1", 1500# RTJ, ASTM A182 Gr.F11 Cl.2, F1D, NACE+H2+PWHT (ITEM CODE 08NH)
Supply
1", 1500# RTJ, ASTM A182 Gr.F304L , F28K, NACE (ITEM CODE 132N)
Supply
1", 1500# RTJ, ASTM A182 Gr.F304L , F14K, NACE+H2 (ITEM CODE 135NH)
Supply
1", 2500# RTJ, ASTM A182 Gr.F321 , G35M, NACE+H2 (ITEM CODE 56NH)
Supply
1", 2500# RTJ, ASTM A182 Gr.F9, G1G, PWHT (ITEM CODE 175)
Supply
1", 1500# RTJ, ASTM B564 UNS N08825 , F15Q/F12Q, NACE+H2 (ITEM CODE 74NH)
Supply
1", 2500# RTJ, ASTM A182 Gr.F316L, G41N, PWHT (ITEM CODE G37)
Supply
1", 2500# RTJ, ASTM A182 Gr.F321 , G43M, NACE+H2 (ITEM CODE G13NH)
Supply
1", 2500# RTJ, ASTM A182 Gr.F321 , G45M, NACE+H2 (ITEM CODE G29NH)
Supply
1", 2500# RTJ, ASTM A182 Gr.F321 , G44M, NACE+H2 (ITEM CODE G46NH)
Supply
1", 2500# RTJ, ASTM A182 Gr.F347, G47M, - (ITEM CODE G21)
Supply
1", 2500# RTJ, ASTM A182 Gr.F9, G42G, PWHT (ITEM CODE G05)
Supply
GASKETS
1/2", 150# RF , Inner AISI 316L/Outer CS, A2A, IBR (ITEM CODE 07I)
Supply
1/2", 300# RF , Inner AISI 316L/Outer CS, B2A, IBR (ITEM CODE 33I)
Supply
3/4", 600#, RTJ, 1.25 Cr-0.5 Mo, D14D, NACE+H2+PWHT (ITEM CODE 165NH)
Supply
3/4", 300#, RTJ, 9 Cr-1 Mo, B1G, PWHT (ITEM CODE 28)
Supply
3/4", 300#, RTJ, 9 Cr-1 Mo, B3G, PWHT (ITEM CODE 137)
Supply
3/4", 300# RF, ASTM A182 GR.F304, A3K, - (ITEM CODE 54)
Supply
3/4", 300# RF, Inner AISI 316L/Outer CS, B36A, NACE+PWHT (ITEM CODE 13N)
Supply
3/4", 150# RF , Inner AISI 316L/Outer CS, A2A, IBR (ITEM CODE 57I)
Supply
3/4", 300# RF, Inner AISI 316L/Outer CS, A37A, NACE+PWHT (ITEM CODE 168N)
Supply
3/4", 150# RF, Inner AISI 316L/Outer CS, A3A, - (ITEM CODE 194)
Supply
3/4", 300# RF , Inner AISI 316L/Outer CS, B10A, H2 (ITEM CODE 03H)
Supply
3/4", 300# RF, Inner AISI 316L/Outer CS, B13K/B35K, NACE+H2 (ITEM CODE 90NH)
Supply
3/4", 300# RF , UNS N10276/Graphite, B18C, NACE (ITEM CODE 176N)
Supply
3/4", 300# RF, Inner AISI 321/Outer CS, B18M, NACE (ITEM CODE 90N)
Supply
3/4", 300# RF, Inner AISI 316L/Outer CS, B1A, - (ITEM CODE 41)
Supply
3/4", 300# RF, Inner AISI 316L/Outer CS, B22K, NACE (ITEM CODE 48N)
Supply
3/4", 300# RF, Inner AISI 316L/Outer CS, B34K, NACE+H2 (ITEM CODE 118NH)
Supply
3/4", 300# RF, Inner AISI 316L/Outer CS, B35A, - (ITEM CODE 67)
Supply
3/4", 300# RF, Inner AISI 316L/Outer CS, B35K, NACE+H2 (ITEM CODE 77NH)
Supply
3/4", 300# RF, Inner AISI 316L/Outer CS, B36K, NACE (ITEM CODE 73N)
Supply
3/4", 300# RF, Inner AISI 316L/Outer CS, B38A/B39A, NACE+PWHT (ITEM CODE 28N)
Supply
3/4", 300# RF , Inner AISI 316L/Outer CS, B2A, IBR (ITEM CODE 94I)
Supply
3/4", 300# RF , Inner AISI 316L/Outer CS, B14A, NACE+H2+PWHT (ITEM CODE 15NH)
Supply
3/4", 300# RTJ, AISI 321, B3M, NACE (ITEM CODE 100N)
Supply
3/4", 300# RF , Inner AISI 316L/Outer CS, D10A, H2+PWHT (ITEM CODE 25H)
Supply
3/4", 600# RF, Inner AISI 316L/Outer CS, D22K, NACE (ITEM CODE 117N)
Supply
3/4", 600# RF, Inner AISI 316L/Outer CS, D26K, NACE+H2 (ITEM CODE 102NH)
Supply
3/4", 600# RF , Inner AISI 316L/Outer CS, D2A, IBR (ITEM CODE 44I)
Supply
3/4", 600# RF , Inner AISI 316L/Outer CS, D2D, IBR+PWHT (ITEM CODE 16I)
Supply
3/4", 600# RTJ, AISI 321, D32M/D35M, NACE+H2 (ITEM CODE 107NH)
Supply
3/4", 600# RF, Inner AISI 316L/Outer CS, D35A, - (ITEM CODE 121)
Supply
1", 1500#, RTJ , 1.25 Cr-0.5 Mo, F1D, NACE+H2+PWHT (ITEM CODE 03NH)
Supply
1", 2500#,RTJ , 9 Cr-1 Mo, G1G, PWHT (ITEM CODE 158)
Supply
1", 300# RF, Inner AISI 316L/Outer CS, A3AL, - (ITEM CODE 06)
Supply
1", 1500#,RTJ , Soft Iron, E14A, NACE+H2+PWHT (ITEM CODE 27NH)
Supply
1", 1500#,RTJ , Soft Iron, E2A, IBR (ITEM CODE 69I)
Supply
1", 1500#,RTJ , Soft Iron, E55A, H2 (ITEM CODE 35H)
Supply
1", 1500#,RTJ , UNS N08825, F12Q/F15Q, NACE+H2 (ITEM CODE 63NH)
Supply
1", 1500#,RTJ , Soft Iron, F14A/F37A/ F9A, NACE+H2+PWHT (ITEM CODE 39NH)
Supply
1", 1500#,RTJ , AISI 304L, F14K, NACE+H2 (ITEM CODE 132NH)
Supply
1", 1500#,RTJ , AISI 304L, F28K, NACE (ITEM CODE 128N)
Supply
1", 1500#,RTJ , Soft Iron, F36A/F38A, NACE+PWHT (ITEM CODE 58N)
Supply
1", 2500#,RTJ , AISI 321, G35M, NACE+H2 (ITEM CODE 51NH)
Supply
1", 2500#,RTJ , Soft Iron, G92A/G35A, - (ITEM CODE 91)
Supply
1", 150# FF,, EPDM, J2AL, - (ITEM CODE 184)
Supply
2", 300# RF, Inner AISI 316L/Outer CS, B36A, NACE+PWHT (ITEM CODE 37N)
Supply
3", 300#, RTJ , 9 Cr-1 Mo, B1G, PWHT (ITEM CODE 78)
Supply
3", 600#, RTJ , 9 Cr-1 Mo, B1G, PWHT (ITEM CODE 117)
Supply
3", 300#, RTJ , 9 Cr-1 Mo, B3G, PWHT (ITEM CODE 144)
Supply
3", 600#, RTJ , 9 Cr-1 Mo, B3G, PWHT (ITEM CODE 152)
Supply
3", 2500#,RTJ , 9 Cr-1 Mo, G1G, PWHT (ITEM CODE 168)
Supply
3", 300# RF, Inner AISI 316L/Outer CS, B13K, NACE+H2 (ITEM CODE 98NH)
Supply
3", 300# RF, Inner AISI 321/Outer CS, B18M, NACE (ITEM CODE 95N)
Supply
3", 300# RF, Inner AISI 316L/Outer CS, B1A, - (ITEM CODE 82)
Supply
3", 300# RF, Inner AISI 316L/Outer CS, B34K, NACE+H2 (ITEM CODE 126NH)
Supply
3", 300# RF, Inner AISI 316L/Outer CS, B35A, - (ITEM CODE 86)
Supply
3", 300# RF, Inner AISI 316L/Outer CS, B35K, NACE+H2 (ITEM CODE 85NH)
Supply
3", 300# RF, Inner AISI 316L/Outer CS, B36A, NACE+PWHT (ITEM CODE 23N)
Supply
3", 300# RF, Inner AISI 316L/Outer CS, B36K, NACE (ITEM CODE 81N)
Supply
3", 300# RF, Inner AISI 316L/Outer CS, B38A, NACE+PWHT (ITEM CODE 33N)
Supply
3", 300# RTJ, AISI 321, B3M, NACE (ITEM CODE 102N)
Supply
3", 600# RF, Inner AISI 316L/Outer CS, D26K, NACE+H2 (ITEM CODE 151NH)
Supply
3", 600# RF, Inner AISI 316L/Outer CS, D35A, - (ITEM CODE 130)
Supply
3", 1500#,RTJ , UNS N08825, F15Q, NACE+H2 (ITEM CODE 71NH)
Supply
3", 1500#,RTJ , Soft Iron, F36A/F38A, NACE+PWHT (ITEM CODE 67N)
Supply
3", 2500#,RTJ , AISI 321, G35M, NACE+H2 (ITEM CODE 141NH)
Supply
3", 2500#,RTJ , Soft Iron, G92A, - (ITEM CODE 99)
Supply
1", 2500#,RTJ , 9 Cr-1 Mo,, G42G, PWHT (ITEM CODE G81)
Supply
1", 2500#,RTJ , AISI 347, G43M, NACE+H2 (ITEM CODE G14NH)
Supply
1", 2500#,RTJ , AISI 321, G45M, NACE+H2 (ITEM CODE G82NH)
Supply
1", 2500#,RTJ , AISI 347, G47M, - (ITEM CODE G83)
Supply
1", 2500#,RTJ , AISI 321, G44M, NACE+H2 (ITEM CODE G47NH)
Supply
1", 2500#,RTJ , AISI 316L, G41N, PWHT (ITEM CODE G38)
Supply
1", 600# RF, Inner AISI 316L/Outer CS, D35A (ITEM CODE 239)
Supply
1", 300#, RTJ, 9 Cr-1 Mo, B3G, PWHT (ITEM CODE 243)
Supply
STUD BOLTS & NUTS Nos. of stud bolts and hexagonal nuts for each stud as described below.
0.5" x 70 mm, Stud bolt with 2 heavy hexagonal nut, (4 nos in 1 set), A193 Gr.B7/A194 Gr.2H, A2A, IBR (ITEM CODE 08I)
Supply
0.5" x 70 mm Stud bolt, Stud bolt with 2 heavy hexagonal nut, (4 nos in 1 set), A193 Gr.B7/A194 Gr.2H, B2A, IBR (ITEM CODE 34I)
Supply
0.5" x 70 mm, Stud bolt with 2 heavy hexagonal nut, (4 nos in 1 set), A193 Gr.B7/A194 Gr.2H, A2A, IBR (ITEM CODE 58I)
Supply
0.5" x 70 mm, Stud bolt with 2 heavy hexagonal nut, (4 nos in 1 set), A193 Gr.B7M/A194 Gr.2HM, A37A, NACE+PWHT (ITEM CODE 169N)
Supply
0.5" x 70 mm, Stud bolt with 2 heavy hexagonal nut, (4 nos in 1 set), A193 Gr.B7/A194 Gr.2H, A3A, - (ITEM CODE 195)
Supply
0.5" x 70 mm, Stud bolt with 2 heavy hexagonal nut, (4 nos in 1 set), ASTM A182 Gr.F304, A3K, - (ITEM CODE 55)
Supply
0.625" x 80 mm, Stud bolt, Stud bolt with 2 heavy hexagonal nut, (4 nos in 1 set), A193 Gr.B7/A194 Gr.2H, B10A, H2 (ITEM CODE 04H)
Supply
0.625" x 80 mm, Stud bolt with 2 heavy hexagonal nut, (4 nos in 1 set), A193 Gr.B7M/A194 Gr.2HM (NACE)+Phosphate treatment, B13K/B35K, NACE+H2 (ITEM CODE 91NH)
Supply
0.625" x 80 mm, Stud bolt with 2 heavy hexagonal nut, (4 nos in 1 set),, A193 Gr.B7M/A194 Gr.2HM (NACE) + Phosphate treatment, B18C, NACE (ITEM CODE 177N)
Supply
0.625" x 80 mm, Stud bolt with 2 heavy hexagonal nut, (4 nos in 1 set), A453 Gr.660 Cl.A (NACE)+Phosphate treatment, B18M/B3M, NACE (ITEM CODE 91N)
Supply
0.625" x 80 mm, Stud bolt with 2 heavy hexagonal nut, (4 nos in 1 set), A193 Gr.B7/A194 Gr.2H, B1A, - (ITEM CODE 42)
Supply
0.625" x 90 mm", Stud bolt with 2 heavy hexagonal nut, (4 nos in 1 set) A193 Gr.B16/A194 Gr.16, B1G, PWHT (ITEM CODE 29)
Supply
0.625" x 80 mm, Stud bolt with 2 heavy hexagonal nut, (4 nos in 1 set), ASTM A182 Gr.F304L (NACE), B22K, NACE (ITEM CODE 46N)
Supply
0.625" x 80 mm, Stud bolt with 2 heavy hexagonal nut, (4 nos in 1 set), A193 Gr.B7/A194 Gr.2H, B2A, IBR (ITEM CODE 95I)
Supply
0.625" x 80 mm, Stud bolt with 2 heavy hexagonal nut, (4 nos in 1 set), A193 Gr.B7M/A194 Gr.2HM (NACE) + Phosphate, B34K, NACE+H2 (ITEM CODE 119NH)
Supply
0.625" x 80 mm, Stud bolt with 2 heavy hexagonal nut, (4 nos in 1 set), A193 Gr.B7/A194 Gr.2H, B35A, - (ITEM CODE 68)
Supply
0.625" x 80 mm, Stud bolt with 2 heavy hexagonal nut, (4 nos in 1 set), A193 Gr.B7M/A194 Gr.2HM (NACE)+Phosphate treatment, B35K, NACE+H2 (ITEM CODE 78NH)
Supply
0.625" x 80 mm, Stud bolt with 2 heavy hexagonal nut, (4 nos in 1 set), A193 Gr.B7M/A194 Gr.2HM, Sour Service + Phosphate, B36A, NACE+PWHT (ITEM CODE 14N)
Supply
0.625" x 80 mm, Stud bolt with 2 heavy hexagonal nut, (4 nos in 1 set), A193 Gr.B7M/A194 Gr.2HM (NACE) + Phosphate treatment, B36K, NACE (ITEM CODE 74N)
Supply
0.625" x 80 mm, Stud bolt with 2 heavy hexagonal nut, (4 nos in 1 set), A193 Gr.B7M/A194 Gr.2HM+Phosphate treatment (NACE), B14A, NACE+H2+PWHT (ITEM CODE 16NH)
Supply
0.625" x 80 mm, Stud bolt with 2 heavy hexagonal nut, (4 nos in 1 set), A193 Gr.B7M/A194 Gr.2HM, Sour Service + Phosphate, B38A/B39A, NACE+PWHT (ITEM CODE 29N)
Supply
0.625" x 90 mm, Stud bolt with 2 heavy hexagonal nut, (4 nos in 1 set), A193 Gr.B16/A194 Gr.16, B3G, PWHT (ITEM CODE 138)
Supply
0.625" x 100 mm, Stud bolt with 2 heavy hexagonal nut, (4 nos in 1 set), A193 Gr.B7/A194 Gr.2H, D10A, H2+PWHT (ITEM CODE 26H)
Supply
0.625" x 100 mm, Stud bolt with 2 heavy hexagonal nut, (4 nos in 1 set), A193 Gr.B16/A194 Gr.16 (NACE) +Phosphate treatment, D14D, NACE+PWHT+H2 (ITEM CODE 166NH)
Supply
0.625" x 100 mm, Stud bolt with 2 heavy hexagonal nut, (4 nos in 1 set), A193 Gr.B7M/A194 Gr.2HM, D22K, NACE (ITEM CODE 118N)
Supply
0.625" x 100 mm, Stud bolt with 2 heavy hexagonal nut, (4 nos in 1 set),, A193 Gr.B7/A194 Gr.2H, D2A, IBR (ITEM CODE 45I)
Supply
0.625" x 100 mm, Stud bolt with 2 heavy hexagonal nut, (4 nos in 1 set), A193 Gr.B16/A194 Gr.16, D2D, IBR+PWHT (ITEM CODE 17I)
Supply
0.625" x 100 mm, Stud bolt with 2 heavy hexagonal nut, (4 nos in 1 set),ASME B18.2.1/ASME B18.2.2, A453 Gr.660 Cl.A (NACE)+Phosphate treatment, D32M/D35M, NACE+H2 (ITEM CODE 108NH)
Supply
0.625" x 100 mm, Stud bolt with 2 heavy hexagonal nut, (4 nos in 1 set), A193 Gr.B7/A194 Gr.2H, D35A, - (ITEM CODE 122)
Supply
0.5" x 70 mm, Stud bolt with 2 heavy hexagonal nut, (4 nos in 1 set), A193 Gr.B7/A194 Gr.2H, Galv., A3AL, - (ITEM CODE 07)
Supply
0.875" x 140 mm, Stud bolt with 3 heavy hexagonal nut, (4 nos in 1 set), A193 Gr.B7M/A194 Gr.2HM+Phosphate treatment (NACE), E14A, NACE+H2+PWHT (ITEM CODE 28NH)
Supply
0.875" x 140 mm, Stud bolt with 3 heavy hexagonal nut, (4 nos in 1 set), A193 Gr.B7/A194 Gr.2H, E2A, IBR (ITEM CODE 70I)
Supply
0.875" x 140 mm, Stud bolt with 3 heavy hexagonal nut, (4 nos in 1 set), A193 Gr.B7/A194 Gr.2H, E55A, H2 (ITEM CODE 36H)
Supply
0.875" x 140 mm, Stud bolt with 3 heavy hexagonal nut, (4 nos in 1 set), A193 Gr.B7M/A194 Gr.2HM (NACE)+Phosphate treatment, F12Q/F15Q/F37A/ F9A, NACE+H2 (ITEM CODE 64NH)
Supply
0.875" x 140 mm, Stud bolt with 3 heavy hexagonal nut, (4 nos in 1 set), A193 Gr.B7M/A194 Gr.2HM+Phosphate treatment (NACE), F14A, NACE+H2+PWHT (ITEM CODE 40NH)
Supply
0.875" x 140 mm, Stud bolt with 3 heavy hexagonal nut, (4 nos in 1 set), A193 Gr.B7M/A194 Gr.2HM (NACE)+Phosphate treatment, F14K, NACE+H2 (ITEM CODE 133NH)
Supply
0.875" x 140 mm, Stud bolt with 3 heavy hexagonal nut, (4 nos in 1 set), A193 Gr.B16/A194 Gr.16+Phosphate treatment (NACE), F1D, NACE+H2+PWHT (ITEM CODE 04NH)
Supply
0.875" x 140 mm, Stud bolt with 3 heavy hexagonal nut, (4 nos in 1 set), A193 Gr.B7M/A194 Gr.2HM, Sour Service + Phosphate, F28K, NACE (ITEM CODE 129N)
Supply
0.875" x 140 mm, Stud bolt with 3 heavy hexagonal nut, A193 Gr.B7M/A194 Gr.2HM, Sour Service + Phosphate, F36A/F38A, NACE+PWHT (ITEM CODE 59N)
Supply
0.875" x 150 mm, Stud bolt with 3 heavy hexagonal nut, (4 nos in 1 set), A193 Gr.B16/A194 Gr.16, G1G, PWHT (ITEM CODE 159)
Supply
0.875" x 150 mm, Stud bolt with 3 heavy hexagonal nut, (4 nos in 1 set), A453 Gr.660 Cl.A+Phosphate treatment (NACE), G35M, NACE+H2 (ITEM CODE 52NH)
Supply
0.875" x 150 mm, Stud bolt with 3 heavy hexagonal nut, (4 nos in 1 set), A193 Gr.B7/A194 Gr.2H, G92A/G35A, - (ITEM CODE 92)
Supply
0.5" x 70 mm, Stud bolt with 2 heavy hexagonal nut, (4 nos in 1 set), A193 Gr.B7/A194 Gr.2H, J2AL, - (ITEM CODE 185)
Supply
0.625" x 100 mm, Stud bolt with 2 heavy hexagonal nut, (8 nos in 1 set), A193 Gr.B7M/A194 Gr.2HM, Sour Service + Phosphate, B36A, NACE+PWHT (ITEM CODE 38N)
Supply
0.75" x 170 mm, stud bolt with 2 heavy hexagonal nuts (8 nos in 1 set), A193 Gr.B7M/A194 Gr.2HM (NACE)+Phosphate treatment, B13K, NACE+H2 (ITEM CODE 99NH)
Supply
0.75" x 170 mm, Stud bolt with 2 heavy hexagonal nut, (8 nos in 1 set), A453 Gr.660 Cl.A (NACE)+Phosphate treatment, B3M, NACE (ITEM CODE 96N)
Supply
0.75" x 170 mm, Stud bolt with 2 heavy hexagonal nut, (8 nos in 1 set), A193 Gr.B7/A194 Gr.2H, B1A, - (ITEM CODE 83)
Supply
0.75" x 170 mm, Stud bolt with 2 heavy hexagonal nut, (8 nos in 1 set), A193 Gr.B16/A194 Gr.16, B1G, PWHT (ITEM CODE 79)
Supply
0.75" x 170 mm, Stud bolt with 2 heavy hexagonal nut, (8 nos in 1 set), A193 Gr.B7M/A194 Gr.2HM (NACE) + Phosphate, B34K, NACE+H2 (ITEM CODE 127NH)
Supply
0.75" x 170 mm, Stud bolt with 2 heavy hexagonal nut, (8 nos in 1 set), A193 Gr.B7/A194 Gr.2H, B35A, - (ITEM CODE 87)
Supply
0.75" x 170 mm, Stud bolt with 2 heavy hexagonal nut, (8 nos in 1 set), A193 Gr.B7M/A194 Gr.2HM (NACE)+Phosphate treatment, D26K, NACE+H2 (ITEM CODE 86NH)
Supply
0.75" x 170 mm, Stud bolt with 2 heavy hexagonal nut, (8 nos in 1 set), A193 Gr.B7M/A194 Gr.2HM, Sour Service + Phosphate, B36A, NACE+PWHT (ITEM CODE 24N)
Supply
0.75" x 170 mm, Stud bolt with 2 heavy hexagonal nut, (8 nos in 1 set), A193 Gr.B7M/A194 Gr.2HM (NACE) + Phosphate treatment, B36K, NACE (ITEM CODE 82N)
Supply
0.75" x 170 mm, Stud bolt with 2 heavy hexagonal nut, (8 nos in 1 set), A193 Gr.B7M/A194 Gr.2HM, Sour Service + Phosphate, B38A, NACE+PWHT (ITEM CODE 34N)
Supply
0.75" x 170 mm, Stud bolt with 3 heavy hexagonal nut, (8 nos in 1 set), A193 Gr.B16/A194 Gr.16, B3G, PWHT (ITEM CODE 145)
Supply
0.75" x 140 mm, Stud bolt with 2 heavy hexagonal nut, (8 nos in 1 set), A193 Gr.B7/A194 Gr.2H, D35A, - (ITEM CODE 131)
Supply
1.125" x 260 mm, Stud bolt with 3 heavy hexagonal nut, (8 nos in 1 set), A193 Gr.B7M/A194 Gr.2HM (NACE)+Phosphate treatment, F15Q, NACE+H2 (ITEM CODE 72NH)
Supply
1.125" x 260 mm, Stud bolt with 3 heavy hexagonal nut, (8 nos in 1 set), A193 Gr.B7M/A194 Gr.2HM, Sour Service + Phosphate, F36A/F38A, NACE+PWHT (ITEM CODE 68N)
Supply
1.125" x 320 mm, Stud bolt with 3 heavy hexagonal nut, (8 nos in 1 set), A193 Gr.B16/A194 Gr.16, G1G, PWHT (ITEM CODE 169)
Supply
1.125" x 320 mm, Stud bolt with 2 heavy hexagonal nut, (8 nos in 1 set), A453 Gr.660 Cl.A(NACE)+Phosphate treatment , G35M, NACE+H2 (ITEM CODE 142NH)
Supply
1.125" x 320 mm, Stud bolt with 3 heavy hexagonal nut, (8 nos in 1 set), A193 Gr.B7/A194 Gr.2H, G92A, - (ITEM CODE 100)
Supply
0.875" x 150 mm, Stud bolt with 3 heavy hexagonal nuts, (4 nos in 1 set), A193 Gr.B16/A194 Gr.16, G42G, PWHT (ITEM CODE G08)
Supply
0.875" x 150 mm, Stud bolt with 3 heavy hexagonal nuts, (4 nos in 1 set), A453 Gr.660 Cl.A,, G43M, NACE+H2 (ITEM CODE G16NH)
Supply
1.125" x 320 mm, Stud bolt with 3 heavy hexagonal nut, (8 nos in 1 set), A193 Gr.B16/A194 Gr.16, G42G, PWHT (ITEM CODE G71)
Supply
0.875" x 150 mm, Stud bolt with 3 heavy hexagonal nuts, (4 nos in 1 set), A453 Gr.660 Cl.A, G47M, - (ITEM CODE G24)
Supply
0.875" x 150 mm, Stud bolt with 3 heavy hexagonal nuts, (4 nos in 1 set), A453 Gr.660 Cl.A,, G44M, NACE+H2 (ITEM CODE G49NH)
Supply
0.875" x 150 mm, Stud bolt with 3 heavy hexagonal nuts, (4 nos in 1 set), A453 Gr.660 Cl.A, G45M, NACE+H2 (ITEM CODE G32NH)
Supply
1.125" x 320 mm, Stud bolt with 3 heavy hexagonal nut, (8 nos in 1 set), A453 Gr.660 Cl.A, G45M, NACE+H2 (ITEM CODE G187NH)
Supply
0.875" x 150 mm, Stud bolt with 3 heavy hexagonal nuts, (4 nos in 1 set), A193 Gr.B7/A194 Gr.2H, G41N, PWHT (ITEM CODE G40)
Supply
1.125" x 320 mm, Stud bolt with 3 heavy hexagonal nut, (8 nos in 1 set), A453 Gr.660 Cl.A, G47M, - (ITEM CODE G61)
Supply
0.625" x 90 mm, Stud bolt with 3 heavy hexagonal nut, (4 nos in 1 set), A193 Gr.B7/A194 Gr.2H, B35A (ITEM CODE 237)
Supply
0.625" x 100 mm, Stud bolt with 3 heavy hexagonal nut, (4 nos in 1 set), A193 Gr.B7/A194 Gr.2H, D35A (ITEM CODE 240)
Supply
0.625" x 90 mm, Stud bolt with 2 heavy hexagonal nut, (4 nos in 1 set), A193 Gr.B16/A194 Gr.16, B3G, PWHT (ITEM CODE 244)
Supply
PLUGS
1/2", 6000# NPTF, ASTM A105N, A2A, IBR (ITEM CODE 09I)
Supply
1/2", 3000# NPTF, ASTM A105N , B2A, IBR (ITEM CODE 36I)
Supply
3/4", 3000# NPTF, ASTM A105N, B1A/ A3A, - (ITEM CODE 39)
Supply
3/4", 3000# NPTF, ASTM A105N , B10A, H2 (ITEM CODE 08H)
Supply
3/4", 3000# NPTF, ASTM A105N , B2A, IBR (ITEM CODE 98I)
Supply
3/4", 6000# NPTF, ASTM A105N, A2A, IBR (ITEM CODE 63I)
Supply
3/4", 6000# NPTF, ASTM A105N , A37A/B36A/B53A/A36A, NACE+PWHT (ITEM CODE 06N)
Supply
3/4", 6000# NPTF, ASTM A105N, B35A, - (ITEM CODE 65)
Supply
3/4", 6000# NPTF, ASTM A105N , B38A/B39A//B6A, NACE+PWHT (ITEM CODE 19N)
Supply
3/4", 6000# NPTF, ASTM A105N , B37A/B54A/B65A/B14A, NACE+H2+PWHT (ITEM CODE 20NH)
Supply
3/4", 3000# NPTF, ASTM A182 Gr.F304L , B36K, NACE (ITEM CODE 78N)
Supply
3/4", 3000# NPTF, ASTM A182 Gr.F304L, B13K/B35K/B34K, NACE+H2 (ITEM CODE 95NH)
Supply
3/4", 3000# NPTF, ASTM A182 Gr.F316L, B14N, - (ITEM CODE 134)
Supply
3/4", 3000# NPTF, ASTM A182 Gr.F321 , B18M/B3M, NACE (ITEM CODE 55N)
Supply
3/4", 3000# NPTF, ASTM A182 Gr.F9, B1G/B3G, PWHT (ITEM CODE 26)
Supply
3/4", 3000# NPTF, ASTM A312 Gr.TP304, A3K, - (ITEM CODE 52)
Supply
3/4", 3000# NPTF, ASTM A312 Gr.TP304L , B22K/B36K, NACE (ITEM CODE 45N)
Supply
3/4", 3000# NPTF, ASTM B564 UNS N08825, B12Q, NACE+H2 (ITEM CODE 145NH)
Supply
3/4", 3000# NPTF, ASTM B564 UNS N10276, B18C, NACE (ITEM CODE 113N)
Supply
1", 3000# NPTF, ASTM A105 Normalized Galvanized, A3AL, - (ITEM CODE 09)
Supply
1", 3000# NPTF, ASTM D1784 Cl.23447, J2AL, - (ITEM CODE 188)
Supply
ADAPTORS
1/2" NPTF x 1/2" SW, 6000#, ASTM A106 Gr.B , A2A, IBR (ITEM CODE 24I)
Supply
COUPLINGS
1/2" X 1/2", NPTF, 3000# , ASTM A105 Normalized Galvanized, A3AL, - (ITEM CODE 03)
Supply
1/2" SW x 1/2" NPTF, 6000#, ASTM A234 Gr.WPB , F14A, NACE+H2+PWHT (ITEM CODE 183NH)
Supply
CONCENTRIC REDUCERS
1"X2", BW,2500# , ASTM A234 Gr.WP9 Cl.1, G42G, PWHT (ITEM CODE G73)
Supply
2"X3", BW,2500# , ASTM A234 Gr.WP9 Cl.1, G42G, PWHT (ITEM CODE G74)
Supply
1"X2", BW,2500# , ASTM A403 Gr.WP321, G45M, NACE+H2 (ITEM CODE G52NH)
Supply
2"X3", BW,2500# , ASTM A403 Gr.WP321, G45M, NACE+H2 (ITEM CODE G53NH)
Supply
1"X2", BW,2500# , ASTM A403 Gr.WP347, G47M, - (ITEM CODE G63)
Supply
2"X3", BW,2500# , ASTM A403 Gr.WP347, G47M, - (ITEM CODE G64)
Supply
TECHNICAL ASSISTANCE/ SUPPORT Assistants in package system & Commissioning & stabilization of field Instruments
In addition to the erection contractor's General and Specific Duties indicated in other inquiry documents, the following are included in the unit rates: Providing technical assistance during commissioning phase by deploying different categories of skilled & semi-skilled personnel as listed below .The quoted man-day rates shall be inclusive of all wages, overtime for working beyond normal hours including holidays / weekly off, travel / accommodation expenses, including PPE’s, all tools & tackles etc and other costs. Prior to deployment of personnel at site, Contractor(bidder) shall submit the detailed CVs of such persons (Instrument Engineer / Supervisor) proposed to be posted at site to Owner for concurrence & approval. The Owner and Contractor(bidder) shall jointly maintain a record of all such personnel chargeable at Manday Rates deployed each day which shall be used as the basis for calculating payments due to the Contractor(bidder) for the services covering assistance during pre-commissioning & commissioning phase. Should the performance of any of Contractor’s(bidder) personnel be found unsatisfactory by EIC/Consultant/EPCM, the replacement of such personnel shall be carried out by Contractor(bidder) immediately. This manpower will be utilized for Commissioning assistance requirement over and above that already described elsewhere in this SOR. Work during extended hours/Holiday shall be paid as per pro rata basis. Rates will be applied on an effective working hourly basis and will therefore not take into account the time required for preparation, handling, relocation and transport from/to work-site. Measurement of works: On the basis of daily time sheets prepared by the erection contractor and approved by EIC/Consultant/EPCM. Below mentioned resources will be utilized as per site requirement and on Instruction of EIC/Consultant/EPCM only. Manpower resource may or may not be consumed also.
SOR item for Assistants in package system & Commissioning & stabilization of field Instruments. a) Manday means 12 hours duty. Also, the deputed manpower will have to work in 2 shift per day and 1 shift per person will be considered as 1 manday i.e. 12 hrs. Accordingly bidder shall quote and provide. b) Unit rates indicated shall be inclusive of all required tools & tackles for Skilled / Semi skilled/ Un skilled manpower, consumables etc. to be provided by contractor(bidder). Contractor for assistance during pre-commissioning and commissioning activities. c) Same rates shall also be applicable in case of any assistance is required for work in other packages, skids where-in activities are to be performed which does not have any specific rates. d) The above (I,e, Assistants in package system & Commissioning & stabilization) are in addition to the manpower/ job scope as mentioned in the tender. e) The above shall be utilized/ consumed as per site requirement only and consumption can't be guaranteed. The below are in addition to the manpower/job scope as mentioned in the tender. → Engineer ( > 5 years exp) 2 nos → Supervisor ( > 5 years exp) 1 nos
ASSISTANCE/ SUPPORT FOR COMMISSIONING/ POST COMMISSIONING STABILIZATION
Fitter/ Electrician/ Technician etc. (Skilled)
Welder
Helper (Semi/unskilled)
SUPPORT FOR OTHER PACKAGES
Fitter/ Electrician/ Technician etc. (Skilled)
Welder
Helper (Semi/unskilled)
TRANSPORTATION OF MATERIAL FROM WAREHOUSE TO SITE
Contractor scope of work includes taking delivery from warehouse or places of storage and transportation, handling, storage, unpacking etc to site. Warehouse/place of storage shall be approx. 25 km away from site.
Miscellenious material e.g.[pipe, pipe fittings, valves (used in hookup)], transmitters, gauges etc.
CALIBRATION AND TESTING
Contractor(bidder) shall test & calibrate all the instruments as per project specification (Iinstrument data sheets) & as per manufacturer's recommendation. This shall also include instruments supplied by the package vendors (i.e pumps, compressors vendor etc.). Instruments mounted on Control panel/local panel/ gauge board mounted etc. are also to be calibrated by the contractor(bidder) . Transportation of cylinder from warehouse to site required for calibration or testing is in contractor(bidder) scope. a) During testing & calibration contactor shall also determine that: i) All scales, charts & measurement range of the instruments, transmitters, controllers etc.are as specified in the data sheets. ii) All the instruments & accessories are as per project specification. iii) Contractor(bidder) shall record & notify to the site inchage any deviation from the specifications or faults found during calibration of the instruments. iv) If required, contractor shall make necessary repairs by repalcing the defective components (using spares). v) Calibration activity may be carried out either prior to or after the installation of the instruments in the plant. This shall be decided at the site by the EIC & client/technip site incharge. (However, client decision shall be final and binding to the contractor(bidder)). vi) If the calibration activity starts when the instruments are already installed, it should be contractor's(bidder) responsibility to remove & re-install the instruments after clibration, without any time & cost implcation to client / MPMC. b) All the instruments test & calibration results shall be recorded by the contractor(bidder) on dedicated forms duly approved by the technip site incharge. Contractor(bidder) shall submit requisite no of copies of the calibration record to client/MPMC. It will be contractor's responsibility & scope of work to supply duly approved forms. c) Testing & calibration shall be witnessed by the client/technip representative. d) To complete the calibration activity with in project schedule, contractor(bidder) shall deploy adequate number of qualified & trained manpower in consultation with site inchage. e) Contractor(bidder) shall provide all the required test & calibration equipments in requisite no. to execute the job within project schedule.
f) For calibration of gauge board or panel mounted instrument, contractor(bidder) shall remove & reinstall these instruments after calibration. No extra claim applicable on this account. g) All the instruments shall be calibrated using appropiate test equipment to make certain that 0%,25%, 50%, 75%, and 100% input (both increasing as well as decreasing inputs) produces out put signal in accordance with specification. h) Testing & calibration of GWR LT/ DP LT requires online with water or actual liquid by Contractor(bidder). i) Assistance to the Analyzer Vendor Specialists for power-up, calibration, loop test activities and Site Acceptance Test. j) Support in filling of calibration (zero & span) and carrier gases from a local certified source of supply into the empty cylinders supplied by the analyser vendor. The regulators, connectors, tubing and other accessories required for connecting the gas cylinders to the analyser system shall be free issued by the analyser vendor. Various gases of the required quantity, type and composition shall be supplied. Certification of the gas cylinders shall be provided with cylinder itself.
k) Any other activity not specified by required for calibration of instruments shall be under contractor's scope of work. l) Cleaning, checking , functional tests and configuration for special Level & Flow Instruments shall be done by the contractor(bidder) as per the directions of Engineer in Charge. m) Loop checking & simulation test (from field instruments upto DCS/ESD-PLC/ and signal back to final control element) shall be joint responsibility of DCS/PLC & instrument erection contractor(bidder). n) Only after successful completion of the Loop check & simulation test erection shall be considered completed. o) For the calibration bidder shall provide sufficient test and calibration instruments like test bench/ test/ calibration set up of PSV/TSV etc., multiple sets of Temperature bath, Dead Weight Tester/Pressure comparator, Master Test gauge (of various ranges), mA source, Multimeter, Thermocouple/ RTD simulator etc. as required. Each master instrument (Master Gauge, Temperature bath, Multimeter, mA source, Pressure calibrator, Thermocouple/ RTD simulator etc.) shall be certified (valid) by NABL accredited lab/ facility and certificate shall be traceable to National or International level. Also, the certificates shall be maintained by the bidder as valid for the entire contractual period till the certification of field instruments. p) For calibration purpose, except electrical power, there is no guarantee of providing of other utilities. The contractor shall arrange for Air Compressor for air supply of their own. q) Calibration set up shall be provided in temporary calibration rooms/ Porta cabin type set up which shall also be in contractor’s(bidder) scope. r) Contractor(bidder) to carry and use wireless (VHF/UHF) handset (Intrinsically safe) for testing/ other purposes. Accordingly sufficient no. of handsets to be provided by the bidders while executing the job. s) For calibration purpose, except electrical power, there is no guarantee of providing of other utilities. Contractor(bidder) shall arrange for Air Compressor for air supply of their own. t) Calibration set up shall be provided in temporary calibration rooms/ Porta cabin type set up which shall also be in contractor’s(bidder) scope.
Testing & Calibration of Pressure Gauges / DP Gauge without diaphragm seal
Testing & Calibration of Pressure Gauges / DP Gauge with diaphragm seal
Testing & Calibration of PressureTransmitters / DP transmitter (Smart) without diaphragm seal
Testing & Calibration of PressureTransmitters / DP transmitter (Smart) with diaphragm seal
Testing & Calibration of Guided Wave Radar, Displacer type level transmitter, Servo level transmitter, Non Contact Radar level transmitter, Capacitance type level transmitter, Agar type level transmitter
Testing & Calibration of Nuclear level transmitter
Testing & Calibration of DP type level transmitter without diaphragm seal
Testing & Calibration of DP type level transmitter with diaphragm seal
Testing of Temperature Element (Single and dual)
Testing & Calibration of Temperature Gauge
Testing & Calibration of Temperature Transmitter
Testing & Calibration of DP type Flow transmitter (Including diaphragm seal, capillary type)
Testing & Calibration of DP type Flow transmitter (without diaphragm seal, capillary type)
Testing & Calibration of Gas Detector (HC/H2/H2S,LOS gas detector & Flame detectors)
Testing of FO system cabinet (includes networking)
Testing & Calibration of Analyser transmitter (H2O,HC,O2,Specific gravity)
Testing & Calibration of Analyser transmitter (Density - Nuclear)
TESTING & CALIBRATION OF CONTROL VALVES
Testing & Calibration of Dampers,Control valves (various sizes & ratings, globe, butterfly & angle valves etc) & accessories along with necessary testing kit to perform the following operation: a) Correct positioning of the valve by feeding the input signal to control valve. input signal shall be varied from 0%, 25%, 50%, 75% & 100% (both increasing & decreasing input) to check the control valve and positioner operation. b) Check the calibration of the valve positioner (smart E/P positioner and Remote positioner). c) Stem travel shall be adjusted (if required) as per manufacturer's recommendation. d) Actuator shall be rotated, if required, to suit the site requirement. Chain pulley arrangement if required for the same shall be arranged by contractor(bidder). e) Few control valves may supplied with solenoid valve & limit switches, check performance of solenoid valve f) If required, replace solenoid valve coil and/or other parts. g) Check limit switch operation, adjust limit switch position, if required. Contractor to check for valve failure position for control valve. h) Check operation of other accessories supplied along with valve such as air set, volume booster, quick exhaust valves etc., i) Control valves calibration (Leakage, shut-off pressure etc) shall be done either in the field ('in-situ postion") or at the place of storage as per instruction of site incharge. j) Scope includes supply portable air compressor with dryer/ Compressed air cylinder to generate dust & oil free dry air for calibration. k) Any other activity not specified above but required for testing & calibration of the valve/damper & its accessories shall be in contractor's(bidder) scope. l) Physical inspection and Shifting from warehouse to the place of installation shall be in contractor's(bidder) scope m) Installation of Valves is covered in Mechanical & Piping contractor's(bidder) Scope however, Mechanical efforts and material handling equipment required during calibration and testing of Valves shall be arranged by Instrumentation contractor(bidder).
n) SS tubing leakage shall be tested with soap solution. n) SS tubing shall be connected from the Air distribution manifold. o) Any damaged SS tubing shall be rectified by Contractork) Any other activity not specified above but required for testing & calibration of the valve/damper & its accessories shall be in contractor's(bidder) scope. p) Physical inspection and Shifting from warehouse to the place of installation shall be in contractor's(bidder) scope. q) Installation of Valves is covered in Mechanical & Piping contractor's(bidder) Scope however, Mechanical efforts and material handling equipment required during calibration and testing of Valves shall be arranged by Instrumentation contractor(bidder). r) SS tubing leakage shall be tested with soap solution. s) SS tubing shall be connected from the Air distribution manifold. t) Any damaged SS tubing shall be rectified by Contractor. u) Glanding and Termination of cables for Positioner, Limit switch , solenoid etc shall be carried out by contractor(bidder). v) Canopy for Remote positioners to be installed by contractor(bidder). w) Glanding and Termination of cables for Positioner, Limit switch , solenoid etc shall be carried out by contractor(bidder). x) Canopy for Remote positioners to be installed by contractor(bidder). y) Free issue to the Contractor : Smart positioners (if required) , Remote positioners (if required) , solenoid valves, proximity type limit switches and special accessories such as quick exhaust valve, volume booster, temperature dependent fuses, O-rings etc
Control valves(Globe)
Pressure Rating: 150#/300#/600#
Pressure Rating: 900#
Pressure Rating: 1500#
Pressure Rating: 2500#
Pressure Rating: 2500#, Hub connection
Control valves(Angle)
Pressure Rating: 150#/300#/600#
Pressure Rating: 900#
Pressure Rating: 1500#
Pressure Rating: 2500#
Control valves(Butterfly)
Pressure Rating: 150#/300#/600#
TESTING & CALIBRATION OF MOTOR OPERATED VALVES
Testing & Calibration of MOV (various sizes & ratings, type of valves, gate) & accessories.The activity includes following operation a) Physical inspection and Shifting from warehouse to the place of installation shall be in contractor's(bidder) scope b) To check the open/close/stop operation locally c) Stem travel shall be adjusted (if required) as per manufacturer's recommendation. d) Check limit switch operation, torque switches , if required. e) Check valve failure position. f) MOV calibration shall be done either in the field or at the place of storage as per instruction of site incharge. g) Any other activity required for calibration (High torque/Low torque setting etc) & testing of the valve & its accessories shall in contractor's(bidder) scope. h) Stroke testing of the MOV h) Chain pulley arrangement if required for adjustment or rotation of MOVs shall be arranged by contractor(bidder). i) Installation of Valves is covered in Mechanical & Piping contractor's(bidder) Scope, however, Mechanical efforts and material handling equipment required during calibration and testing of Valves shall be arranged by Instrumentation contractor(bidder). j) Glanding and Termination of cables shall be carried out by contractor(bidder).
Pressure Rating: 150#/300#/600#
Pressure Rating: 900#
Pressure Rating: 1500#
Pressure Rating: 2500#
Pressure Rating: 2500# Hub connection
TESTING & CALIBRATION OF ON-OFF VALVES and ROSOV
As per site incharge instruction, seat leakage & hydraulic test shall be done by the contractor(bidder) for ON-OFF valves. Unit rates for conducting these test shall be furnished by the contractor(bidder) for each size of the control valve inclusive of Tools & tackles with skilled manpower.
Testing & Calibration of ON - OFF Damper & ON-OFF valves (various sizes & ratings, type of valves, ball, globe, butterfly & angle valves etc) & accessories.The activity includes following operation: a) Physical inspection and Shifting from warehouse to the place of installation shall be in contractor's(bidder) scope. b) Correct positioning of the valve by feeding input signal to on-off valve. Input signal shall be given at 0% and 100%. Wherever PST positioner is available, input signal shall be varied from 0%, 25%, 50%, 75% & 100% (both increasing & decreasing input) and check valve and positioner operation. c) Check the calibration of the valve positioner (smart E/P positioner). d) Stem travel shall be adjusted (if required) as per manufacturer's recommendation. e) Actuator shall be rotated, if required, to suit the site requirement. Chain pulley arrangement if required for the same shall be arranged by contractor(bidder). f) Solenoid valve & limit swithes- check performance of solenoid valve, if required, replace solenoid valve and/or other parts. g) Check limit switch operation, adjust limit switch position, if required. h) Check operation of other accessories supplied along with valve such as air set, volume booster, quick exhaust valves i) Check valve air failure position. j) On-Off valves calibration shall be done either in the field ('in-situ postion") or at the place of storage as per instruction of site incharge. k) Scope includes supply portable air compressor with dryer/ Compressed air cylinder to generate dust & oil free dry air for calibration. l) Any other activity required for Installation, calibration & testing of the valve & its accessories shall in contractor's(bidder) scope.
m) ON-OFF VALVES Stroke checking of the On-Off valves ( ball & butterfly valves in various sizes), testing of solenoid valves & limit switches other accessories supplied along with On-Off valves. n) Installation of Valves is covered in Mechanical & Piping contractor's(bidder) Scope, however, Mechanical efforts and material handling equipment required during calibration and testing of Valves shall be arranged by Instrumentation contractor(bidder). o) Installation of Air volume tank with proper tubing shall be done by contractor(bidder) . PSV and PT installation on the Air volume tank shall be in contractor's(bidder) scope . Testing and calibration of PT & PSV also in contractor's(bidder) scope p) Wherever there is Local push button , Operation shall be checked for the same by contractor(bidder). q) For ROSOV, Local panel installation shall be in contractor's(bidder) scope. Cabling between ROSOV and Local control panel shall be in contractor's(bidder) scope. r) SS Tubing leakage shall be tested with soap solution s) SS Tubing shall be connected from the Air distribution manifold t) Any damaged SS tubing shall be rectified by contractor(bidder). u) Glanding and Termination of cables for Solenoid , Limit switch etc shall be carried out by contractor(bidder)
On-Off valves
Pressure Rating: 150#/300#/600#
Pressure Rating: 1500#
Pressure Rating: 2500#
Pressure Rating: 2500# Hub connection
TESTING & CALIBRATION OF PSV, TSV, ERV & PVRV
a) Testing & Calibration of PSV (Pressure safety valves), TSV (Temperature safety valves), Emergency relief valve(ERV) and Pressure vaccum relief valve(PVRV) . b) Contractor(bidder) shall carry out safety relief valve (various sizes & pressure rating) set pressure check using adequate test bench. Safety relief valve pressure setting shall be as per specification (if required contractor(bidder) shall adjust spring).While performing testing, cap shall be removed and screwed again c) Contractor(bidder) shall also check seat tightness in accordance with API-527. d) Testing of the Safety Valves ( various sizes) shall be done with water (for liquid service) & with nitrogen (steam & vapour service). If required minor adjustment of set pressure shall be done by contractor. Hydraulic pump, test bench , nitrogen cylinders, regulators and other accessories required are to be supplied by contractor(bidder). e) Nitrogen Cylinders as required for calibration and testing purpose shall be arranged by contractor(bidder). f) Chain pulley arrangement if required for adjustment of PSVs shall be arranged by contractor(bidder). g) Providing Necessary test rigs for Safety valves & PRV’s h) Installation of Valves is covered in Mechanical & Piping contractor's(bidder) Scope, however, Mechanical efforts and material handling equipment required during calibration and testing of Valves shall be arranged by Instrumentation contractor(bidder). i) PSV test bench (if required) , arrangement for the same to be done by contractor(bidder) at site. j) Any other activity required for calibration & testing of the Pressure safety shall in contractor's(bidder) scope.
Size : 1" x 2"
Size : 1.5" x 2"
Size : 1.5" X 3"
Size : 2" X 3"
Size : 3" X 4"
Size : 4" X 6"
Size : 6" X 8"
Size : 6" X 10"
Size : 8" X 10"
Size : 3/4" X 1" , Screwed
TESTING & CALIBRATION OF SELF ACTUATED PRESSURE CONTROL VALVE
- Assistance to the correct dismounting and reinstallation of valve, because of flushing operations - Supervision of installation of Self Pressure Regulator (PCV) valves (Self Pressure Regulator valves to be installed by mechanical contractor(bidder) under supervision of instrumentation contractor(bidder)). - Correct positioning of the valve - Check the calibration of the valve - Check operation of other accessories supplied along with valve, if any - Any other activity required for calibration & testing of the valve & its accessories shall in contractor's scope. Testing & Calibration of Self actuated pressure control valve (PCV). Contractor(bidder) shall carry out self actuated pressure control valve (various sizes & pressure rating) set pressure check using adequate test bench. Self actuated valve pressure setting shall be as per specification. For self actuating valves, DCS control shall be required for the size above 1 1/2". Any other activity not specified above but required for testing & calibration of the valve & its accessories (if any) shall in contractor's(bidder) scope.
Pressure Rating: 150#/300#/600#
Pressure Rating: 1500#
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
Tendernotice_1.pdf
PDF • 0.60 MB
BOQ_936744.xls
BOQ • 1.17 MB
MASTERINDEXGROUPA.pdf
Tender Documents • 0.20 MB
PARTIUNPRICEDCOMMERCIALSECTIONGROUPA.pdf
Tender Documents • 25.85 MB
PARTIIPRICEDCOMMERCIALSECTIONGROUPA.pdf
Tender Documents • 1.95 MB
PARTIIITECHNICALSECTIONPART1GROUPA.pdf
Tender Documents • 13.64 MB
PARTIIITECHNICALSECTIONPART2GROUPA.pdf
Tender Documents • 26.97 MB
PARTIIITECHNICALSECTIONPART3GROUPA.pdf
Tender Documents • 28.88 MB
PARTIIITECHNICALSECTIONPART4GROUPA.pdf
Tender Documents • 31.16 MB
PARTIIITECHNICALSECTIONPART5GROUPA.pdf
Tender Documents • 3.25 MB
PARTIIITECHNICALSECTIONPART6GROUPA.pdf
Tender Documents • 21.50 MB
Download all tender documents and submit your bid